Sanyo EMP410WS Schematic

File No :File No :
File No :
File No :File No :
SER SER
SER
SER SER
VICE MANUALVICE MANUAL
VICE MANUAL
VICE MANUALVICE MANUAL
Micr Micr
Micr
Micr Micr
owave Ovenowave Oven
owave Oven
owave Ovenowave Oven
Pr Pr
oduct Code No.oduct Code No.
Pr
oduct Code No.
Pr Pr
oduct Code No.oduct Code No.
EM-P410WS EM-P410WS

EM-P410WS

EM-P410WS EM-P410WS
437 450 34437 450 34
437 450 34
437 450 34437 450 34
(U.S.A.)(U.S.A.)
(U.S.A.)
(U.S.A.)(U.S.A.)
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
WW
ARNING TO SERARNING TO SER
W
ARNING TO SER
WW
ARNING TO SERARNING TO SER
VICE TECHNICIANSVICE TECHNICIANS
VICE TECHNICIANS
VICE TECHNICIANSVICE TECHNICIANS
SERVICING TO AVOID POSSIBLE EXPOSURE TO
EXCESSIVE MICROWAVE ENERGY
(a) Do not operate or allow the oven to be operated with the door open. (b) Make the following safety checks on all ovens to be serviced before activating the magnetron or other
microwave source, and make repairs as necessary : (1) Interlock operation, (2) proper door closing, (3) seal and sealing surfaces (arcing, wear, and other damage), (4) damage to or loosening of hinges and latches, (5) evidence of dropping or abuse.
(c) Before turning on microwave power for any service test or inspection within the microwave generating
compartments, check the magnetron, wave guide or transmission line, and cavity for proper alignment, integrity, and connections.
(d) Any defective or misadjusted components in the interlock, monitor, door seal, and microwave generation and
transmission systems shall be repaired, replaced, or adjusted by procedures described in this manual before the oven is released to the owner.
(e) A microwave leakage check to verify compliance with the Federal per formance standard should be performed
on each oven prior to release to the owner.
REFERENCE NO. SM-860236
CAUTIONCAUTION

CAUTION

CAUTIONCAUTION
For micrFor micr
For micr
For micrFor micr
On every service calls, check for microwave energy emission, must be made according to the following manner.
MeasurMeasur
Measur
MeasurMeasur
Measurement must be made with the microwave oven operating at its maximum output and containing a load of 275±15 milliliters of tap water initially at 20 ±9oF) placed within the cavity at the center.
NOTE : The water container must be a 600 milliliter beaker
A properly operating door and seal assembly will normally register emission on greater than 4mW/cm measurement uncertainty with the cooking shelf or tray in place.
All repairs must be performed in such a manner All repairs must be performed in such a manner
All repairs must be performed in such a manner
All repairs must be performed in such a manner All repairs must be performed in such a manner micrmicr
micr
micrmicr
Follow the instructions supplied with a detector being used and performed an R.F. emission test around the door front and edges and all edges and vent of the outer case. The cabinet (wrapper) must be in place and the oven fully assembled.
When performing emission survey, with the meter on FAST RESPONSE the movement of a detector probe shall not exceed one (1) inch per second.
owave enerowave ener
owave ener
owave enerowave ener
ement of enerement of ener
ement of ener
ement of enerement of ener
and made of an electrically none conductive material such as glass or plastic. The cook tray must be in place when measuring emission.
owave enerowave ener
owave ener
owave enerowave ener
gy emissiongy emission
gy emission
gy emissiongy emission
gy emissiongy emission
gy emission
gy emissiongy emission
gy emission argy emission ar
gy emission ar
gy emission argy emission ar
e minimal.e minimal.
e minimal.
e minimal.e minimal.
o±5o
2
celsius (68
to allow for
thatthat
that
thatthat
In the area emitting the highest reading, switch the meter to SLOW RESPONSE, and take a reading for minimum of three (3) seconds. We recommended the pattern outline shown below when the door surface is surveyed.
NOTE : Periodically check to be sure that the probe tip is
not worn or dirty.
The following U.S. standard applies to microwave ovens : 21 CFR 1030.10, Performance Standard for Microwave Ovens.
It requires that the power density of the microwave radiation emitted by a microwave oven shall not exceed five (5) milliwatts per square centimeter at any point 5 centimeter (about 2 inches) or more from the external surface of the oven.
All microwave ovens exceeding the emission level of 4mW/cm microwave ovens and the manufacturer immediately and the owner should be told not to use the microwave oven until it has been repaired completely.
If a microwave oven is found to operate with the door open, report to Dept. of Service, the manufacturer and CDRH* immediately. Also tell the owner not to use the oven. *CDRH : Center for Device and Radiological Health.
The interlock monitor switch acts as the final safety switch protecting the customer from microwave radiation. If the interlock monitor switch operates to blow the fuse with interlocks failed, you must replace all interlock switches primary and secondary interlock switches and the monitor switch with new ones because the contacts of those interlock switches may be melted and welded together.
2
must be reported to Dept. of Service for
- i -
- TABLE OF CONTENTS -
Adjustment Procedures ................................................... 1
Specifications .................................................................. 2
Power Output Measurement ........................................... 2
Precautions and Repair Service Tips .............................. 2
Circuit Diagram ............................................................... 3
1.1.
ADJUSTMENT PROCEDURESADJUSTMENT PROCEDURES
1.
ADJUSTMENT PROCEDURES
1.1.
ADJUSTMENT PROCEDURESADJUSTMENT PROCEDURES
TT
O AO A
VOID POSSIBLE EXPOSURE TO MICROWVOID POSSIBLE EXPOSURE TO MICROW
T
O A
VOID POSSIBLE EXPOSURE TO MICROW
TT
O AO A
VOID POSSIBLE EXPOSURE TO MICROWVOID POSSIBLE EXPOSURE TO MICROW
ENERGY LEAKAGE, THE FOLLOWINGENERGY LEAKAGE, THE FOLLOWING
ENERGY LEAKAGE, THE FOLLOWING
ENERGY LEAKAGE, THE FOLLOWINGENERGY LEAKAGE, THE FOLLOWING ADJUSTMENT OF THE INTERLOCK SWITCHESADJUSTMENT OF THE INTERLOCK SWITCHES
ADJUSTMENT OF THE INTERLOCK SWITCHES
ADJUSTMENT OF THE INTERLOCK SWITCHESADJUSTMENT OF THE INTERLOCK SWITCHES SHOULD BE MADE ONLSHOULD BE MADE ONL
SHOULD BE MADE ONL
SHOULD BE MADE ONLSHOULD BE MADE ONL SERSER
VICE PERSONNEL.VICE PERSONNEL.
SER
VICE PERSONNEL.
SERSER
VICE PERSONNEL.VICE PERSONNEL.
The SANYO service center should have the designated detector to measure the microwave energy leakage after the repair or adjustment.
NOTE : Detector to be used at the service center is
NARDA 8100, 8200 or the equivalent.
PRIMARPRIMAR
PRIMAR
PRIMARPRIMAR MONITOR SWITCH AND DOOR SENSING SWITCHMONITOR SWITCH AND DOOR SENSING SWITCH
MONITOR SWITCH AND DOOR SENSING SWITCH
MONITOR SWITCH AND DOOR SENSING SWITCHMONITOR SWITCH AND DOOR SENSING SWITCH ADJUSTMENTADJUSTMENT
ADJUSTMENT
ADJUSTMENTADJUSTMENT (Figure 1)(Figure 1)
(Figure 1)
(Figure 1)(Figure 1)
Y INTERLOCK SWITCH, INTERLOCKY INTERLOCK SWITCH, INTERLOCK
Y INTERLOCK SWITCH, INTERLOCK
Y INTERLOCK SWITCH, INTERLOCKY INTERLOCK SWITCH, INTERLOCK
Y BY AUTHORIZEDY BY AUTHORIZED
Y BY AUTHORIZED
Y BY AUTHORIZEDY BY AUTHORIZED
AA
VEVE
A
VE
AA
VEVE
Test Procedures and Troubleshooting .................... 4 ~ 10
Disassembly Instructions ....................................... 11 ~ 14
Exploded View and Parts List ................................ 15 ~ 20
Overall Circuit Diagram .......................................... 21
NOTE : If the interlock monitor circuit operates and at the
same time the fuse blows with the door opened, be sure to replace the control circuit board because relay 2 on the control circuit board, the door sensing switch and the electric circuit related on the door sensing switch, which act as Secondary Interlock Switch.
Door Latch
Lever Stopper
Door Sensing Switch
(1) Loosen 2 screws securing the lever stopper. (2) Adjust the lever stopper position so that it is pushed
forward and pull backward until there is about zero gap between the latch lever and the switch body on the primary interlock switch and at the same time there is about zero gap between the door latch and the switch body on the door sensing switch when
the door latch is securely locked. (3) Tighten the lever stopper screws securely. (4) Make sure the interlock monitor switch closes after
the primary interlock switch opens when the door
is opened very slowly, according to “CHECKOUT
PROCEDURE FOR SWITCHES” on page 6. (5) Make sure the interlock monitor switch opens before
the primary interlock switch closes when the door is
closed very slowly, according to “CHECKOUT
PROCEDURE FOR SWITCHES” on page 6. (6) Make sure the microwave energy leakage should be
no greater than 4mW/cm2 to allow for measurement
uncertainty when measured with a detector.
(All service adjustments must be made for
minimum microwave energy leakage readings.)
Interlock Monitor Switch
Screws
- 1 -
Figure 1Figure 1
Figure 1
Figure 1Figure 1
Latch Lever
Primary Interlock Switch
2.2.
SPECIFICASPECIFICA
2.
SPECIFICA
2.2.
SPECIFICASPECIFICA
Rated Power Consumption .. 1480W.
Microwave Output ................ 1050W.
Frequency ............................. 2,450MHz±50MHz.
Power Supply ........................120V±12V, 60Hz.
Rated Current ....................... 12.9 Amp.
Safety Devices ..................... Thermal Fuse open at
Timer .....................................Electronic Digital, up to
Overall Dimensions ................ 205/8”(W) x 161/2”(D) x 113/8”(H)
Oven Cavity Size .................. 133/4”(W) x 145/8”(D) x 81/2”(H)
Turn Table Diameter ..............107/8”
Effective Capacity of
Oven Cavity .......................... 1.1 Cubic Feet.
Net Weight ........................... Approx. 34.5 Lbs.
3.3.
POWER OUTPUT MEASUREMENTPOWER OUTPUT MEASUREMENT
3.
POWER OUTPUT MEASUREMENT
3.3.
POWER OUTPUT MEASUREMENTPOWER OUTPUT MEASUREMENT
NOTENOTE
NOTE
NOTENOTE
The power output specification, 1050W. on this model is measured with IEC measurement. The power output is measured with two (2) liters water is equivalent to 1050W. in measurement with IEC, when measured with the following power output.
(1) Fill two beakers (glass or plastic) with each one liter of
tap water (about 20°C) and measure the water temperature. (Use a thermometer with a 1/10 degree gauge).
(2) Place the beakers side by side in the centre of the glass tray.
(3) Close the door, set the “TIME” for two minutes. (“200” in
the display window). Touch the “START” key and heat the water exactly for two minutes.
(4) Take the beakers out, immediately stir the water and
measure the water temperature respectively.
(5) Calculate the temperature rise of water in each beaker.
Then calculate the average value of two temperature rises. Output power can be calculated by the equation : Power Output (W) = 70 x ∆t Where ∆t is an average temperature rise in degrees Centigrade.
(6) Power Output shall be in the following range :
Minimum 19.6°F (10.9°C) 763W Maximum 20.0°F (14.0°C) 980W
(7) Power Output is affected by the line voltage under load.
For correct Power Output measurement, the line voltage under load must be 120±1 volts.
TIONSTIONS
TIONS
TIONSTIONS
332°F (167°C) for Cavity. Thermal Protector open at 252°F (122°C) for Magnetron. Fuse (Cartridge Type 20A) Primary Interlock Switch, Door Sensing Switch and Relay 2. Interlock Monitor Switch.
99 min. 99 sec.
Average Temperature Rise Power Output
4.4.
PRECAUTIONS AND REPPRECAUTIONS AND REP
4.
PRECAUTIONS AND REP
4.4.
PRECAUTIONS AND REPPRECAUTIONS AND REP
PRELIMINARPRELIMINAR
PRELIMINAR
PRELIMINARPRELIMINAR A.A.
SINCE NEARLSINCE NEARL
A.
SINCE NEARL
A.A.
SINCE NEARLSINCE NEARL CUITS OF THIS MICROWCUITS OF THIS MICROW
CUITS OF THIS MICROW
CUITS OF THIS MICROWCUITS OF THIS MICROW BE CARRIED OUT WITH GREABE CARRIED OUT WITH GREA
BE CARRIED OUT WITH GREA
BE CARRIED OUT WITH GREABE CARRIED OUT WITH GREA
B.B.
TO ATO A
B.
TO A
B.B.
TO ATO A ENERGY LEAKAGE, THE FOLLOWING PRECAUTIONSENERGY LEAKAGE, THE FOLLOWING PRECAUTIONS
ENERGY LEAKAGE, THE FOLLOWING PRECAUTIONS
ENERGY LEAKAGE, THE FOLLOWING PRECAUTIONSENERGY LEAKAGE, THE FOLLOWING PRECAUTIONS MUST BE TMUST BE T
MUST BE T
MUST BE TMUST BE T
(1) Before the power is applied :
(a) Open and close door several times to make sure the
(b) Make sure the perforated screen and the choke die-
(2) After the power is applied :
(a) Open and close the door to see if the interlock mech-
(b) Check microwave energy leakage with a leakage
(3) Do not operate the unit until it is completely repaired,
if any of the following conditions exists : (a) Door does not close firmly against the cavity front.
(b) The hinge is broken. (c) The choke dielectric or the door seal is damaged. (d) The door is bent or warped, or there is any other
NOTE : (e) Make sure that there are no defective parts in the
(f) Make sure there are no defective parts in the
(4) The following items should be checked after the unit
is repaired : (a) The interlock monitor switch is connected correctly
(b) The magnetron gasket on the magnetron is properly
(c) Waveguide and oven cavity are intact (no leakage of
(d) The door can be properly closed and the safety
(e) The oven must be stopped when the door is opened
The oven must not be operated with any of the aboveThe oven must not be operated with any of the above
The oven must not be operated with any of the above
The oven must not be operated with any of the aboveThe oven must not be operated with any of the above components rcomponents r
components r
components rcomponents r
YY
Y
YY
Y 2,000 VOLY 2,000 VOL
Y 2,000 VOL
Y 2,000 VOLY 2,000 VOL
VOID POSSIBLE EXPOSURE TO MICROWVOID POSSIBLE EXPOSURE TO MICROW
VOID POSSIBLE EXPOSURE TO MICROW
VOID POSSIBLE EXPOSURE TO MICROWVOID POSSIBLE EXPOSURE TO MICROW
AKEN BEFORE SERAKEN BEFORE SER
AKEN BEFORE SER
AKEN BEFORE SERAKEN BEFORE SER
primary interlock switch, the interlock monitor switch and the door sensing switch operate properly. (Listen for the clicking sound from the switches). Make sure the interlock monitor switch closes after the primary interlock switch is opens when the door is opened. (See pages 1 and 6).
lectric of the door are correctly mounted.
anism operates properly.
detector and confirm the energy leakage should be no greater than 4mW/cm uncertainty.
visible damage to the oven that may cause microwave energy leakage.
Always keep the seal clean.Always keep the seal clean.
Always keep the seal clean.
Always keep the seal clean.Always keep the seal clean.
interlock mechanism.
microwave generating and transmission assembly. (especially waveguide).
and firmly.
positioned.
microwave energy).
switches work properly.
or the time is up.
emoved or bypassed.emoved or bypassed.
emoved or bypassed.
emoved or bypassed.emoved or bypassed.
AIR SERAIR SER
AIR SER
AIR SERAIR SER
TS EXISTS IN SOME CIR-TS EXISTS IN SOME CIR-
TS EXISTS IN SOME CIR-
TS EXISTS IN SOME CIR-TS EXISTS IN SOME CIR-
AA
VE OVEN, REPVE OVEN, REP
A
VE OVEN, REP
AA
VE OVEN, REPVE OVEN, REP
T CARE.T CARE.
T CARE.
T CARE.T CARE.
VICING.VICING.
VICING.
VICING.VICING.
2
to allow for measurement
VICE TIPSVICE TIPS
VICE TIPS
VICE TIPSVICE TIPS
AIRS SHOULDAIRS SHOULD
AIRS SHOULD
AIRS SHOULDAIRS SHOULD
AA
VEVE
A
VE
AA
VEVE
- 2 -
5. CIRCUIT DIAGRAM
Figure 2Figure 2
Figure 2
Figure 2Figure 2
WIRING COLOR
O : ORANGE B K : BLACK
R : RED BL : BLUE
W : WHITE Y : YELLOW
- 3 -
6. TEST PROCEDURES AND TROUBLESHOOTING6. TEST PROCEDURES AND TROUBLESHOOTING
6. TEST PROCEDURES AND TROUBLESHOOTING
6. TEST PROCEDURES AND TROUBLESHOOTING6. TEST PROCEDURES AND TROUBLESHOOTING
CAUTIONCAUTION
CAUTION
CAUTIONCAUTION
- DISCONNECT THE POWER SUPPL- DISCONNECT THE POWER SUPPL
- DISCONNECT THE POWER SUPPL
- DISCONNECT THE POWER SUPPL- DISCONNECT THE POWER SUPPL
THE WTHE W
ALL OUTLET WHENEVER REMOVING THEALL OUTLET WHENEVER REMOVING THE
THE W
ALL OUTLET WHENEVER REMOVING THE
THE WTHE W
ALL OUTLET WHENEVER REMOVING THEALL OUTLET WHENEVER REMOVING THE
CABINET FROM THE UNITCABINET FROM THE UNIT
CABINET FROM THE UNIT
CABINET FROM THE UNITCABINET FROM THE UNIT TESTS ONLTESTS ONL
TESTS ONL
TESTS ONLTESTS ONL VOLVOL
TT
VOL
T
VOLVOL
TT
WIRES FROM THE PRIMARWIRES FROM THE PRIMAR
WIRES FROM THE PRIMAR
WIRES FROM THE PRIMARWIRES FROM THE PRIMAR HIGH VOLHIGH VOL
HIGH VOL
HIGH VOLHIGH VOL
A.A.
TEST PROCEDURESTEST PROCEDURES
A.
TEST PROCEDURES
A.A.
TEST PROCEDURESTEST PROCEDURES
Y AFTER DISCHARGING THE HIGHY AFTER DISCHARGING THE HIGH
Y AFTER DISCHARGING THE HIGH
Y AFTER DISCHARGING THE HIGHY AFTER DISCHARGING THE HIGH
AGE CAPAGE CAP
AGE CAP
AGE CAPAGE CAP
ACITOR AND REMOVING THE LEADACITOR AND REMOVING THE LEAD
ACITOR AND REMOVING THE LEAD
ACITOR AND REMOVING THE LEADACITOR AND REMOVING THE LEAD
TT
AGE TRANSFORMER. (SEE FIGURE 3)AGE TRANSFORMER. (SEE FIGURE 3)
T
AGE TRANSFORMER. (SEE FIGURE 3)
TT
AGE TRANSFORMER. (SEE FIGURE 3)AGE TRANSFORMER. (SEE FIGURE 3)
Y CORD FROMY CORD FROM
Y CORD FROM
Y CORD FROMY CORD FROM
, PROCEED WITH THE, PROCEED WITH THE
, PROCEED WITH THE
, PROCEED WITH THE, PROCEED WITH THE
Y WINDING OF THEY WINDING OF THE
Y WINDING OF THE
Y WINDING OF THEY WINDING OF THE
Secondary
Windings
Filament Windings
Primary
Windings
Figure 3Figure 3
Figure 3
Figure 3Figure 3
COMPONENT COMPONENT
COMPONENT
COMPONENT COMPONENT
MAGNETRONMAGNETRON
MAGNETRON
MAGNETRONMAGNETRON
CHECKOUT PROCEDURE CHECKOUT PROCEDURE
CHECKOUT PROCEDURE
CHECKOUT PROCEDURE CHECKOUT PROCEDURE
1)1)
Check for rCheck for r
1)
Check for r
1)1)
Check for rCheck for r terter
minals of the magnetrminals of the magnetr
ter
minals of the magnetr
terter
minals of the magnetrminals of the magnetr
on R x 1 scale.on R x 1 scale.
on R x 1 scale.
on R x 1 scale.on R x 1 scale.
Ohm-meterOhm-meter
Ohm-meter
Ohm-meterOhm-meter
2)2)
Check for rCheck for r
2)
Check for r
2)2)
Check for rCheck for r terter
minal of the magnetrminal of the magnetr
ter
minal of the magnetr
terter
minal of the magnetrminal of the magnetr
grgr
ound with an ohm-meter on highest scale.ound with an ohm-meter on highest scale.
gr
ound with an ohm-meter on highest scale.
grgr
ound with an ohm-meter on highest scale.ound with an ohm-meter on highest scale.
Ohm-meterOhm-meter
Ohm-meter
Ohm-meterOhm-meter
1)1)
Measure the resistance :Measure the resistance :
1)
Measure the resistance :
1)1)
Measure the resistance :Measure the resistance : WW
ith an ohm-meter on R x 1 scale.ith an ohm-meter on R x 1 scale.
W
ith an ohm-meter on R x 1 scale.
WW
ith an ohm-meter on R x 1 scale.ith an ohm-meter on R x 1 scale.
a.a.
a.
a.a. b.b.
b.
b.b. c.c.
c.
c.c.
esistance : Acresistance : Acr
esistance : Acr
esistance : Acresistance : Acr
esistance : Between each filamentesistance : Between each filament
esistance : Between each filament
esistance : Between each filamentesistance : Between each filament
Primary winding :Primary winding :
Primary winding :
Primary winding :Primary winding : Filament winding :Filament winding :
Filament winding :
Filament winding :Filament winding : Secondary winding :Secondary winding :
Secondary winding :
Secondary winding :Secondary winding :
oss the filamentoss the filament
oss the filament
oss the filamentoss the filament
on with an ohm-meteron with an ohm-meter
on with an ohm-meter
on with an ohm-meteron with an ohm-meter
on and the chassison and the chassis
on and the chassis
on and the chassison and the chassis
Figure 4Figure 4
Figure 4
Figure 4Figure 4
Figure 5Figure 5
Figure 5
Figure 5Figure 5
RESUL RESUL
RESUL
RESUL RESUL
Normal reading :Normal reading :
Normal reading :
Normal reading :Normal reading :
Less than 1 ohm.Less than 1 ohm.
Less than 1 ohm.
Less than 1 ohm.Less than 1 ohm.
Normal reading :Normal reading :
Normal reading :
Normal reading :Normal reading :
Infinite ohms.Infinite ohms.
Infinite ohms.
Infinite ohms.Infinite ohms.
Normal readings :Normal readings :
Normal readings :
Normal readings :Normal readings :
ApprAppr
Appr
ApprAppr Less than 1 ohm.Less than 1 ohm.
Less than 1 ohm.
Less than 1 ohm.Less than 1 ohm. ApprAppr
Appr
ApprAppr
TT
T
TT
oximately 0.32 ohms.oximately 0.32 ohms.
oximately 0.32 ohms.
oximately 0.32 ohms.oximately 0.32 ohms.
oximately 75.2 ohms.oximately 75.2 ohms.
oximately 75.2 ohms.
oximately 75.2 ohms.oximately 75.2 ohms.
HIGH-VOLHIGH-VOL
HIGH-VOL
HIGH-VOLHIGH-VOL
TRANSFORMERTRANSFORMER
TRANSFORMER
TRANSFORMERTRANSFORMER
TT
AGEAGE
T
AGE
TT
AGEAGE
2)2)
Measure the resistance :Measure the resistance :
2)
Measure the resistance :
2)2)
Measure the resistance :Measure the resistance : WW
ith an ohm-meter on highest scale.ith an ohm-meter on highest scale.
W
ith an ohm-meter on highest scale.
WW
ith an ohm-meter on highest scale.ith an ohm-meter on highest scale.
a.a.
Primary winding to grPrimary winding to gr
a.
Primary winding to gr
a.a.
Primary winding to grPrimary winding to gr
bb
Filament winding to grFilament winding to gr
b
Filament winding to gr
bb
Filament winding to grFilament winding to gr
Ohm-meterOhm-meter
Ohm-meter
Ohm-meterOhm-meter
Note :Note :
Note :
Note :Note :
Remove varRemove var
Remove var
Remove varRemove var measurmeasur
measur
measurmeasur
ed point.ed point.
ed point.
ed point.ed point.
nish ofnish of
nish of
nish ofnish of
ound.ound.
ound.
ound.ound.
ound.ound.
ound.
ound.ound.
- 4 -
Figure 6Figure 6
Figure 6
Figure 6Figure 6
Normal readings :Normal readings :
Normal readings :
Normal readings :Normal readings :
Infinite ohms.Infinite ohms.
Infinite ohms.
Infinite ohms.Infinite ohms. Infinite ohms.Infinite ohms.
Infinite ohms.
Infinite ohms.Infinite ohms.
COMPONENT COMPONENT
COMPONENT
COMPONENT COMPONENT
CHECKOUT PROCEDURE CHECKOUT PROCEDURE
CHECKOUT PROCEDURE
CHECKOUT PROCEDURE CHECKOUT PROCEDURE
RESUL RESUL
RESUL
RESUL RESUL
TT
T
TT
HIGH-VOLHIGH-VOL
HIGH-VOL
HIGH-VOLHIGH-VOL CAPCAP
ACITORACITOR
CAP
ACITOR
CAPCAP
ACITORACITOR
includingincluding
including
includingincluding BLEEDERBLEEDER
BLEEDER
BLEEDERBLEEDER RESISTORRESISTOR
RESISTOR
RESISTORRESISTOR
HIGH-VOLHIGH-VOL
HIGH-VOL
HIGH-VOLHIGH-VOL DIODEDIODE
DIODE
DIODEDIODE
TT
AGEAGE
T
AGE
TT
AGEAGE
TT
AGEAGE
T
AGE
TT
AGEAGE
MeasurMeasur
Measur
MeasurMeasur with an ohm-meter on highest scale.with an ohm-meter on highest scale.
with an ohm-meter on highest scale.
with an ohm-meter on highest scale.with an ohm-meter on highest scale.
MeasurMeasur
Measur
MeasurMeasur with an ohm-meter on R x 10,000 scale.with an ohm-meter on R x 10,000 scale.
with an ohm-meter on R x 10,000 scale.
with an ohm-meter on R x 10,000 scale.with an ohm-meter on R x 10,000 scale.
e the re the r
e the r
e the re the r
Ohm-meterOhm-meter
Ohm-meter
Ohm-meterOhm-meter
e the re the r
e the r
e the re the r
esistance : Acresistance : Acr
esistance : Acr
esistance : Acresistance : Acr
esistance : Acresistance : Acr
esistance : Acr
esistance : Acresistance : Acr
Ohm-meterOhm-meter
Ohm-meter
Ohm-meterOhm-meter
oss two teross two ter
oss two ter
oss two teross two ter
oss two teross two ter
oss two ter
oss two teross two ter
minalsminals
minals
minalsminals
Figure 7Figure 7
Figure 7
Figure 7Figure 7
minalsminals
minals
minalsminals
Normal reading :Normal reading :
Normal reading :
Normal reading :Normal reading :
Momentarily indicates several ohms,Momentarily indicates several ohms,
Momentarily indicates several ohms,
Momentarily indicates several ohms,Momentarily indicates several ohms, and gradually rand gradually r
and gradually r
and gradually rand gradually r
Abnormal reading :Abnormal reading :
Abnormal reading :
Abnormal reading :Abnormal reading :
Indicates continuity or 10 meg-ohmsIndicates continuity or 10 meg-ohms
Indicates continuity or 10 meg-ohms
Indicates continuity or 10 meg-ohmsIndicates continuity or 10 meg-ohms frfr
om the beginning.om the beginning.
fr
om the beginning.
frfr
om the beginning.om the beginning.
Normal reading :Normal reading :
Normal reading :
Normal reading :Normal reading :
Indicates about the middle position inIndicates about the middle position in
Indicates about the middle position in
Indicates about the middle position inIndicates about the middle position in one dirone dir
ection (forwarection (forwar
one dir
ection (forwar
one dirone dir
ection (forwarection (forwar
infinite ohms in the rinfinite ohms in the r
infinite ohms in the r
infinite ohms in the rinfinite ohms in the r using meter which is prusing meter which is pr
using meter which is pr
using meter which is prusing meter which is pr 9 volt battery.9 volt battery.
9 volt battery.
9 volt battery.9 volt battery.
- Some digital meter may show over- Some digital meter may show over
- Some digital meter may show over
- Some digital meter may show over- Some digital meter may show over even in a forwareven in a forwar
even in a forwar
even in a forwareven in a forwar low measuring voltage of meter doeslow measuring voltage of meter does
low measuring voltage of meter does
low measuring voltage of meter doeslow measuring voltage of meter does not allow the meter currnot allow the meter curr
not allow the meter curr
not allow the meter currnot allow the meter curr thrthr
ough the high voltage diode.ough the high voltage diode.
thr
ough the high voltage diode.
thrthr
ough the high voltage diode.ough the high voltage diode.
eturetur
etur
eturetur
NOTENOTE
NOTE
NOTENOTE
d dird dir
d dir
d dird dir
ns to 10 meg-ohms.ns to 10 meg-ohms.
ns to 10 meg-ohms.
ns to 10 meg-ohms.ns to 10 meg-ohms.
d dird dir
ection) andection) and
d dir
ection) and
d dird dir
ection) andection) and
everse direverse dir
everse dir
everse direverse dir
ection becauseection because
ection because
ection becauseection because
ection,ection,
ection,
ection,ection,
ovided with aovided with a
ovided with a
ovided with aovided with a
ent to passent to pass
ent to pass
ent to passent to pass
CONTROLCONTROL
CONTROL
CONTROLCONTROL CIRCUITCIRCUIT
CIRCUIT
CIRCUITCIRCUIT
BOARDBOARD
BOARD
BOARDBOARD
MeasurMeasur
Measur
MeasurMeasur TP-2 and GrTP-2 and Gr
TP-2 and Gr
TP-2 and GrTP-2 and Gr page 19).page 19).
page 19).
page 19).page 19).
- Pr- Pr
- Pr
- Pr- Pr TT
T
TT values is difvalues is dif
values is dif
values is difvalues is dif
e the voltage : Between test point TP-1,e the voltage : Between test point TP-1,
e the voltage : Between test point TP-1,
e the voltage : Between test point TP-1,e the voltage : Between test point TP-1,
ound. (See Contround. (See Contr
ound. (See Contr
ound. (See Contround. (See Contr
NOTENOTE
NOTE
NOTENOTE
oceed with the check of the Step-Downoceed with the check of the Step-Down
oceed with the check of the Step-Down
oceed with the check of the Step-Downoceed with the check of the Step-Down
ransforransfor
mermer
ransfor
ransforransfor
, to see if any one of the measur, to see if any one of the measur
mer
, to see if any one of the measur
mermer
, to see if any one of the measur, to see if any one of the measur ferfer
ent frent fr
fer
ferfer
om the specified values.om the specified values.
ent fr
om the specified values.
ent frent fr
om the specified values.om the specified values.
ol Cirol Cir
ol Cir
ol Cirol Cir
cuit Boarcuit Boar
cuit Boar
cuit Boarcuit Boar
- 5 -
Figure 8Figure 8
Figure 8
Figure 8Figure 8
d ond on
d on
d ond on
eded
ed
eded
Abnormal reading :Abnormal reading :
Abnormal reading :
Abnormal reading :Abnormal reading :
Indicates continuity or infinite ohmsIndicates continuity or infinite ohms
Indicates continuity or infinite ohms
Indicates continuity or infinite ohmsIndicates continuity or infinite ohms in both dirin both dir
in both dir
in both dirin both dir
TT
estest
T
est
TT
estest
PointPoint
Point
PointPoint
VV
oltageoltage
V
oltage
VV
oltageoltage
ections.ections.
ections.
ections.ections.
TP-1 TP-1
TP-1
TP-1 TP-1
-5V -5V
-5V
-5V -5V DC DC
DC
DC DC
TP-2TP-2
TP-2
TP-2TP-2
-15V-15V
-15V
-15V-15V DC DC
DC
DC DC
Loading...
+ 16 hidden pages