Sanyo SAP – K92AH,SAP – C92AH,SAP – K122AH,SAP – C122AH Technical & Service Manual

General (50Hz)General (50Hz)

TECHNICAL & SERVICE MANUAL

SAP–K92AH + SAP–C92AH SAP–K122AH + SAP–C122AH
FILE NO.
REFERENCE NO. SM700566
Indoor Unit
SPLIT SYSTEM AIR CONDITIONER
SAP–K92AH
SAP–K122AH
SAP–C92AH
SAP–C122AH
Indoor Model No. Product Code No. Destination
SAP–K92AH–S 1 852 083 74
SAP–K122AH–S 1 852 083 75
Outdoor Model No. Product Code No. Destination
SAP–C92AH–S 1 852 084 15
SAP–C122AH–S 1 852 084 16
Australia Australia
i
Important! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
Carefully read this instruction booklet before beginning.
Follow each installation or repair step exactly as shown.
Observe all local, state, and national electrical codes.
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
Special Precautions
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
WARNING
CAUTION
WARNING
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the units weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak­free connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Turn the power off at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
CAUTION

Table of Contents

Page
1. OPERATING RANGE .............................................................................................................................. 1
2. SPECIFICATIONS
2-1. Unit Specifications.......................................................................................................................... 2
2-2. Major Component Specifications.................................................................................................... 4
2-3. Other Component Specifications.................................................................................................... 8
3. DIMENSIONAL DATA.............................................................................................................................. 9
4. REFRIGERANT FLOW DIAGRAM ......................................................................................................... 11
5. PERFORMANCE DATA
5-1. Performance charts ....................................................................................................................... 12
5-2. Air Throw Distance Chart .............................................................................................................. 14
5-3. Cooling Capacity ........................................................................................................................... 16
5-4. Heating Capacity ........................................................................................................................... 18
6. ELECTRICAL DATA
6-1. Electrical Characteristics................................................................................................................ 19
6-2. Electric Wiring Diagram.................................................................................................................. 21
7. INSTALLATION INSTRUCTIONS
7-1. Installation Site Selection ............................................................................................................... 23
7-2. Remote Control Unit Installation Position....................................................................................... 25
7-3. Recommended Wire Length and Diameter ................................................................................... 26
8. FUNCTION
8-1. Room Temperature Control ........................................................................................................... 27
8-2. Dry Operation ................................................................................................................................ 29
8-3. Automatic Switching between Cooling and Heating ...................................................................... 29
8-4. Freeze Prevention ......................................................................................................................... 30
8-5. Compressor overcurrent protection ............................................................................................... 30
8-6. Overload Prevention ...................................................................................................................... 31
8-7. Cold Draft Prevention .................................................................................................................... 32
8-8. Defrosting Operation ..................................................................................................................... 33
8-9. Outdoor Fan Speed Control .......................................................................................................... 34
9. TROUBLESHOOTING
9-1. Check before and after troubleshooting ........................................................................................ 35
9-2. Air conditioner does not operate .................................................................................................... 36
9-3. Some part of air conditioner does not operate ..............................................................................40
9-4. Air conditioner operates, but abnormalities are observed ............................................................. 42
9-5. If a sensor is defective ................................................................................................................... 44
10. CHECKING ELECTRICAL COMPONENTS
10-1. Measurement of Insulation Resistance .......................................................................................... 45
10-2. Checking Continuity of Fuse on PCB Ass'y.................................................................................... 46
10-3. Checking Motor Capacitor ............................................................................................................. 46
11. MAINTENANCE
11-1. Changing Address of Remote Control Unit in Indoor Unit ............................................................. 47
.................................................................................................................................................. 48
APPENDIX
ii
1

1. OPERATING RANGE

Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 32°C D.B. / 23°C W.B. 43°C D.B.
Minimum 19°C D.B. / 14°C W.B. 19°C D.B.
Heating
Maximum 27°C D.B. 24°C D.B. / 18°C W.B.
Minimum 16°C D.B. –8°C D.B. / –9°C W.B.
2

2. SPECIFICATIONS

2-1. Unit Specifications

Indoor Unit SAP–K92AH Outdoor Unit SAP–C92AH
Power Source 220–240V Single phase 50Hz Voltage rating 220/230/240 V Performance Cooling Heating
Capacity kW 2.55 / 2.55 / 2.50 3.20 / 3.25 / 3.20
BTU/h 8,700 / 8,700 / 8,500 10,900 / 11,100 / 10,900
Air circulation (High)
m3/h
430 430
Moisture removal (High) Liters/h 0.85
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 4.3 / 4.3 / 4.4 4.3 / 4.3 / 4.4 Power input W 930 / 950 / 1,020 920 / 940 / 1,020 Power factor % 98 / 96 / 97 97 / 95 / 97 C.O.P . W/W 2.74 / 2.68 / 2.45 3.48 / 3.46 / 3.14 Compressor locked rotor amperes A 22 / 23 / 24 22 / 23 / 24
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hours ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / 1(Hi) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 880 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 39 / 37 / 33 39 / 37 / 33
Outdoor : Hi dB-A 44 44 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 9.52(3/8) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Dimensions & Weight
Indoor Unit
Outdoor Unit
Unit dimensions H e i g h t mm 250 530
Widt h mm 790 680
Depth mm 174 225 Package dimensions H eight mm 242 580
Widt h mm 850 812
Depth mm 312 315 Weight Net kg 7.0 31.0
Shipping kg 10.0 33.0 Shipping volume
m
3
0.06 0.15
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
3
Indoor Unit SAP–K122AH Outdoor Unit SAP–C122AH
Power Source 220–240V Single phase 50Hz Voltage rating 220/230/240 V Performance Cooling Heating
Capacity kW 3.20 / 3.20 / 3.20 3.70 / 3.75 / 3.75
BTU/h 10,900 / 10,900 / 10,900 12,600 / 12,800 / 12,800
Air circulation (High)
m3/h
470 460
Moisture removal (High) Liters/h 1.45
Electrical Rating Cooling Heating
Available voltage range V 198 ~ 264 Running amperes A 5.8 / 5.8 / 6.1 5.9 / 5.9 / 6.0 Power input W 1,220 / 1,240 / 1,350 1,230 / 1,260 / 1,320 Power factor % 96 / 93 / 92 95 / 93 / 92 C.O.P . W/W 2.62 / 2.58 / 2.37 3.01 / 2.98 / 2.84 Compressor locked rotor amperes A 32 / 33 / 35 32 / 33 / 35
Features
Controls / Temperature control Microprocessor / I.C. thermostat Control unit Wireless remote control unit Timer 1-hour OFF / 12-hours ON or OFF Fan speeds Indoor / Outdoor 3 and Auto / Auto (Hi,Lo) Airflow direction (Indoor) Horizontal Manual
Vertical Auto Air filter Washable, Anti-Mold Compressor Rotary (Hermetic) Refrigerant / Amount charged at shipment g R22 / 1,010 Refrigerant control Capillary tube Operation sound Indoor : Hi / Me / Lo dB-A 40 / 38 / 36 39 / 38 / 36
Outdoor : Hi dB-A 45 46 Refrigerant tubing connections Flare type Max. allowable tubing length at shipment m 7.5 Refrigerant Narrow tube mm (in.) 6.35(1/4) tube diameter Wide tube mm (in.) 12.7(1/2) Refrigerant tube kit / Accessories Optional / Hanging wall bracket
Dimensions & Weight
Indoor Unit
Outdoor Unit
Unit dimensions H e i g h t mm 250 530
Widt h mm 790 680
Depth mm 174 225 Package dimensions H eight mm 242 580
Widt h mm 850 812
Depth mm 312 315 Weight Net kg 7.0 34.0
Shipping kg 10.0 36.0 Shipping volume
m
3
0.06 0.15
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Remarks:
Rating conditions are: Cooling : Indoor air temperature 27°C D.B. / 19°C W.B. Outdoor air temperature 35°C D.B. / 24°C W.B. Heating : Indoor air temperature 20°C D.B. Outdoor air temperature 7°C D.B. / 6°C W.B.
4

2-2. Major Component Specifications

2-2-1. Indoor Unit
Indoor Unit SAP–K92AH
Controller PCB
Part No. POW-K2AH Controls Microprocessor C o nt r ol circuit fu se 250 V 3.15 A
Remote Control Unit RCS-3HS4E-G
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø97 / L578 Fan motor model ... Q'ty IBH-884-020 ... 1 No. of poles ... 50Hz rpm (High) 2 ... 1,280 Nominal output W 20 Coil resistance (Ambient temp. 20°C) WHT-BRN : 201
WHT-VLT : 261
Safety devices Type Thermal fuse
Operating temp. Open °C 130
Close
Run capacitor (on the PCB Ass'y) µF 1.5
VAC 440
Flap Motor
Type Stepping motor Model MP24GA3 Rating DC 12 V Coil resistance (Ambient temp. 25°C) A pair of each terminal : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area
m
2
0.110
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
5
Indoor Unit SAP–K122AH
Controller PCB
Part No. POW-K2AH Controls Microprocessor C o nt r ol circuit fu se 250 V 3.15 A
Remote Control Unit RCS-3HS4E-G
Fan & Fan Motor
Type Cross-flow Q'ty ... Dia. and length mm 1 ... ø97 / L578 Fan motor model ... Q'ty IBH-884-020 ... 1 No. of poles ... 50Hz rpm (High) 2 ... 1,340 Nominal output W 20 Coil resistance (Ambient temp. 20°C) WHT-BRN : 201
WHT-VLT : 261
Safety devices Type Thermal fuse
Operating temp. Open °C 130
Close
Run capacitor (on the PCB Ass'y) µF 1.5
VAC 440
Flap Motor
Type Stepping motor Model MP24GA3 Rating DC 12 V Coil resistance (Ambient temp. 25°C) A pair of each terminal : 380 ± 7%
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.4 Face area
m
2
0.110
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
6
2-2-2. Outdoor Unit
Outdoor Unit SAP–C92AH
Controller PCB
Compressor
Type Rotary (Hermetic) Compressor model C-R92H5W 80692945-S Nominal output W 900 Compressor oil ... Amount cc 4GSD-T or SAY-56T ... 550 Coil resistance (Ambient temp. 25°C) C–R : 3.07
C–S : 7.97
Safety devices Type External(OLR A) External(OLR T)
Overload relay MRA99057-9201 CS-7C115 Operating temp. Open °C 145±5 115±3
Clos e °C 69±11 95±5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 18A
Run capacitor µF 22.5
VAC 400
Crank case heater
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty UE6-21AH5PD-S ... 1 No. of poles ... rpm (230 V, High) 6 ... 760 Nominal output W 20 Coil resistance (Ambient temp. 20°C) WHT-BRN : 356.4
WHT-PNK : 439.5
Safety devices Type Thermal fuse
Operating temp. Open °C 145 ± 2
Close °C
Run capacitor µF 1.5
VAC 440
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 1 Fin pitch mm 1.2 Face area
m
2
0.333
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
7
Outdoor Unit SAP–C122AH
Controller PCB
Compressor
Type Rotary (Hermetic) Compressor model C-R112H5X 80616745-S Nominal output W 1,100 Compressor oil ... Amount cc 4GSD-T or SAY-56T ... 550 Coil resistance (Ambient temp. 25°C) C–R : 1.962
C–S : 5.38
Safety devices Type External(OLR A) External(OLR T)
Overload relay MRA98596-9201 CS-7C115 Operating temp. Open °C 145±5 115±3
Clos e °C 69±11 95±5
Operating amp.(Ambient temp. 25°C) Trip in 6 to 16 sec. at 21A
Run capacitor µF 25.0
VAC 400
Crank case heater
Fan & Fan Motor
Type Propeller Q'ty ... Dia. 1 ... ø370 Fan motor model ... Q'ty UE6S-21AC5P-S ... 1 No. of poles ... rpm (230 V, High) 6 ... 750 Nominal output W 20 Coil resistance (Ambient temp. 20°C) BRN-WHT : 341.2
WHT-YEL : 212.7
YEL-PNK : 190.0
Safety devices Type Thermal fuse
Operating temp. Open °C 145 ± 2
Close °C
Run capacitor µF 1.5
VAC 440
Heat Exch. Coil
Coil Aluminum plate fin / Copper tube Rows 2 Fin pitch mm 1.2 Face area
m
2
0.329
External Finish Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.

2-3. Other Component Specifications

8
This power relay is provided to protect the outdoor fan to operate in Low fan speed during heating mode. In heating operation, the outdoor fan should always run in High fan speed to prevent the unit from freezing.
PTC Thermistor (TH) ZPROYCE101A500
Rating 400V, 115A
4-way Valve (20S) LB81012 (Coil), VK1100B (Valve)
Coil rating AC 220/240V, 50/60Hz, 6W Coil resistance (at 20°C) 3,030 ± 7%
NOTE
Power Relay (for outdoor fan motor) HH62S AC220/240V
Coil rating AC 220/240V Contact rating AC 250V, 10A
Thermostat (Fan Speed Control 23S) MQT5S
Switching temp. °C
high LOW 28.5°C ± 1.5 low HIGH 31.5°C ±2
Contact rating AC 220V, 3A
Outdoor Unit SAP–C122AH
4-way Valve (20S) LB81012 (Coil), VK1100B (Valve)
Coil rating AC 220/240V, 50/60Hz, 6W Coil resistance (at 20°C) 3,030 ± 7%
Outdoor Unit SAP–C92AH
Thermistor (Room sensor) DTN-TKS128B
Resistance k 25°C 5.0 ± 3%
Thermistor (Coil sensor) DTN-TKS131B
Resistance k 0°C 15.0 ± 2%
Transformer (TR) ATR-I55
Rating Primary AC 230V, 50/60Hz
Secondary 13.7V, 0.4A Capacity 5.48VA
Coil resistance (at 25°C) Primary (WHT – WHT): 307 ± 10%
Secondary (BRN – BRN): 1.8 ± 10%
Thermal cut-off temp. 150°C
Indoor Unit SAP–K92AH
SAP–K122AH
9

3. DIMENSIONAL DATA

Indoor Unit SAP–K92AH
SAP–K122AH
790
250
174 (3)
Narrow tube ø6.35 (1/4")
Drain hose ø18
58.5
132
41.0
41.0
Center of tubing hole (2 places)
Wide tube ø9.52 (3/8") Wide tube ø12.7 (1/2")
K92 K122
Remote control unit
22.2
14
59.7
64.6
1401037.6
69.5
Unit : mm
11

4. REFRIGERANT FLOW DIAGRAM

Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the wide and narrow tubes of this air conditioner become cold. To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a proper insulation material. The thickness of the insulation should be a min. 8 mm.
After a tube has been insulated, never try to bend it into a narrow curve because it can cause the tube to break or crack.
IMPORTANT
CAUTION
Wide tube
Thickness: Min. 8 mm
Insulation
Narrow tube
Thickness: Min. 8 mm
Indoor Unit SAP–K92AH Outdoor Unit SAP–C92AH
Compressor
4-way valve
Accumulator
Wide tube service valve
Wide tube
O.D. ø9.52 mm (3/8 ")
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Heat exchanger
Heat exchanger
Muffler
Cooling cycle
Heating cycle
Strainer
Indoor unit Outdoor unit
Capillary tube
(for heating)
Check valve
Capillary tubes
(both for heating
and cooling)
Indoor Unit SAP–K122AH Outdoor Unit SAP–C122AH
Compressor
4-way valve
Accumulator
Wide tube service valve
Wide tube
O.D. ø12.7 mm (1/2 ")
Narrow tube service valve
Narrow tube
O.D. ø6.35 mm (1/4")
Heat exchanger
Heat exchanger
Muffler
Cooling cycle
Heating cycle
Indoor unit Outdoor unit
Capillary tubes
(both for heating and cooling)
Strainer
Muffler

5. PERFORMANCE DATA

5-1. Performance charts

12
Indoor inlet air
D.B. temp. (°C)
Cooling Characteristics Heating Characteristics
9 8 7 6 5 4 3 2
1
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
8 7 6 5 4 3 2 1
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
25
9
27 20 15
27 20 15
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)
Outdoor inlet air D.B. temp. (°C)
25 30 35 40 45 50
Low pressure at wide tube serveice valve MPa (kgf/cm
2
G)
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
1.47 (14)
Outdoor inlet air D.B. temp. (
°C)
–5 0 5 10 15 20 25
High pressure at wide tube serveice valve MPa (kgf/cm
2
G)
3.24 (32)
2.95 (30)
2.85 (28)
2.65 (26)
2.46 (24)
2.26 (22)
2.06 (20)
1.87 (18)
1.67 (16)
1.47 (14)
1.28 (12)
1.08 (10)
32 27
21
32 27
21
● ...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B./19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B./24°C W.B. Outdoor air temperature 7°C D.B./6°C W.B.
NOTE
Indoor Unit SAP–K92AH Outdoor Unit SAP–C92AH
13
Indoor inlet air
D.B. temp. (°C)
Cooling Characteristics Heating Characteristics
11 10
9 8 7 6 5 4
3
25 30 35 40 45 50
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
10
9 8 7 6 5 4 3
–5 0 5 10 15 20
Outdoor inlet air D.B. temp. (°C)
Operating current (A)
25
11
27 20 15
27 20 15
Indoor inlet air
D.B. temp. (°C)
HighLow
Outdoor fan speed
HighLow
Outdoor fan speed
Indoor inlet air
D.B. temp. (°C)
Indoor inlet air
D.B. temp. (°C)
Outdoor inlet air D.B. temp. (°C)
–5 0 5 10 15 20 25
High pressure at wide tube serveice valve MPa (kgf/cm
2
G)
3.24 (32)
2.95 (30)
2.85 (28)
2.65 (26)
2.46 (24)
2.26 (22)
2.06 (20)
1.87 (18)
1.67 (16)
1.47 (14)
1.28 (12)
1.08 (10)
Outdoor inlet air D.B. temp. (
°C)
25 30 35 40 45 50
Low pressure at wide tube serveice valve MPa (kgf/cm
2
G)
1.38 (13)
1.28 (12)
1.18 (11)
1.08 (10)
0.98 ( 9 )
0.89 ( 8 )
0.79 ( 7 )
0.69 ( 6 )
0.59 ( 5 )
0.49 ( 4 )
0.39 ( 3 )
1.47 (14)
32 27 21
32 27 21
● ...... Points of Rating condition
Black dots in above charts indicate the following rating conditions.
Cooling: Indoor air temperature 27°C D.B./19°C W.B. Heating: Indoor air temperature 20°C D.B.
Outdoor air temperature 35°C D.B./24°C W.B. Outdoor air temperature 7°C D.B./6°C W.B.
NOTE
Indoor Unit SAP–K122AH Outdoor Unit SAP–C122AH