INDOOR MODEL No.PRODUCT CODE No.OUTDOOR MODEL No.PRODUCT CODE No.
XS4232854 016 10
TS4232854 016 09
Indoor UnitOutdoor Unit
C4232854 016 12
CL4232854 016 11
C4232854 016 12
CL4232854 016 11
FILE NO.
XS4232C4232
CL4232
TS4232
85464869178000REFERENCE NO. SM830078
Important
Please Read Before Starting
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
For safe installation and trouble-free operation, you must :
ⓦ Carefully read this instruction booklet before beginning.
ⓦ Follow each installation or repair step exactly as shown.
ⓦ Observe all local, state, and national electrical codes.
ⓦ Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result in
severe personal injury or death.
This symbol refers to a hazard or
CAUTION
unsafe practice which can result in
personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites
and maintenance conditions. If you require help for a special
problem, contact our sales/service outlet or your certified dealer
for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow
the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
……………………………………………………………………
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions
when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
……………………………………………………………………
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to
reduce strain on your back. Sharp edges or thin aluminum fins
on the air conditioner can cut your fingers.
When Installing
……………………………………………………………………
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to walls
and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents water
damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys-tems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
……………………………………………………………………
• Ventilate the room well, in the event that refrigerant gas
leaks during the installation. Be careful not to allow contact
of the refrigerant gas with a flame as this will cause the
generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the
flare and union tubes before connecting them, then tighten
the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be
either narrow or wide. Therefore, to avoid confusion the
refrigerant tubing for your particular model is specified as either
“narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
……………………………………………………………………
• Turn the power OFF at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site when installation is finished. Check that no
metal scraps or bits of wiring have been left inside the unit.
CAUTION
• Ventilate any enclosed areas when installing or testing the
refrigeration system. Contact of refrigerant gas with fire or
heat can produce poisonous gas.
• Confirm after installation that no refrigerant gas is leaking. If
the gas comes in contact with a burning stove, gas water
heater, electric room heater or other heat source, it can
cause the generation of poisonous gas.
– 2 –
SM830078
Table of Contents
1.OPERATING RANGE ....................................................................................... 5
(2) A Sensor is Defective................................................................................ 61
(3) Operation of Major Electrical Parts ........................................................... 61
(4) Checking the Electrical Components ........................................................ 62
– 3 –
SM830078
Introduction:
This manual will help you understand and service the air conditioner. To help you find the information you need,
we have divided it into 5 main sections. Each section is divided into chapters with charts, tables and explanations to help you find and repair problems.
❑Section 1: Specifications, tells you about the physical and electrical make up of the unit, as well
as its heating and cooling capacities. Look in this section to find the correct values for
components and functions.
❑Section 2: Processes and Functions, explains each different part of the cooling and heating
cycle, and how each control function reacts to changing conditions to keep the room at the set
temperature range.
❑Section 3: Electrical Data, which has fold-out schematic and wiring diagrams so you can find
the parts you need to check when something is wrong, and see how they should be connected.
❑Section 4: Service Procedures, has two main parts, a
specific component to replace or adjust, and a chapter with specific procedures and values to
guide you in checking the electrical components in the unit.
Read Me First!
diagnostic
chapter to help you find the
HOW TO USE THIS MANUAL
You can use this manual both as a
construction of this unit, and as a source of information to help you set up and maintain the unit.
When this unit is not working properly, and the cause is not known, you can use the procedures in
Section 3: Servicing Procedures to find the problem, fix it, and restore the unit to its proper functioning.
This air conditioner has many helpful self diagnostic features to help you identify problem areas quickly.
So you will be ready when a problem happens, we suggest you look this manual over and become familiar with it
by following these steps:
1.Look at the TABLE OF CONTENTS to get an idea of what is in this manual and where to find it.
2.Look at the chapter about TROUBLE SHOOTING, so you are familiar with the way the flow
charts work. They are designed to guide you quickly through the possible causes for each kind of
problem that is likely to happen to the Unit. Particularly read the introduction to this section, and
the parts about the self-diagnosis and error codes which show on the display.
3.Look at the chapter about CHECKING ELECTRICAL COMPONENTS. You already know
about most of these procedures. This chapter gives you the specific values and methods for
these components. If you don’t know some of these procedures, you can easily learn them here.
4.Read the Instruction Manual! The Instruction Manual is included here because it helps you help
the user to set the temperature controls properly and know how to take care of any simple
problems that may happen, as well as know when to call for service. The Instruction Manual also
has illustrations, care, and installation information not found in the rest of the service manual. It is
short, and if you read it carefully, you will be able to answer the customers questions easily, and
also know the most efficient ways for setting times and temperatures.
reference
to find specific information about the capacity, functions and
Please use this manual to make your work easier, keep the air conditioner functioning well, and keep your
customers satisfied.
– 4 –
SM830078
1. OPERATING RANGE
XS4232, TS4232 / C4232
TemperatureIndoor Air Intake Temp.Outdoor Air Intake Temp.
Maximum95 °F DB / 71 °F WB115 °F DB
Minimum67 °F DB / 57 °F WB 67 °F DB
XS4232, TS4232 / CL4232
TemperatureIndoor Air Intake Temp.Outdoor Air Intake Temp.
Maximum95 °F DB / 71 °F WB115 °F DB
Minimum67 °F DB / 57 °F WB 0 °F DB
– 5 –
SM830078
2. SPECIFICATIONS
(1)Unit Specifications
MODEL No.Indoor UnitXS4232
POWER SOURCE230 - 208 V / 1 Phase / 60 Hz
PERFORMANCECooling
CapacityBTU / h42,00040,500
Air circulation (Hi)
Moisture removal (High)Pints / h14.614.8
ELECTRICAL RATINGS
Voltage ratingVAC230208
Available voltage rangeVAC187 - 253
Running amperes*A20.821.1
Max. running amperes**A24.125.3
Power inputW4,2304,120
Power factor%8894
S.E.E.R
Max. starting amperesA134134
Maximum fuse sizeA50
FEATURES
ControlsMicroprocessor
TimerON / OFF 24-hours & Program
Fan speed Indoor / Outdoor3 and Automatic control / 2 (Auto)
Air deflectionHorizontal / Vertical– / Automatic
Air filterWashable, easy access, long life (2,500 hr)
Remote controller (Accessory)RCS - 5PS4U
Refrigerant controlCapillary tube
Refrigerant tubing connectionsFlare type
Drain pump / Drain pipe trade sizeMax. head 9-27/32 in. above drain connection / 3/4 in. (26.7 mm)
CompressorScroll
Operation sound
REFRIGERANT TUBING
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)50 (15)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant tubeNarrow tubein. (mm)3 / 8 (9.52)
Rating conditions (*): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB
Full load conditions (**): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
– 6 –
SM830078
2. SPECIFICATIONS
(1)Unit Specifications
MODEL No.Indoor UnitXS4232
POWER SOURCE230 - 208 V / 1 Phase / 60 Hz
PERFORMANCECooling
CapacityBTU / h42,00040,500
Air circulation (Hi)
Moisture removal (High)Pints / h14.614.8
ELECTRICAL RATINGS
Voltage ratingVAC230208
Available voltage rangeVAC187 - 253
Running amperes*A20.821.1
Max. running amperes**A24.125.3
Power inputW4,2304,120
Power factor%8894
S.E.E.R
Max. starting amperesA134134
Maximum fuse sizeA50
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0 °F
TimerON / OFF 24-hours & Program
Fan speed Indoor / Outdoor3 and Automatic control / 3 (Auto)
Air deflectionHorizontal / Vertical– / Automatic
Air filterWashable, easy access, long life (2,500 hr)
Remote controller (Accessory)RCS - 5PS4U
Refrigerant controlCapillary tube
Refrigerant tubing connectionsFlare type
Drain pump / Drain pipe trade sizeMax. head 9-27/32 in. above drain connection / 3/4 in. (26.7 mm)
CompressorScroll
Operation sound
REFRIGERANT TUBING
Limit of tubing lengthft. (m)165 (50)
Limit of tubing length at shipmentft. (m)50 (15)
Limit of elevation differenceft. (m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant tubeNarrow tubein. (mm)3 / 8 (9.52)
Rating conditions (*): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB
Full load conditions (**): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
– 7 –
SM830078
2. SPECIFICATIONS
(1)Unit Specifications
MODEL No.Indoor UnitTS4232
Outdoor UnitC4232
POWER SOURCE230 - 208 V / 1 Phase / 60 Hz
PERFORMANCECooling
CapacityBTU / h42,00040,500
kW12.3211.88
Air circulation (Hi)
Moisture removal (High)Pints / h14.814.6
ELECTRICAL RATINGS
Voltage ratingVAC230208
Available voltage rangeVAC187 - 253
Running amperes*A20.621.0
Max. running amperes**A21.422.7
Power inputW4,1904,100
Power factor%8894
S.E.E.R
Max. starting amperesA134134
Maximum fuse sizeA50
FEATURES
ControlsMicroprocessor
TimerON / OFF 24-hours & Program
Fan speed Indoor / Outdoor3 and Automatic control / 2 (Auto)
Air deflectionHorizontal / VerticalManual / Automatic
Air filterWashable, easy access, long life (2,500 hr)
Remote controller (Accessory)RCS - 5PS4U
Refrigerant controlCapillary tube
Refrigerant tubing connectionsFlare type
Drain pipe trade size3 / 4 in. (26.7 mm)
CompressorScroll
Operation soundIndoor - Hi / Me / LodB - A42 / 40 / 35
REFRIGERANT TUBING
Limit of tubing lengthft.(m)165 (50)
Limit of tubing length at shipmentft.(m)50 (15)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant tubeNarrow tubein. (mm)3 / 8 (9.52)
Rating conditions (*): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB
Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
cu.ft. / min.
BTU / Wh
900800
10.210.3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 8 –
SM830078
2. SPECIFICATIONS
(1)Unit Specifications
MODEL No.Indoor UnitTS4232
Outdoor UnitCL4232
POWER SOURCE230 - 208 V / 1 Phase / 60 Hz
PERFORMANCECooling
CapacityBTU / h42,00040,500
kW12.3211.88
Air circulation (Hi)
Moisture removal (High)Pints / h14.814.6
ELECTRICAL RATINGS
Voltage ratingVAC230208
Available voltage rangeVAC187 - 253
Running amperes*A20.621.0
Max. running amperes**A21.422.7
Power inputW4,1904,100
Power factor%8894
S.E.E.R
Max. starting amperesA134134
Maximum fuse sizeA50
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0 °F
TimerON / OFF 24-hours & Program
Fan speed Indoor / Outdoor3 and Automatic control / 3 (Auto)
Air deflectionHorizontal / VerticalManual / Automatic
Air filterWashable, easy access, long life (2,500 hr)
Remote controller (Accessory)RCS - 5PS4U
Refrigerant controlCapillary tube
Refrigerant tubing connectionsFlare type
Drain pipe trade size3 / 4 in. (26.7 mm)
CompressorScroll
Operation soundIndoor - Hi / Me / LodB - A42 / 40 / 35
Outdoor - HidB - A56
REFRIGERANT TUBING
Limit of tubing lengthft.(m)165 (50)
Limit of tubing length at shipmentft.(m)50 (15)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant tubeNarrow tubein. (mm)3 / 8 (9.52)
Rating conditions (*): Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB
Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
cu.ft. / min.
BTU / Wh
900800
10.210.3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 9 –
SM830078
2. SPECIFICATIONS
(2)Major Component Specifications
(A)Indoor Unit
MODEL No.XS4232
Source230 - 208 V / 1 phase / 60 Hz
Remote controller (Accessory)RCS - 5PS4U
Controller P. C. B Ass'yCR - TS2432
Control circuit fuse250 V, 3 A
Switch Ass'ySW - X363GS
Fan (Number … diameter)in.(mm)Turbo (1…19-9/32 (490))
Fan motor
ModelSFG6X - 61A3P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm6 … 560
Nominal outputW60
Coil resistanceΩBRW - WHT:71.1,ORG - YEL:22.7
(Ambient temperature 68 °F)WHT - VLT:8.7,VLT - PNK:43.2
VLT - ORG :13.3,YEL - BLK: 54.32
Safety device
Operating temperatureOpen°F266± 14.4
Close°F174.2 ± 27
Run capacitorVAC,µF440 V , 6 µF
Heat exchanger
CoilAluminum plate fin / Copper tube
Rows … Fins per inch2 … 14.9
Face areaft.
Panel
Model No.PNR - XS3632
Indicator Lamp Ass'yIND - XS3632
Auto louver motorMT8 - 3C
Auto louver motor … RatedV, W, rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16,430 Ω± 8 %
2
(m2)5.17 (0.48)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 10 –
SM830078
2. SPECIFICATIONS
(2)Major Component Specifications
(A)Indoor Unit
MODEL No.TS4232
Source230 - 208 V / 1 phase / 60 Hz
Remote controller (Accessory)RCS- 5PS4U
Controller P. C. B Ass'yCR - TS2432
Control circuit fuse250 V, 3 A
Switch Ass'ySW - X363GS
Fan (Number … diameter)in.(mm)Centrifugal (4 ... 5-29/32(150))
Fan motor
ModelKFG4X - 101C6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm1,015
Nominal outputW100
Coil resistanceΩBRW - WHT:61.05,ORG - YEL:13.23
(Ambient temperature 68 °F)WHT - VLT:9.955 ,YEL - BLK:19.25
VLT - ORG :9.576 ,BLK - PNK: 10.81
Safety device
Operating temperatureOpen°F266± 14.4
Close°F174.2 ± 27
Run capacitorVAC,µF440 V , 4 µF
Heat exchanger
CoilAluminum plate fin / Copper tube
Rows … Fins per inch3 … 14.9
Face areaft.
Auto louver motor
Model No.MT8 - 3C
Auto louver motor … RatedV, W, rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16,430 Ω± 8 %
2
(m2)3.51 (0.326)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 11 –
SM830078
2. SPECIFICATIONS
(2)Major Component Specifications
(B)Outdoor Unit
MODEL No.C4232
Source230 - 208 V / 1 phase / 60 Hz
CompressorScroll (Hermetic)
ModelZR47KC - PFV
Source230 - 208 V / 1 phase / 60 Hz
Nominal outputW4,270
Compressor oilcc1,240
Coil resistance (Ambient temperature 77 °F)ΩR - W : 0.475 , S - W : 1.850
Safety deviceInternal type
Air intake grille
Air outlet
Refrigerant liquid line (ø3/8")
Refrigerant gas line (ø3/4")
Drain connection
Power supply entry
For discharge duct
Humidifier (option) mounting hole
Suspension bolt mounting
– 18 –
1813_X_S
SM830078
3. DIMENSIONAL DATA
Drain connection
Drain connection for left side
Refrigerant liquid line (3/8") Flare connection
Refrigerant gas line (3/4") Flare connection
Hole for rear side refrigerant tubing
Hole for through-the-wall refrigerant tubing (ø3-15/16" hole)
Hole for fresh air intake (Knockout hole)
Hole for right side refrigerant tubing (Knockout hole)
Hole for left side drain connection (Knockout hole)
Hole for power supply (Conduit size 1/2")
Infrared rays receiver for wireless remote controller
Cutting position for fresh air intake
1341_TS_I
Dimension : inch
Air intake
Air outlet
2 ft. or more
Hole for wall-through piping (View from front)
2-13/3223/32
9-7/8
6-25/32
9-7/16
8-7/16
62
26-3/8
11-1/32
12-7/32
61-7/32
7-3/4
12-19/32 6-5/16
5-15/16
• Remote controller (Accessory)
5-1/2
7-3/4
6-11/16
4-1/2
7-1/4
7-3/4
1-3/326-5/16
3-5/324-3/4
5-3/4
7-7/32
4-1/16
9-7/8
5-9/16
1-3/859-1/4 (Suspension bolt hole pitch)
3-1/2
5-25/32
2-25/325-3/16
11-1/32
3-15/161-31/32
3-3/8
6-3/327-31/32
Front
(Service space)(Service space)
Holes in the rear side (View from front)
(Suspension bolt hole pitch)
10
or more
10
or more
(1)Indoor Unit: TS4232
– 19 –
SM830078
3. DIMENSIONAL DATA
(2)Outdoor Unit: C4232, CL4232
1-31/321-31/32
4-21/64266-11/16
1-3/16
13-3/8
48-5/8
37
15-3/4
14-31/3213/32
22-27/32
23-29/32
– 20 –
Dimension : inch
Hole for anchor bolt (4-ø13)
Refrigerant tube joint (narrow tube)
Flare connection 3/8 in (9.52 mm)
Refrigerant tube joint (wide tube)
Flare connection 3/4 in (19.05 mm)
Refrigerant tubing inlet
Power supply inlet
Limit of elevation differencethan indoor unit
between the 2 units
Outdoor unit is lower
(ft.)100
than indoor unit
Max. allowable tubing length at shipement(ft.)50
Required additional refrigerant*
1
(oz./ft.)0.86
Refrigerant charged at shipment(lbs.)9.7
C4232
CL4232
Tubing length (L)
OUTDOOR
UNIT
0711_M_I
No additional charge of compressor oil is necessary.
*1If total tubing length becomes 50 to 165 ft., charge additional refrigerant (R22) by 0.86 oz./ft..
– 33 –
SM830078
8. INSTALLATION INSTRUCTIONS
2)Selecting the Installation Site
Indoor Unit
AVOID:
ãareas where leakage of flammable gas may
be expected.
Ceiling-Mounted Type
Ceiling
ãplaces where large amounts of oil mist exist.
ãdirect sunlight.
ãlocations near heat sources which may
affect performance of the unit.
ãlocations where external air may enter the
room directly. This may cause “sweating”
on the air discharge ports, causing them to
spray or drip.
ãlocations where the remote control unit will
be splashed with water or affected by
dampness or humidity.
ãinstalling the remote control unit behind
curtains or furniture.
ãlocations where the receiver in the indoor
unit is exposed to the inverter lamp light.
Faulty operation of the unit occurs.
DO:
ãselect an appropriate position from which
every corner of the room can be uniformly
cooled.
ãselect a location where the ceiling is strong
enough to support the weight of the unit.
Wall
Min.10 inch
NOTE
The rear of the indoor unit can be installed flush
against the wall.
3 ft.
Front view
Air
discharge
Min.2ft.
Side view
Recessed Type
3 ft.
3 ft.
Min.10 inch
Ceiling
Air intake
1379_T_I
3 ft.
3 ft.
ãselect a location where tubing and drain pipe
have the shortest run to the outdoor unit.
ãallow room for operation and maintenance as
well as unrestricted air flow around the unit.
ãinstall the unit within the maximum elevation
difference above or below the outdoor unit
and within a total tubing length from the
outdoor unit as detailed in Table 1.
ãallow room for mounting the remote control
unit about 3 ft. off the floor, in an area that
is not in direct sunlight nor in the flow of
cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from
the floor to the ceiling is greater than 10 ft..
– 34 –
1330_X_S
SM830078
8. INSTALLATION INSTRUCTIONS
Outdoor Unit
AVOID:
ãheat sources, exhaust fans, etc. (Fig. 2)
ãdamp, humid or uneven locations.
DO:
ãchoose a place as cool as possible.
ãchoose a place that is well ventilated and
outside air temperature does not exceed
maximum 115°F constantly.
ãallow enough room around the unit for air
intake/ exhaust and possible maintenance. (Fig. 3)
ãprovide a solid base; about 6 inch above
ground level to reduce humidity and
possible water damage in the unit and
decreased service life. (Fig. 4)
ãuse lug bolts or equivalent to bolt down
unit, reducing vibration and noise.
Min.
1 inch
Hot air
4 in.
Outdoor
unit
Min. 2 ft.
Fig. 2
Min.
1 inch
0931_C_I
Fig. 3
Exhaust fan
Heat source
0591_C_I
Obstacle above
Min.
7 ft.
Air
discharge
Ground
0932_C_I
In case of multiple installations
Unit spacing if air discharge chamber is not used.Unit spacing when air discharge chamber is used.
Min. 4 ft.Min. 4 ft.Min. 5 ft.
Min. 1 ft.
Min. 12 ft.
Min. 8 inch
If you would like to make the separation smaller on the air
discharge side, use an air discharge chamber.
You can install any number of units side-by -side.
Min. 4 ft.
Min. 1 ft. 2 inch
Min. 1 ft. 2 inch
Only up to 3 units can be installed side-by-side under the above
conditions. The next group must be spaced at least 1 ft. away
from the first group.
Concrete block
4 inch × 1 ft. 4 inch
beams or equal
Min. 8 inch
Air in
Air
discharge
Anchor bolts
(4 pieces)
Min. 1 ft.
Fig. 4
Min. 4 ft.
Air
discharge
chamber
Min. 1 ft.
0933_C_S
Air in
Min. 6 inch
0934_C_I
– 35 –
SM830078
8. INSTALLATION INSTRUCTIONS
I
Air Discharge Chamber for Top Discharge
Install the air-discharge chamber in the field when:
ãit is difficult to keep a space of minimum 2
ft. between the air-discharge outlet and
the obstacle.
ãthe air-discharge outlet is facing the side-
walk and discharged hot air can annoy
the passers-by. Refer to Fig. 5.
Wind Shield for “CL” Model
IMPORTANT
It is recommended to use wind shields for
“CL” model (Fig. 6). “CL” model is designed
to use in low outdoor temperature conditions.
General
When the outdoor unit is installed in a position
exposed to strong wind (like seasonal winds
with low air temperature in winter), wind shield
must be installed on the outdoor unit.
This unit is designed so that the fan of the
outdoor unit runs at low speed when the air
conditioner is operated at low outdoor air
temperatures. When the outdoor unit is exposed to strong wind, the system pressure
drops because of the freeze protector.
For outer dimensions of wind shield, please
see Fig. 7.
22-5/16"
3-ø2-3/8" hole
Air discharge
0426_C_I
Fig. 5
Wind shield
(air discharge side)
Front
0935_C_I
Fig. 6
Recommended outer dimensions of wind shield
(field supply)
8-ø1/4" hole
11-13/16"
21-13/16"
43-15/16"
9-7/8"9-7/8"17-3/4"3-15/16"
5-3/16"
23-5/16"
CL3032, 3632CL2432
5-5/32"
1352_C_
21-13/16"
CL4232
– 36 –
3 - ø1-9/16" hole
9-27/32"21-5/8"15/16"
6 - ø15/64" hole
Fig. 7
22-7/16"1/2"
23-15/32"
5-3/16"
5-5/32"9-27/32"9-27/32"1-7/32"
0936_C_I
SM830078
8. INSTALLATION INSTRUCTIONS
3)Electrical Wiring
General Precautions on Wiring
(1) Before wiring, confirm the rated voltage
of the unit as shown on its nameplate,
then carry out the wiring closely following
the wiring diagram.
(2) Provide a power outlet to be used exclu-
sively for each unit, and a power supply
disconnect and circuit breaker for
overcurrent protection should be provided in the exclusive line.
(3) To prevent possible hazards from insula-
tion failure, the unit must be grounded.
(4) Each wiring connection must be done in
accordance with the wiring system diagram. Wrong wiring may cause the unit
to misoperate or become damaged.
(5) Do not allow wiring to touch the refriger-
ant tubing, compressor, or any moving
parts of the fan.
(6) Unauthorized changes in the internal
wiring can be very dangerous. The manufacturer will accept no responsibility for
any damage or misoperation that occurs
as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from
locality to locality. For field wiring rules,
please refer to your LOCAL ELECTRICAL CODES before beginning. You must
ensure that installation complies with all
relevant rules and regulations.
(8) To prevent malfunction of the air condi-
tioner caused by electrical noise, care
must be taken when wiring as follows:
ã The inter-unit control wiring and the remote
control wiring (option) should be wired
apart from the inter-unit power wiring.
ã It is recommended that shielding wires or
twisted pair wires be used for the remote
control and the inter-unit control wiring if
the air conditioner is installed where it is
exposed to the influence of electrical and/
or electro-magnetic noise.
Recommended Wire Length and Wire Diameter for Power Supply System
Power Supply Terminal Base
(Outdoor Unit)
Capacity
1
2
G
4
(A)
L1
L2
G
1
2
G
Ground
4
Time Delay
Fuse or
Circuit
Capacity
Disconnect sw
(Field supply)
(B)
(A)*1 Power Supply
Models
C4232, CL423265 ft. (AGW #10)164 ft.50 A50 AAWG #6
*1 Refer to the Wiring System Diagrams (See below diagram) for the meaning of “A”, “B”.
AWG = American Wire Gauge
NOTE
(B)*1 Inter-unit
Wiring
AGW #14
Indoor UnitOutdoor Unit
To access the electrical component box,
open the air intake grille and remove the
electrical component box cover.
Wiring System Diagram
Outdoor Unit : “C”, “CL” models
Single-phase
60 Hz, 208 / 230 V
Compressor Motor
Outdoor Fan Motor
Outdoor Fan Motor Thermal Protector
Compressor Motor Magnetic Contactor
High Pressure Switch
Fan Speedcontrol Thermostat
Running Capacitor
Auxiliary Relay
Connector
Terminal Plate
Compressor Motor
Crankcase Heater
Outdoor Fan Motor
Outdoor Fan Motor Thermal Protector
Compressor Motor Magnetic Contactor
Power Transformer
Thermistor (Outdoor Temperature)
Running Capacitor
Auxiliary Relay
Auxiliary Relay
Outdoor Controller
52C
• Schematic Diagram
F1 (3A)
1
RY2
HLM
FMO2
RC3
RY1
7591
2Y
657
1
2
13
RY3
3Y
2Y1Y4Y
1
52C
4142
1
1Y
63PH
2
F2 (3A)
3
3
52C
1413
3
49FO1
4
3
49FO2
4
3
COMCOM
3Y
657
FMO1
1 2
RC2
4Y
RY1
RY2
RY3
CR-CL2432
Controller
Temp
+12V
L
PRY
M
SEC
HGBV
TH
1
2
Outdoor
Temperature
3
AC 208V
1
1
AC 14V
2
TR
230V
SymbolsDescription
F1, 2
63PH
Fuse
High Pressure Switch
Terminal Plate
Connector
Terminal
– 46 –
S 854-2-5268-897-00-0 (CL4232)
SM830078
11. PROCESSES AND FUNCTIONS
(1)Room Temperature Control
The Unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF.
This process is controlled by the thermostat located in the remote control unit.
The figures on this and the next pages show how each part of the system performs when the
room temperature changes and the thermostat activates the compressor to start (thermo ON)
or stop (thermo OFF). Fig. 8 shows about the cooling cycle.
ROOM TEMPERATURE
WITHIN 3 MINUTE
MORE THAN 3 MINUTES
S. T.+ 1°F
SET TEMP. T°F
(S.T.)
COMPRESSOR
INDOOR FAN
OUTDOOR FAN
THERMO OFF
3 MINUTES
ON
ONON
THERMO ON
MORE THAN
5 MINUTES
OFF
SET SPEED (MANUAL)
OFFOFF
ONON
THERMO OFF
OFF
Fig. 8
Chart Summary and Explanations
❑Once the compressor starts, it keeps running for 5 minutes.
❑Once the compressor stops, it will not start running again for 3 minutes.
❑If you change the operation mode during the cooling cycle, the control circuit stops the
compressor for 3 minutes.
❑For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,
the compressor is not controlled by the room sensor.
❑Thermo ON: When room temperature rises 1 °F above the set temperature T˚, (T ˚+1 °F):
Compressor ➞ON
❑Thermo OFF: When the room temperature is equal to or below the set temperature T˚:
Compressor ➞OFF
THERMO ON
ON
1028_X_S
– 47 –
SM830078
11. PROCESSES AND FUNCTIONS
(2)Freeze Prevention
Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the
efficiency of the unit, and frost buildup on the coil blocks cool air circulation from the indoor
unit’s fan.
INDOOR COIL
TEMPERATURE
MORE THAN 10 MINUTES
FREEZE
PREVENTION
6 MINUTES10 MINUTES
FREEZE
PREVENTION
6 MINUTES
30°F
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
ON
ON
(THERMO OFF)
OFF
OFFOFF
SET SPEED
ON
ON
(THERMO ON)
OFF
ON
ON
1029_X_S
Fig. 9
(3)Drain Pump Control
Drain pump operates when compressor starts to operate or when Float Switch turns off.
FLOAT SWITCH
ON: low water level
OFF: high water level
COMPRESSOR
DRAIN PUMP
OUTDOOR FAN
INDOOR FAN
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
SET SPEED
– 48 –
OFF
20 MINUTES
OFF
ON
OFF
ON
ON
ON
0609_X_S
Fig. 10
SM830078
11. PROCESSES AND FUNCTIONS
(4)Outdoor Fan Speed Control
1)C4232 Type
• In low outdoor temperature, the outdoor fan is set automatically from HIGH to LOW to
prevent the indoor heat exchanger from freezing.
• When the outdoor temperature falls below 78 °F, the outdoor fan is set from HIGH to
LOW automatically. When the outdoor temperature rises to 82 °F, the outdoor fan is
set from LOW to HIGH automatically.
2)CL4232 Type
• In low outdoor temperature, the outdoor fan is set automatically from HIGH to MED,
LOW to prevent the indoor heat exchanger from freezing.
• When the outdoor temperature falls below 77 °F, the outdoor fan is set from HIGH to
MED automatically. When the outdoor temperature rises to 81 °F, the outdoor fan is
set from MED to HIGH automatically.
• When the outdoor temperature falls below 59 °F, the outdoor fan is set from MED to
LOW automatically. When the outdoor temperature rises to 63 °F, the outdoor fan is
set from LOW to MED automatically.
• When the outdoor temperature falls below 47 °F, the outdoor upper fan is set from
LOW to OFF and Lower fan is set from LOW to MED antomatically. When the outdoor
temperature rises to 50 °F, the outdoor upper fan is set from OFF to LOW and Lower
fan is set from MED to LOW antomatically.
870
380
Upper fan: OFF
Lower fan: M
FAN ROTATION RPM
230
Upper fan: M
Lower fan: M
Upper fan: L
Lower fan: L
475059637781
OUTDOOR AIR TEMPERATURE °F DB
Upper fan: H
Lower fan: H
1344_X_S
Fig. 11
– 49 –
SM830078
12. SERVICE PROCEDURES
(1)Troubleshooting
1)Check before and after Troubleshooting
Many problems may happen because of wiring or power supply problems, so you
should check these areas first. Problems here can cause false results in some of
the other tests, and so should be corrected first.
11
1Check power supply wiring
11
(a) Single-phase
❑Check that power supply wires are correctly connected to terminal No. 1
through No. 4 on the 4P terminal plate in the indoor unit and L1 and L2 on
the 6P terminal in the outdoor unit.
22
2Check inter-unit wiring
22
❑Check that inter-unit control wiring (AC 230 - 208 V Line voltage) is cor-
rectly connected between the indoor unit and outdoor unit.
Single-phase outdoor unit
Disconnect SW
Indoor UnitOutdoor Unit
(Field supply)
1
2
G
Ground
4
Inter-Unit
Wiring
(Line voltage)
B
Fig. 12
1
2
G
4
L1
L2
G
Power supply
A
Ground
1089_M_I
33
3Check power supply
33
❑Check that voltage is within the specified range (±10 % of the rating).
❑Check that power is being supplied.
If the following troubleshooting must be done with power being supplied, be
careful not to touch any uninsulated live part that can cause ELECTRIC
SHOCK.
44
4Check the lead wires and connectors in indoor and outdoor units.
44
❑Check that the sheath of lead wires is not damaged.
❑Check that the lead wires are firmly connected at the terminal plate.
❑Check that the wiring is correct.
55
5Reference
55
•Condition of general cooling operation (Thermo. ON)
SWEEP .................. ON
Indoor fan speed .... HIGH
– 50 –
SM830078
12. SERVICE PROCEDURES
2)Air Conditioner does not Operate
11
1Circuit breaker trips (or fuse blows).
11
(a) When the circuit breaker is set to ON, it is tripped soon.
• There is a possibility of ground fault.
• Check insulation resistance.
If resistance value is 1 MΩ or less, it is a defect of insulation.
(Example)
13
Outdoor
unit
L1
Circuit
breaker
*Set the circuit breaker to OFF.
Power
supply
cords
+
+
Ground
L2
G
1
2
G
4
2
4
+
+
+
Inter-unit
power line
+
+
+
Indoor
unit
1
2
G
4
1
Remove power supply cords
from the terminal plate in
the outdoor unit.
• Check insulation resistance
of power supply cords.
OK
Remove inter-unit power line
2
from the terminal plate in
the outdoor unit.
• Check insulation resistance
of outdoor unit.
OK
3
Remove inter-unit power line
from the terminal plate in
the indoor unit.
• Check insulation resistance
of indoor unit.
NO
NOInsulation of
NO
Execute
rewiring.
outdoor unit
is defective.
Insulation of
indoor unit
is defective.
• Check insulation
resistance of
electrical parts
in the outdoor unit.
• Check insulation
resistance of
electrical parts
in the indoor unit.
OK
Inter-unit power lines are
defective.
Execute
rewiring.
1340_X_S
SM830078
– 51 –
12. SERVICE PROCEDURES
(b)
Circuit breaker trips in several minutes after turning the air conditioner on.
• There is a possibility of short circuit.
• Check capacity of circuit
breaker.
Is capacity of circuit
breaker sufficient ?
• Check resistance of
outdoor fan motor winding.
• Check resistance of
compressor motor winding.
22
2Neither indoor unit nor outdoor unit runs.
22
NO
A. Power is not supplied
Circuit breaker
• Check power supply.
Is power being supplied
to outdoor unit ?
NO
is tripped.
Power failure.
Replace it with a
suitable one.
(= larger capacity)
0614_X_S
Reset the breaker.
Wait for recovery
or consult power
supply company.
0615_X_S
B. Check remote control unit.
• Try to run both indoor and
outdoor units with another
remote control unit.
OK
The other remote control
unit is defective.
NO
Refer to item C.
0616_X_S
SM830078
– 52 –
12. SERVICE PROCEDURES
C. Check “Operation selector” switch in the indoor unit.
• Has “Operation selector”
switch been set to ON
YES
position ?
NO
Set “Operation selector”
switch to ON.
But neither unit runs.
Switch Ass’y or P.C.B.
Ass’y in the indoor unit
is defective.
D. Check compressor motor protectors.
(a) High pressure switch (63PH)
• Check high pressure switch.
Does high pressure switch
actuate ? (63PH)
IND. LAMP Ass’y or P.C.B.
Ass’y in the indoor unit
is defective.
0617_X_S
Disconnect the socket from 2P (WHT) connector.
Check the continuity between No.1 and No.2 poles
of the socket.
YES
• Is outdoor heat exchanger
coil dirty or are there
obstacles near air suction
inlet of outdoor unit ?
NO
• Check if outdoor fan rotates.
Refer to “Only outdoor fan
does not run.”
E. Transformer in indoor unit.
• Check resistance of
transformer winding. (TR1)
1033_X_S
YES
Clean heat exchanger coil
or remove obstacles.
0618_X_S
– 53 –
SM830078
12. SERVICE PROCEDURES
F.Check. auxiliary relay. (1Y or 2Y)
• Check coil resistance of
auxiliary relay.
(1Y or 2Y)
G. Check indoor fan motor thermal protector (49FMI)
• Disconnect the socket from 9P (WHT) connector.
• Check the continuity
between No. 8 and No.9
poles of the 9P socket.
No continuity.
The thermal protector (49FMI)
is operated.
• Check fan rotation.
Rotate the fan gently once
or twice by hand.
OK
• Check fan motor capacitor.
0620_X_S
Fan cannot
be rotated.
Check fan casing
for foreign matter
on the inside.
Fan motor burnout
or foreign matter
in bearing.
Remove foreign
matter or repair.
Repair or replace.
0621_X_S
H. Check fuse on the P.C.B. Ass’y in the indoor unit.
• Check fuse on the P.C.B.
Ass'y in the indoor unit
for continuity.
When the fuse blows.
• Check transformer. (TR1)
OK
• Check resistance of indoor
fan motor winding.
(FMI)
OK
• Check resistance of louver
motor winding. (LM)
OK
• Check resistance of drain
pump winding. (DP)
• Check coil of compressor
motor magnetic contactor.
(52C)
• P.C.B. Ass'y is defective.
(XS Type only)
OK
OK
1034_X_S
– 54 –
SM830078
12. SERVICE PROCEDURES
3)Outdoor Unit does not Run.
A. Check COOL / FAN selector switch in the remote control unit.
• Is COOL/FAN selector switch
set to COOL ?
B. Check set temperature.
Try to lower set
temperature by Temperature
setting button “COOLER”.
YES
• Set “Operation selector”
switch to TEST in the
indoor unit.
Outdoor unit runs.
Is room temperature too
low ?
NO
Set to COOL.
0623_X_S
NO
• Try to run both indoor and
outdoor units with another
remote control unit.
OK
The other remote control
unit is defective.
(Room sensor in the remote
control unit is defective.)
0624_X_S
– 55 –
SM830078
12. SERVICE PROCEDURES
C. Check compressor motor magnetic contactor.
• Check coil resistance of
compressor motor magnetic
contactor. (52C)
1035_X_S
D. Check indoor unit P.C.B.
• Check P.C.B. Ass’y.
• Check voltage between
terminals No.2 and No.4 at
terminal plate.
No voltage appears.
P.C.B. Ass’y is defective.
0628_X_S
F.Check float switch. (XS Type only)
• Refer to “2-3 Drain Pump Control”
E. Check outdoor unit P.C.B.
(CL3632 Type)
• Check P.C.B. Ass’y.
• Check voltage between
terminals L1 and L2 at
terminal plate.
No voltage appears.
P.C.B. Ass’y is defective.
1036_X_S
Is drainage prevented from
flowing ?
YES
• Check drain hose.
NO (Wait for 20 minutes.)
• Check float switch (FS).
0629_X_S
SM830078
– 56 –
12. SERVICE PROCEDURES
4)Indoor Unit does not Run.
(Indoor fan and louver motor do not run.)
P.C.B. Ass’y is defective.
0630_X_S
5)Some Part does not Operate.
A. Indoor fan does not run.
• Check fan rotation.
Rotate the fan gently once
or twice by hand.
Fan cannot
be rotated.
Check fan casing
for foreign matter
on the inside.
Fan motor burnout
or foreign matter
in bearing.
Remove foreign
matter or repair.
Repair or replace.
• Check resistance of fan
motor winding.
OK
• Check fan motor capacitor.
OK
Relay RY1 or RY2 on the
P.C.B. Ass’y is defective.
B. Louver motor does not run.
• Check resistance of
louver motor winding.
OK
P.C.B. Ass’y or remote
control unit is defective.
0632_X_S
0631_X_S
– 57 –
SM830078
12. SERVICE PROCEDURES
6)Outdoor Fan does not Run.
• Check fan rotation.
Rotate the fan gently once
or twice by hand.
• Check resistance of fan
motor winding.
OK
• Check fan motor capacitor
• Check continuity between
terminals on the compressor
motor magnetic contactor.
Fan cannot
be rotated.
• Check fan casing
for foreign matter
on the inside.
• Fan motor burnout
or foreign matter
in bearing.
Remove foreign
matter or repair.
Repair or replace.
0633_X_S
7)Outdoor Fan Speed is not Switched from High to Low even when the Outdoor
Temperature Falls below 78 °F. (C4232 Type)
• Check the thermostat (23S).
1037_X_S
8)Outdoor Fan Speed is not Switched from High to Med even when the Outdoor
Temperature Falls below 77 °F.
Outdoor Fan Speed is not Switched from Med to Low even when the Outdoor
Temperature Falls below 59 °F. (CL4232 Type)
• Check outdoor unit P.C.B.
Ass’y
OK
• Check resistance of outdoor
temp sensor.
0722 _X_S
– 58 –
SM830078
12. SERVICE PROCEDURES
9)Outdoor Fan does not Run for CL4232.
• Check fuse on PCB Ass’y in
outdoor unit for continuity.
If fuse blows,
• Check resistance of primary
winding of transformer. (TR)
1038_X_S
10) Compressor does not Run.
• Check compressor motor capacitor
(RC1).
OK
• Check PTC.
OK
• Check resistance of compressor
motor winding.
Wait for 30 minutes until com pressor has cooled.
Compressor runs.
Compressor internal thermal
protector is operated.
• Check power supply voltage.
Is voltage abnormally low?
NO
• Is outdoor heat exchanger coil dirty
or are there obstacles near air
suction inlet?
1039_X_S
– 59 –
SM830078
12. SERVICE PROCEDURES
11) Poor Cooling
Check installation position
of remote control unit.
• Does cool air from air condi tioner reach remote control
unit directly ?
• Is wide tube between indoor unit
and outdoor unit insulated ?
YES
• Measure temperatures of suction
and discharge air of indoor unit.
Temperature difference between
suction and discharge air is
large enough (Approx. 10 deg. or more).
• Check clogging of air
filter.
• Is fan speed set to LOW ?
YES
NO
Temperature
difference
is small.
Possibility of
refrigerant
shortage.
Air filter is clogged.
YES
Change installation
position of remote
control unit.
Insulate wide tube and
then execute taping with
narrow tube.
Charge
refrigerant
(R22).
Clean filter.
Set fan speed to either
HIGH or MEDIUM.
• Review cooling load estimate,
if performance of air conditioner
is normal.
12) Excessive Cooling.
• The set temperature is too low.
• Is the remote control unit installed
at a place where it can
detect the room temperature
properly ?
YES
NO
Reduce cooling load or
replace the unit with
higher cooling capacity.
1040_X_S
Set the temperature to
higher value using
temperature setting
button of the remote
control unit.
Change installation
position of the remote
control unit.
0637_X_S
– 60 –
SM830078
12. SERVICE PROCEDURES
(2)A Sensor is Defective
11
1Indoor (heat exchanger) coil temp. Sensor is defective.
11
(a) Open (=No continuity in sensor)
Compressor and outdoor fan repeat ON for 10 minutes and OFF for 6
minutes when sensor opens.
(b) Short
“Freeze Prevention” does not operate when dehumidified water is frozen on the
indoor coil.
22
2Room temp. Sensor (in the remote control unit) is defective.
22
(a) Open (=No continuity in sensor)
Neither outdoor fan nor compressor runs.
(b) Short
Outdoor fan and compressor do not stop. — Excessive cooling.
(3)Operation of Major Electrical Parts
Operation Mode
(Function)
Manual
Night
Cool
setback
-ing
Timaer
(set)
Freeze preventionVVV
Fan
Sweep
Flap
Stop
NOTE V* Refer to Cooling Mode.
Operation
Room
Temp.
Thermo.ONVVVVV
Thermo.OFFVVV
Thermo.ONVVVVVV
Thermo.OFFVVV
ON TimerV
OFF TimerVVVVVV
VV
CoolVV*V*VV*V*
FanVV
CoolVV*V*VV*V*
FanVV
Indoor unit and Remote Control unit
Indicator lamps
Cool
Timer
Night setback
Energy saver
Sweep
Fan Compressor
Fan
Oudoor unit
– 61 –
SM830078
12. SERVICE PROCEDURES
(4)Checking the Electrical Components
1)Measurement of Insulation
Resistance
• The electrical insulation is acceptable
when the resistance exceeds 1 MΩ.
11
1Power Supply Wires
11
Clamp the earthed wire of the Power
Supply wires with a lead clip of the insulation resistance tester and measure the
resistance by placing a probe on either
of the power wires. (Fig. 13)
Then measure the resistance between
the earthed wire and the other power
wires. (Fig. 13)
22
2Indoor Unit
22
Clamp an aluminum plate fin or copper
tube with the lead clip of the insulation
resistance tester and measure the
resistance by placing a probe on the
terminal plate (Fig. 14)
33
3Outdoor Unit
33
Probe
Copper
tube or
metallic part
Clip
Clip
Earthed wire
Insulation
tester
Terminal plate
0638_X_S
Insulation
tester
Probe
0639_X_S
Fig. 13
Fig. 14
Measure the resistance by placing a
probe on the terminal plate in the same
manner as explained above 2. (Fig. 14)
44
4Measurement of Insulation Resis-
44
tance for Electrical parts
• Disconnect the connector of the desired electric part from terminal plate,
P.C.B. Ass’y, etc. (Fig. 15)
•
Similarly, disconnect the lead wires from
compressor, capacitor, etc. (Fig. 16)
• Measure the resistance in the same
manner as illustrated on the right.
Refer to Electrical Wiring Diagram.
NOTE
If the probe does not enter the hole because the
hole is too narrow, use a probe with a
thinner pin.
Copper
tube or
metallic part
Metallic
part
Clip
Clip
Insulation
tester
From fan motor,
compressor and other
parts.
Probe
Insulation
tester
Probe
0640_X_S
0641_X_S
Fig. 15
Fig. 16
– 62 –
SM830078
12. SERVICE PROCEDURES
2)Checking the Protective Devices
• Disconnect the connector, which consists of P (plug) and S (socket) when you want
to check the protective device.
• Then check continuity among plug’s (and/or socket’s) terminal as in Fig. 17.
• Normality of the protective device can be judged by the following table.
The Protective Device is proved normal if there is a continuity between terminals.
socket
Multimeter
Ω
0642_X_S
11
1Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit
11
Fig. 17
• Disconnect the connector which leads to the indoor fan motor (FMI).
• Check the socket’s terminals.
22
2Compressor motor thermal protector . . . . . . Outdoor unit
22
• Disconnect the wires from terminals of compressor.
• Check the terminals of compressor.
33
3Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit
33
• Disconnect both the connector which leads to the outdoor fan motor (FMO).
• Check socket’s terminal.
– 63 –
SM830078
12. SERVICE PROCEDURES
3)Checking the Electrical Parts
11
1Power transformer (TR1) ................. Indoor unit*Measure the coil resistance.
11
• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals
of socket connected to power transformer.
• Secondary 10.6 V ; Measure the resistance between two BRN lead wires.
Refer to “1–3–(A) Other component specifications”.
22
2Power transformer (TR) ................. Outdoor unit*Measure the coil resistance.
22
• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals
of socket jointed to power transformer.
• Secondary 14 V; Measure the resistance between two BRN lead wires.
Refer to “1–3–(B) Other component specifications”.
33
3Indoor fan motor (FMI) ............... Indoor unit*Measure the coil resistance.
33
• Measure the resistance between each terminal of the socket connected to the
indoor fan motor.
Refer to “1–2–(A) Major component specifications”.
44
4Outdoor fan motor (FMO) ........... Outdoor unit*Measure the coil resistance.
44
• Measure the resistance in the same manner as explained above 3.
Refer to “1–2–(B) Major component specifications”.
55
5Motor capacitor ............ Both in indoor and outdoor unit
55
• Remove the lead wires from the
capacitor terminals, and then place a
probe on the capacitor terminals as
shown in Fig. 18. Observe the deflection of the pointer, setting the resis-
Multimeter
tance measuring range of the multimeter to the maximum value.
• The capacitor is “good” if the pointer
Ω
bounces to a great extent and then
gradually returns to its original position.
NOTE
The range of deflection and the deflection time differ according to the
capacity of the capacitor.
– 64 –
Compressor motor
capacitor
Fig. 18
Fan motor
capacitor
1041_X_S
SM830078
12. SERVICE PROCEDURES
1042_X_S
Fuse
66
6Continuity of fuse on P.C.B. Ass’y
66
• Check for continuity using a multimeter
as shown in Fig. 19.
NOTE
Method Used to Replace Fuse on PCB
Ass’y
1. Remove the PCB Ass’y from the electri-
cal component box.
2. Remove the fuse from PCB Ass’y using
pliers while heating the soldered leads
on the back side of the PCB Ass’y with
a soldering iron (30W or 60W). (Fig. 20)
3. For replacement, insert a fuse of the
same rating to the intended position and
solder it.
(Allow time to radiate heat during soldering so that the fuse does not melt.)
Fig. 19
Soldering iron
PCB Ass’y
FuseVaristor
When replacing the
CAUTION
fuse, be sure not to
break down the varistor.
4)Thermistor Characteristic Curve
1Room temp. sensor
(KTEC-35)
10
9
8
7
6
5
Resistance (kn )
4
3
1Coil sensor
(PBC-41E)
40
35
30
25
20
15
10
Resistance (kn )
5
Pliers
1043_X_S
Fig. 20
2
1
505968778695104
Temperature (°F)
1044_M_I
– 65 –
0
–4 5 14233241505968
Temperature (°F)
1045_M_I
SM830078
• The specifications, designs, and information in this brochure are subject to change without notice.
SANYO FISHER Service Company
CENTRAL REGION
1739 Sands Place, Suite G
Marietta, GA 30067
Phone: (770) 951-8284
Fax: (770) 951-2077
Jun. / ’2000Printed in U.S.A.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.