Sanyo XHX3652, XMHX1252, XMHX1852, AHX0752, AHX0952 Installation Instructions Manual

...
– W-3WAY ECO-i System Air Conditioner –
R410A Models
for Refrigerant R410A
This air conditioner uses the new refrigerant R410A.
INSTALLATION INSTRUCTIONS
External diameter of service port R410A: 5/16"
NOTE
Indoor Units
Class 9 12 15 18 2419 36 5448
UM Slim Concealed-Duct UMHX0762 UMHX1262UMHX0962 UMHX1562 UMHX1862
XM
4-Way Air Discharge Mini Semi-Concealed
XMHX1252 XMHX1852
U Concealed-Duct UHX0762 UHX1262UHX0962 UHX1562 UHX1862 UHX2462 UHX3662 UHX4862 UHX5462
X
4-Way Air Discharge Semi-Concealed
XHX1252 XHX1852 XHX2452 XHX3652
A
1-Way Air Discharge Semi-Concealed
AHX0752 AHX1252AHX0952
T Ceiling-Mounted THX1252 THX1852 THX2452
D
Concealed-Duct High Static Pressure
DHX3652 DHX4852
FHX0762 FHX1262FHX0962 FHX1562 FHX1862 FHX2462F Floor-Standing
FMHX0762
FMHX1262
FMHX0962
FMHX1562
FMHX1862
FMHX2462
FM
Concealed-Floor Standing
KHX0752 KHX1252KHX0952K Wall-Mounted KHX1862 KHX1962 KHX2452
Optional Controllers
Timer Wired Remote Controller RCS-TM80BG
Wireless Remote Controller (For X Type) RCS-SH80AAB.WL
Wireless Remote Controller (For XM Type) RCS-XM18AAB.WL
Wireless Remote Controller (For U, UM, D, F, FM Types) RCS-BH80AAB.WL
Wireless Remote Controller (For A, T Types) RCS-TRP80AAB.WL
RC
Wireless Remote Controller (For K Type) RCS-SH1AAB
Simplified Remote Controller RCS-KR1EG
System Controller SHA-KC64UG
Schedule Timer SHA-TM64AGB
Intelligent Controller SHA-KT256EA
Communication Adaptor SHA-KA128AAB
Remote Sensor ART-K45AGB
LonWorks Interface SHA-LN16UAB
SANYO North America Corporation
Commercial Solutions Division 2055 Sanyo Ave., San Diego CA 92154, U.S.A.
In Canada
SANYO Canada Inc.
201 Creditview Road, Woodbridge Ontario, L4L 9T1, Canada
7
Class 96
CHDZ09663
CHDZR09663
Outdoor Units
C
72
Eco-i W-3WAY
CHDZ07263
CHDZR07263
Refrigerant R410A is used in the outdoor units.
IMPORTANT!
WARNING
WARNING
CAUTION
CAUTION
Please Read Before Starting
This air conditioning system meets strict safety and oper­ating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including fail­ure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
When Installing…
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free con­nection.
• Check carefully for leaks before starting the test run.
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inad­equate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm after installation that no refrigerant gas is leak­ing. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
2
3
Check of Density Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrig­erant gas leaking out, its density will not exceed a set limit.
The refrigerant (R410A), which is used in the air condition­er, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its density should rise excessively. Suf­focation from leakage of refrigerant is almost non-existent. With the recent increase in the number of high density buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effec­tive use of floor space, individual control, energy conserva­tion by curtailing heat and carrying power, etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation pro­cedure so that if the refrigerant accidentally leaks out, its density does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).
ASHRAE and the International Mechanical Code of the ICC as well as CSA provide guidance and define safe­guards related to the use of refrigerants, all of which define a Refrigerant Concentration Level (RCL) of 25 pounds per 1,000 cubic feet for R410A refrigerant. For additional guidance and precautions related to refrigerant safety, please refer to the following documents:
International Mechanical Code 2009 (IMC-2009) (or more recently revised) ASHRAE 15 ASHRAE 34
New tool?
Precautions for Installation Using New Refrigerant
Vacuum pump
Outlet Inlet
CAUTION
1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.” For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes.
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).
When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to prevent dirt, moisture, or other foreign substances from entering. These substances can result in system malfunction.
Copper tube
Wall thickness 1/32 (0.8) 1/32 (0.8) 1/32 (0.8) 5/128 (1.0)
Copper tube Wall thickness 5/128 (1.0) 5/128 (1.0) 5/128 (1.0) 3/64 (1.1)
Material O
Outer diameter 1/4 (6.35) 3/8 (9.52) 1/2 (12.7) 5/8 (15.88) 3/4 (19.05)
Material 1/ 2 H, H
Outer diameter 7/8 (22.22) 1 (25.4) 1-1/8 (28.58) 1-1/4 (31.75) 1-1/2 (38.1) 1-5/8 (41.28)
Unit: in. (mm)
over 5/128 (1.0)
over 3/64 (1.15)
over
Unit: in. (mm)
3/64 (1.20)
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refriger-
ant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects
in the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining refriger-
ant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1. Tool specifications have been changed due to the characteristics of R410A. Some tools for R22- and R407C-type refrigerant systems cannot be used.
Item compatible Remarks with R410A?
Manifold gauge Yes No Types of refrigerant, refrigerating machine oil, and pressure gauge are different.
Charge hose Yes No To resist higher pressure, material must be changed.
Vacuum pump Yes Yes Use a conventional vacuum pump if it is equipped with a check valve. If it has no check valve, purchase and attach a vacuum pump adapter.
Leak detector Yes No Leak detectors for CFC and HCFC that react to chlorine do not function because R410A contains no chlorine. Leak detector for HFC134a can be used for R410A.
Flaring oil Yes No For systems that use R22, apply mineral oil (Suniso oil) to the flare nuts on the tubing to prevent refrigerant leakage. For machines that use R407C or R410A, apply synthetic oil (ether oil) to the flare nuts.
R407C tools
Manifold gauge
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
4
5
3-2. Use R410A exclusive cylinder only.
New refrigerant R410A cannot be used for earlier models
1. Compressor specifications are different.
If recharging a R22 or R407C compressor with R410A, durability will significantly decrease since some of the materials used for compressor parts are different.
2. Existing tubing cannot be used (especially R22).
Completely cleaning out residual refrigerating
machine oil is impossible, even by flushing.
Valve
Single-outlet valve
(with siphon tube) Liquid refrigerant should be recharged with the cylinder standing on end as shown.
Liquid
3. Refrigerating machine oil differs (R22).
Since R22 refrigerating machine oil is mineral oil, it does not dissolve in R410A. Therefore, refrigerating machine oil discharged from the compressor can cause compressor damage.
R22 refrigerating machine oil Mineral oil (Suniso oil)
R407C refrigerating machine oil Synthetic fluid (ether oil)
R410A refrigerating machine oil Synthetic fluid (ether oil)
R410A
CONTENTS
Page Page
IMPORTANT! ............................................................... 2
Please Read Before Starting Check of Density Limit Precautions for Installation Using New Refrigerant New refrigerant R410A cannot be used for earlier models
1. GENERAL ............................................................... 7
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied 1-3. Type of Copper Tube and Insulation Material 1-4. Additional Materials Required for Installation 1-5. Tubing Length 1-6. Tubing Size 1-7. Straight Equivalent Length of Joints 1-8. Additional Refrigerant Charge 1-9. System Limitations 1-10. Installation Standards 1-11. Check of Limit Density 1-12. Installing Distribution Joint 1-13. Optional Distribution Joint Kits 1-14. Optional Solenoid Valve Kit 1-15. Example of Tubing Size Selection and
Refrigerant Charge Amount
2. SELECTING THE INSTALLATION SITE .............. 20
2-1. Outdoor Unit 2-2. Precautions When Installing in Heavy Snow
Areas 2-3. Dimensions of Wind Ducting 2-4. Dimensions of Snow Ducting
5.HOW TO PROCESS TUBING ................................. 32
5-1. Connecting the Refrigerant Tubing 5-2. Connecting Tubing Between Indoor and
Outdoor Units 5-3. Insulating the Refrigerant Tubing 5-4. Taping the Tubes 5-5. Finishing the Installation
6. AIR PURGING ...................................................... 36
Air Purging with a Vacuum Pump (for Test Run)
Preparation
7. TEST RUN............................................................. 39
7-1. Preparing for Test Run 7-2. Test Run Procedure 7-3. Main Outdoor Unit PCB Setting 7-4. Auto Address Setting 7-5. Remote Controller Test Run Settings 7-6. Caution for Pump Down 7-7. Meaning of Alarm Messages
3. HOW TO INSTALL THE OUTDOOR UNIT ............... 24
3-1. Transporting 3-2. Installing the Outdoor Unit 3-3. Remove the Brackets Used for Transport 3-4. Routing the Tubing 3-5. Prepare the Tubing 3-6. Connect the Tubing
4. ELECTRICAL WIRING .......................................... 28
4-1. General Precautions on Wiring 4-2. Recommended Wire Length and Wire
Diameter for Power Supply System
4-3. Wiring System Diagram
6
7
CAUTION
1. GENERAL
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the outdoor unit and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Flathead screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied
See Table 1-1.
1-3. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a
local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tubing.
2. Foamed polyethylene insulation for copper tubes as
required to precise length of tubing. Wall thickness of the
insulation should be not less than 5/16 in.
3. Use insulated copper wire for field wiring. Wire size varies
with the total length of wiring.
Refer to
4. ELECTRICAL WIRING” for details.
Check local electrical codes and
regulations before obtaining
wire. Also, check any specified
instructions or limitations.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Table 1-1 Outdoor Unit
Part name
Connection tubing
Outer diameter o1-1/8"(o28.58)
Outer diameter o7/8"(o22.22)
Outer diameter o3/4"(o19.05)
Figure
Instruction manual paper
Inner diameter o3/4"(o19.05)
Inner diameter o3/4"(o19.05)
Inner diameter o5/8"(o15.88)
07263 Model
(8 hp)
0
1
0
1
Q’ty
09663 Model
(10 hp)
1
1
1
1
(hp = horse power)
1-5. Tubing Length
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.
Balance tubing (ø
3/8"
)
Explanation of symbols
Distribution joint (APR: purchased separately)
1. Main tubing length LM = LA + LB … b 262 ft
2. Main distribution tubes LC – LH are selected according to the capacity after the
3. The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
4. Sizes of indoor unit connection tubing
Max. 1.3 ft
Max. 1.3 ft
distribution joint.
tubing sizes on the indoor units.
For extension
For extension
1 – 40 are determined by the connection
T-joint tubing (header joint system)
Solenoid valve kit
Ball valve (field supply)
T-joint (field supply)
Solidly welded shut (pinch weld)
Note: Do not use commercially available T-joints for the liquid tubing
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor
unit connections and tubing branches.
and parts.
R410A distribution joint APR-CHRZP900BAB (for outdoor unit) APR-RZP224BAB (for indoor unit) APR-RZP680BAB (for indoor unit) APR-RZP1350BAB (for indoor unit)
Table 1-2 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Item Mark Contents Length (ft.)
131
*2
984
32
49 13
6.6
Allowable tubing length
Allowable elevation difference
Allowable length of joint tubing
L = Length, H = Height
L1 Max. tubing length
$L (L2 – L4)
Difference between max. length and min. length from the No. 1 distribution joint
Actual length 492
Equivalent length 574
LM Max. length of main tubing (at max. diameter) 262
40
, 2...
2
1
L1+
+
...
1
A+B
+LF+LG+LH each distribution tube (only liquid tubing)
L5
H1
Max. length of each distribution tube 98
40
+
Total max. tubing length including length of
Distance between outdoor units
When outdoor unit is installed higher than indoor unit 164
When outdoor unit is installed lower than indoor unit 131 H2 Max. difference between indoor units H3 Max. difference between outdoor units
L3
T-joint tubing (field-supply); Max. tubing length between
the first T-joint and solidly welded-shut end point
NOTE
1:
The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
2:
If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for the discharge tubes, suction tubes, and narrow tubes. (field supplied)
3:
If the longest main tube length (LM) exceeds 164 feet, increase the main tube size at the portion before 164 ft. by 1 rank for the suction tubes and discharge tubes. (field supplied)
(For the portion that exceeds 164 feet, set based on the main tube sizes (LA) listed in the table on the following page.)
8
9
1-6. Tubing Size
ø3/4"
(ø19.05)
ø1-1/8"
(ø28.58)
ø1-3/8"
(ø34.92)
ø5/8"
(ø15.88)
ø1-1/8"
(ø28.58)
ø1/2"
(ø12.70)
ø1-1/8"
(ø28.58)
ø3/8"
(ø9.52)
ø7/8"
(ø22.22)
ø5/8"
(ø15.88)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
ø3/8"
(ø9.52)
ø3/8"
(ø9.52)
ø3/8"
(ø9.52)
ø1/2"
(ø12.70)
238.900
(25 hp)
200.600
(21 hp)
24.200
(2.5 hp)
24.200
(2.5 hp)
334.400
(35 hp)
85.300
(9 hp)
54.600
(6 hp)
54.600
(6 hp)
85.300
(9 hp)
258.000
(27 hp)
ø3/4"
(ø19.05)
ø1-1/8"
(ø28.58)
ø1-1/2"
(ø38.10)
334.400
(35 hp)
ø3/4"
(ø19.05)
ø1-1/8"
(ø28.58)
258.000
(27 hp)
238.900
(25 hp)
102.400
(11 hp)
ø1/2"
(ø12.70)
ø1-1/8"
(ø28.58)
ø3/4"
(ø19.05)
102.400
(11 hp)
124.200
(13 hp)
124.200
(13 hp)
Below BTU/h
Over BTU/h
143.300
(15 hp)
ø1/2"
(ø12.70)
ø1-1/8"
(ø28.58)
ø7/8"
(ø22.22)
ø7/8"
(ø22.22)
ø1-1/8"
(ø28.58)
143.300
(15 hp)
162.400
(17 hp)
ø5/8"
(ø15.88)
ø1-1/8"
(ø28.58)
162.400
(17 hp)
200.600
(21 hp)
Total capacity after distribution
Tubing size
Suction tubing
Liquid tubing
Discharge tubing
hp = horsepower
Unit: in. (mm)
Below BTU/h
Over BTU/h
Total capacity after distribution
Tubing size
ø1-3/8"
(ø34.92)
Suction tubing
Liquid tubing
Discharge tubing
Table 1-5 Outdoor Unit Tubing Connection Size ( A D)
o3/8" (o9.52)
o3/8" (o9.52)
72,000
(21.1)
96,000
(28.1)
Flare connection
Brazing connection
Brazing connection
o3/8" (o9.52)
Flare connection
Balance tubing
Liquid tubing
Discharge tubing
Suction tubing
BTU/h
(kW)
Unit: in. (mm)
*1 If the size of tubing (LA) is less than 16.4 feet, it is recommended that the tubing diameter be larger than
Ø7/8" (Ø22.22).
*2 If the size of tubing (LA) is less than 16.4 feet, it is recommended that the tubing diameter be larger than Ø1-1/8" (Ø28.58).
o5/8"
(o15.88)
o3/4"
(o19.05)
o3/4"
*
1
(o19.05)
*
1
o7/8"
*
2
(o22.22)
*
2
Table 1-3 Main Tubing Size (LA)
BTU/h
(kW)
Total system horsepower
72,000
(21.1)
8
96,000
(28.1)
10
144,000
(42.2)
16
168,000
(49.2)
18
192,000
(56.2)
20
216,000
(63.3)
24
240,000
(70.3)
26
264,000
(77.3)
28
Unit: in. (mm)
288,000
(84.3)
30
Combined outdoor units
Suction tubing
Discharge tubing
Liquid tubing
*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension.
*2: The balance tube (outdoor unit tube) diameter is ø3/8" (ø9.52). *3: Type 1 tubing should be used for the refrigerant tubes. *4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the
*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for
Size of tubing (LO) between outdoor units
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.
Table 1-4 Main Tubing Size After Distribution (LB, LC...)
10
8
(o28.58)
o7/8"
(o22.22)
o1-1/8"
10 10
o5/8"
(o15.88)
8 8 8
10
8 8
(o28.58)
o1-1/8"
10 10
8
o1-3/8"
(o34.92)
o3/4"
(o19.05)
(o22.22)
o5/8"
(o15.88)
o7/8"
o3/8"
(o9.52)
108
o3/4"
(o19.05)
8 8
o1/2"
(o12.7)
However extension is not possible if the resulting tubing size is two ranks higher.
suction, discharge, and liquid tubes. (Use field-supply reducers.) (Select from Table 1-3 and Table 1-9.)
the suction tubes and discharge tubes. (For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)
*1: The outdoor unit connection tubing (LO) is
determined by the total capacity of the outdoor units connected to the tube ends. The tubing size is selected based on the table of main tube sizes after the branch.
*2: If the total capacity of the indoor units con-
nected to the tube ends is different from the total capacity of the outdoor units, then the main tube size is selected based on the total capacity of the outdoor units. (For LA, LB, and LF in particular)
10 10 10
Gas tubing size (in.(mm))
1/2"
(12.7)
5/8"
(15.88)
3/4"
(19.05)
7/8"
(22.22)1"(25.4)
1-1/8"
(28.58)
1-1/4"
(31.8)
1-1/2" (38.1)
90 o elbow
1 ft.
(0.30 m)
1.1 ft.
(0.35 m)
1.4 ft.
(0.42 m)
1.6 ft.
(0.48 m)
1.7 ft.
(0.52 m)
1.9 ft.
(0.57 m)
2.3 ft.
(0.70m)
2.6 ft.
(0.79 m)
45 o elbow
0.8 ft.
(0.23 m)
0.9 ft.
(0.26 m)
1 ft.
(0.32 m)
1.2 ft.
(0.36 m)
1.3 ft.
(0.39 m)
1.4 ft.
(0.43 m)
1.7 ft.
(0.53 m)
1.9 ft.
(0.59 m)
U-shape tube bent (R2–23/64–3–15/16 in.)
3 ft.
(0.90 m)
3.4 ft.
(1.05 m)
4.1 ft.
(1.26 m)
4.7 ft.
(1.44 m)
5.1 ft.
(1.56 m)
5.6 ft.
(1.71 m)
6.9 ft.
(2.10 m)
7.8 ft.
(2.37 m)
T r ap bend
7.5 ft.
(2.30 m)
9.2 ft.
(2.80 m)
10.5 ft.
(3.20 m)
12.5 ft.
(3.80 m)
14.1 ft.
(4.30 m)
15.4 ft.
(4.70 m)
16.4 ft.
(5.00 m)
14.0 ft.
(5.80 m)
Y -br anch distr ib ution joint Equiv alent length con v ersion not needed.
Ball v alv e f or ser vice Equiv alent length con v ersion not needed.
Table 1-6 Refrigerant Charge Amount at Shipment (for outdoor unit)
DC
CHDZR07263 CHDZR09663
(oz)
CHDZ07263 CHDZ09663
416 416
Table 1-7 Indoor Unit Tubing Connection Size ( 1 40)
Indoor unit type
Total system horsepower
Distribution joint-solenoid valve kit tubing
Solenoid valve kit-Indoor unit tubing connection
Suction tubing Discharge tubing Liquid tubing
Gas tubing
Liquid tubing
7 9 12 15 18 19 24 36 48 54
0.8 1 1.3 1.7 2 2.1 3 4 5 5.5
o1/2" (o12.7)
o1/4" (o6.35)
o5/8" (o15.88)
o1/2" (o12.7)
o3/8" (o9.52)
o5/8" (o15.88)
o3/8" (o9.52)
Unit: in. (mm)
*1: For the solenoid valve kits, use type 160 with parallel specifications. Branch the tubing before and after the solenoid valve kits.
1-7. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 1-8 Straight Equivalent Length of Joints
Table 1-9 Refrigerant tubing (Existing tubing can be used.)
Material O Material 1/2H • H
ø1/4" (ø6.35) t1/32 (t0.8)
ø3/8" (ø9.52) t1/32 (t0.8) ø1-1/8" (ø28.58) t5/128 (t1.0)
ø1/2" (ø12.7) t1/32 (t0.8) ø1-1/4" (ø31.75) t3/64 (t1.1)
ø5/8" (ø15.88) t5/128 (t1.0) ø1-1/2" (ø38.10) over t3/64 (t1.15)
ø3/4" (ø19.05)
ø7/8" (ø22.22) t5/128 (t1.0)
Tubing size (in. (mm))
over t5/128 (t1.0)
ø1-5/8" (ø41.28) over t3/64 (t1.20)
1-8. Additional Refrigerant Charge
Additional refrigerant charge amount is calculated from the liquid tubing total length and a type of outdoor unit as follows.
ø3/8"
(ø9.52)
Table 1-10-1 Amount of Refrigerant Charge Per ft.,
According to Liquid Tubing Size
Liquid tubing size
Amount of refrigerant charge (oz/ft.)
ø1/4"
(ø6.35)
0.279 0.602 1.38 1.99 2.78 3.93
ø1/2"
(ø12.7)
ø5/8"
(ø15.88)
ø3/4"
(ø19.05)
ø7/8"
(ø22.22)
Required amount of additional refrigerant charge =
10
[ (Amount of additional refrigerant charge per ft. of each size of liquid tube × its tube length) + (...) + (...)] + [(Necessary amount of additional refrigerant charge per outdoor unit + (...) + (...)]
* Always charge accurately using a scale for weighing.
* When bending the tubes, use a bending
radius that is at least 4 times the outer diameter of the tubes. In addition, take sufficient care to avoid crushing or damaging the tubes when bending them.
11
Outdoor unit Outdoor unit Indoor unit
Suction tube
Discharge tube
Liquid tube
Balance tube
Suction tube
Discharge tube
Liquid tube
Gas tube
Liquid
tube
4-tube layout 3-tube layout 2-tube layout
Solenoid
valve kit
Indoor unit
Room
Hallway
Indoor unit
Room
Indoor unit
Room
Hallway
Indoor unit
Room
Solenoid valve kit
Solenoid valve kit
Table 1-10-2 Necessary Amount of Refrigerant Charge Per Outdoor Unit
Further charge a certain amount listed below in addition to the amount of refrigerant charge.
CHDZ07263
CHDZR07263
42 oz/unit 42 oz/unit
CHDZ09663
CHDZR09663
1-9. System Limitations
Table 1-11 System Limitations
Max. No. allowable connected outdoor units 3
Max. capacity allowable connected outdoor units
Max. connectable indoor units 40
288,000 BTU/h (30 hp, 84.3 kw)
*1
Max. allowable indoor/outdoor capacity ratio 50 – 130 %
*1: In the case of 20 hp (type 191.100 BTU/h) or smaller units, the number is limited by the total capacity of the connected indoor units.
1-10. Installation Standards
Relationship between A/C units and refrigerant tubing
Install the solenoid valve kit 98 ft. or less from the indoor unit.
In quiet locations such as hospitals, libraries, and hotel rooms, the refrigerant noise may be somewhat notice-
able. It is recommended that the solenoid valve kit be installed inside the corridor ceiling, at a location outside the room.
Desirable
Undesirable
Common solenoid valve kit
Multiple indoor units under group control can utilize a solenoid valve kit in common.
Categories of connected indoor unit capacities are determined by the solenoid valve kit.
Type of solenoid valve kit Total capacity of indoor units (BTU/h)
160 19.000
56 7.500
<
Total capacity < 54.600
<
Total capacity < 19.000
If the capacity range is exceeded, use 2 solenoid valves connected in parallel.
WARNING
Always check the gas density
15 to 30
B
A
B
A
Tube branching methods (horizontal use)
Arrow view
Horizontal line
View as seen from arrow
Ball valve
(BV: purchased
separately)
Main tubing
Types of vertical trap specifications
(If only 1 unit is connected, a ball valve is also needed on this side.)
Indoor unit (1)
(When not using ball valve)
(When using ball valve)
Branch tubing is directed upward.
(Each unit is connected to tubing that is either level or is directed downward.)
Main tubing
Indoor unit
More than 7–7/8"
Indoor unit (more than 2 units)
Horizontal
Indoor unit is directed downward
CAUTION
limit for the room in which the unit is installed.
1-11. Check of Limit Density
When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally leaks out, its density does not exceed the limit level for that room.
1-12. Installing Distribution Joint
Pay special attention to any location, such as a basement, etc., where leaking refrigerant can accumulate, since refrig­erant gas is heavier than air.
(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT”
enclosed with the optional distribution joint kit (APR-CHRZP900BAB, RZP224BAB, RZP680BAB, RZP1350BAB).
(2) When creating a branch using a commercially available
T-joint (header joint system), orient the main tubing so that it is either horizontal (level) or vertical. In order to prevent accumulation of refrigerant oil in stopped units, if the main tubing is horizontal then each branch tubing length should be at an angle that is greater than horizon­tal. If the main tubing is vertical, provide a raised starting portion for each branch.
Header joint system (Indoor)
Install at a positive angle
Outdoor
Indoor
Horizontal line
L3 6.56 ft.
Indoor
Indoor
Horizontal line
Install at a positive angle (15 – 30°)
Solidly welded shut (X)
[Header joint system]
Be sure to solidly weld shut the T-joint end (marked
by “X” in the figure). In addition, pay attention to the insertion depth of each connected tube so that the flow of refrigerant within the T-joint is not impeded.
When using the header joint system, do not make fur-
ther branches in the tubing.
Do not use the header joint system on the outdoor
unit side.
(3) If there are height differences between indoor units or if
branch tubing that follows a distribution joint is connect­ed to only 1 unit, a trap or ball valve must be added to that distribution joint. (When adding the ball valve, locate it within 15 - 3/4" of the distribution joint.)
If a trap or ball valve is not added, do not operate the system before repairs to a malfunctioning unit are completed. (The refrigerant oil sent through the tub-
ing to the malfunctioning unit will accumulate and may damage the compressor.)
12
13
1-13. Optional Distribution Joint Kits
11-13/16 11-13/16
13-25/64
D
C
B
EDF
3/41-1/8 3/85/8 1/21
Size
7/81-1/4
Part B Part C Part D Part E Part F Part G Part H Part I
Inch
InsulationInsulation
Joint
Distribution
Insulation
C
C
H
I
HI
E
G
F
E
EFG
E
F
G
#C
C
E
D
DE
#C
D
#C
E F
#C
Suction Tube
Discharge Tube
Liquid Tube
Unit: in.
*Insulators for both the Suction tube and the Discharge tube are the same. *Suction tube and Discharge tube are similar in sizes and both the tube entrances have the same diameter. So the both Distribution joints can fit into different tubes. Since the diameter of the tube ends for both Suction and Discharge tube are different, take care not to connect the distribution joint different. See the " # " marks on the above figures.
Note that the dimension marked with every alphabetical letter in the diagram shows the inner diameter.
Table 1-13 Dimensions for connections of each part
See the installation instructions packaged with the distribution joint kit for the installation procedure.
Table 1-12
Model name Cooling capacity after distribution Remarks
1. APR-CHRZP900BAB 307.100 BTU/h or less For outdoor unit
2. APR-RZP224BAB 76.400 BTU/h or less For indoor unit
3. APR-RZP680BAB 232.000 BTU/h or less For indoor unit
4. APR-RZP1350BAB 460.700 BTU/h or less For indoor unit
Tubing size (with thermal insulation)
1. APR-CHRZP900BAB For outdoor unit (Capacity after distribution joint is 307.100 BTU/h or less.)
HG
G
Insulation
Insulation
Insulation
*Insulators for both the Suction tube and the Discharge tube are the same. *Suction tube and Discharge tube are similar in sizes and both the tube entrances have the same diameter. So the both Distribution joints can fit into different tubes. Since the diameter of the tube ends for both Suction and Discharge tube are different, take care not to connect the distribution joint different. See the " # " marks on the above figures.
Note that the dimension marked with every alphabetical letter in the diagram shows the inner diameter.
I
H
IH
I
H
EFD
D
C
C
#C
#D
#D
#C
EF
GF E
EFG
E
F
G
E F
D
E F
FED
FE
H
G
G
Suction Tube
Discharge Tube
Liquid Tube
11-13/16
13-25/64
11-13/16
Table 1-14 Dimensions for connections of each part
Unit: in.
Position A B C D E F G H I J
Dimension ø1-1/2" ø1-1/4" ø1-1/8" ø1" ø7/8" ø3/4" ø5/8" ø1/2" ø3/8"
2. APR-RZP224BAB Use: For indoor unit (Capacity after distribution joint is 76.400 BTU/h or less.)
Example: (F below indicates inner diameter. below indicates outer diameter.)
F
Liquid tubing
9–1/4
I H
HIIH
2–23/32
2–11/64
Suction tubing
F
G
F
8–17/64
5–45/64
Discharge tubing
7–21/64
F
F
GH
F
F
G H
3–5/8 15/32
2–11/64
1–37/64
H
G
5–23/64
H
G
HH
H
H
G
3–1/32 9/32
Thermal insulation
Thermal insulation
Thermal insulation
Unit: in.
3. APR-RZP680BAB Use: For indoor unit (Capacity after distribution joint is greater than 76.400 BTU/h and no more than 232.000 BTU/h.)
4. APR-RZP1350BAB Use: For indoor unit (Capacity after distribution joint is greater than 232.000 BTU/h and no more than 460.700 BTU/h.)
Example: (B below indicates inner diameter. below indicates outer diameter.)
Suction tubing • Discharge tubing
H G
2–11/64
Thermal insulation
F
BB
3–35/64
F E D C
C A
B
B
BBC
4–9/64 4–13/32
1–49/64
C
B
Liquid tubing
I
H
G
G
F
G
E
G
F
I
H
ECDAFFADCE
E
13–25/64
Thermal insulation
14
E
F
G
G
HI
5–1/8
1–31/32
Unit: in.
Unit: in.
15
Part
Number
Cover of relay kit
14
Relay kit
13
Cover of control box
12
Earth (M5 with washer)
11
Terminal for communication line
10
Terminal for power line
9
Base of control box
8
Service panel
7
Discharge tube: ID1/2"
6
Suction tube: ID5/8"
5
Liquid tube : ID3/8"
4
Suspension hook
3
Liquid tube : ID1/4"
2
Types and specifications of tubing connections
1
ATK-RZP56BAWB
Gas tube: ID1/2"
Specifications
12
1
2
6
4
5
10
1314
5-25/32
9-13/32
5-55/64
53/64 2-63/64
9-29/64
63/64
63/64
2-31/64
3-15/16
6-29/64
8-15/32
2-31/64
3-15/16
5-55/64
7/16
1-7/64
43/64
4-21/64 4-21/64
5-3/64 4-1/4 3-25/32
2-3/64
5-9/32
4-49/64
5-55/64
1-21/32
4-7/32
1-21/32
3-21/32
3-21/32
Unit: in.
3
7
9
11
8
ATK-RZP56BAWB
Compatibility Power source Power input Net weight
Accessories
7.500 Total capacity of indoor units (BTU/h) < 19.000 Single-phase AC 208–230V 60Hz (supplied by indoor unit) 33 W max.
151.7 oz.
Washer x 2 Hanging hook M4 screw x 4 Tapping screw x 4 Wire holder 3-WAY connect wire ACC-3WAY-AAB (Solenoid Valve Relay Kit)
1-14. Optional Solenoid Valve Kit
Precautions on Installation of Solenoid Valve Kit
(1) Clean base metals thoroughly.
(2) Use proper ventilation to carry fumes away from the work area.
(3) Use a high quality silver based solder of at least 15 % silver.
(4) Heat the base materials broadly and uniformly.
(5) Take precautions not to overheat the device which could damage sensitive internal components.
(6) Insure compliance with all local codes!
Part
Number
Cover of relay kit
14
Relay kit
13
Cover of control box
12
Earth (M5 with washer)
11
Terminal for communication line
10
Terminal for power line
9
Base of control box
8
Service panel
7
Discharge tube: ID1/2"
6
Suction tube: ID5/8"
5
Liquid tube : ID3/8"
4
Suspension hook
3
Liquid tube : ID3/8"
2
Types and specifications of tubing connections
ATK-RZP160BAWB
Compatibility Power source Power input Net weight
Accessories
1
ATK-RZP160BAWB
19.000 Total capacity of indoor units (BTU/h) < 54.600 Single-phase AC 208–230V 60Hz (supplied by indoor unit) 40 W max.
165.8 oz.
Gas tube: ID5/8"
Specifications
9
11
10
8
12
1
3
2
6
4
5
10
1314
5-25/32
5-55/64 5-55/64
43/64
4-49/64
5-9/32
2-3/64
5-3/64
3-25/32
4-1/4
1-7/64
7/16
5-55/64
9-29/64
4-21/64 4-21/64
1-21/32
63/64
63/64
2-31/64
3-15/16
2-31/64
3-15/16
6-29/64
8-15/32
3-21/32
4-7/32
1-21/32
3-21/32
9-13/32
53/64 2-63/64
7
Unit: in.
Washer x 2 Hanging hook M4 screw x 4 Tapping screw x 4 Wire holder 3-WAY connect wire ACC-3WAY-AAB (Solenoid Valve Relay Kit)
16
17
Suspension bolt (3/8" or M10) (field supplied)
Nut (field supplied) (3/8" or M10)
Washer
M4 screws (12 pcs.)
Suspension hook
Installation of Solenoid Valve Kit
1. Install the relay kit into the indoor unit. Refer to the Installation Manual for the solenoid valve kit.
2. Connect the solenoid valve kit and the relay kit in the field.
Gas tube
Liquid tube
Connect with conduit for power supply
Suspension hook
Top surface
Discharge tube
Relay kit
Front
Liquid tube
Suction tube
Cover of control box
NOTE
Notes on Installation
• Be sure to secure the valve body by using its structure with the suspension bolt, etc.
• Install the valve body within a distance of 98 ft. from the indoor unit. Some refrigerant noise will be produced. Therefore in hospitals, libraries, hotel guest rooms, and other quiet locations, it is recommended that the solenoid valve kit be installed on the ceiling reverse side of a hallway or another location separated from the room.
• When installing the valve body, install with the top surface facing up. Secure 7-7/8" or more of space to the front so that the front service panel can be removed.
• If the supplied suspension hook will not be used, and other fastening devices will be attached in the field, use the 4 screw holes on the top surface. DO NOT use any long screws other than the supplied screws. Use of other screws may puncture the internal tubing, resulting in refrigerant leakage.
• Do not block the air holes.
Front
Service space
7-7/8" or more