ECO-i™ Submittal Data
CHDZ14053
Heat Recovery: 12 tons VRF Outdoor Unit
Job Name: |
|
Approval: |
|
||||||||
Location: |
|
Date: |
|
||||||||
Engineer: |
|
Construction: |
|
||||||||
Submitted to: |
|
Unit #: |
|
||||||||
Submitted by: |
|
Drawing #: |
|
||||||||
Reference: |
|
|
|
|
|
|
|
Compressor Warranty: 6 Years
Parts Warranty: 1 Year
Coil Coated to Protect Against Corrosion
Salt Protection also avilable
Capacities |
|
Cooling: Btu/h |
153,600 |
Power Input: KW |
13.3 |
Heating: Btu/h |
170,600 |
Power Input: KW |
13.2 |
Cooling Mode Nominal Conditions |
|
Indoor: °F DB/°F WB |
80/67 |
Outdoor: °F DB |
95 |
Pipe Length (feet): |
25 |
Level Difference (feet): |
0 |
Heating Mode Nominal Conditions |
|
Indoor: °F DB |
70 |
Outdoor: °F DB/ °F WB |
47/43 |
Pipe Length (feet): |
25 |
Level Difference (feet): |
0 |
Operating Range |
|
Cooling: °F DB: |
14 to 109 |
Heating: °F DB: |
-4 to 59 |
Compressor |
|
Quantity/Type: |
1 Inverter driven rotary & 2 fxed speed scroll |
Capacity Control Range: |
10-100% |
Fan |
|
Quantity/Type: |
1 Propeller |
Fan Motor Output (KW): |
0.7 |
Power Supply |
|
V/PH/Hz. |
208-230 / 3 / 60 |
Minimum circuit Amps (MCA): Amps |
59 |
Max. Overcurrent Protection (MOCP): |
70 |
Weight (lbs): |
789 |
Refrigerant: |
410A |
Coil |
|
Coil Face Area (sq. ft.): |
22.5 |
Number of Rows: |
4 |
Protection Devices |
|
High Pressure Switch: |
Yes |
Overcurrent (CT Method): |
Yes |
Crankcase Heaters (W): |
25 + 32 x 2 |
External Finish: |
Electrostatic Powder Coating |