Built-in type: RCS-SH80UA.WL (Optional part)for X and T type Indoor units
(WL)
Controller
External type: RCS-BH80UA.WL (Optional part)for U type Indoor units
Built-in type: RCS-SH80UA (Accessory part / Optional part)for K type Indoor units
Timer Remote
for X, T and U type Indoor units.
TRC
Controller
RCS-TM80BG* (Accessory part / Optional part)
* Timer Remote Controller comes with
Owner’s Manual and Installation Instructions.
SCSystem ControllerSHA-KC64UG (Optional part)
SANYO Commercial SolutionsIn Canada
A division of SANYO North America CorporationSANYO Canada Inc.
Cornerstone Business Park1-300 Applewood Crescent
1062 Thorndale AvenueConcord, Ontario
Bensenville, IL 60106, U.S.A.L4K 5C7, Canada
07-115 SSHP_II 5/7/07 3:59 PM Page a
2
IMPORTANT!
Please Read Before Starting
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for
improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing
are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminum fins
on the air conditioner can cut your fingers.
When Installing…
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Ventilate the room well, in the event that is refrigerant
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power OFF at the main power box (mains)
before opening the unit to check or repair electrical parts
and wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left
inside the unit being serviced.
• Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously toxic
gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas
water heater, electric room heater or other heat source,
it can cause the generation of poisonous gas.
07-115 SSHP_II 5/7/07 3:59 PM Page 2
WARNING
CAUTION
WARNING
CAUTION
2. The standards for minimum room volume are as
follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adja-
cent room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top
or bottom of the door).
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected,
the smallest room of course becomes the object.
But when mechanical ventilation is installed interlocked with a gas leakage detector in the smallest
room where the density limit is exceeded, the volume of the next smallest room becomes the object.
3. The minimum indoor floor space compared with the
amount of refrigerant is roughly as follows (when
the ceiling is 9 ft. high):
Check of Density Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its density will not
exceed a set limit.
The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of
ammonia, and is not restricted by laws imposed to protect the ozone layer. However, since it contains more
than air, it poses the risk of suffocation if its density
should rise excessively. Suffocation from leakage of
refrigerant is almost non-existent. With the recent
increase in the number of high density buildings, however, the installation of multi air conditioner systems is
on the increase because of the need for effective use
of floor space, individual control, energy conservation
by curtailing heat and carrying power, etc.
Most importantly, the multi air conditioner system is
able to replenish a large amount of refrigerant compared to conventional individual air conditioners. If a
single unit of the multi air conditioner system is to be
installed in a small room, select a suitable model and
installation procedure so that if the refrigerant accidentally leaks out, its density does not reach the limit
(and in the event of an emergency, measures can be
made before injury can occur).
In a room where the density may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device. The density is as given below.
Total amount of refrigerant (oz.)
Min. volume of the indoor unit installed room (ft.3)
< Density limit (oz./ft.
3
)
The density limit of refrigerant which is used in multi air conditioners is 0.3 oz./ft.
3
(ISO 5149).
1. If there are 2 or more refrigerating systems in a single refrigerating device, the amount of refrigerant
should be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms
A, B and C is 22 lbs.
The possible amount of leaked refrigerant gas in rooms
D, E and F is 33 lbs.
3
07-115 SSHP_II 5/7/07 3:59 PM Page 3
NOTE
Outdoor unit
Refrigerant tubing
Refrigerant tubing
Very
small
room
Small
room
Mechanical ventilation device – Gas leak detector
Medium
room
Large room
Indoor unit
Outdoor unit
Indoor unit
e.g., charged
amount (22 lbs.)
Indoor unit
Outdoor unit
e.g., charged
amount (33 lbs.)
Room A Room B Room C Room D Room E Room F
3
ft.
430
Range below the
376
density limit
of 0.3 oz./ft.
323
(countermeasures
not needed)
269
215
161
108
Min. indoor floor space
54
0
3
Range above
the density limit
of 0.3 oz./ft.
(countermeasures
needed)
224466
Total amount of refrigerant
3
lbs.
4
R407C tools
Itemcompatible Remarks
with R410A?
Manifold gauge Yes No Types of refrigerant, refrigerating machine oil, and
pressure gauge are different.
Charge hose Yes No To resist higher pressure, material must be changed.
Vacuum pump Yes YesUse a conventional vacuum pump if it is equipped
with a check valve. If it has no check valve,
purchase and attach a vacuum pump adapter.
Leak detector Yes No Leak detectors for CFC and HCFC that
react to chlorine do not function because
R410A contains no chlorine. Leak detector
for HFC134a can be used for R410A.
Flaring oil Yes No For systems that use R22, apply mineral oil (Suniso oil)
to the flare nuts on the tubing to prevent refrigerant
leakage. For machines that use R407C or R410A, apply
synthetic oil (ether oil) to the flare nuts.
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating
machine oil, the prevention of water and other impurities becomes more important than ever.
2. Be sure to recharge the refrigerant only in liquid form.
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause
defects of the unit.
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.
3. Different tools required
3-1. Tool specifications have been changed due to the characteristics of R410A.
Some tools for R22- and R407C-type refrigerant systems cannot be used.
Unit: inch
MaterialO
Copper tube
Outer diameter1/43/81/25/8
Wall thickness1/321/321/325/128
Precautions for Installation Using New Refrigerant
1. Care regarding tubing
1-1. Process tubing
Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seam-
less Pipes and Tubes.”
Tubing size: Be sure to use the sizes indicated in the table below.
Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution
joints (optional).
When bending tubing ø5/8" or smaller, use a bending radius that is 4 times the outer diameter of the tubing or larger.
* Using tools for R22 and R407C and new tools for R410A together can cause defects.
Use sufficient care in handling the tubing. Seal the tubing ends with
caps or tape to prevent dirt, moisture, or other foreign substances
from entering. These substances can result in system malfunction.
New
tool?
07-115 SSHP_II 5/7/07 3:59 PM Page 4
CAUTION
Manifold gauge
Vacuum pump
Outlet
Inlet
5
3-2. Use R410A exclusive cylinder only.
When charging with a refrigerant cylinder, use an
electronic scale for charging refrigerant. In this
case, if the volume of refrigerant in the cylinder
becomes less than 20% of the fully-charged
amount, the composition of the refrigerant starts
to change. Thus, do not use the refrigerant if the
amount in the charging cylinder is less than 20%.
Also, charge the minimum necessary amount to
the charging cylinder before using it to charge the
air conditioning unit.
07-115 SSHP_II 5/7/07 3:59 PM Page 5
Configuration and characteristics of cylinders
Valve
Liquid
Single valve
Charge liquid refrigerant with
cylinder inup-side-down position.
Fig. 1
Valve
Liquid
Single valve (with siphon tube)
Charge with cylinder innormal position.
Fig. 2
6
Concealed-Duct Type (U Type) . . . . . . . . . . . . . . 51
3-22. Required Minimum Space for Installation and
Service
3-23. Suspending the Indoor Unit
3-24. Installing the Drain Piping
3-25. Checking the Drainage
3-26. Increasing the Fan Speed
4.
HOW TO INSTALL THE OUTDOOR UNIT
. . . . . 56
4-1. Installing the Outdoor Unit
4-2. Drainage Work
4-3. Routing the Tubing and Wiring
5-1. General Precautions on Wiring
5-2. Recommended Wire Length and Wire
Diameter for Power Supply System
5-3. Wiring System Diagrams
5-4. How to Connect Wiring to the Terminal
6. HOW TO INSTALL THE WIRED REMOTE
CONTROLLER (OPTIONAL PART) . . . . . . . . . . 60
6-1. Installation Site Selection
6-2. Wired Remote Controller Installation
6-3. Basic Wiring Diagram
6-4. Wiring System Diagram for Group Control
6-5. Wiring System Diagram for Multiple Remote
Controllers
6-6. How to Switch the Indoor Temperature Sensor
6-7. Trouble Diagnostics
7. HOW TO INSTALL THE WIRELESS REMOTE
CONTROLLER
(ACCESSORY PART / OPTIONAL PART) . . . . . 68
7-1. Wireless Remote Controller Installation
7-2. Room Temperature Sensor Setting
7-3. Address Switches
7-4. Setting the Model Code
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Outdoor Unit
1-3. Type of Copper Tube and Insulation Material
1-4. Additional Materials Required for Installation
1-5. Tubing Size
2. SELECTING THE INSTALLATION SITE . . . . . . 16
2-1. Indoor Unit
2-2. Outdoor Unit
2-3. Air-Discharge Chamber for Top Discharge
2-4. Installing the Unit in Heavy Snow Areas
2-5. Precautions for Installation in Heavy Snow
Areas
2-6. Dimensions of Wind Ducting
2-7. Dimensions of Snow Ducting
3. HOW TO INSTALL THE INDOOR UNIT . . . . . . . 26
3-1. Suspending the Indoor Unit
3-2. Preparation for Suspending
3-3. Placing the Unit Inside the Ceiling
3-4. Installing the Drain Piping
3-5. Checking the Drainage
3-6. Before Installing the Ceiling Panel
3-7. Installing the Ceiling Panel
3-8. When Removing the Ceiling Panel
3-10. Removing the Wall Fixture from the Unit
3-11. Selecting and Making a Hole
3-12. Installing the Rear Panel on the Wall
3-13. Removing the Grille to Install the Indoor Unit
3-14. Preparing the Indoor Side Tubing
3-15. Wiring Instructions
3-16. Wiring Instructions for Inter-Unit Connections
3-17. Shaping the Tubing
3-18. Installing the Drain Hose
3-19. Suspending the Indoor Unit
3-20. Duct for Fresh Air
3-21. Installing the Drain Piping
CONTENTS
Page
07-115 SSHP_II 5/7/07 3:59 PM Page 6
7
<RCS-BH80UA.WL>
7-12. Separate Type Signal Receiving Unit Installation
7-13. Electrical Wiring
7-14. Test Run Switch
7-15. Misoperation Alarm Indicators
7-16. Basic Wiring Diagram
7-17. Wiring System Diagram for Group Control
7-18. Wiring System Diagram for Multiple Remote Controllers
<RCS-SH1UA>
7-19. Test Run Procedure
7-20. Check Items Before the Test Run
7-21. Preparing for the Test Run
7-22. Precautions
7-23. When Setting Indoor Unit Control PCB Switch for
8-1.System Controller Installation
8-2.Electrical Wiring
8-3.Address Switch Setting
8-4.Mode Setting
8-5.How to Perform Zone Registration
8-6.Connection with Other Equipment
8-7.Memory Back Up Switch
8-8.Test Run
11-1. Preparing for Test Run
11-2. Caution
11-3. Test Run Procedure
11-4. Items to Check Before the Test Run
11-5. Test Run Using the Remote Controller
11-6. Precautions
11-7. Table of Self-Diagnostic Functions and Corrections
(X, T, U, K Type)
11-8. Examples of Wiring Diagrams
Page
07-115 SSHP_II 5/7/07 3:59 PM Page 7
8
1. GENERAL
This booklet briefly outlines where and how to install
the air conditioning system. Please read over the
entire set of instructions for the indoor and outdoor
units and make sure all accessory parts listed are
with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1.Standard screwdriver
2.Phillips head screwdriver
3.Knife or wire stripper
4.Tape measure
5.Level
6.Sabre saw or key hole saw
7.Hacksaw
8.Core bits
9.Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-2. Accessories Supplied with Outdoor Unit
See Tables 1-1 to 1-9.
1-3. Type of Copper Tube and Insulation Material
Copper tubing for connecting the outdoor unit to the
indoor unit is available in kits which contain the liquid
and gas tubing, fittings and insulation. Consult your
nearest sales outlet or A/C workshop.
If you wish to purchase these materials separately
from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant
tubing.
2. Foamed polyethylene insulation for copper tubes
as required to precise length of tubing.
Wall thickness of the insulation should be not less
than 5/16 in.
3. Use insulated copper wire for field wiring. Wire size
varies with the total length of wiring. Refer to
Section 5. “Electrical Wiring” for details.
1-4. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See your local codes.)
3. Putty
4. Refrigeration tubing lubricant
5. Clamps or saddles to secure refrigerant tubing
6. Scale for weighing
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions
or limitations.
TableType
1-14-Way Air Discharge Semi-Concealed
1-2Wall-Mounted
1-3Ceiling-Mounted
1-4Concealed-Duct
1-5Outdoor Unit
1-6Wired Remote Controller
1-7Wireless Remote Controller
1-8Timer Remote Controller
1-9System Controller
07-115 SSHP_II 5/7/07 3:59 PM Page 8
CAUTION
9
Table 1-2 KH / KHS (Wall-Mounted)
Table 1-1 XH / XHW (4-Way Air Discharge Semi-Concealed)
07-115 SSHP_II 5/7/07 3:59 PM Page 9
Part NameFigure
Full-scale installation diagram1
Flare insulator2
Washer8
Insulating tape1
(White)
Hose band2
Packing1
Drain insulator1
Drain hose1
Drain hose adaptor1
Sealing putty1
Tube connector1
Wired remote controller
(comes with 7-7/8 in. wire)
Wood screws2
Wire joints
Owner’s Manual1
Installation Instructions1
Q’ty
For determining suspension bolt pitch
For gas and liquid tubes
For suspending indoor unit from ceiling
For gas tube flare nuts
For securing drain hose
For drain joint
For drain joint
For drain outlet
For sealing recessed portion of power supply
For sizing up of liquid tube from 1/4 in. to 3
(only for 26 type)
1
For XHW type
For XHW type
For XHW type
2
For XHW type
For XHW type
Remarks
/8 in.
Part NameFigureRemarks
Wall fixture
Insulator
Mounting plate
Tappingscrew
*1
*1
*1
*1
Truss-head
Phillips
4 × 1 in.
Full-scale diagram
Wall fixture
Rawl plug
Cover
Tappingscrew
Insulator
Tube connector
L shape tube connector
*2
*2
*2
*2
*2
Truss-head
Phillips
4× 5/8 in.
‘Q’ty
For supporting indoor unit
1
1
For insulation of tubing of the indoor unit
For securing indoor unit
1
For attaching wall fixture
20
For determining location where indoor unit is
1
installed
1
For supporting indoor unit
10
For attaching wall fixture
1
For improved tubing appearance
10
For attaching wall fixture
1
For insulation of tubing of indoor unit
For sizing up of liquid t
1
(only for 26 type)
Simplifies on-site tubing work
1
ube from 1/4 in. to 3/8 in.
Wireless remote controller1
Wireless remote controller
mounting cradle
Tr uss-head tapping screws
4 × 5/8 in.
Batteries
*1
KH(S)3672R
*2
KH(S)3072R
KH(S)3672R
For KHS type
For KHS type
1
2
For KHS type
2
For KHS type
10
Table1-4 UH / UHW (Concealed-Duct)
Table 1-3 TH / THW (Ceiling-Mounted)
07-115 SSHP_II 5/7/07 3:59 PM Page 10
Part NameFigureRemarks
Special washer
Drain insulator1
Flare insulator
T5
Drain hose adaptor1
Drain hose clamp4
Insulating tape
Vinyl clamp2
Full-scale installation
diagram
Sealing putty1
Drain hose1
Tube connector1
Wired remote controller
(comes with 7-7/8 in. wire)
Wood screws2
Wire joints
Owner’s Manual1
Black
White
(heat-resisting)
‘Q’ty
For temporarily suspending indoor unit
4
from ceiling
For drain hose joint
T3
1 Set
For gas tube joints
For gas tube and drain hose joint
2
For gas flare joints
1
For ends of flare insulator
For determiningsuspension bolt pitch
1
For sealing recessed portion of power supply
For sizingup of liquid tube from 1/4 in. to 3/8 in.
(only for 26 type)
1
For THW type
For THW type
For THW type
2
For THW type
Installation Instructions1
Part NameFigure
Flare insulator2
Insulating tape
Tappingscrew TOTA4-10
Jumper cable*1
Hose band1
Packing1
Sealing putty1
Drain insulator1
Drain hose1
Drain hose adaptor1
Clamp9
Tube connector1
Wired remote controller
(comes with 7-7/8 in. wire)
Wood screws2
(Black)
(White)
For THW type
‘Q’ty
2
2
14 or 20 or 24
1
Remarks
For gas and liquid tubes
For gas and liquid tubes
For gas and liquid tube flare nuts
For air intake duct connection
For increasing fan speed
For securing
drain hose
For drain joint
For sealing recessed portion of power supply
For drain joint
For securing drain hose & refrigerant tubing
For sizingup of liquid tube from 1/4 in. to 3/8 in.
(only for 26 type)
For UHW type
For UHW type
Wire joints
2
Owner’s Manual1
Installation Instructions1
* Jumper cable is housed inside the electrical component box.
For UHW type
For UHW type
For UHW type
11
07-115 SSHP_II 5/7/07 3:59 PM Page 11
Table 1-5 (Accessories for the Wired Remote Controller)
Part NameFigure
Wired remote controller
(comes with 7-7/8 in. wire)
Machine screws
M4 × 1 in.
‘Q’ty
1Spacers2
2Wire joints4
Part NameFigure
‘Q’ty
Wood screws2
Table 1-6 (Accessories for the Wireless Remote Controller)
<RCS-SH80UA.WL>
Part NameFigure
‘Q’ty
Part NameFigure
‘Q’ty
Operation controller1Spacers2
Run Timer
Indicator section14
Heating preparations
Pan-head tapping screws
4× 13/32 in.
Wireless remote controller12
Wireless remote controller
mounting cradle
Tr uss-head tapping screws
4 × 5/8 in.
Vinyl clamps
13
L 5-29/32
Batteries2Wire joints4
<RCS-SH1UA>
Part NameFigurePart NameFigure
Wireless remote controller12
Wireless remote controller
‘Q’ty‘Q’ty
Tr uss-head tapping screws
4 × 5/8 in.
12
Batteries
mounting cradle
12
07-115 SSHP_II 5/7/07 3:59 PM Page 12
<RCS-BH80UA.WL>
Part NameFigure
Separate type signal receivingunit
(comes with 7-7/8 in. wire)
‘Q’ty
Small screws
12
M4 × 1-9/16 in.
Part NameFigure
Carrier for ceiling installation1Wood screws2
Wireless remote controller1Spacers4
Wireless remote controller
1Wire joints4
mounting cradle
Batteries2Clamp
Machine screws
M4 × 1 in.
Ceiling installation paper pattern
21
(
3-3/4 × 2-1/32 in.
)
Table 1-7 (Accessories for the Timer Remote Controller)
‘Q’ty
1
Part NameFigure
Timer Remote Controller
Connecting wiring
length 4 ft.
Machine screws
‘Q’ty
Part NameFigure
1Wood screws
1Spacers2
2Clamps
M4 × 1 in.
Table 1-8 (Accessories for the System Controller)
Part NameFigure
System controller11
Rubber bushing
(7/8 in.)
Screws for fixture
(1-3/16 in.)
‘Q’ty
Label
(Identification label)
Label
41
(Terminal base label)
Part NameFigure
SYSTEM CONTROLLER IDENTIFICATION LABEL
ALL Central Control ALL RCU.
ZONE1 Central Control
ZONE1 RCU.
ZONE2 RCU.
ZONE2 Central Control
ZONE3 Central Control
ZONE3 RCU.
ZONE4 Central Control
ZONE4 RCU.
*Please attach this label on surface of the lid after cleaning.
*If need to write down some detail, use magic marker.
ALL ON
U1
INPUT
Interunit
control
wiring
ALL OFF
U2
INPUT
COMMON
U2 Aux.
INPUT
OPERATION
STATE
UNUSED
OUTPUT
ALARM
OUTPUT
DC12V
FROM
INDOOR
UNIT PCB.
COMMON
OUTPUT
2
‘Q’ty
2
2
‘Q’ty
13
1-5. Tubing Size
Single type
Refrigerant tubing between the indoor and outdoor units
should be kept as short as possible.
The length of the refrigerant tubes between the indoor
and outdoor units are limited by the elevation difference
between the 2 units. During tubing work, try to make both
the tubing length (L) and the difference in elevation (H1)
as short as possible. Refer to Table 1-10.
Outdoor unit is placed
higher(ft.)
Outdoor unit is placed
lower(ft.)
Max. allowable tubing length at shipment (ft.)
Required additional refrigerant *
Refrigerant charged at shipment(lbs.)4.26.27.9
No additional charge of compressor oil is necessary.
1
*
If total tubing length becomes 100 to 165 ft., charge additional refrigerant by 0.43 oz./ft.
Type capacity of indoor units
Gas tube
Liquid tube
Amount of additional charge per 1 ft.
Models
1
Main tubing (L)
(oz./ft.)
26 – 42
ø5/8"
ø3/8"
0.43 oz.
C(H)2672R
C(H)3072R
C(H)3672R
C(H)4272R
165165165
100100100
505050
10 – 10010 – 10010 – 100
a) 0.43b) 0.43b) 0.43
15
1. This unit requires no additional refrigerant charge up to 100 ft. tubing length.
In case of more than 100 ft., additional
refrigerant charge is required. Refer to
Table 1-11.
2. In case of multi type installation,
indoor units should be installed within
the same room. If multi type indoor
units are installed in different rooms,
temperature control may develop problems because thermostat operation
must follow the thermostat condition of
1 indoor unit only (the main unit).
Always check the gas density
for the room in which the unit is
installed.
Pay special attention to any
location, such as a basement
or recessed area, etc. where
leaked refrigerant can collect,
since refrigerant gas is heavier than air.
Check of limit density
When installing an air conditioner in a room, it is necessary to ensure that even if the refrigerant gas accidentally escapes, its density does not exceed the limit level.
If the density might exceed the limit level, it is necessary to set up an opening between it and the adjacent
room, or to install mechanical ventilation which is interlocked with the leak detector.
(Total refrigerant charged amount: oz.)
(Min indoor volume where the indoor unit is installed: ft.3)
<
Limit density 0.3 (oz./ft.3)
The limit density of refrigerant which is used in this unit
is 0.3 oz./ft.
3
(ISO 5149).
The shipped outdoor unit comes charged with the
amount of refrigerant fixed for each type; so add it to
the amount that is charged at the field. (For the refrigerant charge amount at shipment, refer to the unit’s
nameplate.)
Minimum indoor volume & floor area relative to
the amount of refrigerant is roughly as given in
the following table.
07-115 SSHP_II 5/7/07 3:59 PM Page 15
CAUTION
WARNING
2
ft.
538
484
430
376
323
269
215
161
Min. indoor floor area
(when the ceiling is 9 ft. high)
108
54
3
ft.
4,842
4,356
3,870
3,384
2,907
2,421
1,935
1,449
Min. indoor volume
Range below the
density limit of
0.3 oz./ft.
(Countermeasures
not needed)
972
486
22
Total amount of refrigerant
3
446688 lbs.
CAUTION
Range above the
density limit of
0.3 oz./ft.
(Countermeasures
needed)
3
16
2. SELECTING THE INSTALLATION SITE
2-1. Indoor Unit
AVOID:
areas where leakage of flammable gas may be
expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near inverter lamps which may affect the
performance of the unit.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room
directly. This may cause “sweating” on the air discharge ports, causing them to spray or drip.
locations where the remote controller will be splashed
with water or affected by dampness or humidity.
installing the remote controller behind curtains or
furniture.
locations where the receiver in the indoor unit is
exposed to the inverter lamp light. Faulty operation of
the unit occurs.
DO:
select an appropriate position from which every
corner of the room can be uniformly cooled.
select a location where the ceiling is strong enough
to support the weight of the unit.
select a location where tubing and drain pipe have
the shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
install the unit within the maximum elevation
difference above or below the outdoor unit and within
a total tubing length (L) from the outdoor unit as
detailed in Table 1-11.
allow room for mounting the remote controller about
3 ft. off the floor, in an area that is not in direct
sunlight nor in the flow of cool air from the indoor
unit.
Air delivery will be degraded if the distance from the
floor to the ceiling is greater than 10 ft.
07-115 SSHP_II 5/7/07 3:59 PM Page 16
Ceiling-Mounted Type
Ceiling
Wall
Min. 10 inch
Front view
Min. 10 inch
NOTE
The rear of the indoor unit can be installed flush
against the wall.
Air
discharge
Min. 2 ft.
Ceiling
Air intake
Side view
4-Way Air Discharge Type
Concealed-Duct Type
3 ft.
3 ft.
3 ft.
3 ft.
3 ft.
NOTE
Min.
6 inch
Wall-Mounted Type
Min.
6 inch
Min.
12 inch
2-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 2-1)
damp, humid or uneven locations
DO:
choose a place as cool as possible.
choose a place that is well ventilated and outside
air temperature does not exceed maximum 115°F
constantly.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 2-2)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
if cooling operation is to be used when the outdoor
air temperature is 23°F or below, install a duct on
the outdoor unit.
Installation space
Distance between obstructions and the unit air inlet
and outlet must be as shown below.
Fig. 2-1
Fig. 2-3
Fig. 2-4
Installation requirements
provide a solid base (concrete block, 4" × 16"
beams or equal), a minimum of 6" above ground
level to reduce humidity and protect the unit against
possible water damage and decreased service life.
(Fig. 2-4)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
Concerning inlet-side distance “C” (Fig. 2-2)
The minimum for distance “C” is 6" if there are no obstructions on the outlet side
(wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance
“C” is 8".
If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-
tions on 2 of the remaining 3 sides: *2, *3, *4.
If wall *1 is on the outlet side (Fig. 2-2), or if obstructions are present on all 3 sides *2,
*3, and *4 (Fig. 2-2), then the minimum distance for “A” and “B” is 80" (Fig. 2-3). Even
if there is no wall on the outlet side, a minimum of 3.3 ft. is required.
Fig. 2-2
17
07-115 SSHP_II 5/7/07 3:59 PM Page 17
More than 25/64"
*3
Inlet side C
Outlet side
More than
3.3 ft.
*1
More than 25/64"
*4*2
Hot air
Air direction chamber
(field supply)
Exhaust fan
Outdoor
unit
(Obstruction above unit)
*1
Heat source
B
A
Inlet side
More than 8"
(Obstruction on
inlet side)
(Ground)
CAUTION
Anchor bolts
(4 pieces)
18
Fig. 2-5
Fig. 2-6
Fig. 2-7
2-3. Air-Discharge Chamber for Top Discharge
Be sure to install an air discharge chamber in the
field when:
it is difficult to keep a space of min. 20" between
the air discharge outlet and an obstacle.
the air discharge outlet is facing a sidewalk and
discharged hot air may bother passers-by.
Refer to Fig. 2-5.
2-4. Installing the Unit in Heavy Snow Areas
In locations with strong wind, snow-proof ducting
should be fitted and direct exposure to the wind
should be avoided as much as possible.
Countermeasures against snow and wind
In regions with snow and strong wind, the following
problems may occur when the outdoor unit is not provided with a platform and snow-proof ducting:
a) The outdoor fan may not run and damage to the
unit may occur.
b) There may be no air flow.
c) The tubing may freeze and burst.
d) The condenser pressure may drop because of
strong wind, and the indoor unit may freeze.
2-5. Precautions for Installation in Heavy Snow
Areas
(1) The platform should be higher than the max. snow
depth. (Fig. 2-6)
(2) The 2 anchoring feet of the outdoor unit should be
used for the platform, and the platform should be
installed beneath the air intake side of outdoor
unit.
(3) The platform foundation must be firm and the unit
must be secured with anchor bolts.
(4) In case of installation on a roof subject to strong
wind, countermeasures must be taken to prevent
the unit from being blown over.
In regions with significant snowfall, the outdoor unit should
be provided with a platform and snow-proof duct.
07-115 SSHP_II 5/7/07 3:59 PM Page 18
Air discharge
Air discharge
Without snowproof ducting
(Low platform)
Outdoor
Unit
Duct
With snowproof ducting
(High platform)
Air
Intake
2-6. Dimensions of Wind Ducting
Reference diagram for air-discharge chamber (field supply)
STK–DRV80U for 2672R / 3072R / 3672R unit
STK-DRE140A for 4272R unit
Unit: inch
Note: In snowy regions, if there is concern that snow may enter the air discharge
chamber, remove the base of the chamber (10 screws) before using.
Unit: inch
19
07-115 SSHP_II 5/7/07 3:59 PM Page 19
1 Air discharge chamber
2 Air discharge chamber (base)
3-ø5/32 hole
2
1
2
21-13/16
21-13/16
9-27/32
(25/32)
6-ø15/64 hole
22-7/16
23-15/32
21-39/64
9-27/329-27/32
1-1/16
15/16 17/32
(25/32)
Rectangular hole
(both sides)
5-3/16
5-5/32
(25/32)(25/32)
1 Unit front, air discharge chamber
2 Unit left side, air discharge chamber
3 Unit light side, air discharge chamber
4 Reinforcement brackets, 4 locations
2
9-7/161-1/8
1
Rectangular
hole
Rectangular
hole
1-3/821-5/3212-15/32
2-3/4
22-13/32
21-13/3211
4
11-13/16
3
9-27/32
9-27/32
12-7/329-27/32
39-1/4
42-29/32
9-7/16
Rectangular
hole
Rectangular
hole
1-1/8
1-3/8
12-15/3221-5/32
2-3/4
Dimensions of Outdoor Unit with air-discharge chamber (field supply)
2672R / 3072R / 3672R unit with STK-DRV80U
4272R unit with STK-DRE140A
Unit: inch
Unit: inch
20
07-115 SSHP_II 5/7/07 3:59 PM Page 20
4-5/16
Wind
direction
13-3/8
6-11/16
25-31/32
1/21/2
Wind direction
2-17/32
30-23/32
Wind direction
1/2
21-13/16
37
Wind direction
Wind direction
25/3225/32
13/32
14-31/32
15-15/16
19/32
21-5/84-1/16
9-27/32
Wind direction
5-3/16
23/32
Wind
direction
13-3/8
2-11/3621-13/32
Wind
direction
25-31/326-11/16
Wind direction
1/21/2
37
11-13/16
Wind
direction
1/2
4-5/16
25/3225/32
14-31/3213/3219/32
15-15/16
4-1/439-1/4
11- 13/ 16
Wind direction
Wind direction
48-7/16
Wind
direction
23/32
Wind
direction
21
Reference diagram for air-discharge chamber (field supply)
If the air discharge chamber is used, the space shown below must be secured around the outdoor unit.
If the unit is used without the required space, a protective device may activate, preventing the unit from operating.
(1) Single-unit installation
The top and both sides must remain open. If there are obstacles to the front and rear of
the outdoor unit, the obstacle at either the front or rear must be no taller than the height of
the outdoor unit.
(2) Multiple-unit installation
Installation in lateral rows
The front and top must remain open.
The obstacles must be no taller than the height of the outdoor unit.
The front and both sides must remain open.
Installation in front-rear rows
Installation with intakes facing outletsInstallation with intakes facing
intakes or outlets facing outlets
More than 15-3/4
More than 11-13/16More than 11-13/16
More than 7-7/8
Unit: inch
Unit: inch
Unit: inch
07-115 SSHP_II 5/7/07 3:59 PM Page 21
Min. 7-7/8
Min. 39-3/8
CAUTION
CAUTION
More than 59-1/16
More than 15-3/4
More than 78-3/4
CAUTION
22
2-7. Dimensions of Snow Ducting
Reference diagram for snow-proof vents (field supply)
STK-BDRE80A for 2672R / 3072R / 3672R unit
STK-BDR140U for 4272R unit
Unit: inch
Unit: inch
07-115 SSHP_II 5/7/07 3:59 PM Page 22
1 Unit top, snow-proof vent
2 Unit left side
3 Unit right side
4 Unit reverse side
5 Unit reverse side
6 Unit sides, reinforcement brackets for snow-proof vent
Fastened by screws at 13 locations
25-13/32
17-15/32
9-3/16
16-25/32
27-29/32
Fastened by screws at 3 locations
(also on reverse side)
Unit anchor hole
Fastened by screw at 1
location (also on reverse side)
(6 – ø7 hole)
5-3/32
19-11/16
1-21/32
25/32
3-3/4
5
30-3/32
19-11/16
28-3/4
30-11/16
4
1
11-29/32
3-31/32
9-3/8
6
13-25/32
5/8
9-3/16
16-25/32
27-29/32
2
1 Unit top, snow-proof vent
2 Unit left side
3 Unit right side
4 Unit reverse side
5 Unit reverse side
6 Unit sides, reinforcement brackets for snow-proof vent
3
9-3/16
28-13/16
47-19/32
Fastened by screws at
3 locations (also on reverse side)
25-13/32
17-15/32
Fastened by screws at 13 locations
3-3/419-11/16
25-32
5-29/32
17-23/3219-11/16
30-3/32
Unit anchor hole
(7 – ø7 hole)
13-5/1619-11/16
5/8
4
1
11-7/8
3-31/32
2
9-3/16
28-13/16
47-19/32
Fastened by screw at
1 location (also on reverse side)
15-9/32
1-5/828-3/4
30-5/8
1-13/16
23
2672R / 3072R / 3672R unit with STK-BDRE80A
Dimensions of outdoor unit with snow-proof vents (field supply)
4272R unit with STK-BDR140U
Unit: inch
Unit: inch
07-115 SSHP_II 5/7/07 3:59 PM Page 23
Wind direction
30-3/32
Wind direction
7-1/16
25-13/32
Wind directionWind direction
37
30-23/32
25/32
14-31/3213/3219/32
3/4
Wind direction
15-15/16
11-29/32
Wind direction
16-3/4
25-13/32
48-7/16
47-19/37
Wind direction
Wind direction
24-7/8
30-3/32
Wind direction
37
7-1/16
Wind direction
25/3225/32
14-31/3213/3219/32
15-15/16
Wind direction
11-29/32
28-13/16
Wind direction
Reference diagram for snow-proof vents – 1
Space requirements for setting – (1)
C(H)2672R / 3072R / 3672R / 4272R with STK-BDRE80A & STK-BDR140U
Unit: inch
24
07-115 SSHP_II 5/7/07 3:59 PM Page 24
[Obstacle to the rear of unit]
[Obstacle to the front of unit]
Top is open:Top is open:
(1) Single-unit installation
(2) Obstacles on both sides
(1) Single-unit installation
Min. A
Min. B
Min. C
Min. D
(2) Multiple-unit installation (2 or more units)
(3) Multiple-unit installation (2 or more units)
Min. G
Min. EMin. E
Note:
In cases 2 and 3 the
height of the obstacle
must be no taller than
the height of the
outdoor unit.
Outdoor unit
A
B
C
D
E
F
G
Min. E
Min. F
C(H)2672R / 3072R /
3672R / 4872R
5-29/32
5-29/32
11-13/16
7-7/8
11-13/16
5-29/32
7-7/8
Min. IMin. I
Outdoor unit
C(H)2672R / 3072R /
3672R / 4272R
H
19-11/16
Top is blocked by an obstacle:
Min. H
Min. J
I
11-13/16J39-3/8
Top is blocked by an obstacle:
Min. K
Outdoor unit
C(H)2672R / 3072R /
3672R / 4272R
L
19-11/16
Min. L
K
5-29/32
Min. M
Outdoor unit
C(H)2672R / 3072R /
3672R / 4272R
M
39-3/8
Min. N
N
39-3/8
25
Reference diagram for snow-proof vents – 2
Space requirements for setting – (2)
C(H)2672R / 3072R / 3672R / 4272R with STK-BDRE80A & STK-BDR140U
Unit: inch
07-115 SSHP_II 5/7/07 3:59 PM Page 25
[Obstacles to the front and rear of unit]
The top and both sides must remain open. Either the obstacle to the front or
the obstacle to the rear must be no taller than the height of the outdoor unit.
(1) Single-unit installation
Q
Min. P
Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 19-11/16 in. or more.
Min. O
Outdoor unit
C(H)2672R / 3072R /
3672R / 4272R
O
39-3/8
P
5-29/32
(2) Obstacles on both sides
Q
Min. 11-13/36
Min. 11-13/16
Min. 7-7/8
Min. 39-3/8
[Installation in front-rear rows]
• The top and both sides must remain open. Either the obstacle to the front or the obstacle
to the rear must be no taller than the height of the outdoor unit.
Min. 11-13/16
Min. 39-3/8Min. 7-7/8
Min. 59-1/16Min. 78-3/4
0
Dimension Q
If a snow protection duct is
attached after the unit is
installed, verify that dimension
Q is 19-11/16 in. or more.
X
26
3. HOW TO INSTALL THE INDOOR UNIT
4-Way Air Discharge Semi-Concealed Type
(X Type)
3-1. Suspending the Indoor Unit
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.
3-2. Preparation for Suspending
(1) Fix the suspension bolts securely in the ceiling
using the method shown in the diagrams (Figs. 3-1
and 3-2), by attaching them to the ceiling support
structure, or by any other method that ensures that
the unit will be securely and safely suspended.
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in
the ceiling.
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The
diagram and table (Fig. 3-3 and Table 3-2) show
the relationship between the positions of the suspension fitting, the unit, and the panel.
Fig. 3-1
Fig. 3-2
Unit: inch
Fig. 3-3
Unit: inch
07-115 SSHP_II 5/7/07 3:59 PM Page 26
Hole-in-anchor
Hole-in-plug
ConcreteInsert
Suspension bolt (M10 or 3/8")
(field supply)
Table 3-1
Type
XH(W)2672R
(PNR-XH2442)
XH(W)3672R, XH(W)4272R
(PNR-XH3642)
Length
A
32-9/32
(820)
43-11/16
(1,110)
Unit: inch (mm)
B
22-9/32
(566)
33-11/16
(856)
)gninepo gnilieC( 23/9-23
nsion bolt pitch)epsuS( 61/31-92
A (Ceiling opening)
(Suspension bolt pitch)
Grille center
X
B
Drain hose
side
Refrigerant
tubingside
Table 3-2
Type
Length
XH(W)2672R
(PNR-XH2442)
XH(W)3672R, XH(W)4272R
(PNR-XH3632)
A
6-3/16
(157)
6-3/16
(157)
Refrigerant tubing joint (gas tube side)
Suspension lug
E
7-5/32
(182)
7-5/32
(182)
10-9/32
(261)
11-15/32
(291)
13-1/16
DEBC
12-1/8
(308)
(338)
Unit: inch (mm)
4-7/8
(124)
4-7/8
(124)
Drain connection (other side)
(VP25)
Refrigerant tubing joint
(liquid tube side)
D
61/3
C
B
A
1
27
X
3-3. Placing the Unit Inside the Ceiling
(1) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the
supplied full-scale installation diagram. (Fig. 3-4)
The size of the opening for the indoor unit can be
confirmed by attaching the full-scale installation
diagram beneath the unit. (Fig. 3-4)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position
for connection to the unit before placing the unit
inside the ceiling.
(2) The length of each suspension bolt must be
appropriate for a distance between the bottom of
the bolt and the bottom of the ceiling of 19/32 in.
or more as shown in Fig. 3-4.
(3) Thread the 2 hexagonal nuts (field supply) and
washers onto the 4 suspension bolts as shown in
Fig. 3-5.
Use 2 sets of nuts and washers (upper and lower),
so that the unit will not fall off the suspension lugs.
(4) Remove the protective cardboard used to protect
the fan parts during transport.
(5) Adjust the distance between the unit and surface
of the ceiling. (1-7/8 in.) (Fig. 3-4)
Fig. 3-4
Fig. 3-5
07-115 SSHP_II 5/7/07 3:59 PM Page 27
erom ro hcni 23/91
Nuts and washers
(Use above and below)
Full-scale installation diagram
(printed on a cardboard packing)
Double nuts
Suspension bolt
Upper
Lower
1-7/8 inch
Full-scale installation
diagram
Suspension lug
Notch
hc
n
i
8/7-
1
X
28
3-4. Installing the Drain Piping
(1) Prepare standard hard PVC pipe for the drain and
use the supplied drain hose and hose band to prevent water leaks.
The PVC pipe must be purchased separately. The
transparent part allows you to check drainage.
(Fig. 3-6)
(2) After checking the drainage, wrap the supplied
packing and drain pipe insulator around the pipe.
(Fig. 3-7)
Ensure the drain pipe has a downward gradient (1/100
or more) and that there are no water traps.
Tighten the hose clamps so
their locking nuts face upward.
(Fig. 3-6)
Do not install an air bleeder tube, as this may cause
water to spray from the drain tube outlet. (Fig. 3-8)
If it is necessary to increase the height of the drain
pipe, the section directly after the connection port
can be raised a maximum of 19-11/16 in. Do not
raise it any higher than 19-11/16 in., as this could
result in water leaks. (Fig. 3-9)
Do not install the pipe with an upward gradient from
the connection port. This will cause drain water to
flow backwards and leak when the unit is stopped.
(Fig. 3-10)
Do not apply force to the piping on the unit side
when connecting the drain pipe. The pipe should
not be allowed to hang unsupported from its
connection to the unit. Fasten the pipe to a wall,
frame, or other support as close to the unit as
possible. (Fig. 3-11)
Provide insulation for any drain pipe that is run
indoors.
Fig. 3-6
Fig. 3-7
Fig. 3-8
Fig. 3-9
Fig. 3-10
Fig. 3-11
07-115 SSHP_II 5/7/07 3:59 PM Page 28
Hard PVC pipe
(not supplied)
Drain hose
adapter
(supplied)
CAUTION
Transparent part for
checking drainage
Packing
(supplied)
Drain hose
(supplied)
Hose band
(supplied)
Drain insulator (supplied)
NOTE
Air bleeder
CAUTION
11-3/4 in. or less (as short as possible)
19-11/16 in. or less
Upward gradient
Support
pieces
29
X
3-5. Checking the Drainage
After wiring and piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch
and wipe up spilled water.
(1) Take off the tube cover and through the opening,
slowly pour about 43 oz. of water into the drain pan
to check drainage.
(2) Do Test Run to check the drainage after complet-
ing installation. When performing Test Run, be
sure to observe the Test Run procedure.
Refer to page 105.
(3) After drain checking is finished, return the Opera-
tion Selector switch to the RUN position (ON position ) and remount the tube cover.
Do not supply power to the
unit until the tubing and
wiring to the outdoor unit are
completed.
Be careful since the fan will
start turning when checking
the drainage.
To mount the tube cover, use
5/16" (4
××
8 mm) tapping
screws. Do not use long
screws as they may puncture
the drain pan and cause water
leakage.
Fig. 3-12
07-115 SSHP_II 5/7/07 3:59 PM Page 29
WARNING
CAUTION
WARNING
5/16"(4 × 8 mm)
tapping screw
Tube cover
Siphon
X
30
Ceiling Panel
3-6. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the
ceiling panel. (Figs. 3-13 and 3-14)
(a) Remove the 2 screws on the latch of the air-
intake grille. (Fig. 3-13)
(b) Press on the 2 latches of the air-intake grille
with your thumbs in the direction of the arrow
to open the grille. (Fig. 3-13)
(c) With the air-intake grille open about 45°,
remove the safety cord (hook on the grille
side). (Fig. 3-14)
(d) Pull the air-intake grille towards you to remove
it from the ceiling panel.
(2) Pull down the two panel catches on the body of
the indoor unit body. (Fig. 3-15)
Never touch or attempt to
move the air direction louver
by hand or you may damage
the unit. Instead, use the
remote control unit if you want
to change the direction or air
flow.
Fig. 3-13
Fig. 3-14
Fig. 3-15
07-115 SSHP_II 5/7/07 3:59 PM Page 30
Latch
CAUTION
Screw
Air-intake grille
Ceiling panel
Air filter
Safety cord
45°
Ceiling panel
Panel catch
Electrical
component box
Electrical
component box
Clamp
Ceiling panel wiring
connector
Unit body
Panel catch
(arrange facing downwards)
(2 locations)
Screws M5 with washer
(supplied)
Air filter
Air-intake grille
Loading...
+ 81 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.