Sanyo C4232, CL4232 User Manual

TECHNICAL DATA
&
SERVICE MANUAL
XS4232 / C4232, CL4232 TS4232 / C4232, CL4232
SPLIT SYSTEM AIR CONDITIONER
INDOOR MODEL No. PRODUCT CODE No. OUTDOOR MODEL No. PRODUCT CODE No.
XS4232 854 016 10
TS4232 854 016 09
Indoor Unit Outdoor Unit
CL4232 854 016 11
CL4232 854 016 11
FILE NO.
XS4232 C4232
CL4232
TS4232
85464869178000 REFERENCE NO. SM830078
Important
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must :
Carefully read this instruction booklet before beginning.Follow each installation or repair step exactly as shown.Observe all local, state, and national electrical codes.Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or
CAUTION
unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
……………………………………………………………………
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate ground­ing can cause accidental injury or death.
Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheat­ing at connection points and a possible fire hazard.
When Transporting
…………………………………………………………………… Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
……………………………………………………………………
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys-tems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
……………………………………………………………………
• Ventilate the room well, in the event that refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either “narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
……………………………………………………………………
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site when installation is finished. Check that no metal scraps or bits of wiring have been left inside the unit.
CAUTION
• Ventilate any enclosed areas when installing or testing the refrigeration system. Contact of refrigerant gas with fire or heat can produce poisonous gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
– 2 –
SM830078
Table of Contents
1. OPERATING RANGE ....................................................................................... 5
2. SPECIFICATIONS ............................................................................................ 6
(1) Unit Specifications ...................................................................................... 6
(2) Major Component Specifications .............................................................. 10
(A) Indoor Unit .......................................................................................... 10
(B) Outdoor Unit........................................................................................ 12
(3) Other Component Specifications .............................................................. 14
(A) Indoor Unit .......................................................................................... 14
(B) Outdoor Unit........................................................................................ 16
3. DIMENSIONAL DATA..................................................................................... 18
(1) Indoor Unit ................................................................................................ 18
(2) Outdoor Unit.............................................................................................. 20
4. COOLING CAPACITY .................................................................................... 21
5. PERFORMANCE CHARTS ............................................................................ 25
(1) Operating Current ..................................................................................... 25
(2) High and Low Pressure............................................................................. 29
6. AIR THROW DISTANCE CHART...................................................................31
7. REFRIGERANT FLOW DIAGRAM ................................................................. 32
8. INSTALLATION INSTRUCTIONS .................................................................. 33
9. ELECTRICAL DATA ....................................................................................... 38
10. ELECTRICAL WIRING DIAGRAMS ............................................................... 39
(1) Indoor Unit ................................................................................................ 39
(2) Outdoor Unit.............................................................................................. 43
11. PROCESSES AND FUNCTIONS .................................................................. 47
(1) Room Temperature Control ...................................................................... 47
(2) Freeze Prevention..................................................................................... 48
(3) Drain Pump Control .................................................................................. 48
(4) Outdoor Fan Speed Control...................................................................... 49
12. SERVICE PROCEDURES.............................................................................. 50
(1) Troubleshooting ........................................................................................ 50
(2) A Sensor is Defective................................................................................ 61
(3) Operation of Major Electrical Parts ........................................................... 61
(4) Checking the Electrical Components ........................................................ 62
– 3 –
SM830078
Introduction:
This manual will help you understand and service the air conditioner. To help you find the information you need, we have divided it into 5 main sections. Each section is divided into chapters with charts, tables and explana­tions to help you find and repair problems.
Section 1: Specifications, tells you about the physical and electrical make up of the unit, as well
as its heating and cooling capacities. Look in this section to find the correct values for components and functions.
Section 2: Processes and Functions, explains each different part of the cooling and heating
cycle, and how each control function reacts to changing conditions to keep the room at the set temperature range.
Section 3: Electrical Data, which has fold-out schematic and wiring diagrams so you can find
the parts you need to check when something is wrong, and see how they should be connected.
Section 4: Service Procedures, has two main parts, a
specific component to replace or adjust, and a chapter with specific procedures and values to guide you in checking the electrical components in the unit.
Read Me First!
diagnostic
chapter to help you find the
HOW TO USE THIS MANUAL
You can use this manual both as a construction of this unit, and as a source of information to help you set up and maintain the unit. When this unit is not working properly, and the cause is not known, you can use the procedures in Section 3: Servicing Procedures to find the problem, fix it, and restore the unit to its proper functioning.
This air conditioner has many helpful self diagnostic features to help you identify problem areas quickly.
So you will be ready when a problem happens, we suggest you look this manual over and become familiar with it by following these steps:
1. Look at the TABLE OF CONTENTS to get an idea of what is in this manual and where to find it.
2. Look at the chapter about TROUBLE SHOOTING, so you are familiar with the way the flow
charts work. They are designed to guide you quickly through the possible causes for each kind of problem that is likely to happen to the Unit. Particularly read the introduction to this section, and the parts about the self-diagnosis and error codes which show on the display.
3. Look at the chapter about CHECKING ELECTRICAL COMPONENTS. You already know
about most of these procedures. This chapter gives you the specific values and methods for these components. If you don’t know some of these procedures, you can easily learn them here.
4. Read the Instruction Manual! The Instruction Manual is included here because it helps you help
the user to set the temperature controls properly and know how to take care of any simple problems that may happen, as well as know when to call for service. The Instruction Manual also has illustrations, care, and installation information not found in the rest of the service manual. It is short, and if you read it carefully, you will be able to answer the customers questions easily, and also know the most efficient ways for setting times and temperatures.
reference
to find specific information about the capacity, functions and
Please use this manual to make your work easier, keep the air conditioner functioning well, and keep your customers satisfied.
– 4 –
SM830078
1. OPERATING RANGE
XS4232, TS4232 / C4232
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Maximum 95 °F DB / 71 °F WB 115 °F DB
Minimum 67 °F DB / 57 °F WB 67 °F DB
XS4232, TS4232 / CL4232
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Maximum 95 °F DB / 71 °F WB 115 °F DB
Minimum 67 °F DB / 57 °F WB 0 °F DB
– 5 –
SM830078
2. SPECIFICATIONS
(1) Unit Specifications
MODEL No. Indoor Unit XS4232
POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling
Capacity BTU / h 42,000 40,500
Air circulation (Hi) Moisture removal (High) Pints / h 14.6 14.8
ELECTRICAL RATINGS
Voltage rating VAC 230 208 Available voltage range VAC 187 - 253 Running amperes* A 20.8 21.1 Max. running amperes** A 24.1 25.3 Power input W 4,230 4,120 Power factor % 88 94 S.E.E.R Max. starting amperes A 134 134 Maximum fuse size A 50
FEATURES
Controls Microprocessor Timer ON / OFF 24-hours & Program Fan speed Indoor / Outdoor 3 and Automatic control / 2 (Auto) Air deflection Horizontal / Vertical – / Automatic Air filter Washable, easy access, long life (2,500 hr) Remote controller (Accessory) RCS - 5PS4U Refrigerant control Capillary tube Refrigerant tubing connections Flare type Drain pump / Drain pipe trade size Max. head 9-27/32 in. above drain connection / 3/4 in. (26.7 mm) Compressor Scroll Operation sound
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 165 (50)
between the two units Outdoor unit is lower than indoor unit: 100 (30) Refrigerant tube Narrow tube in. (mm) 3 / 8 (9.52)
outer diameter Wide tube in. (mm) 3 / 4 (19.05) Refrigerant amount at shipment lbs. (kg) R22 : 9.7 (4.4)
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm) 11-1/32 (280) 48-5/8 (1,235)
Net weight lbs. (kg) 60 (27) 205 (93)
Indoor grille dimensions Height in. (mm) 3-1/16 (78)
Net weight lbs. (kg) 15 (7)
Indoor Unit Height in. (mm) 12-7/16 (316) 52-7/32 (1,326)
Package dimensions Width in. (mm) 43-27/32 (1,114) 40 (1,016)
Shipping weight lbs. (kg) 71 (32) 229 (104) Shipping volume cu. ft. (m3) 10.3 (0.293) 19.8 (0.56)
Indoor grille Height in. (mm) 4-3/32 (104)
Package dimensions Width in. (mm) 49-1/2 (1,257)
Shipping weight lbs. (kg) 29 (10) – Shipping volume cu. ft. (m3) 4.6 (0.131)
Outdoor Unit C4232
kW 12.32 11.88
cu.ft. / min.
BTU / Wh
Indoor - Hi / Me / Lo Outdoor - Hi dB - A 56
Width in. (mm) 41-11/32 (1,050) 37 (940) Depth in. (mm) 29-29/32 (760) 13-3/8 (340)
Width in. (mm) 45-9/32 (1,150) – Depth in. (mm) 33-27/32 (860)
Depth in. (mm) 32-25/32 (833) 16-3/8 (416)
Depth in. (mm) 39-11/32 (999)
dB - A 43 / 40 / 36
980 880
10.2 10.3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Cooling :
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
– 6 –
SM830078
2. SPECIFICATIONS
(1) Unit Specifications
MODEL No. Indoor Unit XS4232
POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling
Capacity BTU / h 42,000 40,500
Air circulation (Hi) Moisture removal (High) Pints / h 14.6 14.8
ELECTRICAL RATINGS
Voltage rating VAC 230 208 Available voltage range VAC 187 - 253 Running amperes* A 20.8 21.1 Max. running amperes** A 24.1 25.3 Power input W 4,230 4,120 Power factor % 88 94 S.E.E.R Max. starting amperes A 134 134 Maximum fuse size A 50
FEATURES
Controls Microprocessor Low ambient control Built-in 0 °F Timer ON / OFF 24-hours & Program Fan speed Indoor / Outdoor 3 and Automatic control / 3 (Auto) Air deflection Horizontal / Vertical – / Automatic Air filter Washable, easy access, long life (2,500 hr) Remote controller (Accessory) RCS - 5PS4U Refrigerant control Capillary tube Refrigerant tubing connections Flare type Drain pump / Drain pipe trade size Max. head 9-27/32 in. above drain connection / 3/4 in. (26.7 mm) Compressor Scroll Operation sound
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 165 (50)
between the two units Outdoor unit is lower than indoor unit: 100 (30) Refrigerant tube Narrow tube in. (mm) 3 / 8 (9.52)
outer diameter Wide tube in. (mm) 3 / 4 (19.05) Refrigerant amount at shipment lbs. (kg) R22 : 9.7 (4.4)
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm) 11-1/32 (280) 48-5/8 (1,235)
Net weight lbs. (kg) 60 (27) 205 (93)
Indoor grille dimensions Height in. (mm) 3-1/16 (78)
Net weight lbs. (kg) 15 (7)
Indoor Unit Height in. (mm) 12-7/16 (316) 52-7/32 (1,326)
Package dimensions Width in. (mm) 43-27/32 (1,114) 40 (1,016)
Shipping weight lbs. (kg) 71 (32) 229 (104) Shipping volume cu. ft. (m3) 10.3 (0.293) 19.8 (0.56)
Indoor grille Height in. (mm) 4-3/32 (104)
Package dimensions Width in. (mm) 49-1/2 (1,257)
Shipping weight lbs. (kg) 29 (10) – Shipping volume cu. ft. (m3) 4.6 (0.131)
Outdoor Unit CL4232
kW 12.32 11.88
cu.ft. / min.
BTU / Wh
Indoor - Hi / Me / Lo Outdoor - Hi dB - A 56
Width in. (mm) 41-11/32 (1,050) 37 (940) Depth in. (mm) 29-29/32 (760) 13-3/8 (340)
Width in. (mm) 45-9/32 (1,150) – Depth in. (mm) 33-27/32 (860)
Depth in. (mm) 32-25/32 (833) 16-3/8 (416)
Depth in. (mm) 39-11/32 (999)
dB - A 43 / 40 / 36
980 880
10.2 10.3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
Cooling :
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
– 7 –
SM830078
2. SPECIFICATIONS
(1) Unit Specifications
MODEL No. Indoor Unit TS4232
Outdoor Unit C4232 POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling
Capacity BTU / h 42,000 40,500
kW 12.32 11.88 Air circulation (Hi) Moisture removal (High) Pints / h 14.8 14.6
ELECTRICAL RATINGS
Voltage rating VAC 230 208 Available voltage range VAC 187 - 253 Running amperes* A 20.6 21.0 Max. running amperes** A 21.4 22.7 Power input W 4,190 4,100 Power factor % 88 94 S.E.E.R Max. starting amperes A 134 134 Maximum fuse size A 50
FEATURES
Controls Microprocessor Timer ON / OFF 24-hours & Program Fan speed Indoor / Outdoor 3 and Automatic control / 2 (Auto) Air deflection Horizontal / Vertical Manual / Automatic Air filter Washable, easy access, long life (2,500 hr) Remote controller (Accessory) RCS - 5PS4U Refrigerant control Capillary tube Refrigerant tubing connections Flare type Drain pipe trade size 3 / 4 in. (26.7 mm) Compressor Scroll Operation sound Indoor - Hi / Me / Lo dB - A 42 / 40 / 35
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 165 (50)
between the two units Outdoor unit is lower than indoor unit: 100 (30) Refrigerant tube Narrow tube in. (mm) 3 / 8 (9.52)
outer diameter Wide tube in. (mm) 3 / 4 (19.05) Refrigerant amount at shipment lbs. (kg) R22 : 9.7 (4.4)
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm) 9-7/16 (240) 48-5/8 (1,235)
Package dimensions Height in. (mm) 12-15/32 (317) 52-7/32 (1,326)
Net weight lbs. (kg) 84 (38) 205 (93) Shipping weight lbs. (kg) 97 (44) 229 (104) Shipping volume cu.ft. (m3) 14.8 (0.42) 19.8 (0.56)
Outdoor - Hi dB - A 56
Width in. (mm) 62 (1,575) 37 (940) Depth in. (mm) 26-3/8 (670) 13-3/8 (340)
Width in. (mm) 66-1/16 (1,678) 40 (1,016) Depth in. (mm) 31-1/16 (789) 16-3/8 (416)
Cooling :
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
cu.ft. / min.
BTU / Wh
900 800
10.2 10.3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 8 –
SM830078
2. SPECIFICATIONS
(1) Unit Specifications
MODEL No. Indoor Unit TS4232
Outdoor Unit CL4232 POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling
Capacity BTU / h 42,000 40,500
kW 12.32 11.88 Air circulation (Hi) Moisture removal (High) Pints / h 14.8 14.6
ELECTRICAL RATINGS
Voltage rating VAC 230 208 Available voltage range VAC 187 - 253 Running amperes* A 20.6 21.0 Max. running amperes** A 21.4 22.7 Power input W 4,190 4,100 Power factor % 88 94 S.E.E.R Max. starting amperes A 134 134 Maximum fuse size A 50
FEATURES
Controls Microprocessor Low ambient control Built-in 0 °F Timer ON / OFF 24-hours & Program Fan speed Indoor / Outdoor 3 and Automatic control / 3 (Auto) Air deflection Horizontal / Vertical Manual / Automatic Air filter Washable, easy access, long life (2,500 hr) Remote controller (Accessory) RCS - 5PS4U Refrigerant control Capillary tube Refrigerant tubing connections Flare type Drain pipe trade size 3 / 4 in. (26.7 mm) Compressor Scroll Operation sound Indoor - Hi / Me / Lo dB - A 42 / 40 / 35
Outdoor - Hi dB - A 56
REFRIGERANT TUBING
Limit of tubing length ft. (m) 165 (50) Limit of tubing length at shipment ft. (m) 50 (15) Limit of elevation difference ft. (m) Outdoor unit is higher than indoor unit: 165 (50)
between the two units Outdoor unit is lower than indoor unit: 100 (30) Refrigerant tube Narrow tube in. (mm) 3 / 8 (9.52)
outer diameter Wide tube in. (mm) 3 / 4 (19.05) Refrigerant amount at shipment lbs. (kg) R22 : 9.7 (4.4)
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm) 9-7/16 (240) 48-5/8 (1,235)
Width in. (mm) 62 (1,575) 37 (940) Depth in. (mm) 26-3/8 (670) 13-3/8 (340)
Package dimensions Height in. (mm) 12-15/32 (317) 52-7/32 (1,326)
Width in. (mm) 66-1/16 (1,678) 40 (1,016)
Depth in. (mm) 31-1/16 (789) 16-3/8 (416) Net weight lbs. (kg) 84 (38) 205 (93) Shipping weight lbs. (kg) 97 (44) 229 (104) Shipping volume cu.ft. (m3) 14.8 (0.42) 19.8 (0.56)
Cooling :
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75 °F WB Full load conditions (**) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115 °F DB
cu.ft. / min.
BTU / Wh
900 800
10.2 10.3
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 9 –
SM830078
2. SPECIFICATIONS
(2) Major Component Specifications
(A) Indoor Unit
MODEL No. XS4232 Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Accessory) RCS - 5PS4U Controller P. C. B Ass'y CR - TS2432 Control circuit fuse 250 V, 3 A Switch Ass'y SW - X363GS Fan (Number … diameter) in. (mm) Turbo (1…19-9/32 (490)) Fan motor
Model SFG6X - 61A3P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m. (230 V, High) rpm 6 … 560 Nominal output W 60 Coil resistance BRW - WHT : 71.1 , ORG - YEL : 22.7 (Ambient temperature 68 °F) WHT - VLT : 8.7 , VLT - PNK : 43.2
VLT - ORG : 13.3 , YEL - BLK : 54.32
Safety device
Operating temperature Open °F266± 14.4
Close °F 174.2 ± 27
Run capacitor VAC, µF 440 V , 6 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube Rows … Fins per inch 2 … 14.9 Face area ft.
Panel
Model No. PNR - XS3632 Indicator Lamp Ass'y IND - XS3632 Auto louver motor MT8 - 3C Auto louver motor … Rated V, W, rpm 240 VAC , 3 W , 3 rpm Coil resistance (Ambient temperature 77 °F) 16,430 ± 8 %
2
(m2) 5.17 (0.48)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 10 –
SM830078
2. SPECIFICATIONS
(2) Major Component Specifications
(A) Indoor Unit
MODEL No. TS4232 Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Accessory) RCS- 5PS4U Controller P. C. B Ass'y CR - TS2432 Control circuit fuse 250 V, 3 A Switch Ass'y SW - X363GS Fan (Number … diameter) in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor
Model KFG4X - 101C6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m. (230 V, High) rpm 1,015 Nominal output W 100 Coil resistance BRW - WHT : 61.05 , ORG - YEL : 13.23 (Ambient temperature 68 °F) WHT - VLT : 9.955 , YEL - BLK : 19.25
VLT - ORG : 9.576 , BLK - PNK : 10.81
Safety device
Operating temperature Open °F266± 14.4
Close °F 174.2 ± 27
Run capacitor VAC, µF 440 V , 4 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube Rows … Fins per inch 3 … 14.9 Face area ft.
Auto louver motor
Model No. MT8 - 3C Auto louver motor … Rated V, W, rpm 240 VAC , 3 W , 3 rpm Coil resistance (Ambient temperature 77 °F) 16,430 ± 8 %
2
(m2) 3.51 (0.326)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 11 –
SM830078
2. SPECIFICATIONS
(2) Major Component Specifications
(B) Outdoor Unit
MODEL No. C4232 Source 230 - 208 V / 1 phase / 60 Hz Compressor Scroll (Hermetic)
Model ZR47KC - PFV Source 230 - 208 V / 1 phase / 60 Hz Nominal output W 4,270 Compressor oil cc 1,240 Coil resistance (Ambient temperature 77 °F) R - W : 0.475 , S - W : 1.850 Safety device Internal type
Overload relay models — Operating temperature Open °F 320 ± 9
Close °F 189 ± 20
Operating ampere (at 77 °F) A
Run capacitor VAC, µF 400 V, 50 µF
Refrigerant amount charged at shipment lbs. (kg) R22 : 9.7 (4.4) High pressure switch ACB - 1UB11
Set pressure OFF kg/cm
ON kg/cm
Fan Propeller
Number...diameter in. (mm) 1 … 18-3/32 (460)
Fan speeds 2 (AUTO) Fan motor
Model KFC6T - 91D6P × 2 Source 230 - 208 V / 1 phase / 60 Hz No. of pole … rpm (230 V, High) rpm 6 … 879 Nominal output W 110 × 2 Coil resistance BRW – WHT : 67.14 , VLT – YEL : 11.42
(Ambient temperature 68 °F) Safety device
Operating temperature Open °F248± 9
Close °F171± 27
Run capacitor VAC, µF 440 V, 4 µF × 2
Heat exchanger
Coil Aluminum plate fin / Copper tube Rows … Fins per inch 2 … 12.7 Face area ft.
2
2
2
WHT – VLT : 64.85 , YEL – PNK : 10.60
(m2) 11.63 (1.08)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
+ 2.0
30
+ 0.5
24 ± 2.0
– 12 –
SM830078
2. SPECIFICATIONS
(2) Major Component Specifications
(B) Outdoor Unit
MODEL No. CL4232 Source 230 - 208 V / 1 phase / 60 Hz Controller P.C.B. Ass'y CR - CL2432 (Microprocessor)
Control circuit fuse 250 V, 3 A
Compressor Scroll (Hermetic)
Model ZR47KC - PFV Source 230 - 208 V / 1 phase / 60 Hz Nominal output W 2,200 Compressor oil cc 1,240 Coil resistance (Ambient temperature 77 °F) R – W : 0.475 , S – W : 1.850
Safety device Internal type
Overload relay models — Operating temperature Open °F 320 ± 9
Close °F 189 ± 20
Operating ampere (at 77 °F) A — Run capacitor VAC, µF 400 V, 50 µF Crank case heater V, W 230 V, 30 W
Refrigerant amount charged at shipment lbs. (kg) R22 : 9.7 (4.4) High pressure switch ACB-1UB11
Set pressure OFF kg/cm
ON kg/cm
Fan Propeller
Number...diameter in. (mm) 1 ... 18 - 3/32 (460)
Fan speeds 3 (AUTO) Fan motor
Model KFC6T - 91D6P × 2 Source 230 - 208 V / 1 phase / 60 Hz
No. of pole ..... rpm (230 V, High) 6 ... 879
Nominal output W 110 × 2 Coil resistance BRN – WHT : 67.14 , VLT – YEL : 11.42
(Ambient temperature 68 °F) WHT – VLT : 64.85 , YEL – PNK : 10.60 Safety device Internal type
Operating temperature Open °F 248 ± 9
Close °F 171 ± 27
Run capacitor VAC, µF 440 V, 4 µF × 2
Heat exchange
Coil Aluminum plate fin / Copper tube
Rows ..... Fins per inch 2 ... 12.7
Face area ft.
2
2
2
(m2) 11.63 (1.08)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
+ 2.0
30
+ 0.5
24 ± 2.0
– 13 –
SM830078
2. SPECIFICATIONS
(3) Other Component Specifications
(A) Indoor Unit
MODEL No. XS4232 Power Transformer ATR – I104A
Rated Primary AC 220 V, 60 Hz
Secondary 10.6 V, 0.93 A Capacity 9.85 VAC
Coil resistance (Ambient temprature 77 °F)
Thermistor cut off temperature °F266
Thermistor (Coil sensor) PBC - 41E - S36
Coil resistance k 14 °F : 23.7 , 41 °F : 12.1
Thermistor (Room or coil sensor) KTEC - 35 - S6
Coil resistance k 32 °F : 16.5 , 104 °F : 2.7
Drain pump WP20SL - 21
Rated AC 200 V, 14.7 W
Float switch FS - 0218 - 103
MAX Rated (Contact rated) AC 200 V, 50 W
Switch Ass'y SW - X363GS Indicator Lamp Ass'y IND - XS3632 Synchronized Motor MT8 - 3C
WHT - WHT : 101 , BRN - BRN : 0.42
23 °F : 18.8 , 50 °F : 9.7 32 °F : 15.0 , 59 °F : 8.0
41 °F : 12.8 , 113 °F : 2.2 50 °F : 10.0 , 122 °F : 1.8 68 °F : 6.3 , 131 °F : 1.5 86 °F : 4.0 ,
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 14 –
SM830078
2. SPECIFICATIONS
(3) Other Component Specifications
(A) Indoor Unit
MODEL No. TS4232 Power Transformer ATR – I104A
Rated Primary AC 220 V, 60 Hz
Secondary 10.6 V, 0.93 A Capacity 9.85 VAC
Coil resistance (Ambient temprature 77 °F)
Thermistor cut off temperature °F266
Thermistor (Coil sensor) PBC - 41E - S36
Coil resistance k 14 °F : 23.7 , 41 °F : 12.1
Thermistor (Room or coil sensor) KTEC - 35 - S6
Coil resistance k 32 °F : 16.5 , 104 °F : 2.7
Switch Ass'y SW - X363GS Indicator Lamp Ass'y IND - TS2432 Synchronized Motor MT8 - 3C
WHT - WHT : 101 , BRN - BRN : 0.42
23 °F : 18.8 , 50 °F : 9.7 32 °F : 15.0 , 59 °F : 8.0
41 °F : 12.8 , 113 °F : 2.2 50 °F : 10.0 , 122 °F : 1.8 68 °F : 6.3 , 131 °F : 1.5 86 °F : 4.0 ,
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 15 –
SM830078
2. SPECIFICATIONS
(3) Other Component Specifications
(B) Outdoor Unit
MODEL No. C4232 Compressor Motor Magnetic Contactor FC - 2SUL
Coil rated AC 240 V, 60 Hz Coil resistance (at 68 °F) 350 ± 10 % Contact rated (Main) AC 240 V, 35 A Contact rated (Auxiliary) AC 240 V, 3 A
Power Relay HH62S
Coil rated AC 240 V, 60 Hz Coil resistance (at 77 °F) k 17.2 Contact rated AC 220 V, 5 A
Thermostat (Coil sensor) YTB - 4U305F
Operating Temperature °F 79 ± 3 OFF
Contact rated 200 to 240 V, 1 A
DATA SUBJECT TO CHANGE WITHOUT NOTICE
+ 3
75 ON
– 1
– 16 –
SM830078
2. SPECIFICATIONS
(3) Other Component Specifications
(B) Outdoor Unit
MODEL No. CL4232 Compressor Motor Magnetic Contactor FC - 2SUL
Coil rated AC 240 V, 60 Hz Coil resistance (at 68 °F) 350 ± 10 % Contact rated (Main) AC 240 V, 35 A Contact rated (Auxiliary) AC 240 V, 3 A
Power Relay HH62S
Coil rated AC 240 V, 60 Hz Coil resistance (at 77 °F) k 17.2 Contact rated AC 220 V, 5 A
Power Transformer ATR - I35B
Rated
Primary AC 220 V, 60 Hz
Secondary 14 V, 0.2 A Capacity 2.8 VAC Coil resistance (at 78 °F ) WHT – WHT : 482.5 , BRN – BRN : 3.95 Thermal cut off temperature °F266
Thermistor (Outdoor Temp. sensor)
Coil resistance k 14 °F : 23.7 , 50 °F : 9.7
23 °F : 18.8 , 68 °F : 6.5 32 °F : 15.0 , 86 °F : 4.4 41 °F : 12.1 , 104 °F : 3.1
PBC - 41E - S4
113 °F : 2.6
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 17 –
SM830078
3. DIMENSIONAL DATA
(1) Indoor Unit: XS4232
8-19/32
2-13/32
32-9/32 (Ceiling opening)
23-7/32 (Suspention bolt pitch)
13-15/32 19/32
X-view
5-23/321-3/8
29-29/32
2-3/4
8-9/32
6-1/2
11-7/32
12-29/32
8-19/32
4-29/32
2-3/8
1-3/16
15/32
33-27/32 19-11/16
Panel center
• Remote controller (Accessory)
6-25/32
2-13/32 23/32
19-9/32 1-9/16
41-11/32
43-11/16 (Ceiling opening)
40-5/32 (Suspention bolt pitch)
9
3-15/16 3-15/16
1-7/8
8-9/32
45-9/32
31-3/32
15/32
Dimension : inch
Air intake grille Air outlet Refrigerant liquid line (ø3/8") Refrigerant gas line (ø3/4") Drain connection Power supply entry For discharge duct Humidifier (option) mounting hole Suspension bolt mounting
– 18 –
1813_X_S
SM830078
3. DIMENSIONAL DATA
Drain connection Drain connection for left side Refrigerant liquid line (3/8") Flare connection Refrigerant gas line (3/4") Flare connection Hole for rear side refrigerant tubing Hole for through-the-wall refrigerant tubing (ø3-15/16" hole) Hole for fresh air intake (Knockout hole) Hole for right side refrigerant tubing (Knockout hole) Hole for left side drain connection (Knockout hole) Hole for power supply (Conduit size 1/2") Infrared rays receiver for wireless remote controller Cutting position for fresh air intake
1341_TS_I
Dimension : inch
Air intake
Air outlet
2 ft. or more
Hole for wall-through piping (View from front)
2-13/32 23/32
9-7/8
6-25/32
9-7/16
8-7/16
62
26-3/8
11-1/32
12-7/32
61-7/32
7-3/4
12-19/32 6-5/16
5-15/16
• Remote controller (Accessory)
5-1/2
7-3/4
6-11/16
4-1/2
7-1/4
7-3/4
1-3/326-5/16
3-5/324-3/4
5-3/4
7-7/32
4-1/16
9-7/8
5-9/16
1-3/859-1/4 (Suspension bolt hole pitch)
3-1/2
5-25/32
2-25/325-3/16
11-1/32
3-15/16 1-31/32
3-3/8
6-3/32 7-31/32
Front
(Service space)(Service space)
Holes in the rear side (View from front)
(Suspension bolt hole pitch)
10
or more
10
or more
(1) Indoor Unit: TS4232
– 19 –
SM830078
3. DIMENSIONAL DATA
(2) Outdoor Unit: C4232, CL4232
1-31/32 1-31/32
4-21/64266-11/16
1-3/16
13-3/8
48-5/8
37
15-3/4
14-31/32 13/32
22-27/32
23-29/32
– 20 –
Dimension : inch
Hole for anchor bolt (4-ø13) Refrigerant tube joint (narrow tube) Flare connection 3/8 in (9.52 mm) Refrigerant tube joint (wide tube) Flare connection 3/4 in (19.05 mm) Refrigerant tubing inlet Power supply inlet
1342_C_S
SM830078
4. COOLING CAPACITY
11
1 Indoor Unit: XS4232 Outdoor Unit: C4232, CL4232
11
• 230V / 1 phase / 60Hz
RATING CAPACITY : 42,000 BTU / h AIR FLOW RATE : 980 CFM
EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
(23.9) (29.4) (35.0) (40.6) (46.1)
TC 42,550 40,490 38,140 35,490 32,550
CI 3.01 3.28 3.58 3.98 4.38
72(22.2) SHC 29,220 28,050 26,750 25,330 23,810
59 76(24.4) SHC 32,330 31,160 29,860 28,440 26,920
(15.0) 80(26.7) SHC 35,580 34,410 33,110 31,690 30,170
84(28.9) SHC 38,690 37,520 36,220 34,800 32,550 88(31.1) SHC 41,800 40,490 38,140 35,490 32,550
TC 44,140 42,170 40,070 37,670 35,070
CI 3.04 3.33 3.63 4.04 4.45
72(22.2) SHC 25,140 24,120 23,050 21,870 20,610
63 76(24.4) SHC 28,250 27,230 26,160 24,970 23,720
(17.2) 80(26.7) SHC 31,500 30,480 29,410 28,220 26,970
84(28.9) SHC 34,610 33,590 32,520 31,330 30,080 88(31.1) SHC 37,720 36,700 35,630 34,440 33,190
TC 45,820 44,020 # 42,000 39,770 37,340
CI 3.06 3.36 3.67 4.08 4.49
72(22.2) SHC 21,050 20,190 19,250 18,240 17,160
67 76(24.4) SHC 24,160 23,300 22,360 21,350 20,270
(19.4) 80(26.7) SHC 27,410 26,550 25,610 24,600 23,520
84(28.9) SHC 30,520 29,660 28,720 27,710 26,630 88(31.1) SHC 33,630 32,770 31,830 30,820 29,740
TC 48,260 46,580 44,770 42,800 40,610
CI 3.1 3.39 3.73 4.14 4.56
72(22.2) SHC 17,040 16,320 15,550 14,720 13,830
71 76(24.4) SHC 20,150 19,420 18,650 17,830 16,940
(21.7) 80(26.7) SHC 23,400 22,680 21,910 21,080 20,190
84(28.9) SHC 26,510 25,780 25,010 24,190 23,300 88(31.1) SHC 29,620 28,890 28,120 27,300 26,410
TC 49,220 47,630 45,950 44,020 41,960
CI 3.16 3.45 3.78 4.2 4.62
75 76(24.4) SHC 15,650 15,040 14,400 13,670 12,910
(23.9) 80(26.7) SHC 18,910 18,290 17,650 16,920 16,160
84(28.9) SHC 22,010 21,400 20,750 20,030 19,270 88(31.1) SHC 25,120 24,510 23,860 23,140 22,380
TC : Total Cooling Capacity (BTU / h) SHC : Sensible Heat Capacity (BTU / h) CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB : Indoor Unit Entering Air Temp. 80 °F DB / 67°F WB
SM830078
– 21 –
4. COOLING CAPACITY
11
1 Indoor Unit: XS4232 Outdoor Unit: C4232, CL4232
11
• 208V / 1 phase / 60Hz
RATING CAPACITY : 40,500 BTU / h AIR FLOW RATE : 880 CFM
EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
(23.9) (29.4) (35.0) (40.6) (46.1)
TC 41,030 39,040 36,770 34,220 31,390
CI 2.97 3.24 3.53 3.95 4.37
72(22.2) SHC 27,990 26,830 25,550 24,150 22,650
59 76(24.4) SHC 30,830 29,680 28,400 27,000 25,500
(15.0) 80(26.7) SHC 33,810 32,650 31,370 29,980 28,480
84(28.9) SHC 36,660 35,500 34,220 32,820 31,320 88(31.1) SHC 39,500 38,350 36,770 34,220 31,390
TC 42,570 40,660 38,640 36,330 33,820
CI 3 3.29 3.58 4.01 4.44
72(22.2) SHC 24,210 23,190 22,140 20,970 19,730
63 76(24.4) SHC 27,050 26,030 24,980 23,810 22,580
(17.2) 80(26.7) SHC 30,030 29,010 27,960 26,790 25,560
84(28.9) SHC 32,880 31,860 30,810 29,640 28,400 88(31.1) SHC 35,720 34,710 33,650 32,480 31,250
TC 44,190 42,440 # 40,500 38,350 36,000
CI 3.02 3.31 3.62 4.05 4.48
72(22.2) SHC 20,400 19,550 18,620 17,620 16,560
67 76(24.4) SHC 23,250 22,390 21,470 20,470 19,400
(19.4) 80(26.7) SHC 26,220 25,370 24,450 23,450 22,380
84(28.9) SHC 29,070 28,220 27,290 26,290 25,230 88(31.1) SHC 31,920 31,060 30,140 29,140 28,070
TC 46,530 44,910 43,170 41,270 39,160
CI 3.06 3.35 3.67 4.11 4.55
72(22.2) SHC 16,690 15,970 15,210 14,400 13,510
71 76(24.4) SHC 19,530 18,810 18,050 17,240 16,360
(21.7) 80(26.7) SHC 22,510 21,790 21,030 20,220 19,340
84(28.9) SHC 25,360 24,640 23,880 23,070 22,180 88(31.1) SHC 28,200 27,480 26,720 25,910 25,030
TC 47,470 45,930 44,310 42,440 40,460
CI 3.11 3.4 3.73 4.17 4.61
75 76(24.4) SHC 15,330 14,720 14,090 13,370 12,620
(23.9) 80(26.7) SHC 18,310 17,700 17,060 16,340 15,600
84(28.9) SHC 21,160 20,540 19,910 19,190 18,450 88(31.1) SHC 24,000 23,390 22,760 22,040 21,290
TC : Total Cooling Capacity (BTU / h) SHC : Sensible Heat Capacity (BTU / h) CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB : Indoor Unit Entering Air Temp. 80 °F DB / 67°F WB
SM830078
– 22 –
4. COOLING CAPACITY
22
2 Indoor Unit: TS4232 Outdoor Unit: C4232, CL4232
22
• 230V / 1 phase / 60Hz
RATING CAPACITY : 42,000 BTU / h AIR FLOW RATE : 900 CFM
EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
(23.9) (29.4) (35.0) (40.6) (46.1)
TC 42,550 40,490 38,140 35,490 32,550
CI 3.01 3.28 3.58 3.98 4.38
72(22.2) SHC 29,380 28,220 26,940 25,530 24,020
59 76(24.4) SHC 32,550 31,390 30,110 28,700 27,190
(15.0) 80(26.7) SHC 35,860 34,710 33,420 32,020 30,500
84(28.9) SHC 39,030 37,880 36,590 35,190 32,550 88(31.1) SHC 42,200 40,490 38,140 35,490 32,550
TC 44,140 42,170 40,070 37,670 35,070
CI 3.04 3.33 3.63 4.04 4.45
72(22.2) SHC 25,250 24,240 23,190 22,010 20,770
63 76(24.4) SHC 28,420 27,410 26,360 25,180 23,940
(17.2) 80(26.7) SHC 31,740 30,720 29,670 28,490 27,250
84(28.9) SHC 34,910 33,890 32,840 31,660 30,420 88(31.1) SHC 38,080 37,060 36,010 34,830 33,590
TC 45,820 44,020 # 42,000 39,770 37,340
CI 3.06 3.36 3.67 4.08 4.49
72(22.2) SHC 21,110 20,260 19,330 18,330 17,260
67 76(24.4) SHC 24,280 23,430 22,500 21,500 20,430
(19.4) 80(26.7) SHC 27,590 26,750 25,820 24,810 23,740
84(28.9) SHC 30,760 29,920 28,990 27,980 26,910 88(31.1) SHC 33,930 33,090 32,160 31,150 30,080
TC 48,260 46,580 44,770 42,800 40,610
CI 3.1 3.39 3.73 4.14 4.56
72(22.2) SHC 17,050 16,330 15,570 14,750 13,870
71 76(24.4) SHC 20,220 19,500 18,740 17,920 17,040
(21.7) 80(26.7) SHC 23,530 22,810 22,050 21,240 20,350
84(28.9) SHC 26,700 25,980 25,220 24,410 23,520 88(31.1) SHC 29,870 29,150 28,390 27,580 26,690
TC 49,220 47,630 45,950 44,020 41,960
CI 3.16 3.45 3.78 4.2 4.62
75 76(24.4) SHC 15,680 15,070 14,430 13,710 12,960
(23.9) 80(26.7) SHC 18,990 18,380 17,740 17,030 16,270
84(28.9) SHC 22,160 21,550 20,910 20,200 19,440 88(31.1) SHC 25,330 24,720 24,080 23,360 22,610
TC : Total Cooling Capacity (BTU / h) SHC : Sensible Heat Capacity (BTU / h) CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB : Indoor Unit Entering Air Temp. 80 °F DB / 67°F WB
SM830078
– 23 –
4. COOLING CAPACITY
22
2 Indoor Unit: TS4232 Outdoor Unit: C4232, CL4232
22
• 208V / 1 phase / 60Hz
RATING CAPACITY : 40,500 BTU / h AIR FLOW RATE : 800 CFM
EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
(23.9) (29.4) (35.0) (40.6) (46.1)
TC 41,030 39,040 36,770 34,220 31,390
CI 2.97 3.24 3.53 3.95 4.37
72(22.2) SHC 28,050 26,900 25,620 24,230 22,740
59 76(24.4) SHC 30,910 29,760 28,490 27,100 25,610
(15.0) 80(26.7) SHC 33,910 32,760 31,490 30,100 28,600
84(28.9) SHC 36,780 35,630 34,360 32,970 31,390 88(31.1) SHC 39,650 38,500 36,770 34,220 31,390
TC 42,570 40,660 38,640 36,330 33,820
CI 3 3.29 3.58 4.01 4.44
72(22.2) SHC 24,250 23,240 22,190 21,020 19,800
63 76(24.4) SHC 27,120 26,100 25,060 23,890 22,660
(17.2) 80(26.7) SHC 30,120 29,100 28,060 26,890 25,660
84(28.9) SHC 32,990 31,970 30,930 29,760 28,530 88(31.1) SHC 35,850 34,840 33,790 32,630 31,400
TC 44,190 42,440 # 40,500 38,350 36,000
CI 3.02 3.31 3.62 4.05 4.48
72(22.2) SHC 20,430 19,580 18,660 17,660 16,600
67 76(24.4) SHC 23,290 22,450 21,530 20,530 19,470
(19.4) 80(26.7) SHC 26,290 25,450 24,520 23,530 22,470
84(28.9) SHC 29,160 28,310 27,390 26,400 25,340 88(31.1) SHC 32,030 31,180 30,260 29,270 28,210
TC 46,530 44,910 43,170 41,270 39,160
CI 3.06 3.35 3.67 4.11 4.55
72(22.2) SHC 16,690 15,980 15,220 14,410 13,540
71 76(24.4) SHC 19,560 18,850 18,090 17,280 16,410
(21.7) 80(26.7) SHC 22,560 21,840 21,090 20,280 19,400
84(28.9) SHC 25,430 24,710 23,960 23,150 22,270 88(31.1) SHC 28,300 27,580 26,830 26,020 25,140
TC 47,470 45,930 44,310 42,440 40,460
CI 3.11 3.4 3.73 4.17 4.61
75 76(24.4) SHC 15,350 14,740 14,110 13,390 12,650
(23.9) 80(26.7) SHC 18,350 17,740 17,110 16,390 15,650
84(28.9) SHC 21,220 20,600 19,970 19,260 18,520 88(31.1) SHC 24,080 23,470 22,840 22,130 21,390
TC : Total Cooling Capacity (BTU / h) SHC : Sensible Heat Capacity (BTU / h) CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB : Indoor Unit Entering Air Temp. 80 °F DB / 67°F WB
SM830078
– 24 –
5. PERFORMANCE CHARTS
(1) Operating Current
11
1 Indoor Unit: XS4232 Outdoor Unit: C4232
11
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V
Outdoor fan speed
Low
23 22 21 20 19 18 17
Operating current (A)
16
High
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
208V
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
Outdoor fan speed
Low
23 22 21 20 19 18 17
Operating current (A)
16
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
High
1792_X_S
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1793_X_S
– 25 –
SM830078
5. PERFORMANCE CHARTS
(1) Operating Current
22
2 Indoor Unit: TS4232 Outdoor Unit: C4232
22
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V
Outdoor fan speed
Low
23 22 21 20 19 18 17
Operating current (A)
16
High
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
208V
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
Outdoor fan speed
Low
23 22 21 20 19 18 17
Operating current (A)
16
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
High
1794_X_S
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1795_X_S
– 26 –
SM830078
5. PERFORMANCE CHARTS
(1) Operating Current
33
3 Indoor Unit: XS4232 Outdoor Unit: CL4232
33
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V
23 22 21 20 19 18 17
Operating current (A)
16 15
(-5) (0) (5) (10) (15) (20)
208V
23 22 21 20 19 18 17
Operating current (A)
16 15
Outdoor fan speed (Upper / Lower)
STOP / Med
23 32 41 50 59 68
STOP / Med
Low / Low Med / Med High / High
Outdoor ambient temp. °F (°C)
Outdoor fan speed (Upper / Lower)
Low / Low Med / Med High / High
77
(25)
86
(30)
95
(35)
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
104
(40)
1796_X_S
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
23 32 41 50 59 68
(-5) (0) (5) (10) (15) (20)
Outdoor ambient temp. °F (°C)
– 27 –
77
(25)
86
(30)
95
(35)
104
(40)
1797_X_S
SM830078
5. PERFORMANCE CHARTS
(1) Operating Current
44
4 Indoor Unit: TS4232 Outdoor Unit: CL4232
44
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V
23 22 21 20 19 18 17
Operating current (A)
16 15
(-5) (0) (5) (10) (15) (20)
208V
23 22 21 20 19 18 17
Operating current (A)
16 15
Outdoor fan speed (Upper / Lower)
STOP / Med
23 32 41 50 59 68
STOP / Med
Low / Low Med / Med High / High
Outdoor ambient temp. °F (°C)
Outdoor fan speed (Upper / Lower)
Low / Low Med / Med High / High
77
(25)
86
(30)
95
(35)
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
104
(40)
1798_X_S
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
23 32 41 50 59 68
(-5) (0) (5) (10) (15) (20)
Outdoor ambient temp. °F (°C)
– 28 –
77
(25)
86
(30)
95
(35)
104
(40)
1799_X_S
SM830078
5. PERFORMANCE CHARTS
(2) High and Low Pressure
11
1 Indoor Unit: XS4232, TS4232 Outdoor Unit: C4232
11
• High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V / 208V
Outdoor fan speed
Low
340 320 300 280 260 240 220 200
Discharge pressure (psig)
180 160
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
High
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1442_X_S
• Low Pressure
Low pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V / 208V
Outdoor fan speed
Low
100
90 80 70 60 50
Suction pressure (psig)
40
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
High
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1800_X_S
– 29 –
SM830078
5. PERFORMANCE CHARTS
(2) High and Low Pressure
22
2 Indoor Unit: XS4232, TS4232 Outdoor Unit: CL4232
22
• High Pressure
High pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V / 208V
Outdoor fan speed (Upper / Lower)
340 320 300 280 260 240 220 200
Discharge pressure (psig)
180 160 140
23 32 41 50 59 68
(-5) (0) (5) (10) (15) (20)
STOP / Med
Low / Low Med / Med High / High
77
(25)
Outdoor ambient temp. °F (°C)
86
(30)
95
(35)
• Low Pressure
Low pressure characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
104
(40)
1444_X_S
230V / 208V
100
90 80 70 60 50
Suction pressure (psig)
40
23 32 41 50 59 68
(-5) (0) (5) (10) (15) (20)
STOP / Med
Outdoor fan speed (Upper / Lower)
Low / Low Med / Med High / High
77
(25)
Outdoor ambient temp. °F (°C)
– 30 –
86
(30)
95
(35)
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
104
(40)
1801_X_S
SM830078
6. AIR THROW DISTANCE CHART
MODEL: XS4232
HORIZONTAL DISTANCE (ft.)
03 7 10131720
0
MODEL: TS4232
0
3
7
10
VERTICAL DISTANCE (ft.)
AXIS AIR VELOCITY (ft./sec)
13
FAN SPEED ROOM AIR TEMP.
LOUVER ANGLE
5
AXIS AIR VELOCITY
COOLING
HIGH
80°F
30°
: COOLING
1428_X_S
Horizontal distance (ft.)
100 1520253033
5
10
Axis air velocity (ft./sec.)
Vertical distance (ft.)
15
Axis air velocity
1454_X_S
COOLING FAN SPEED HIGH ROOM AIR TEMP. 80°F LOUVER ANGLE – 7°
SM830078
– 31 –
7. REFRIGERANT FLOW DIAGRAM
Indoor Unit: 4232 Type Outdoor Unit: C4232, CL4232
Wide tube service valve
O. D. 3/4" (19.05 mm)
Evaporator
Capillary
Strainer
O. D. 3/8" (9.52 mm)
Narrow tube service valve
Insulation of Refrigerant Tubing
IMPORTANT
When installing “CL” models,
CAUTION
insulate both wide and narrow tube.
Accumulator
Sub-condenser
High
pressure
HP
switch
Thickness: Min. 5/16 in.
Compressor
Condenser
1802_X_S
Insulation
Thickness: Min. 5/16 in.
When outdoor temperature is low, condensation can also from on a narrow tube. So always insulate both wide and narrow tubes.
After a tube has been insulated,
CAUTION
never try to bend it into a narrow curve because it can casue the tube to break or crack.
– 32 –
Wide tube
Wide tube
Narrow tube
0999_C_I
CL type
Insulator Thickness: Min. 5/16 in.
Narrow tube
1005_C_I
C type
SM830078
8. INSTALLATION INSTRUCTIONS
1) Tubing Length
• Refrigerant tubing between the indoor and outdoor units should be kept as short as
INDOOR UNIT
possible.
• Select and decide the installation location
Elevation difference (H)
so that the length of the refrigerant tubing will be within the limits given in Table 1.
Fig. 1
Table 1
Model
Tubing Data
Tubing size
Narrow tube in. (mm) 3/8 (9.52) outer dia. Wide tube in. (mm) 3/4 (19.05) Limit of tubing length (ft.) 165
Outdoor unit is higher
(ft.) 165
Limit of elevation difference than indoor unit between the 2 units
Outdoor unit is lower
(ft.) 100
than indoor unit Max. allowable tubing length at shipement (ft.) 50
Required additional refrigerant*
1
(oz./ft.) 0.86
Refrigerant charged at shipment (lbs.) 9.7
C4232
CL4232
Tubing length (L)
OUTDOOR UNIT
0711_M_I
No additional charge of compressor oil is necessary. *1If total tubing length becomes 50 to 165 ft., charge additional refrigerant (R22) by 0.86 oz./ft..
– 33 –
SM830078
8. INSTALLATION INSTRUCTIONS
2) Selecting the Installation Site
Indoor Unit
AVOID:
ã areas where leakage of flammable gas may
be expected.
Ceiling-Mounted Type
Ceiling
ã places where large amounts of oil mist exist. ã direct sunlight. ã locations near heat sources which may
affect performance of the unit.
ã locations where external air may enter the
room directly. This may cause “sweating” on the air discharge ports, causing them to spray or drip.
ã locations where the remote control unit will
be splashed with water or affected by dampness or humidity.
ã installing the remote control unit behind
curtains or furniture.
ã locations where the receiver in the indoor
unit is exposed to the inverter lamp light. Faulty operation of the unit occurs.
DO:
ã select an appropriate position from which
every corner of the room can be uniformly cooled.
ã select a location where the ceiling is strong
enough to support the weight of the unit.
Wall
Min.10 inch
NOTE
The rear of the indoor unit can be installed flush against the wall.
3 ft.
Front view
Air discharge
Min.2ft.
Side view
Recessed Type
3 ft.
3 ft.
Min.10 inch
Ceiling
Air intake
1379_T_I
3 ft.
3 ft.
ã select a location where tubing and drain pipe
have the shortest run to the outdoor unit.
ã allow room for operation and maintenance as
well as unrestricted air flow around the unit.
ã install the unit within the maximum elevation
difference above or below the outdoor unit and within a total tubing length from the outdoor unit as detailed in Table 1.
ã allow room for mounting the remote control
unit about 3 ft. off the floor, in an area that is not in direct sunlight nor in the flow of cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from the floor to the ceiling is greater than 10 ft..
– 34 –
1330_X_S
SM830078
8. INSTALLATION INSTRUCTIONS
Outdoor Unit
AVOID:
ã heat sources, exhaust fans, etc. (Fig. 2) ã damp, humid or uneven locations.
DO:
ã choose a place as cool as possible. ã choose a place that is well ventilated and
outside air temperature does not exceed maximum 115°F constantly.
ã allow enough room around the unit for air
intake/ exhaust and possible mainte­nance. (Fig. 3)
ã provide a solid base; about 6 inch above
ground level to reduce humidity and possible water damage in the unit and decreased service life. (Fig. 4)
ã use lug bolts or equivalent to bolt down
unit, reducing vibration and noise.
Min. 1 inch
Hot air
4 in.
Out­door unit
Min. 2 ft.
Fig. 2
Min. 1 inch
0931_C_I
Fig. 3
Exhaust fan
Heat source
0591_C_I
Obstacle above
Min. 7 ft.
Air dis­charge
Ground
0932_C_I
In case of multiple installations
Unit spacing if air discharge chamber is not used. Unit spacing when air discharge chamber is used.
Min. 4 ft. Min. 4 ft.Min. 5 ft.
Min. 1 ft.
Min. 12 ft.
Min. 8 inch
If you would like to make the separation smaller on the air discharge side, use an air discharge chamber. You can install any number of units side-by -side.
Min. 4 ft.
Min. 1 ft. 2 inch
Min. 1 ft. 2 inch
Only up to 3 units can be installed side-by-side under the above conditions. The next group must be spaced at least 1 ft. away from the first group.
Concrete block 4 inch × 1 ft. 4 inch beams or equal
Min. 8 inch
Air in
Air discharge
Anchor bolts (4 pieces)
Min. 1 ft.
Fig. 4
Min. 4 ft.
Air discharge chamber
Min. 1 ft.
0933_C_S
Air in
Min. 6 inch
0934_C_I
– 35 –
SM830078
8. INSTALLATION INSTRUCTIONS
I
Air Discharge Chamber for Top Discharge
Install the air-discharge chamber in the field when: ã it is difficult to keep a space of minimum 2
ft. between the air-discharge outlet and the obstacle.
ã the air-discharge outlet is facing the side-
walk and discharged hot air can annoy the passers-by. Refer to Fig. 5.
Wind Shield for “CL” Model
IMPORTANT
It is recommended to use wind shields for “CL” model (Fig. 6). “CL” model is designed to use in low outdoor temperature conditions.
General
When the outdoor unit is installed in a position exposed to strong wind (like seasonal winds with low air temperature in winter), wind shield must be installed on the outdoor unit.
This unit is designed so that the fan of the outdoor unit runs at low speed when the air conditioner is operated at low outdoor air temperatures. When the outdoor unit is ex­posed to strong wind, the system pressure drops because of the freeze protector.
For outer dimensions of wind shield, please see Fig. 7.
22-5/16"
3-ø2-3/8" hole
Air discharge
0426_C_I
Fig. 5
Wind shield (air discharge side)
Front
0935_C_I
Fig. 6
Recommended outer dimensions of wind shield (field supply)
8-ø1/4" hole
11-13/16"
21-13/16"
43-15/16"
9-7/8"9-7/8" 17-3/4" 3-15/16"
5-3/16"
23-5/16"
CL3032, 3632 CL2432
5-5/32"
1352_C_
21-13/16"
CL4232
– 36 –
3 - ø1-9/16" hole
9-27/32"21-5/8"15/16"
6 - ø15/64" hole
Fig. 7
22-7/16"1/2"
23-15/32"
5-3/16"
5-5/32"9-27/32"9-27/32"1-7/32"
0936_C_I
SM830078
8. INSTALLATION INSTRUCTIONS
3) Electrical Wiring
General Precautions on Wiring
(1) Before wiring, confirm the rated voltage
of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclu-
sively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be pro­vided in the exclusive line.
(3) To prevent possible hazards from insula-
tion failure, the unit must be grounded.
(4) Each wiring connection must be done in
accordance with the wiring system dia­gram. Wrong wiring may cause the unit to misoperate or become damaged.
(5) Do not allow wiring to touch the refriger-
ant tubing, compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal
wiring can be very dangerous. The manu­facturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes.
(7) Regulations on wire diameters differ from
locality to locality. For field wiring rules, please refer to your LOCAL ELECTRI­CAL CODES before beginning. You must ensure that installation complies with all relevant rules and regulations.
(8) To prevent malfunction of the air condi-
tioner caused by electrical noise, care must be taken when wiring as follows:
ã The inter-unit control wiring and the remote
control wiring (option) should be wired apart from the inter-unit power wiring.
ã It is recommended that shielding wires or
twisted pair wires be used for the remote control and the inter-unit control wiring if the air conditioner is installed where it is exposed to the influence of electrical and/ or electro-magnetic noise.
Recommended Wire Length and Wire Diameter for Power Supply System
Power Supply Terminal Base (Outdoor Unit)
Capacity
1 2
G
4
(A)
L1 L2
G
1 2
G
Ground
4
Time Delay Fuse or Circuit Capacity
Disconnect sw (Field supply)
(B)
(A)*1 Power Supply
Models
C4232, CL4232 65 ft. (AGW #10) 164 ft. 50 A 50 A AWG #6
*1 Refer to the Wiring System Diagrams (See below diagram) for the meaning of “A”, “B”.
AWG = American Wire Gauge
NOTE
(B)*1 Inter-unit
Wiring
AGW #14
Indoor Unit Outdoor Unit
To access the electrical component box, open the air intake grille and remove the electrical component box cover.
Wiring System Diagram
Outdoor Unit : “C”, “CL” models Single-phase 60 Hz, 208 / 230 V
Max. Wire Diameter
Ground
1368_M_I
– 37 –
SM830078
9. ELECTRICAL DATA
Electrical characteristics
Indoor model: XS4232 / Outdoor model: C4232, CL4232
Indoor Unit Outdoor Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
A 0.9 - 0.8 1.8 - 1.8 18.1 - 18.5 20.8 - 21.1
Rating conditions
kW 0.2 - 0.16 0.36 - 0.34 3.67 - 3.62 4.23 - 4.12
A 0.9 - 0.8 1.8 - 1.8 21.44 - 22.7 24.1 - 25.3
Full load conditions
kW 0.2 - 0.16 0.36 - 0.34 4.49 - 4.48 5.05 - 4.98
Starting amperes A 1 - 1 2 - 2 131 - 131 134 - 134
Complete Unit
Indoor model: TS4232 / Outdoor model: C4232, CL4232
Indoor Unit Outdoor Unit
Fan Motor Fan Motor Compressor
Performance at 230 - 208 V / 1 phase / 60 Hz 230 - 208 V / 1 phase / 60 Hz
A 0.7 - 0.7 1.8 - 1.8 18.1 - 18.5 20.6 - 21.0
Rating conditions
kW 0.16 - 0.14 0.36 - 0.34 3.67 - 3.62 4.19 - 4.10
Complete Unit
Full load conditions
Starting amperes A 1 - 1 2 - 2 131 - 131 134 - 134
A 0.7 - 0.7 1.8 - 1.8 21.44 - 22.7 23.9 - 25.2
kW 0.16 - 0.16 0.36 - 0.34 4.49 - 4.48 5.01 - 4.96
Rating Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 95 °F DB
Full Load Conditions : Indoor Air Temperature 80 °F DB / 67 °F WB
Outdoor Air Temperature 115 °F DB
– 38 –
SM830078
10. ELECTRICAL WIRING DIAGRAMS
(1) Indoor Unit
11
1 XS4232
11
• Electric Wiring Diagram
E
GRN/YEL
Earth Terminal
TH1 (Coil)
BLK
BLK
21
2P(RED)
TH1
RED
1
Terminal Plate(4P)
To Outdoor Unit
TH2 (Room)
2P(YEL)
SUP
5P(WHT)
WHT
2G
TH2
BLK
21
4
BLK
BRN
Switch Assy
213
RED
ORG
BRN
213
3P(WHT) SW ASSY
Controller (CR-TS2432)
PRY
2P(WHT)
WHT
GRN/YEL
21
WHT
SEC
2P(WHT)DP3P(BLU)FS3P(RED)
21
BRN
P
S
TR1
BRN
22 11
BRN
Connector
Earth Terminal
PS
BRN
2P(YEL)
IND Lamp Assy
7P(WHT)
31
BLK
BLK
DP
GRN/YEL
W/LESS
71
71
31
BLK
SP123
3P(GRN)
FM
COM
RC1
BLK
P
123456789 1
S
FS
GRN/YEL
Earth Terminal
LM
GRN/YEL
GRY
BLK
123
Connector 3P(WHT)
GRN/YEL
Earth
GRY
BLK
Terminal
31
LM
7P(WHT)
MHL
3175315
ORG
VLT
PNK
BRN
3456789
2
YEL
ORG
PNK
BRN
BLK
FMI
3P(WHT)
49FMI
31
GRY
WHT
VLT
WHT
BRN
GRY
BRN
Connector
GRY
9P(WHT)
– 39 –
W 854-2-5268-578-00-0 (XS3632)
SM830078
10. ELECTRICAL WIRING DIAGRAMS
(1) Indoor Unit
11
1 XS4232
11
4P-1
4P-4
4P-2
• Schematic Diagram
3
F1
(3A)
RY5
RY3
5
1
RY4
1
1
1
DP
LM
2
3
3
RY2
HLM
RY1
RY2
735
456
FMI
12
RC1
8
49FI
9
1
1
3
49FMI
PRY
2
122
1
TR1
RY1
RY2
RY3
RY4
RY5
1
CR-TS2432
Controller
SEC
LM
DP
W/ LESS
SW ASSY
FS
TH1
TH2
717
1 2
3
1
3
1
2
1
2
1
1 2 3
FS
TH1
Coil
TH2
Room
IND
SW
Symbols Description
FMI 49FI RC1 F1 DP LM TR1 RY1-RY5 FS
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Drain Pump Auto Louver Motor Power Transformer Auxiliary Relay Float Switch
Symbols Description
TH1 TH2 CR-TS2432 IND SW
Thermistor (Indoor Coil) Room Thermistor Indoor Controller Indicator Lamp Assy Switch Assy Terminal Plate Connector Terminal
S 854-2-5268-578-00-0 (XS3632)
– 40 –
SM830078
10. ELECTRICAL WIRING DIAGRAMS
(1) Indoor Unit
22
2 TS4232
22
• Electric Wiring Diagram
LM
E
GRN/YEL
Earth Terminal
TH1 (Coil)
BLK
BLK
21
2P(RED)
TH1
RED
1
Terminal Plate(4P)
To Outdoor Unit
TH2 (Room)
2P(YEL)
TH2
SUP
5P(WHT)
WHT
2G
BLK
21
4
BLK
BRN
Switch Assy
213
RED
ORG
BRN
213
3P(WHT)
SW ASSY
Controller (CR-TS2432)
PRY
2P(WHT)
WHT
GRN/YEL
Earth Terminal
21
WHT
SEC
2P(WHT)DP3P(BLU)FS3P(RED)
21
BRN
P
S
TR1
BRN
22 11
BRN
Connector
PS
BRN
2P(YEL)
P
Connector 2P(WHT)
BLU
12
IND Lamp Assy
7P(WHT)
W/LESS
31
WHT
71
71
31
BLK
P
12 12
S
BLK
Earth Terminal
3P(GRN)
FM
COM
RC1
BLK
P
123456789 1
S
Connector
2P(BLK)
GRN/YEL
BLK
WHT
GRN/YEL
31
LM
7P(WHT)
MHL
3175315
ORG
VLT
PNK
BRN
3456789
2
YEL
ORG
PNK
BRN
BLK
FMI
3P(WHT)
49FMI
31
GRY
WHT
VLT
WHT
BRN
GRY
BRN
Connector
9P(WHT)
GRY
– 41 –
W 854-2-5268-593-00-0 (TS3632)
SM830078
10. ELECTRICAL WIRING DIAGRAMS
(1) Indoor Unit
22
2 TS4232
22
4P-1
4P-4
4P-2
• Schematic Diagram
3
F1
(3A)
RY5
RY3
5
1
RY4
1
1
1
LM
2
3
3
RY1
RY2
HDP LM
RY2
735
456
FMI
12
RC1
8
49FI
9
1
1
3
49FMI
PRY
2
122
1
TR1
RY1
RY2
RY3
RY4
RY5
1
CR-TS2432
Controller
SEC
LM
DP
W/ LESS
SW ASSY
TH1
TH2
1
IND
717
1
1
2
2
SW
3
3
1
FS
1
3
2
TH1
1 2
Coil
TH2
1 2
Room
Symbols Description
FMI 49FI RC1 F1 DP LM TR1 RY1~RY5 FS
Indoor Fan Motor Indoor Motor Thermal Protector Running Capacitor Fuse Drain Pump Auto Louver Motor Power Transformer Auxiliary Relay Float Switch
Symbols Description
TH1 TH2 CR-TS2432 IND SW
Thermistor (Indoor Coil) Room Thermistor Indoor Controller Indicator Lamp Assy Switch Assy Terminal Plate Connector Terminal
S 854-2-5268-593-00-0 (TS3632)
– 42 –
SM830078
10. ELECTRICAL WIRING DIAGRAMS
(2) Outdoor Unit
11
1 C4232
11
2
6
RED
14
5
RED
BLU
RED
RED
6
3
7
1Y
23S
C
HL
41
42
13
14
T
W
S
V
R
U
A1
A2
52C
BLU
2
8
BRN
GRY
BRNWHT
BRN
BRN
BLK
• Electric Wiring Diagram
14
5
3
BRN
RED
RC3
RC2
WHT
8 76
P
BLK BLU
54
3
BRN
21
PNK
P
Connector
8 76
VLT WHT
54
GRY GRY
3
BRN
21
PNK
P
Connector
RC1
P
S
2
2
1
1
2P (WHT)
Connector
8 76
S
54
3 21
S
8P (WHT)
Earth
8 76
54
3 21
S
8P (WHT)
WHT BLK RED
GRY WHT
YEL VLT WHT GRY GRY BRN PNK
Terminal
YEL VLT WHT GRY GRY BRN PNK
S
R
C
63PH
49FO2
FMO2
49FO1
FMO1
CM
W 854-2-5268-896-00-0 (C4232)
GRN/YEL GRN/YEL
7
Terminal
Plate (6P)
8
2Y
PNK
WHT
1
RED
2
REDRED
WHT
4
G
L1
To Indoor Unit
GRN/YEL
L1
L2
L2
G
Power Supply
Earth
60Hz 1PH 208 V / 230 V
Terminal
Earth
Terminal
SM830078
– 43 –
10. ELECTRICAL WIRING DIAGRAMS
(2) Outdoor Unit
11
1 C4232
11
Terminal Plate (6P)
-1
-2
-G
-4
-L1
-L2
2Y
52C
• Schematic Diagram
2Y
2Y
Symbols Description
CM FMO1, 2 49FO1, 2 52C 63PH 23S RC1, 2, 3 1Y, 2Y
3
49FO1
4
1
3
49FO263PH
4
2
Compressor Motor Outdoor Fan Motor Outdoor Fan Motor Thermal Protector Compressor Motor Magnetic Contactor High Pressure Switch Fan Speedcontrol Thermostat Running Capacitor Auxiliary Relay Connector Terminal Plate
SVR
52C
RC1
R
SC
CM
52C
TW
U
5
31
65
23S
C
H
L
FMO1
1Y
2 1
RC2
S 854-2-5268-896-00-0 (C4232)
6
1Y
42
65
FMO2
2 1
RC3
– 44 –
SM830078
10. ELECTRICAL WIRING DIAGRAMS
(2) Outdoor Unit
22
2 CL4232
22
AC 208V
AC 230V
TH
AC 14V
TR
BLK
BRN
BRN
1
2
SEC
2P (WHT)
WHT 1
3P (WHT)
WHT 3
PRY
2
2P (WHT)
FMO
9P (WHT)
COMHGBV LMH
BLK 1
TEMP
31 75 931
YEL VLT
WHT
BLK
BRN
BRN
YEL
VLT
VLT
Controller (CR-CL2432)
BRN
RED
3P (RED)
SUP
1
3
RED
WHT
3P (YEL)
3P (BLU)
MGSW
1
3
GRY
ORG
E
GRN/YEL
GRN/YEL
Earth
RED
BRN
BLK
Terminal
BRN
RED
• Electric Wiring Diagram
24
6
13
5
BLU
BLU
7
2Y
RED
RC3
WHT
BRN
7
BRN
RC2
24
6
13
5
7
8
1Y
GRY
ORG
8
BLU
WHT BLK
BRN PNK
YEL
24
6
13
5
8
4Y
YEL VLT WHT GRY GRY BRN
PNK
P
S7
87
8
65
65
43
43
21
21
WHT
S7
P 87
8
65
65
43
43
21
21
Connector
8P (WHT)
Connector
21
WHT
P
Connector
WHT
21
WHT
P
Earth
Terminal
Connector
8P (WHT)
YEL VLT WHT GRY GRY BRN PNK
6
5
7
YEL VLT WHT GRY GRY BRN PNK
2P (WHT) 21
S
2P (WHT) 21
S
3Y
24
13
GRY WHT
WHT WHT
8
49FO2
FMO2
49FO1
FMO1
63PH
CH
GRN/YEL
GRN/YEL
W 854-2-5268-897-00-0 (CL4232)
Terminal
Plate (6P)
RED
1
2
BLK
RED
WHT
4
G
L1
To Indoor Unit
RED
WHT
L1
L2
L2
– 45 –
13
GRY
RST 41
A1
G
Power Supply
BLK
UVW 4214
52C
A2
BRN
60Hz 1PH 208 V / 230 V
Earth
Terminal
RC1
WHT BLK RED
S
R
CM
C
SM830078
10. ELECTRICAL WIRING DIAGRAMS
(2) Outdoor Unit
22
2 CL4232
22
Terminal Plate (6P)
-1
-2
-G
-4
-L1
-L2
RUS
52C
C
1Y
1
V
RC1
R
S
CH
2
CM
Symbols Description
CM CH FMO1, 2 49FO1, 2 52C TR TH RC1, 2, 3 RY1, 2, 3 1Y~4Y CR-CL2432
Compressor Motor Crankcase Heater Outdoor Fan Motor Outdoor Fan Motor Thermal Protector Compressor Motor Magnetic Contactor Power Transformer Thermistor (Outdoor Temperature) Running Capacitor Auxiliary Relay Auxiliary Relay Outdoor Controller
52C
• Schematic Diagram
F1 (3A)
1
RY2
HLM
FMO2
RC3
RY1
75 9 1
2Y
65 7
1
2
1 3
RY3
3Y
2Y1Y4Y
1
52C
4142
1
1Y
63PH
2
F2 (3A)
3
3
52C
1413
3
49FO1
4
3
49FO2
4
3
COM COM
3Y
65 7
FMO1
1 2
RC2
4Y
RY1
RY2
RY3
CR-CL2432
Controller
Temp
+12V
L
PRY
M
SEC
HGBV
TH
1 2
Outdoor Temperature
3
AC 208V
1
1
AC 14V
2
TR
230V
Symbols Description
F1, 2 63PH
Fuse High Pressure Switch Terminal Plate Connector Terminal
– 46 –
S 854-2-5268-897-00-0 (CL4232)
SM830078
11. PROCESSES AND FUNCTIONS
(1) Room Temperature Control
The Unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF. This process is controlled by the thermostat located in the remote control unit. The figures on this and the next pages show how each part of the system performs when the room temperature changes and the thermostat activates the compressor to start (thermo ON) or stop (thermo OFF). Fig. 8 shows about the cooling cycle.
ROOM TEMPERATURE
WITHIN 3 MINUTE
MORE THAN 3 MINUTES
S. T.+ 1°F SET TEMP. T°F (S.T.)
COMPRESSOR
INDOOR FAN
OUTDOOR FAN
THERMO OFF 3 MINUTES
ON
ON ON
THERMO ON
MORE THAN 5 MINUTES
OFF
SET SPEED (MANUAL)
OFF OFF
ON ON
THERMO OFF
OFF
Fig. 8
Chart Summary and Explanations
Once the compressor starts, it keeps running for 5 minutes. Once the compressor stops, it will not start running again for 3 minutes. If you change the operation mode during the cooling cycle, the control circuit stops the
compressor for 3 minutes.
For 5 minutes after the compressor is first turned on, and for 3 minutes after it is turned off,
the compressor is not controlled by the room sensor.
Thermo ON: When room temperature rises 1 °F above the set temperature T˚, (T ˚+1 °F):
Compressor ON
Thermo OFF: When the room temperature is equal to or below the set temperature T˚:
Compressor OFF
THERMO ON
ON
1028_X_S
– 47 –
SM830078
11. PROCESSES AND FUNCTIONS
(2) Freeze Prevention
Freeze Prevention keeps the indoor heat exchange coil from freezing. Freezing reduces the efficiency of the unit, and frost buildup on the coil blocks cool air circulation from the indoor unit’s fan.
INDOOR COIL TEMPERATURE
MORE THAN 10 MINUTES
FREEZE PREVENTION
6 MINUTES 10 MINUTES
FREEZE PREVENTION
6 MINUTES
30°F
COMPRESSOR
OUTDOOR FAN
INDOOR FAN
ON
ON
(THERMO OFF)
OFF
OFF OFF
SET SPEED
ON
ON
(THERMO ON)
OFF
ON
ON
1029_X_S
Fig. 9
(3) Drain Pump Control
Drain pump operates when compressor starts to operate or when Float Switch turns off.
FLOAT SWITCH
ON: low water level OFF: high water level
COMPRESSOR
DRAIN PUMP
OUTDOOR FAN
INDOOR FAN
ON
ON
ON
ON
OFF
OFF
OFF
ON
ON
SET SPEED
– 48 –
OFF
20 MINUTES
OFF
ON
OFF
ON
ON
ON
0609_X_S
Fig. 10
SM830078
11. PROCESSES AND FUNCTIONS
(4) Outdoor Fan Speed Control
1) C4232 Type
• In low outdoor temperature, the outdoor fan is set automatically from HIGH to LOW to prevent the indoor heat exchanger from freezing.
• When the outdoor temperature falls below 78 °F, the outdoor fan is set from HIGH to LOW automatically. When the outdoor temperature rises to 82 °F, the outdoor fan is set from LOW to HIGH automatically.
2) CL4232 Type
• In low outdoor temperature, the outdoor fan is set automatically from HIGH to MED, LOW to prevent the indoor heat exchanger from freezing.
• When the outdoor temperature falls below 77 °F, the outdoor fan is set from HIGH to MED automatically. When the outdoor temperature rises to 81 °F, the outdoor fan is set from MED to HIGH automatically.
• When the outdoor temperature falls below 59 °F, the outdoor fan is set from MED to LOW automatically. When the outdoor temperature rises to 63 °F, the outdoor fan is set from LOW to MED automatically.
• When the outdoor temperature falls below 47 °F, the outdoor upper fan is set from LOW to OFF and Lower fan is set from LOW to MED antomatically. When the outdoor temperature rises to 50 °F, the outdoor upper fan is set from OFF to LOW and Lower fan is set from MED to LOW antomatically.
870
380
Upper fan: OFF Lower fan: M
FAN ROTATION RPM
230
Upper fan: M Lower fan: M
Upper fan: L Lower fan: L
47 50 59 63 77 81
OUTDOOR AIR TEMPERATURE °F DB
Upper fan: H Lower fan: H
1344_X_S
Fig. 11
– 49 –
SM830078
12. SERVICE PROCEDURES
(1) Troubleshooting
1) Check before and after Troubleshooting
Many problems may happen because of wiring or power supply problems, so you should check these areas first. Problems here can cause false results in some of the other tests, and so should be corrected first.
11
1 Check power supply wiring
11
(a) Single-phase
Check that power supply wires are correctly connected to terminal No. 1
through No. 4 on the 4P terminal plate in the indoor unit and L1 and L2 on the 6P terminal in the outdoor unit.
22
2 Check inter-unit wiring
22
Check that inter-unit control wiring (AC 230 - 208 V Line voltage) is cor-
rectly connected between the indoor unit and outdoor unit.
Single-phase outdoor unit
Disconnect SW
Indoor Unit Outdoor Unit
(Field supply)
1 2 G
Ground
4
Inter-Unit Wiring (Line voltage)
B
Fig. 12
1 2 G
4 L1 L2
G
Power supply
A
Ground
1089_M_I
33
3 Check power supply
33
Check that voltage is within the specified range (±10 % of the rating). Check that power is being supplied.
If the following troubleshooting must be done with power being supplied, be careful not to touch any uninsulated live part that can cause ELECTRIC SHOCK.
44
4 Check the lead wires and connectors in indoor and outdoor units.
44
Check that the sheath of lead wires is not damaged. Check that the lead wires are firmly connected at the terminal plate. Check that the wiring is correct.
55
5 Reference
55
Condition of general cooling operation (Thermo. ON)
SWEEP .................. ON
Indoor fan speed .... HIGH
– 50 –
SM830078
12. SERVICE PROCEDURES
2) Air Conditioner does not Operate
11
1 Circuit breaker trips (or fuse blows).
11
(a) When the circuit breaker is set to ON, it is tripped soon.
• There is a possibility of ground fault.
• Check insulation resistance. If resistance value is 1 M or less, it is a defect of insulation.
(Example)
1 3
Outdoor
unit
L1
Circuit breaker
*Set the circuit breaker to OFF.
Power supply cords
+ +
Ground
L2
G
1 2
G
4
2
4
+ +
+
Inter-unit power line
+ +
+
Indoor
unit 1 2
G
4
1
Remove power supply cords from the terminal plate in the outdoor unit.
• Check insulation resistance of power supply cords.
OK
Remove inter-unit power line
2
from the terminal plate in the outdoor unit.
• Check insulation resistance of outdoor unit.
OK
3
Remove inter-unit power line from the terminal plate in the indoor unit.
• Check insulation resistance of indoor unit.
NO
NO Insulation of
NO
Execute rewiring.
outdoor unit is defective.
Insulation of indoor unit is defective.
• Check insulation resistance of electrical parts in the outdoor unit.
• Check insulation resistance of electrical parts in the indoor unit.
OK
Inter-unit power lines are defective.
Execute rewiring.
1340_X_S
SM830078
– 51 –
12. SERVICE PROCEDURES
(b)
Circuit breaker trips in several minutes after turning the air conditioner on.
• There is a possibility of short circuit.
• Check capacity of circuit breaker.
Is capacity of circuit breaker sufficient ?
• Check resistance of outdoor fan motor winding.
• Check resistance of compressor motor winding.
22
2 Neither indoor unit nor outdoor unit runs.
22
NO
A. Power is not supplied
Circuit breaker
• Check power supply. Is power being supplied to outdoor unit ?
NO
is tripped.
Power failure.
Replace it with a suitable one. (= larger capacity)
0614_X_S
Reset the breaker.
Wait for recovery or consult power supply company.
0615_X_S
B. Check remote control unit.
• Try to run both indoor and outdoor units with another remote control unit.
OK
The other remote control unit is defective.
NO
Refer to item C.
0616_X_S
SM830078
– 52 –
12. SERVICE PROCEDURES
C. Check “Operation selector” switch in the indoor unit.
• Has “Operation selector” switch been set to ON
YES
position ?
NO
Set “Operation selector” switch to ON.
But neither unit runs.
Switch Ass’y or P.C.B. Ass’y in the indoor unit is defective.
D. Check compressor motor protectors. (a) High pressure switch (63PH)
• Check high pressure switch. Does high pressure switch actuate ? (63PH)
IND. LAMP Ass’y or P.C.B. Ass’y in the indoor unit is defective.
0617_X_S
Disconnect the socket from 2P (WHT) connector. Check the continuity between No.1 and No.2 poles of the socket.
YES
• Is outdoor heat exchanger coil dirty or are there obstacles near air suction inlet of outdoor unit ?
NO
• Check if outdoor fan rotates. Refer to “Only outdoor fan does not run.”
E. Transformer in indoor unit.
• Check resistance of transformer winding. (TR1)
1033_X_S
YES
Clean heat exchanger coil or remove obstacles.
0618_X_S
– 53 –
SM830078
12. SERVICE PROCEDURES
F. Check. auxiliary relay. (1Y or 2Y)
• Check coil resistance of auxiliary relay. (1Y or 2Y)
G. Check indoor fan motor thermal protector (49FMI)
• Disconnect the socket from 9P (WHT) connector.
• Check the continuity between No. 8 and No.9 poles of the 9P socket.
No continuity.
The thermal protector (49FMI) is operated.
• Check fan rotation. Rotate the fan gently once or twice by hand.
OK
• Check fan motor capacitor.
0620_X_S
Fan cannot be rotated.
Check fan casing for foreign matter on the inside.
Fan motor burnout or foreign matter in bearing.
Remove foreign matter or repair.
Repair or replace.
0621_X_S
H. Check fuse on the P.C.B. Ass’y in the indoor unit.
• Check fuse on the P.C.B. Ass'y in the indoor unit for continuity.
When the fuse blows.
• Check transformer. (TR1) OK
• Check resistance of indoor
fan motor winding. (FMI)
OK
• Check resistance of louver
motor winding. (LM)
OK
• Check resistance of drain pump winding. (DP)
• Check coil of compressor motor magnetic contactor. (52C)
• P.C.B. Ass'y is defective.
(XS Type only)
OK
OK
1034_X_S
– 54 –
SM830078
12. SERVICE PROCEDURES
3) Outdoor Unit does not Run.
A. Check COOL / FAN selector switch in the remote control unit.
• Is COOL/FAN selector switch set to COOL ?
B. Check set temperature.
Try to lower set temperature by Temperature setting button “COOLER”.
YES
• Set “Operation selector” switch to TEST in the indoor unit.
Outdoor unit runs.
Is room temperature too low ?
NO
Set to COOL.
0623_X_S
NO
• Try to run both indoor and outdoor units with another remote control unit.
OK
The other remote control unit is defective. (Room sensor in the remote control unit is defective.)
0624_X_S
– 55 –
SM830078
12. SERVICE PROCEDURES
C. Check compressor motor magnetic contactor.
• Check coil resistance of
compressor motor magnetic contactor. (52C)
1035_X_S
D. Check indoor unit P.C.B.
• Check P.C.B. Ass’y.
• Check voltage between terminals No.2 and No.4 at terminal plate.
No voltage appears.
P.C.B. Ass’y is defective.
0628_X_S
F. Check float switch. (XS Type only)
• Refer to “2-3 Drain Pump Control”
E. Check outdoor unit P.C.B.
(CL3632 Type)
• Check P.C.B. Ass’y.
• Check voltage between terminals L1 and L2 at terminal plate.
No voltage appears.
P.C.B. Ass’y is defective.
1036_X_S
Is drainage prevented from flowing ?
YES
• Check drain hose.
NO (Wait for 20 minutes.)
• Check float switch (FS).
0629_X_S
SM830078
– 56 –
12. SERVICE PROCEDURES
4) Indoor Unit does not Run.
(Indoor fan and louver motor do not run.)
P.C.B. Ass’y is defective.
0630_X_S
5) Some Part does not Operate.
A. Indoor fan does not run.
• Check fan rotation. Rotate the fan gently once or twice by hand.
Fan cannot be rotated.
Check fan casing for foreign matter on the inside.
Fan motor burnout or foreign matter in bearing.
Remove foreign matter or repair.
Repair or replace.
• Check resistance of fan motor winding.
OK
• Check fan motor capacitor. OK
Relay RY1 or RY2 on the P.C.B. Ass’y is defective.
B. Louver motor does not run.
• Check resistance of
louver motor winding.
OK
P.C.B. Ass’y or remote control unit is defective.
0632_X_S
0631_X_S
– 57 –
SM830078
12. SERVICE PROCEDURES
6) Outdoor Fan does not Run.
• Check fan rotation. Rotate the fan gently once or twice by hand.
• Check resistance of fan motor winding.
OK
• Check fan motor capacitor
• Check continuity between terminals on the compressor motor magnetic contactor.
Fan cannot be rotated.
• Check fan casing for foreign matter on the inside.
• Fan motor burnout or foreign matter in bearing.
Remove foreign matter or repair.
Repair or replace.
0633_X_S
7) Outdoor Fan Speed is not Switched from High to Low even when the Outdoor
Temperature Falls below 78 °F. (C4232 Type)
• Check the thermostat (23S).
1037_X_S
8) Outdoor Fan Speed is not Switched from High to Med even when the Outdoor
Temperature Falls below 77 °F. Outdoor Fan Speed is not Switched from Med to Low even when the Outdoor
Temperature Falls below 59 °F. (CL4232 Type)
• Check outdoor unit P.C.B. Ass’y
OK
• Check resistance of outdoor temp sensor.
0722 _X_S
– 58 –
SM830078
12. SERVICE PROCEDURES
9) Outdoor Fan does not Run for CL4232.
• Check fuse on PCB Ass’y in outdoor unit for continuity.
If fuse blows,
• Check resistance of primary winding of transformer. (TR)
1038_X_S
10) Compressor does not Run.
• Check compressor motor capacitor (RC1).
OK
• Check PTC. OK
• Check resistance of compressor motor winding.
Wait for 30 minutes until com­ pressor has cooled.
Compressor runs.
Compressor internal thermal protector is operated.
• Check power supply voltage. Is voltage abnormally low?
NO
• Is outdoor heat exchanger coil dirty or are there obstacles near air suction inlet?
1039_X_S
– 59 –
SM830078
12. SERVICE PROCEDURES
11) Poor Cooling
Check installation position of remote control unit.
• Does cool air from air condi­ tioner reach remote control unit directly ?
• Is wide tube between indoor unit and outdoor unit insulated ?
YES
• Measure temperatures of suction and discharge air of indoor unit.
Temperature difference between suction and discharge air is large enough (Approx. 10 deg. or more).
• Check clogging of air filter.
• Is fan speed set to LOW ?
YES
NO
Temperature difference is small.
Possibility of refrigerant shortage.
Air filter is clogged.
YES
Change installation position of remote control unit.
Insulate wide tube and then execute taping with narrow tube.
Charge refrigerant (R22).
Clean filter.
Set fan speed to either HIGH or MEDIUM.
• Review cooling load estimate, if performance of air conditioner is normal.
12) Excessive Cooling.
• The set temperature is too low.
• Is the remote control unit installed at a place where it can detect the room temperature properly ?
YES
NO
Reduce cooling load or replace the unit with higher cooling capacity.
1040_X_S
Set the temperature to higher value using temperature setting button of the remote control unit.
Change installation position of the remote control unit.
0637_X_S
– 60 –
SM830078
12. SERVICE PROCEDURES
(2) A Sensor is Defective
11
1 Indoor (heat exchanger) coil temp. Sensor is defective.
11
(a) Open (=No continuity in sensor)
Compressor and outdoor fan repeat ON for 10 minutes and OFF for 6 minutes when sensor opens.
(b) Short “Freeze Prevention” does not operate when dehumidified water is frozen on the
indoor coil.
22
2 Room temp. Sensor (in the remote control unit) is defective.
22
(a) Open (=No continuity in sensor) Neither outdoor fan nor compressor runs.
(b) Short Outdoor fan and compressor do not stop. — Excessive cooling.
(3) Operation of Major Electrical Parts
Operation Mode
(Function)
Manual
Night
Cool
setback
-ing Timaer
(set) Freeze prevention VV V
Fan
Sweep
Flap
Stop
NOTE V* Refer to Cooling Mode.
Operation
Room Temp.
Thermo.ON VV VV V Thermo.OFF VV V Thermo.ON VV V VV V Thermo.OFF VV V ON Timer V OFF Timer VVV VV V
VV
Cool VV* V* VV* V* Fan VV Cool VV* V* VV* V* Fan VV
Indoor unit and Remote Control unit
Indicator lamps
Cool
Timer
Night setback Energy saver
Sweep
Fan Compressor
Fan
Oudoor unit
– 61 –
SM830078
12. SERVICE PROCEDURES
(4) Checking the Electrical Components
1) Measurement of Insulation Resistance
• The electrical insulation is acceptable when the resistance exceeds 1 M.
11
1 Power Supply Wires
11
Clamp the earthed wire of the Power Supply wires with a lead clip of the insu­lation resistance tester and measure the resistance by placing a probe on either of the power wires. (Fig. 13)
Then measure the resistance between the earthed wire and the other power wires. (Fig. 13)
22
2 Indoor Unit
22
Clamp an aluminum plate fin or copper tube with the lead clip of the insulation resistance tester and measure the resistance by placing a probe on the terminal plate (Fig. 14)
33
3 Outdoor Unit
33
Probe
Copper tube or metallic part
Clip
Clip
Earthed wire
Insulation tester
Terminal plate
0638_X_S
Insulation tester
Probe
0639_X_S
Fig. 13
Fig. 14
Measure the resistance by placing a probe on the terminal plate in the same manner as explained above 2. (Fig. 14)
44
4 Measurement of Insulation Resis-
44
tance for Electrical parts
• Disconnect the connector of the de­sired electric part from terminal plate, P.C.B. Ass’y, etc. (Fig. 15)
Similarly, disconnect the lead wires from compressor, capacitor, etc. (Fig. 16)
• Measure the resistance in the same manner as illustrated on the right.
Refer to Electrical Wiring Diagram.
NOTE
If the probe does not enter the hole be­cause the hole is too narrow, use a probe with a thinner pin.
Copper tube or metallic part
Metallic part
Clip
Clip
Insulation tester
From fan motor, compressor and other parts.
Probe
Insulation tester
Probe
0640_X_S
0641_X_S
Fig. 15
Fig. 16
– 62 –
SM830078
12. SERVICE PROCEDURES
2) Checking the Protective Devices
• Disconnect the connector, which consists of P (plug) and S (socket) when you want to check the protective device.
• Then check continuity among plug’s (and/or socket’s) terminal as in Fig. 17.
• Normality of the protective device can be judged by the following table. The Protective Device is proved normal if there is a continuity between terminals.
socket
Multimeter
0642_X_S
11
1 Indoor fan motor thermal protector (49FI) . . . . . . Indoor unit
11
Fig. 17
• Disconnect the connector which leads to the indoor fan motor (FMI).
• Check the socket’s terminals.
22
2 Compressor motor thermal protector . . . . . . Outdoor unit
22
• Disconnect the wires from terminals of compressor.
• Check the terminals of compressor.
33
3 Outdoor fan motor thermal protector (49FO) . . . . . . Outdoor unit
33
• Disconnect both the connector which leads to the outdoor fan motor (FMO).
• Check socket’s terminal.
– 63 –
SM830078
12. SERVICE PROCEDURES
3) Checking the Electrical Parts
11
1 Power transformer (TR1) ................. Indoor unit *Measure the coil resistance.
11
• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals
of socket connected to power transformer.
• Secondary 10.6 V ; Measure the resistance between two BRN lead wires.
Refer to “1–3–(A) Other component specifications”.
22
2 Power transformer (TR) ................. Outdoor unit *Measure the coil resistance.
22
• Primary 230-208 V ; Measure the resistance between two WHT lead wire terminals
of socket jointed to power transformer.
• Secondary 14 V ; Measure the resistance between two BRN lead wires.
Refer to “1–3–(B) Other component specifications”.
33
3 Indoor fan motor (FMI) ............... Indoor unit *Measure the coil resistance.
33
• Measure the resistance between each terminal of the socket connected to the
indoor fan motor.
Refer to “1–2–(A) Major component specifications”.
44
4 Outdoor fan motor (FMO) ........... Outdoor unit *Measure the coil resistance.
44
• Measure the resistance in the same manner as explained above 3.
Refer to “1–2–(B) Major component specifications”.
55
5 Motor capacitor ............ Both in indoor and outdoor unit
55
• Remove the lead wires from the
capacitor terminals, and then place a probe on the capacitor terminals as shown in Fig. 18. Observe the deflec­tion of the pointer, setting the resis-
Multimeter
tance measuring range of the multim­eter to the maximum value.
• The capacitor is “good” if the pointer
bounces to a great extent and then gradually returns to its original posi­tion.
NOTE
The range of deflection and the de­flection time differ according to the capacity of the capacitor.
– 64 –
Compressor motor capacitor
Fig. 18
Fan motor capacitor
1041_X_S
SM830078
12. SERVICE PROCEDURES
1042_X_S
Fuse
66
6 Continuity of fuse on P.C.B. Ass’y
66
• Check for continuity using a multimeter as shown in Fig. 19.
NOTE
Method Used to Replace Fuse on PCB Ass’y
1. Remove the PCB Ass’y from the electri-
cal component box.
2. Remove the fuse from PCB Ass’y using
pliers while heating the soldered leads on the back side of the PCB Ass’y with a soldering iron (30W or 60W). (Fig. 20)
3. For replacement, insert a fuse of the
same rating to the intended position and solder it. (Allow time to radiate heat during sol­dering so that the fuse does not melt.)
Fig. 19
Soldering iron
PCB Ass’y
Fuse Varistor
When replacing the
CAUTION
fuse, be sure not to break down the varis­tor.
4) Thermistor Characteristic Curve
1 Room temp. sensor
(KTEC-35)
10
9 8 7 6 5
Resistance (kn )
4 3
1 Coil sensor
(PBC-41E)
40
35
30
25
20
15
10
Resistance (kn )
5
Pliers
1043_X_S
Fig. 20
2 1
50 59 68 77 86 95 104
Temperature (°F)
1044_M_I
– 65 –
0
4 5 14233241505968
Temperature (°F)
1045_M_I
SM830078
• The specifications, designs, and information in this brochure are subject to change without notice.
SANYO FISHER Service Company CENTRAL REGION
1739 Sands Place, Suite G Marietta, GA 30067 Phone: (770) 951-8284
Fax: (770) 951-2077
Jun. / ’2000 Printed in U.S.A.
Loading...