Sanyo FPW-EXA025 Service Manual

Page 1
FPW
-
Multi
-
Deck Self Service
F
PW
-
EXA0
85
Multi-Deck Self Service Fresh Meat Merchandiser
Multi-Deck Self Service
Fresh Meat Merchandiser
Fresh Meat Merchandiser
INSTALLATION AND SERVICE MANUAL
REMOTE TYPE DISPLAY CASE
FPW-EXA085 FPW-EXA025
FPW-EXA025
FPW-EXA025
Page 2
T
ABLE OF CONTENTS
1 SPECIFICATIONS .................................................................................................................................. 4
2
DIMENSIONS........................................................................................................................................ 5
2.1 E
2.2 F
XTERNAL DIMENSIONS
OOTPRINT
........................................................................................................................................ 5
...................................................................................................................... 5
3 UNLOADING AND CARPENTRY PROCEDURES ................................................................................. 6
3.1 NSF C
3.2 L
3.3 S
3.4 U
3.5 A
3.6 C
3.7 J
3.7.1 Applying gasket (for connecting cases or installing side panels).
3.7.2 Connecting cases.
3.8
I
ERTIFICATION
OCATION
HIPPING DAMAGE
NLOADING INSTRUCTIONS
LIGNING CASES
ASE LEVELING
OINING INSTRUCTIONS
......................................................................................................................................... 6
........................................................................................................................... 6
............................................................................................................................ 6
................................................................................................................................ 7
................................................................................................................................. 7
...................................................................................................................... 8
.......................................................................................................................... 9
NSTALLING PATCH ENDS
& P
RECAUTIONS
........................................................................................ 6
........................................................... 8
................................................................................................................... 10
3.9 I
3.10 I
3.11 I
NSTALLING PRICE TAG MOLDING
NSTALLING KICKPLATE
NSTALLING HANDRAIL AND BUMPER
..................................................................................................................... 11
....................................................................................................... 11
.................................................................................................. 12
4 REFRIGERATION, PLUMBING & ELECTRICAL PROCEDURES......................................................... 13
4.1 P
4.2 E
4.3 E
4.4 W
IPING (PLUMBING
LECTRICAL DATA
LECTRICAL
IRING
4.4.1
Wiring Color Code...................................................................................................................... 14
, R
EFRIGERATION
) ................................................................................................... 13
.............................................................................................................................. 14
– G
UIDELINES
& P
RECAUTIONS
....................................................................................... 14
........................................................................................................................................... 14
4.4.2 Wiring Diagram ...................................................................................................................... 15
5 OPERATION ........................................................................................................................................ 16
5.1 L
5.2 I
OAD LIMITS
NSTALLING
................................................................................................................................... 16
FDA/NSF T
HERMOMETER
.............................................................................................. 17
2
Page 3
6 CARE AND CLEANING GUIDELINES ................................................................................................. 18
6.1 E
6.2 A
6.3 S
6.4 S
6.5 M
6.6
XTERIOR PANELS (DAILY CLEANING
CRYLIC SHELF GUARD
HELF SURFACES (DAILY CLEANING
HELF ASSEMBLIES (WEEKLY CLEANING
IRRORS
H
ONEYCOMB ASSEMBLIES (AT LEAST EVERY 3 MONTHS
, F
LUORESCENT LAMPS
& P
RICE TAG MOLDING (DAILY CLEANING
)................................................................................................. 18
).................................................................................................. 19
) ........................................................................................... 19
, D
RAIN TRAP (MONTHLY CLEANING
) ...................................................... 18
) ................................................. 20
) ..................................................................... 20
7 SERVICE .............................................................................................................................................. 21
7.1 R
7.2 R
7.3 R
EPLACING FAN MOTORS AND BLADES
EPLACING ELECTRONIC BALLASTS
EPLACING FLUORESCENT LAMPS
................................................................................................... 24
..................................................................................................... 25
.............................................................................................. 21
3
Page 4
Model Name
FPW
-
EXA085
FPW
-
EXA025
-
404A
R-
404A
1182 BTU/h/ft.
2771W)
Dimensions
1 Specifications
General
Application Medium Temperature (Meat) Medium Temperature (Meat) Refrigerant Cooling Capacity Discharge Air 31°F (-0.8°C) 31°F (-0.8°C) Evaporator Temperature 24°F (-4.2°C) 24°F (-4.2°C)
Defrost (electric)
Frequency (hr) 4 4 Temp Term (°F) 50 50 Failsafe (min) 30 30
Electrical
Anti-condensation Heater
Standard
High Efficiency
Exterior
Interior
Total
Fan Motor
Illumination
1-phase 120V
1 row of lamps
2 rows of lamps
Top panel
Shelves
Total
Medium Temperature Medium Temperature
(W) (A)
N/A N/A
195 2.28
84 1.29
N/A N/A
N/A N/A
55 0.47
3-shelf
4-shelf
3-shelf
4-shelf
165 1.41
220 1.88
220 1.88
275 2.35
1 lamp
2 lamps
Top panel
Shelves
Total
1182 BTU/h/ft. (4157W)
1-phase 120V
(W) (A)
N/A N/A
285 3.42
126 1.93
N/A N/A
N/A N/A
83 0.71
3-shelf
4-shelf
3-shelf
4-shelf
248 2.12
330 2.82
331 2.83
413 3.53
Components
Anti-condensation heater N/A N/A
Fan Motor
Fan Blade Pitch Illumination FO32/XP (T8) (Output 32W) FO32/XP (T8) (Output 32W) Pipe Diameter Liquid ” Suction ¾” Liquid ” Suction ¾” Refrigerant Type R-404A R-404A
Measurements
Outer Dimensions 77” (H) × 42 ½” (W) × 96 ” (L) 77” (H) × 42 ½” (W) × 144 ” (L) Open Space 53 53 ” Display Area 56.0 sq.ft. 84.1 sq.ft. Effective Capacity 58.9 cu.ft. 88.4 cu.ft.
Weight 661 lbs 992 lbs Waste Outlet Dimensions 1 ½” 1 ½”
Standard Ambient Conditions : Indoor temperature 75°F (24°C), relative humidity 55%, wind speed under 39.4 fpm.
All specifications are based upon temperature, humidity, and wind speed values equal to or less than Standard Ambient Conditions.
Products described in this manual are designed for indoor use only. Products should not be exposed to direct sunlight.
Fan motors are available in standard-type (AC fan motors) or high-efficiency type (DC fan motors).
Standard
High Efficiency
3-shelf 6 shelves (18” depth) 9 shelves (18” depth) Shelf 4-shelf 2 shelves (16” depth), 6 shelves (18” depth) 3 shelves (16” depth), 9 shelves (18” depth)
SPFBE141 x 3 SPFBE141 x 3 , SPFBE91T x 2
SSC2B12CNHBV1 x 3 SSC2B12CNHBV1 x 3 , SSC2B12BVHBV1 x 2
Inside128×2 Outside128 x 1 Inside128 x 3 Outside117 x 2
4
Page 5
Electrical Field Connection
* Dimensions given in inches and millimeters (mm in parentheses).
2 Dimensions
2.1 External Dimensions
2.2 Footprint
Waste Outlet ② ③ Refrigeration Outlet
Page 6
3 Unloading and Carpentry Procedures
3.1 NSF Certification
The merchandisers described in this manual are built to meet the requirements of American National Standard/NSF International Standard 7. Each merchandiser bears a nameplate identifying the type of application for which it was certified:
Type I display refrigerator / freezer: Intended for use in an area where the environmental conditions are controlled and maintained so that the ambient temperature typically does not exceed 75°F.
3.2 Location
As noted above, the merchandisers described in this manual are design for the display of products in interior spaces with climate control, with ambient conditions typically maintained below 75°F and 55% relative humidity. Proper merchandiser performance cannot be guaranteed when ambient temperature and/or humidity exceeds this level.
Merchandisers should not be exposed to direct sunlight or other sources of heat.
Merchandisers should not be exposed to strong air currents, as these may disrupt the dual air curtains used to maintain proper temperature inside the merchandiser display area.
3.3 Shipping Damage
All equipment should be examined for shipping damage prior to and during offloading. All equipment goes through outgoing inspection upon leaving our warehouse, and the carrier assumes responsibility for the safe arrival of our merchandisers.
APPARENT DAMAGE: Any obvious loss or damage should be noted immediately at the time of receipt on the freight bill or express receipt and signed by the carrier’s agent. Failure to do so may lead to rejection of the claim by the carrier.
CONCEALED DAMAGE: If damage that is not apparent during unloading is found after unpacking, retain all packing materials and submit a written request to the carrier for inspection within 15 days.
LOST ITEMS: Any claims related to lost or missing items must be made to SANYO Commercial Solutions Company within 48 hours of receipt of equipment.
3.4 Unloading Instructions & Precautions
WARNING
Cases are heavy and bulky, and require at least two people for unloading, moving, and installation.
Do not remove the wooden beam from the bottom front edge of each case until the cases have been moved into place in the store lineup.
Do not walk on the top of the merchandisers. Walking on the top of the merchandiser may lead to serious injury and/or damage to the merchandiser. Do not place other heavy loads on the top of the merchandiser.
Recommended Practices for Unloading Merchandisers:
1. Use a J-bar (Johnson bar) to lift one end of the merchandiser.
2. Insert one or more dollies under the base leg.
3. Lift the other side with the J-bar.
4. (Optional) Insert one or more dollies.
5. Move merchandiser out of container.
6. Use dollies on both ends of the merchandiser to move to lineup location after unloading from container.
6
Page 7
3.5 Aligning Cases
WARNING
Cases are heavy and bulky, and require at least two people for unloading, moving, and installation.
Do not walk on the top of the merchandisers. Walking on the top of the merchandiser may lead to serious injury and/or damage to the merchandiser. Do not place other heavy loads on the top of the merchandiser.
1. Review layout drawings for spaces where merchandisers are to be installed.
2. Based on the layout drawings and the merchandiser footprint drawings, mark the floor to indicate the exact locations of the base legs (back edge and front edge) on each merchandiser. Multiple merchandisers should be aligned based upon the position of the base legs.
3. Snap chalk lines for the front and rear positions of the legs on each row of merchandisers.
4. Mark the location showing the outside edge of each base leg on each merchandiser.
3.6 Case Leveling
Merchandisers must be installed level in order to ensure proper performance and drainage.
1. For each lineup of cases to be joined, use a level (preferably a laser level) to find the highest point on the front and rear chalk lines marked in step 3 above (during Case Alignment).
2. Determine which of the two points marked on the line is higher. This is the highest point in the case lineup.
3. Estimate the number of shims needed for the four corners of each case position, in order to bring all positions to the same height as the highest point found in step 2.
4. For each row, place the first merchandiser case where it will sit over the highest point in the lineup. Ensure that the case is level, using shims as needed.
NOTE: Each base leg should rest on solid supports. Insert shims as needed if there are any gaps between the floor and each base leg.
5. Continue placing cases in the lineup, working outward to both sides from the position of the first case placed. Use shims to ensure that all cases in the lineup are level.
7
Page 8
3.7 Joining Instructions
3.7.1 Applying gasket (for connecting cases or installing side panels).
Make sure that all merchandisers are resting level.
Make sure that all required parts for joining are present (gasket, bolts, joint covers, nuts, etc.).
Remove shelves, rear interior panels, wire racks, deck pans, and front air grilles from the far right and left ends of each case being joined.
Place gasket along the areas shown in bold in the drawing at right. When connecting two cases, apply gasket to one case only.
Perimeter gasket is required by NSF.
Do not stretch or twist gasket when applying.
Do not leave gaps. Always overlap gasket rather than leaving gaps.
Gasket ends that are open must be sealed off by applying silicone at the installation site.
Insufficient or improper sealing may lead to insufficient cooling and condensation.
Gasket
Important for preventing condensation.
8
Page 9
Note : To connect exterior top, insert exterior top joint
Silicon
e
seal
Note: Gasket ends that are open must
be sealed off by applying silicone
3.7.2 Connecting cases.
Apply gasket as described above.
Connect cases by using the attached bolts, joint covers, and nuts.
Gasket
Note: Connection point must
at the installation site.
be silicone sealed.
from rear, and fasten it with screws as shown.
9
Page 10
3.8 Installing patch ends
3
1. Apply gasket to case body (per previous instructions).
2. If present, remove protective film from inside wall of patch end. Fix washers to outside of patch end with M8 bolts, and install the patch end on the merchandiser.
3. Fix washers and nuts (item 3 in above drawing) to the ends of the M8 bolts inside the merchandiser in the two locations indicated.
4. Place insulation over M8 bolt heads outside the patch end.
5. Cover the M8 bolt heads and insulation outside the patch end with patch end caps.
6. Cover ends of M8 bolts inside the merchandiser with caps (item 6 in above drawing).
NOTE: NSF requires that any bolt or screw in the product area be
capped or cut off. No exposed threads are allowed in the splash zone. After side panel is attached and bolts have been tightened, use the provided caps to cover threads completely for all exposed bolts.
7. Attach side cover (item 7 in above drawing)
2
Gasket
M8 Bolts with washers
Washers & nuts inside patch end
Insulation
Patch End Cap
Caps for M8 bolts listed in item 3 above
Side Cover
Before installing left patch end, install cage nut in the frame at the case side (at position A in the above drawing).
Manually insert one tab of cage nut in open corner, and insert the other tab with a screwdriver.
Flathead
screwdriver
Apply silicone sealant
Corner hole
10
Page 11
3.9 Installing price tag molding
1. Remove protective covering from acrylic guard.
2. Attach price tag molding to front of shelf by sliding along the shelf’s front edge. Hold in place while preparing acrylic guard.
3. Insert acrylic guard into shelf from above.
Note : Price tag mold can fall off shelf unless acrylic guard is inserted fully.
3.10 Installing kickplate
11
Page 12
3.11 Installing handrail and bumper
Handrail
Handrail
Attaching the Bumper
1. Attach Maintenance Bumper (length 39-3/8 inches) to bumper brackets over the electrical connection box (“raceway”) on each merchandiser. The raceway is located on the right end of each merchandiser.
2. Attach Full-Length Bumpers between Maintenance Bumpers on separate merchandisers, and also between Maintenance Bumpers and patch ends.
* Cut Full-Length Bumpers to size on-site. Cut to correct size so that no gaps remain between pieces.
Attaching the Handrail
1. Starting at one end of merchandiser line-up, attach pieces of Handrail to handrail retainer, butting the pieces end-to-end without gaps.
2. When you reach the final piece of Handrail to be installed between the last merchandiser in the line-up and the patch end, cut that piece to length so there are no gaps between handrails or between handrails and patch ends.
12
Page 13
4 Refrigeration, Plumbing & Electrical Procedures
4.1 Piping (Plumbing, Refrigeration)
U-trap installation
Install U-trap referring to the drawing below.
Sealing the refrigerant pipe opening
Seal pipe completely.
Insufficient sealing may cause the following problems:
Insufficient cooling
Excessive frost
Icing over
Condensation on the bottom of case.
Part Name Part Number
Drain Screen 8FL-2-1620-005-00
O-ring 8FL-2-6460-001-00
Drain Trap 8FL-2-6580-002-00
13
Page 14
4.2 Electrical Data
Please refer to Specifications section and nameplate attached to merchandiser for electrical information.
4.3 Electrical – Guidelines & Precautions
All wiring and electrical field work must comply with the National Electrical Code (“NEC”) and other applicable local codes. All electrical connections must be made inside the raceway area.
4.4 Wiring
4.4.1 Wiring Color Code
14
Page 15
4.4.2 Wiring Diagram
15
Page 16
A minimum spacing of 2 inches must be maintained
between the top of merchandise and the bottom of
Loading merchandise beyond the maximum level will
result in merchandise touching or entering the cold
5 Operation
5.1 Load Limits
In order to maintain proper temperature and unit performance, the dual air curtains in each merchandiser must remain unobstructed:
Do not stock shelves beyond the marked load limits.
Do not block honeycombs or return air grilles.
Do not block airflow in any other way (with signs, tools, packages, etc.)
Failure to follow these precautions will lead to insufficient temperature control, spoilage of stored merchandise, and excessive frost.
the shelf above it.
air curtain.
16
Page 17
5.2 Installing FDA/NSF Thermometer
Magnet
Suggested locations for the thermometer required by NSF/ANSI 7 and the FDA Food Code are
indicated above. It is the responsibility of the purchaser/end user of this product to determine the
location within the food storage area that best meets these code requirements .
17
Page 18
6 Care and Cleaning Guidelines
In order to keep merchandisers sanitary and in good working order, we recommend thorough periodic cleaning as follows:
6.1 Exterior Panels (Daily Cleaning)
a. Exterior panels should be cleaned with water only. Wet a soft cloth and wring it out to wipe down panels.
b. If required, you may use a mild detergent and warm water to remove stains. You should follow by wiping down with
water only in order to prevent discoloration.
c. Take particular care to clean areas that may be exposed to salt or saline solutions.
d. DO NOT use scrapers, blades or other sharp objects to remove adhesive, as you may damage panels. You may use
rubbing alcohol to remove adhesive if water and mild detergents alone are insufficient.
6.2 Acrylic Shelf Guard & Price Tag Molding (Daily Cleaning)
a. Grasp shelf guard firmly and pull up. Keep your eye on the price tag molding, as it may come loose.
b. Carefully wipe the shelf guard using a soft, damp cloth. You may use a mild detergent, but should complete cleaning
by wiping down each shelf guard with water only.
c. You may remove the price tag molding easily when the shelf guards are removed.
d. Wipe down the entire price tag molding, taking care to remove food particles, drips, garbage, dust and any other
foreign substances.
18
Page 19
6.3 Shelf Surfaces (Daily Cleaning)
a. Clean the entire shelf surface, preferably with water only. If required, you may use a mild detergent and warm water
to remove stains. You should follow by wiping down with water only in order to prevent discoloration.
b. Make sure to clean under mats or objects resting on the shelf surfaces.
6.4 Shelf Assemblies (Weekly Cleaning)
a. Start shelf assembly cleaning by turning all fluorescent
lamps off.
b. Remove all shelf guards and price tag molding (see
Section 6.2 above).
c. Disconnect all fluorescent lamp plugs, pulling by the
terminals. DO NOT PULL ON CORDS.
d. Remove shelves (see drawings below).
e. Thoroughly check the underside of each shelf for drips or
other foreign substances and clean.
f. Clean the entire shelf surface, preferably with water only.
If required, you may use a mild detergent and warm water to remove stains. You should follow by wiping down with water only in order to prevent discoloration.
g. Reset shelves by following the steps above in reverse
order.
WARNING: MAKE SURE ALL FLUORESCENT LAMP PLUGS ARE PLACED FIRMLY IN THEIR SOCKETS.
19
Page 20
6.5 Mirrors, Fluorescent Lamps, Drain Trap (Monthly Cleaning)
When cleaning mirrors and fluorescent lamps,
1. Turn off the fluorescent lamps prior to cleaning.
2. DO NOT place your weight on the shelves. If mirrors or lamps are difficult to reach, use a stepladder or other means to reach them.
Clean mirrors with a mild detergent and water, then dry with a non-abrasive cloth.
Wipe fluorescent lamps with a soft, dry cloth. If required you may use a water-dampened cloth that has been squeezed well to remove most moisture. At this time you may also wish to check for lamps needing replacing.
Please make sure to check and clean the drain trap at least once a month. Remove any material that has gathered in the drain trap and dispose of it. Clean the drain trap and put it back in its original position.
6.6 Honeycomb Assemblies (At least every 3 months)
Because honeycomb assemblies may deform under pressure, DO NOT use vacuum cleaners to clean them.
a. When merchandise is in place under the honeycomb assembles, first cover the
merchandise with a cloth or other material to keep dust from falling.
b. Remove honeycomb assemblies by pulling down on the wire clips attached to the
assemblies.
c. Rinse honeycombs in running water in order
to flush out dust, etc. Dust is best removed by spraying/flushing from the cleaner side toward the dirtier side.
d. After thoroughly shaking and drying rinsed
honeycomb assemblies, replace them in their original positions in the merchandisers.
20
Page 21
7 Service
7.1 Replacing Fan Motors and Blades
To replace the fan motors:
Remove the outer air curtain duct cover and socket covers. Unplug the fan motor harness and push through hole in plenum. Detach fan motor mounting bracket from plenum and pull up to remove.
21
Page 22
Fan Motor Assembly Part Codes (Standard-Type Fan Motors)
Cap nut
-a Vibration-damping washer
Fan blade
-b Vibration-damping
washer
-c Fan motor
Motor mount
Bracket
For models with standard-type (AC) fan motors:
No. Part Name Model Part Code
Cap nut - 9FL-2-6450-001-00 5 3
-a -b -c
Fan blade
Motor mount - 9FL-2-8140-001-00 5 3
Bracket - 9FL-2-1750-017-01 10 6
Fan motor
SPFBE141 8FC-4-M140-000-10 3 3
SPFBE91T 8FC-4-M140-000-20 2 -
#128 9FL-2-4230-001-00 3 3
#117 9FL-2-4230-002-00 2 -
FPW-EXA025 FPW-EXA085
Quantity used Quantity used
22
Page 23
Fan Motor Assembly Part Codes (High-Efficiency-Type Fan Motors)
Cap nut
-a Vibration-damping washer
Fan blade
-b Fan motor
Bracket
For models with high-efficiency-type (DC) fan motors:
No. Part Name Model Part Code
Cap nut - 9FL-2-6450-001-00 5 3
-a -b
Fan blade
Bracket - 9FL-2-1750-017-01 10 6
Fan motor
SSC2B12CNHBV1 8FC-4-M110-000-10 3 3
SSC2B12BVHBV1 8FC-4-M110-000-20 2 -
#128 9FL-2-4230-001-00 3 3
#117 9FL-2-4230-002-00 2 -
FPW-EXA025 FPW-EXA085
Quantity used Quantity used
23
Page 24
7.2 Replacing Electronic Ballasts
Electronic Ballast Part Codes
Type Model Part Code
To replace electronic ballasts:
Remove the Exterior Top Panel. Unplug the electronic ballast harness(es). Remove the electronic ballast(s).
FPW-EXA025 FPW-EXA085
Quantity used Quantity used
4-lamp
3-lamp
2-lamp
QHE4X32T8/UNV ISN-SC-1-CC-B
QHE3X32T8/UNV ISN-SC-1-CC-B
QHE2X32T8/UNV ISN-SC-1-CC-B
8FC-0-5400-000-40-1 3 2
8FC-0-5400-000-30-1 1 -
8FC-0-5400-000-20-1 - 1
24
Page 25
7.3 Replacing Fluorescent Lamps
The unit comes with covers placed over each fluorescent lamp. Ensure that these covers are placed over the new lamps before reinstallation.
LAMP COVER
LAMP END CAP
NOTICE! Always use Sanyo lamp covers and end caps when replacing lamp covers and end caps. Using non-Sanyo brand replacement parts can result in decreased performance and/or part lifetime.
25
Page 26
26
Page 27
27
Page 28
MDMN 001.04 July 2008
Loading...