Sanyo CMH2472A, KMHS0772, CMH1972, KMHS0972, CMH2472 Installation Instructions Manual

...
Page 1
85264189993000 © SANYO 2006
In Canada
SANYO FISHER COMPANY SANYO Canada Inc.
A DIVISION OF SANYO NORTH AMERICA CORPORATION 300 Applewood Crescent, Concord 21605 Plummer Street Ontario, L4K 5C7, Canada Chatsworth, CA 91311 U.S.A.
Contents
IMPORTANT!
Please Read Before Starting .................................. 2
1. GENERAL .......................................................... 3
1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION ................... 4
2-1. Indoor Unit 2-2. Connecting Indoor Units 2-3. Outdoor Unit 2-4. Outer Dimensions of Outdoor Unit 2-5. Diagram of Outdoor Unit Installation
3. INSTALLATION PROCESS .............................. 13
3-1. Embedding the Tubing and Wiring 3-2. Use of the Flaring Method 3-3. Flaring Procedure with a Flare Tool 3-4. Caution before Connecting Tubes Tightly 3-5. Tubing Connections 3-6. Insulation of Refrigerant Tubing 3-7. Taping the Tubes 3-8. Finishing the Installation
4. AIR PURGING................................................... 16
I Air Purging with a Vacuum Pump (for Test Run) I Pump Down
5. WIRING INSTRUCTIONS ................................ 19
5-1. General Precautions on Wiring 5-2. Recommended Wire Length and Diameter 5-3. Wiring System Diagram 5-4. How to Connect Wiring to the Terminal 5-5. Wiring Instructions for the Outdoor Unit
6. TEST RUN......................................................... 23
7. CONNECTING A HOME AUTOMATION
DEVICE ............................................................. 24
8. INSTALLATION CHECK SHEET ...................... 24
INSTALLATION INSTRUCTIONS
Model Combinations
Combine indoor and outdoor units only as listed below.
Indoor Unit Outdoor Unit
KMHS0772 CMH1972
KMHS0972 CMH2472
KMHS1272 CMH3172
KMHS1872
KMHS2472
Combine indoor and outdoor units only as listed in the combination tables for 3-room or 4-room outdoor unit as shown in its respective manual.
Power Source: 60 Hz, single-phase, 230 / 208 VAC
– Inverter Multi Split System Air Conditioner –
COOL/DRY/HEAT Model
This air conditioner uses the new refrigerant R410A.
Be sure to read the yellow instruction sheet attached to the outdoor unit for models using the new refrigerant R410A.
The illustrations are based on the typical appearance of a standard model. Consequently, the shape may differ from that of the air conditioner that you are installing.
NOTE
Indoor unit A
Indoor unit B
Indoor unit C
Indoor unit D
Outdoor unit
Combination example
For Outdoor Unit
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page a
Page 2
2
IMPORTANT! Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must:
G
Carefully read this instruction booklet before beginning.
G
Follow each installation or repair step exactly as shown.
G
Observe all local, state, and national electrical codes.
G
Pay close attention to all warning and caution notices given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or prod­uct or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improp­er installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or
death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over­heating at connection points and a possible fire hazard.
When Transporting
Be careful when picking up and moving the indoor and out­door units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin alu­minum fins on the air conditioner can cut your fingers.
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the unit’s weight. It may be necessary to construct a strong wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before star ting the test run.
When Servicing
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have been left inside the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing the refrigeration system. Escaped refrigerant gas, on contact with fire or heat, can produce dangerously toxic gas.
• Confirm upon completing installation that no refrigerant gas is leaking. If escaped gas comes in contact with a stove, gas water heater, electric room heater or other heat source, it can produce dangerously toxic gas.
• Do not install only a single indoor unit.
WARNING
WARNING
CAUTION
CAUTION
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 2
Page 3
3
1. General
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning. If the electric wiring diagram does not appear in this manual, please check for the diagram on the indoor unit.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
16. Vacuum pump (For R410A)
17. Manifold valve
1-2. Accessories Supplied with Unit
Table 1
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide tubing, fittings and insulation. Consult your nearest sales outlet or A/C workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tub­ing as detailed in Table 2.
Cut each tube to the appropriate lengths 1' to 1'4" (30 cm to 40 cm) to dampen vibration between units.
Table 2
2. Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness of the insulation should be not less than 5/16" (8 mm).
3. Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 5. Wiring Instructions for details.
Labels for inter-unit cable and tube
Reducer (3/8" 1/2")
1
Packed in the outdoor unit.
1
4 each
Hex wrench Cushion rubber 4
Parts Figure Q’ty Parts Figure Q’ty Parts Figure Q’ty
CMH1972
CMH2472
CMH3172
2
1
ABCD
Reducer (1/2" 3/8")
CAUTION
Check local electrical codes and regulations before obtaining wire. Also, check any specified instructions or limitations.
Model
Narrow Tube Wide Tube
Outer Dia. Thickness Outer Dia. Thickness
KMHS0772 1/4" (6.35 mm) 0.0314" (0.8 mm) 3/8" (9.52 mm) 0.0314" (0.8 mm)
KMHS0972 1/4" (6.35 mm) 0.0314" (0.8 mm) 3/8" (9.52 mm) 0.0314" (0.8 mm)
KMHS1272 1/4" (6.35 mm) 0.0314" (0.8 mm) 3/8" (9.52 mm) 0.0314" (0.8 mm)
KMHS1872 1/4" (6.35 mm) 0.0314" (0.8 mm) 1/2" (12.70 mm) 0.0314" (0.8 mm)
KMHS2472 1/4" (6.35 mm) 0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 3
Page 4
4
1-5. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire (See local codes)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
AVOID:
G direct sunlight.
G nearby heat sources that may affect performance of the
unit.
G areas where leakage of flammable gas may be expected.
G placing or allowing any obstructions near the A/C inlet or
outlet.
G installing in rooms that contain instant-on (rapid-start)
fluorescent lamps. (These may prevent the A/C from receiving signals.)
G places where large amounts of oil mist exist.
G installing in locations where there are devices that
generate high-frequency emissions.
DO:
G select an appropriate position from which every corner of
the room can be uniformly cooled. (High on a wall is best.)
G select a location that will hold the weight of the unit.
G select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
G allow room for operation and maintenance as well as
unrestricted air flow around the unit. (Fig. 2)
G install the unit within the maximum elevation difference
(H1, H2, H3, H4) above or below the outdoor unit and within a total tubing length (L1+L2+L3, L1+L2+L3+L4) from the outdoor unit as detailed in Table 3 and Fig. 3a.
Drain hose
Indoor unit
Outside drainage
Fig. 1
2" (5 cm)
min.
6" (15 cm) min.
Front View
2" (5 cm)
min.
Fig. 2
INDOOR UNIT (1)
INDOOR UNIT (4)
INDOOR UNIT (3)
INDOOR UNIT (2)
Tubing length (L1)
L2
L3
L4
H2
H3
H4
OUTDOOR UNIT
Elevation difference (H1)
Fig. 3a
WARNING
To prevent abnormal heat generation and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow.
Indoor unit
Floor level
Wall
Minimum height from floor level
5' (1.5 m)
Fig. 3b
For stable operation of the air conditioner, do not install wall-mounted type indoor units less than 5' (1.5 m) from floor level.
CAUTION
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 4
Page 5
5
G Install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for tele­vision, radio, telephone, security system, or intercom. Electrical noise from any of these sources may affect operation.
G install in a sturdy manner to avoid increased operating
noise.
Table 3
* If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.
No additional charge of compressor oil is necessary.
Max. Max. Allowable Total Limit of Limit of Elevation Required Amount
Allowable Tubing Length Total Tubing Length Difference of Additional
Model Tubing Length at shipment (L1+L2+L3) or (H1, H2, H3, H4) Refrigerant
per unit (L1+L2+L3) or (L1+L2+L3+L4) (ft.) (oz./ft.)*
(ft.) (L1+L2+L3+L4) (ft.)
(ft.)
CMH1972 82 150 (L1+L2+L3) 150 (L1+L2+L3) 50
CMH2472 82 150 (L1+L2+L3+L4) 200 (L1+L2+L3+L4) 50 0.22
CMH3172 100 150 (L1+L2+L3+L4) 230 (L1+L2+L3+L4) 50 0.22
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 5
Page 6
6
(B)
Fig. 4b
Union 1/2"(12.70mm)
1/2"(12.70
mm
)
Flare 3/8"(9.52
mm
)
A joint for connecting tubes of different sizes (3/8"(9.52mm) 1/2"(12.70mm)) Supplied Reducer
1/4"(6.35mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
C
B
A
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
(KMHS1872)
3/8"(9.52mm)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
(A)
Fig. 4c
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70mm) 3/8"(9.52mm)) Supplied Reducer
C
B
A
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
D
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
1/2"(12.70mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
(2) Connecting indoor unit for CMH2472
(A)
Fig. 4a
3/8"(9.52mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
3/8"(9.52
mm
)
C
B
A
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
2-2. Connecting Indoor Units
(1) Connecting indoor unit for CMH1972
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 6
Page 7
7
(B)
Fig. 4d
C
B
A
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
D
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
(D)
Fig. 4f
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70
mm
) 5/8"(15.88mm))
Locally purchased
C
B
A
(KMHS1872)
(KMHS0772,KMHS0972,KMHS1272)
D
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS2472)
Union 1/2"(12.70mm)Flare 3/8"(9.52mm)
(3/8"(9.52
mm
) 1/2"(12.70mm))
Locally purchased
1/2"(12.70mm)
1/2"(12.70
mm
)
5/8"(15.88mm)
3/8"(9.52
mm
)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
(C)
Fig. 4e
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70mm) 5/8"(15.88mm)) Locally purchased
C
B
A
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
D
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS2472)
1/2"(12.70mm)
3/8"(9.52mm)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
5/8"(15.88mm)
3/8"(9.52mm)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35mm)
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 7
Page 8
8
(A)
Fig. 4g
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70mm) 3/8"(9.52mm)) Supplied Reducer
C
B
A
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
D
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
1/2"(12.70mm)
1/2"(12.70
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
(3) Connecting indoor unit for CMH3172
(B)
Fig. 4h
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70mm 3/8"(9.52mm)) Supplied Reducer
C
B
A
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
D
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS1872)
1/2"(12.70mm)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35mm)
1/4"(6.35
mm
)
(C)
Fig. 4i
C
B
A
(KMHS1872)
(KMHS0772,KMHS0972,KMHS1272)
D
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS1872)
1/2"(12.70
mm
)
1/2"(12.70
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/2"(12.70mm)
1/2"(12.70
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35mm)
1/4"(6.35
mm
)
1/4"(6.35mm)
1/4"(6.35
mm
)
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 8
Page 9
9
(D)
Fig. 4j
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70mm) 5/8"(15.88mm)) Locally purchased
C
B
A
(KMHS0772,KMHS0972,KMHS1272)
(KMHS0772,KMHS0972,KMHS1272)
D
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS2472)
Union 3/8"(9.52mm)Flare 1/2"(12.70mm)
(1/2"(12.70mm) 3/8"(9.52mm)) Supplied Reducer
1/2"(12.70mm)
1/2"(12.70
mm
)
5/8"(15.88
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
3/8"(9.52mm)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35mm)
1/4"(6.35
mm
)
(E)
Fig. 4k
Union 5/8"(15.88mm)Flare 1/2"(12.70mm)
(1/2"(12.70mm) 5/8"(15.88mm)) Locally purchased
C
B
A
(KMHS1872)
(KMHS0772,KMHS0972,KMHS1272)
D
Outdoor unit Indoor unit
(KMHS0772,KMHS0972,KMHS1272)
(KMHS2472)
1/2"(12.70mm)
1/2"(12.70
mm
)
5/8"(15.88
mm
)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/2"(12.70mm)
3/8"(9.52
mm
)
3/8"(9.52
mm
)
1/4"(6.35
mm
)
1/4"(6.35
mm
)
1/4"(6.35mm)
1/4"(6.35
mm
)
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 9
Page 10
10
2-3. Outdoor Unit
AVOID:
G heat sources, exhaust fans, etc. (Fig. 5a)
G damp, humid or uneven locations.
DO:
G choose a place as cool as possible.
G choose a place that is well ventilated.
G allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 5b)
G provide a solid base (level concrete pad, concrete
block, 6" ¥ 1'4" (15 ¥ 40 cm) beams or equal), a mini­mum of 6" (15 cm) above ground level to reduce humidity and protect the unit against possible water damage and decreased service life. (Figs. 5c and 5d)
G Install cushion rubber under unit’s feet to reduce
vibration and noise. (Fig. 5e)
G use lug bolts or equal to bolt down unit, reducing
vibration and noise.
G Install in a location where no antenna of a television
or radio exists within 10' (3 m).
Outdoor unit
Hot air
Heat source
Exhaust fan
NO
Fig. 5a
Fig. 5b
Fig. 5d
Air intake Min. 8" (20 cm)
Air discharge
Min.
4" (10 cm)
Min. 1ʼ8" (50 cm)
Valve side Min. 10" (25 cm)
Min.
7' (2 m)
Min.
7' (2 m)
Ground
Obstacle
Obstacle above
Air discharge
Min. 8" (20 cm)
Air intake
Air intake
Concrete or equal
About 6" (15 cm)
Min. 6" (15 cm)
Anchor bolts (4 pcs.)
About 16" (40 cm)
Fig. 5e
Cushion rubber
CAUTION
A solid base must not cover the hole of the bottom plate.
Drain holes
Fig. 5c
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 10
Page 11
11
Fig. 6a
23-15/16
5-11/32
15/32
35-7/16 (900)
13-19/32
12-19/32
14-17/32
2-29/32
29-1/8 (740)
23/32
1-13/16
2-1/16
5-29/32
2-27/32
2-3/4
2-1/32
4-7/16
2-15/16
2-3/4
4-1/2
A
Service valve on narrow tube side (Outer diameter 1/4"(
6.35
))
Service valve on wide tube side (Outer diameter 3/8"(
9.52
))
A
(1) CMH1972
Fig. 6b
23-15/16
5-11/32
15/32
12-19/32
13-19/32
14-17/32
35-7/16 (900)
29-1/8 (740)
2-1/16
1-13/16
2-29/32
2-13/32
A
4-1/2
2-1/32
5-29/32
2-27/32
2-3/4
4-7/16
2-15/16
2-3/4
Service valve on narrow tube side (Outer diameter 1/4"(
6.35
))
Service valve on wide tube side (Outer diameter 3/8"(
9.52
))
Service valve on wide tube side (Outer diameter 1/2"(
12.70
))
A
23/32
Fig. 6c
23-15/16
15/32
12-19/32
13-19/32
14-17/32
5-11/32
35-7/16 (900)
23/32
35-1/32 (890)
2-29/32
2-1/16
1-13/16
2-13/32
4-1/2
2-1/32
4-7/16
5-29/32
2-15/16
2-27/32
2-3/4
2-3/4
A
Service valve on narrow tube side (Outer diameter 1/4"(
6.35
))
Service valve on wide tube side (Outer diameter 1/2"(
12.70
))
Service valve on wide tube side (Outer diameter 3/8"(
9.52
))
A
(2) CMH2472
(3) CMH3172
2-4. Outer Dimensions of Outdoor Unit
unit: inch (mm)
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 11
Page 12
12
2-5. Diagram of Outdoor Unit Installation
Never install only a single indoor unit.
Be sure to connect indoor and outdoor units only in combinations that are listed in the catalog or in the combination table that was provided with the outdoor unit. (Use caution. Connecting any other model may result in operation failure and malfunction.)
The dimensions indicated by in the figure below are spaces that are required in order to maintain performance. Install in a location where the dimensions indicated by are ensured, and where 2 or more faces of the unit are unobstructed. In principle, the top direction should be unobstructed.
Indoor unit C
Indoor unit B
Indoor unit A
Indoor unit D
Service space
Power breaker
Ground wire (not provided)
Ensure 6"(15cm) of space if a drain hose is to be used.
Base (not provided) (concrete or similar material)
Fasten with anchor bolts (not provided) (3/8" or M10, 4 locations)
A
B
C
D
Access panel C
Over 10"(25cm)
Over 8"(20cm)
Over 4"(10cm)
Over 1'8"(50cm)
Fig. 7
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 12
Page 13
13
3. Installation Process
3-1. Embedding the Tubing and Wiring
G Do not connect tubes to locations that are embedded.
G Be sure to bind refrigerant tubing and inter-unit cables
together with vinyl tape.
G The power cable must be obtained on-site.
(#12: Less than 85 ft.) # ... AWG (American Wire Gauge)
G Be sure to apply the provided labels to both ends of
the inter-unit cables to prevent miswiring.
G Securely seal the end of embedded tubing with vinyl
tape in order to prevent dirt or moisture entry.
G In order to prevent insulation breakdown and ground
faults, do not allow the wire ends to contact rainwater, or be subject to dew condensation.
Deburring
Before
After
Fig. 8
3-2. Use of the Flaring Method
Many of the conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts.
3-3. Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 12" to 20" (30 to 50 cm) longer than the tubing length you estimate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and should be done carefully to make a good flare. (Fig. 8)
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 13
Page 14
14
When reaming, hold the tube end downward and be sure that no copper scraps fall into the tube. (Fig. 9)
(3) Remove the flare nut from the unit and be sure to mount
it on the copper tube.
(4) Make a flare at the end of copper tube with a flare tool.*
(Figs. 10 and 11)
(*Use “RIGID” or equivalent.)
A good flare should have the following characteristics:
G inside surface is glossy and smooth.
G edge is smooth.
G tapered sides are of uniform length.
3-4. Caution before Connecting Tubes Tightly
a) Be sure to apply a sealing cap or water-proof tape to
prevent dust or water from getting into the tubes before they are used.
b) Be sure to apply refrigerant lubricant to the matching
surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig. 12)
c) For proper connection, align the union tube and flare
tube straight with each other, then screw in the flare nut lightly at first to obtain a smooth match. (Fig. 13)
3-5. Tubing Connections
a) Temporary connection:
Screw in 3 – 5 rotations by hand. (Fig.14)
b) To fasten the flare nuts, apply specified torque as:
Table 4
NOTE
NOTE
Reamer
Copper tubing
Fig. 9
Flare tool
Flare nut
Copper tubing
Fig. 11
Fig. 10
Apply refrigerant lubricant here and here
Fig. 12
Flare nut
Union
Fig. 13
0 to 0.0196" (0 to 0.5 mm)
If the special R410A flare tool is used:
0.0472" (1.2 mm)
If the previous flare tool (clutch-type) is used:
Adjust so that the amount of tube
p
rotrusion is as shown in the figure.
Tube Dia. Tightening Torque
1/4" (6.35 mm) Approx. 120 – 160 lbs·in (140 – 180 kgf· cm)
3/8" (9.52 mm) Approx. 300 – 360 lbs·in (340 – 420 kgf· cm)
1/2" (12.70 mm) Approx. 430 – 540 lbs· in (490 – 610 kgf·cm)
5/8" (15.88 mm) Approx. 590 – 710 lbs· in (680 – 820 kgf·cm)
Apply the provided labels to the indoor and outdoor unit tubing connectors to prevent errors in connections.
Service valve on narrow tube side
Service valve on wide tube side
A
B
C
D
Fig. 14
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 14
Page 15
15
3-6. Insulation of Refrigerant Tubing
To prevent heat loss and wet floors due to dripping of con­densation, both tubes must be well insulated with a
proper insulation material.
The thickness of the insulation should be a minimum 5/16" (8 mm). (Fig. 17)
3-7. Taping the Tubes
(1) At this time, the 2 refrigerant tubes (and electrical wire
if local codes permit) should be taped together with armoring tape. The drain hose may also be included and taped together as 1 bundle with the tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As you wrap the tubing, overlap half of each previous tape turn. (Fig. 18)
(3) Clamp the tubing bundle to wall, using 1 clamp approx.
every 47" (120 cm).
Do not wind the armoring tape too tightly, since this will decrease the heat insulation effect. Also, be sure the con­densation drain hose splits away from the bundle and drips clear of the unit and the tubing.
3-8. Finishing the Installation
After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft from entering. (Fig. 19)
NOTE
IMPORTANT
Indoor unit
Outdoor unit
Spanner
Torque wrench
Fig. 15
Insulation
Min. 5/16" (8 mm)
Thickness: min. 5/16" (8 mm)
Fig. 17
Fig. 18
Clamp
Insulated tubes
Apply putty here
Tubing
Fig. 19
CAUTION
After a tube has been insulated, never try to bend it into a narrow curve, as this may cause the tube to break or crack.
Insulation
Fig. 16
CAUTION
Be sure to match refrigerant tubing and electric wiring between indoor and outdoor units. For more details, refer to “Tubing Check Control” in the Technical & Service Manual.
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 15
Page 16
16
4. Air Purging
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below. Therefore, they must be purged completely.
G pressure in the system rises
G operating current rises
G cooling efficiency drops
G moisture in the air may freeze and block capillary tubing
G water may lead to corrosion of parts in the refrigerant
system
I
Air Purging with a Vacuum Pump (for Test Run)
G In order to protect the earth’s environment, be sure to use
a vacuum pump to perform the air purge. (Never perform an air purge by using the refrigerant gas cylinder or other external gas, or by using the gas inside the outdoor unit.)
Perform the air purge for tubes A, B, C, and D. Use the same procedures for all tubes.
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been properly connected and all wiring for the test run has been completed. Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage.
(2) Using an adjustable wrench or box wrench, remove
the valve caps from the service valve on both narrow and wide tubes.
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide tube service valve. (Fig. 20).
Fig. 20
Fig. 21
CAUTION
Be sure to use a manifold valve for air purging. If it is not available, use a stop valve for this purpose. The “Hi” knob of the manifold valve must always be kept closed.
CAUTION
CAUTION
Before using the vacuum pump adapter, read the vacuum pump adapter manual, and use the adapter correctly.
In order to prevent charging errors with A/C that uses R410A, the screw diameter at the service valve charging port has been changed. When recharging or per­forming other servicing, use the special charging hose and manifold gauge.
G When using a hex wrench to open the spindle, an
extremely small amount of refrigerant may leak. This does not indicate a problem.
G Use a hex wrench of a type to which force can be
easily applied.
Service valve on wide tube side
Service valve on narrow
A
B
C
D
Vacuum pump
Vacuum pump adapter (for preventing reverse flow) (special for R410A)
High-pressure valve
Manifold gauge (special for R410A)
Low-pressure valve
Leave the valve open.
Open
Charging hose (special for R410A)
Hex wrench
With push-pin
HiLo
Cap tightening torque: 170 – 215 lbs·in (200 – 250 kgf·cm) (Tighten by hand, then use a wrench to turn.)
Stopper
Spindle
Screw diameter: 1/2 UNF 20 threads
Valve core
Cap nut tightening torque: 60 – 95 lbs·in (70 – 110 kgf·cm) (Tighten by hand, then use a wrench to turn approximately 30 .)
<Structure of service valve on wide tube side>
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 16
Page 17
17
(4) With the “Lo” knob of the manifold valve open and
high-pressure valve (“Hi”) closed completely, run the vacuum pump. Run the pump until the pres­sure is –101 kPa (–76 cmHg). The operation time for the vacuum pump varies with tubing length and the capacity of the pump. The following table shows the amount of time required for evacuation:
Table 5
The required time in the above table is calculated based on the assumption that the ideal (or target) vac­uum condition is around 10 mmHg abs.
(5) With the vacuum pump still running, close the “Lo”
knob of the manifold valve. Then stop the vacuum pump. Fully close the low-pressure valve and stop the vacuum pump. (Wait 1 – 2 minutes and check that the manifold gauge pointer does not return. If it does return, find and repair the leak, then apply the vacuum again.)
(6) With a hex wrench, turn the valve stem on the nar-
row tube service valve counter-clockwise by 90 degrees (1/4 turn) for 10 seconds, and then turn the stem clockwise to close it again.
(7) With a standard screwdriver, turn the wide tube
service valve stem counterclockwise to fully open the valve.
(8) Turn the narrow tube service valve stem counter-
clockwise to fully open the valve.
(9) Loosen the vacuum hose connected to the wide
tube service port slightly to release the pressure. Then, remove the hose.
(10) Leak test all joints at the tubing (both indoor and
outdoors) with liquid soap. Bubbles indicate a leak. Be sure to wipe off the soap with a clean cloth.
NOTE
CAUTION
Be sure to completely insert the hex wrench before attempting to turn the valve.
Required time for evacuation when capacity
of 100 liter/h vacuum pump is used
20 min. or more
CAUTION
If a CFC gas detector is used, use a special detector for HFC refrigerant (such as R410 and R134a).
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 17
Page 18
18
I Pump Down
G When relocating or disposing of the A/C, request this service from
the dealer where the unit was purchased, or from an appropriate agent. Perform pump-down as described below.
What is pump-down?
G Pump-down refers to recovering the refrigerant gas from the refrig-
erant cycle at the outdoor unit. This work must be performed dur­ing cooling operation. The refrigerant gas cannot be recovered during heating operation.
G During winter, or if the temperature sensor prevents cooling opera-
tion, perform “forced cooling operation.”
Pump-down procedure
(1) Fully close the spindles at the valves on the narrow tube side of
tubes A, B, C and D. (Refer to Fig. 22.)
(2) Connect the manifold gauge to the charging port at the valve on
the wide tube side of tube D. Purge the air from the charging hose. (Refer to Fig. 23.)
(3) Perform cooling operation or forced cooling
operation. When the pressure at the low-pressure side is 0.15 – 0.2 MPa (0.5 – 1 kg/cm
2
G), fully close the spindles at the valves on the wide tube side of tubes A, B, C, and D, and immediately stop operation. (Refer to Fig. 23.) In the winter, the outdoor unit may stop after 5 - 10 minutes of operation. This is in order to protect the indoor unit heat exchanger from freezing and does not indicate a problem.
(4) Disconnect the manifold gauge and the inter-unit tubes, and
attach the caps and flare nuts. At this point, pump-down is com­pleted. (If the caps and flare nuts are not reattached, there is the danger of gas leakage.) (Refer to Fig. 24.)
If pump-down is not possible
If the A/C cannot be operated because of a malfunction or other cause, use a refrigerant recovery device to recover the refrigerant.
In order to protect the earth’s environment, be sure to perform pump-down to recover refrigerant
gas without releasing it into the atmosphere.
Fig. 22
(11) Replace the flare nut on the wide tube service port and fasten the flare nut securely with an adjustable wrench or
box wrench. Next, mount the valve cap and tighten it with a torque wrench (the cap needs to be tightened with the torque of 180 lbs·in (200 kgf·cm)). This process is very important to prevent gas from leaking from the system.
(12) Test run the air conditioner. (See page 23.)
(13) While the air conditioner is running, apply liquid soap to check for any gas leaks around the service valves or caps.
(14) If there is no leakage, stop the air conditioner.
(15) Wipe off the soap on the tubing.
This completes air purging with a vacuum pump and the air conditioner is ready for actual operation.
Fig. 23
C
D
B
A
Manifold gauge
Wide tube side
Cap
Cap
Cap
Cap
After disconnecting the inter-unit tubes, attach the flare nuts with flare bonnets.
Fig. 24
D
C
B
A
Charging port
Narrow tube side
Close
Close
Close
Close
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 18
Page 19
19
5. Wiring Instructions
5-1. General Precautions on Wiring
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each
unit, with a power supply disconnect and circuit break­er for overcurrent protection provided in the exclusive line.
(3) To prevent possible hazard due to insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done tightly and in
accordance with the wiring system diagram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
5-2. Recommended Wire Length and Diameter
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local elec­trical codes. Carefully observe these regulations when car­rying out the installation. Table 6 shows maximum wire lengths for control line and power line and fuse or circuit capacity.
Refer to the wiring system diagram (Fig. 25a or 25b) for the meaning of (A), (B), and (C) in Table 6.
Refer to your local codes or in the absence of local codes see the National Electric Code: ANSI/NFPA70.
NOTE
Table 6
AWG
Max. Power Line Length (ft.)
(A)
Max. Control Line Length (ft.)
(B) (C)
Fuse
or
Circuit Capasity
Model
(#12) (#14)
CMH1972 85 (Max.) 82 (Max.) 20 A
CMH2472 85 (Max.) 82 (Max.) 20 A
CMH3172 85 (Max.) 100 (Max.) 20 A
# ... AWG (American Wire Gauge)
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 19
Page 20
20
WARNING
G Be sure to comply with local codes on running the
wire from the indoor unit to the outdoor unit (size of wire and wiring method, etc.).
G Each wire must be firmly connected. G No wire should be allowed to touch refrigerant
tubing, the compressor, or any moving part.
G Be sure to connect power wires correctly match-
ing up numbers on terminals of the outdoor unit and respective indoor units A – D.
CAUTION
G Be sure to connect the power supply line to the
outdoor unit as shown in the wiring diagram. The indoor unit draws its power from the outdoor unit.
G Do not run wiring for antenna, signal, or power
lines of television, radio, stereo, telephone, secu­rity system, or intercom any closer than 3'4" (1 m) from the power cable and wires between the indoor and outdoor units. Electrical noise may affect the operation.
G To avoid the risk of electric shock, each air conditioner
unit must be grounded.
G For the installation of a grounding device, please
observe local electrical codes.
G Grounding is necessary, especially for units using
inverter circuits, in order to release charged electricity and electrical noise caused by high tension. Otherwise, electrical shock may occur.
G Place a dedicated ground more than 7' (2 m) away from
other grounds and do not have it shared with other electric appliances.
WARNING
Fig. 25a
Fig. 25b
4 indoor units with CMH2472, CMH3172
1
2
3
Terminal
INDOOR UNIT
1
2
3
INDOOR UNIT
1
2
3
1
UNIT B
2
3
4
UNIT C
5
6
7
8
9
1
2
TerminalTerminal
L1
L2
INDOOR UNIT
UNIT A
(A)
(B)
(C)
Terminal
(2P)
Ter m i n al(9P
)
OUTDOOR UNIT
Disconnect switch
230/208V
230/208V
230/208V
230/208V
230/208V
230/208V
230/208V
230/208V
230/208V
Grounding line
Grounding line
Disconnect switch
Field supply
Disconnect switch
Field supply
Field supply
Power supply
Single-phase 230/208VAC 60HZ
Grounding
line
Grounding line
(A)
(B)
(B)
(B)
(B)
(B)
(B)
(C)
(C)
(C)
1
2
3
Terminal
1
UNIT B
2
3
4
UNIT C
5
6
7
UNIT D
8
9
10
11
12
1
2
L1
L2
INDOOR UNIT
UNIT A
(A)
1
2
3
Terminal
INDOOR UNIT
(B)
Terminal
(
2P
)
Terminal(12P
)
OUTDOOR UNIT
Disconnect switch
230/208V
230/208V
230/208V
230/208V
230/208V
230/208V
Grounding line
Grounding line
Field supply
230/208V
230/208V
230/208V
230/208V
1
2
3
Terminal
INDOOR UNIT
(C)
1
2
3
Terminal
INDOOR UNIT
(D)
(Inter-unit)
power line
230/208V
230/208V
Power supply
Single-phase 230/208VAC 60HZ
Grounding line
Grounding line
Grounding line
Disconnect switch
Field supply
Disconnect switch Field supply
Disconnect switch
Field supply
(A)
(B)
(B)
(B)
(B)
(B)
(B)
(B)
(B)
(C)
(C)
(C)
(C)
3 indoor units with CMH1972
5-3. Wiring System Diagram
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 20
Page 21
21
When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten the wire securely tight with the fixing screw of the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the wire about 9/32" (7 mm). See the label (Fig. 26) near the terminal plate.
(2) Using a screwdriver, loosen the terminal screw on
the terminal plate.
(3) Inser t the wire and tighten the terminal screw com-
pletely using a screwdriver.
b) For Outdoor Unit
I For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 15/16" (25 mm). (Fig. 27)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
(4) Shape the loop wire properly, place it on the termi-
nal plate and fix it securely with the removed termi­nal screw using a screwdriver.
I For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the stranded wiring about 3/8" (10 mm) and tightly twist the wire ends. (Figs. 28 and 29)
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connector. (Fig. 28)
(4) Place the ring connector wire, and replace and
tighten the removed terminal screw using a screw­driver. (Fig. 30)
Solid wire
Loop
Insulation
Strip 15/16" (25 mm)
Fig. 27
STRIP SIZE
9/32"
(7 mm)
(ACTUAL
SIZE)
Fig. 26
Stranded wire
Ring connector
Strip 3/8" (10 mm)
Fig. 28
Screw
Ring connector
Terminal plate
Wire
Special washer
Fig. 30
Screw and special washer
Ring connector
Wire
WARNING
Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. There­fore, be sure all wiring is tightly connected.
Twist wire ends
Fig. 29
5-4. How to Connect Wiring to the Terminal
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 21
Page 22
1
2
3
1
2
3
1
2
3
1
2
3
Indoor unit D
Indoor unit B
Indoor unit A
Indoor unit C
Ground
Powe r: Single-phase, 230/208VAC 60HZ
Power switch (not provided)
Outdoor unit A
Terminal board
Label A
Inter-unit cables #14 (not provided)
Terminal board
Inter-unit cables #14 (not provided)
Terminal board
Label B
Label C
Inter-unit cables #14 (not provided)
Terminal board
Inter-unit cables #14 (not provided)
Terminal board
Label D
A
B
C
D
Power cable (not provided) (#12: Less than 85 ft.)
Be sure to perform grounding.
Attach a ground wire to either the outdoor unit or indoor unit. If there is a grounding terminal inside the room, use the grounding screw inside the indoor unit.
Be sure to apply the provided labels to both ends of the inter-unit cables to prevent mis­wiring. The units will not function if the wiring connections are incorrect.
A is the indoor unit with refrigerant tubing that is connected to service valve A (top) of the outdoor unit.
refrigerant tubing that is connected to service valve B (top) of the outdoor unit.
B is the indoor unit with
refrigerant tubing that is connected to service valve C (top) of the outdoor unit.
C is the indoor unit with
refrigerant tubing that is connected to service valve D (top) of the outdoor unit.
D is the indoor unit with
1 2
1 2 3 4 5 6 7 8 9 10 11 12
Power supply (conduit)
Inter Unit (conduit)
# ... AWG (American Wire Gauge)
22
5-5. Wiring Instructions for the Outdoor Unit
G Be sure to correctly align inter-unit cables A, B, C and D.
G Use a dedicated A/C circuit for power. G To make connections to the outdoor unit, remove the
inspection panel and tubing panel.
G Do not bring the inter-unit cables or power cable into
contact with tubing or service valves.
G Use outdoor unit cable fasteners and fasten the inter-
unit cables at the location where the cables are double­sheathed.
G Arrange the wiring so that the inter-unit cables are con-
tained in the inspection panel and tubing panel, as shown in Fig. 31.
CAUTION
Fig. 31
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 22
Page 23
23
Regulations on wire size differ from locality to locality. For field wiring requirements, please refer to your local electri­cal codes. Make sure that the installation fully complies with all local and national regulations.
(1) Remove access panel “C”. (Fig. 32)
(2) Connect the inter-unit and power supply line accord-
ing to the drawing on the panel side.
(3) Be sure to size each wire allowing approx. 4"
(10 cm) longer than the required length for wiring. Store excess wiring inside the cabinet.
(4) When connections are completed, check that all con-
nections are correct as shown in the wiring system diagram on panel side.
(5) Be sure to ground the unit according to your local
codes.
Fig. 32
Lock nut
Conduit plate
Plug
Inter unit (Conduit)
Power supply (Conduit)
Cabinet
Terminal block
Access panel “C”
Fig. 33
Conduit plate
Make sure there is no gap between access panel “C” and the conduit plate.
Access panel C
CAUTION
6. Test Run
Performing a test run
G Refer to the test run procedures in the indoor unit
installation manual.
G Perform the test run separately for each connected
indoor unit. If 2 units are operated simultaneously, it is not possible to correctly check for errors in tubing and wiring.
G If the room temperature is 59°F (15°C) or below, it may
not be possible to check for tubing errors with cooling operation. If this occurs, perform heating operation for each unit individually, and check that warm air is discharged from each unit. If there is cold air mixed in with the warm air, check the tubing connections again.
Checking tubing and wiring
Perform the test run and check that operation is normal. If there is an error in tubing or wiring, the refrigerant may flow to indoor unit B when indoor unit A is operated (for example).
G Stop operation immediately if there is an error in tubing
or wiring. Turn the power (breaker) to OFF, and check whether the inter-unit cables are connected incorrectly, or whether the narrow tubes A and B are connected in reverse. Correct the connections.
G If there is an error in tubing, pump-down must be per-
formed. Be sure to perform pump-down. After making corrections, again purge the air from the tubes.
CAUTION
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 23
Page 24
24
7. Connecting a Home Automation device
The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will be used, connect it to this terminal.
8. Installation Check Sheet
The strength of the installation location is sufficient to support the A/C weight.
The indoor and outdoor units are installed level and vertically.
The power and voltage are as specified.
Inter-unit cables are securely fastened to the terminal board.
Inter-unit cables are securely fixed.
The power cord and inter-unit cables are not connected anywhere along their paths.
The ground wire is securely connected.
An air purge of the refrigerant circuit has been conducted.
A leak test of the tubing connections has been performed.
Thermal insulation has been applied to the tubing connections.
Drain connections are secure and water drains properly.
Putty has been used to close the hole in the wall.
All service valves are fully open.
Remote controller signals are being positively received.
05-352 KMHS0772_outdoor 3/17/06 2:56 PM Page 24
Loading...