Sanyo C2462R, CL2462R User Manual

TECHNICAL DATA
SERVICE MANUAL
KS2462R / C2462R, CL2462R
SPLIT SYSTEM AIR CONDITIONER
INDOOR MODEL No. PRODUCT CODE No. OUTDOOR MODEL No. PRODUCT CODE No.
KS2462R 854 019 00
Indoor Unit Outdoor Unit
C2462R 854 019 01
CL2462R 854 019 02
FILE NO.
854648419200
KS2462R C2462R
CL2462R
REFERENCE NO. SM830092
– 1 –
SM830092
Important
Please Read Before Starting
This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently.
For safe installation and trouble-free operation, you must :
Carefully read this instruction booklet before beginning. Follow each installation or repair step exactly as shown. Observe all local, state, and national electrical codes. Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or
CAUTION
unsafe practice which can result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites and maintenance conditions. If you require help for a special problem, contact our sales/service outlet or your certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to follow the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
……………………………………………………………………
ELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these instructions when wiring. Improper connections and inadequate ground­ing can cause accidental injury or death.
Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheat­ing at connection points and a possible fire hazard.
When Transporting
…………………………………………………………………… Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Installing
……………………………………………………………………
…In a Room
Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a solid, level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys-tems)
Install the outdoor unit on a raised platform that is higher than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
……………………………………………………………………
• Ventilate the room well, in the event that refrigerant gas leaks during the installation. Be careful not to allow contact of the refrigerant gas with a flame as this will cause the generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be either narrow or wide. Therefore, to avoid confusion the refrigerant tubing for your particular model is specified as either “narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
……………………………………………………………………
• Turn the power OFF at the main power box (mains) before opening the unit to check or repair electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site when installation is finished. Check that no metal scraps or bits of wiring have been left inside the unit.
CAUTION
• Ventilate any enclosed areas when installing or testing the refrigeration system. Contact of refrigerant gas with fire or heat can produce poisonous gas.
• Confirm after installation that no refrigerant gas is leaking. If the gas comes in contact with a burning stove, gas water heater, electric room heater or other heat source, it can cause the generation of poisonous gas.
– 2 –
SM830092
Table of Contents
1. OPERATING RANGE ....................................................................................... 4
2. SPECIFICATIONS............................................................................................ 5
(1) Unit Specifications ...................................................................................... 5
(2) Major Component Specifications ................................................................ 7
(A) Indoor Unit ............................................................................................ 7
(B) Outdoor Unit.......................................................................................... 8
(3) Other Component Specifications .............................................................. 10
(A) Indoor Unit .......................................................................................... 10
(B) Outdoor Unit........................................................................................ 12
3. DIMENSIONAL DATA..................................................................................... 13
(1) Indoor Unit ................................................................................................ 13
(2) Outdoor Unit.............................................................................................. 14
4. COOLING CAPACITY..................................................................................... 15
5. PERFORMANCE CHARTS ............................................................................ 17
(1) Operating Current ..................................................................................... 17
(2) High and Low Pressure............................................................................. 19
6. AIR THROW DISTANCE CHART................................................................... 21
7. REFRIGERANT FLOW DIAGRAM ................................................................. 22
8. INSTALLATION INSTRUCTIONS .................................................................. 23
9. ELECTRICAL DATA ....................................................................................... 29
10. ELECTRICAL WIRING DIAGRAMS ............................................................... 30
(1) Indoor Unit ................................................................................................ 30
(2) Outdoor Unit.............................................................................................. 31
11. PROCESSES AND FUNCTIONS.................................................................. 35
(1) Room Temperature Control ...................................................................... 35
(2) Dry Operation............................................................................................ 36
(3) Freeze Prevention..................................................................................... 37
(4) Outdoor Fan Speed Control......................................................................38
12. SERVICE PROCEDURES.............................................................................. 39
(1) Troubleshooting ........................................................................................ 39
(2) A Sensor is Defective................................................................................ 50
(3) Checking the Electrical Components ........................................................ 51
– 3 –
SM830092
1. OPERATING RANGE
KS2462R / C2462R
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Maximum 95 °F DB / 71 °F WB 115 °F DB
Minimum 67 °F DB / 57 °F WB 67 °F DB
KS2462R / CL2462R
Temperature Indoor Air Intake Temp. Outdoor Air Intake Temp.
Maximum 95 °F DB / 71 °F WB 115 °F DB
Minimum 67 °F DB / 57 °F WB 0 °F DB
– 4 –
SM830092
2. SPECIFICATIONS
1-1 Unit Specifications
MODEL No. Indoor Unit
Outdoor Unit C2462R
POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling
Capacity
Air circulation (Hi) Moisture removal (High) Pints / h 6.5
ELECTRICAL RATINGS
Voltage rating VAC Available voltage range 187 – 253 Running amperes* A 10.2 Max. running amperes** A 12.5 Power input W 2,240 Power factor % 95.5 S.E.E.R 13.0 Max. starting amperes A 61
FEATURES
Controls Microprocessor Timer ON/OFF 24-hours & Program Fan speed Indoor / Outdoor 3 and Automatic control / 2 (Auto) Air deflection Horizontal / Vertical – / Automatic Air filter Washable, easy access Remote controller (Accessory) RCS - 1PS4U - G Refrigerant control Capillary tube Refrigerant tubing connections Flare type Compressor Scroll Operation sound
REFRIGERANT TUBING
Limit of tubing length ft. (m) Limit of tubing length at shipment 23 ( 7 ) Limit of elevation difference between the two units Refrigerant tube Narrow tube 3 / 8 (9.52) outer diameter Wide tube 3 / 4 (19.05) Refrigerant amount at shipment lbs. (kg) R410A - 6.6 (3)
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm)
Package dimensions Height
Net weight lbs. (kg) Shipping weight Shipping volume
Cooling:
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75°F WB Full load conditions (**):Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115°F DB
Indoor - Hi/Me/Lo Outdoor - Hi
Width Depth
Width Depth 15-31/32 (406)
BTU / h
kW
Cu.ft. / min.
VAC
BTU / Wh
dB - A 48 / 42 / 38 dB - A 55
ft. (m) ft. (m)
in. (mm) in. (mm)
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
lbs. (kg)
cu. ft.(m )
3
27,000
7.912 559
230
13 (330) 44-7/8 (1,140) 8-31/32 (228) 12-25/32 (325) 48-15/32 (406)
40 (18) 44 (20)
5.7 (0.162)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
KS2462R
26,000
7.619 519
6.4
208
10.9
13.5
2,200
97.0
13.0 61
132 ( 40 )
50 ( 15 )
36-5/8 (930) 37 (940) 13-3/8 (340) 39-3/4 (1,010) 39-3/8 (1,000) 15-3/4 (400) 150 (68) 190 (86.5)
14.1 (0.40)
– 5 –
SM830092
2. SPECIFICATIONS
1-1 Unit Specifications
MODEL No. Indoor Unit
Outdoor Unit CL2462R
POWER SOURCE 230 - 208 V / 1 Phase / 60 Hz PERFORMANCE Cooling
Capacity
Air circulation (Hi) Moisture removal (High) Pints / h 6.5
ELECTRICAL RATINGS
Voltage rating VAC Available voltage range 187 – 253 Running amperes* A 10.2 Max. running amperes** A 12.5 Power input W 2,240 Power factor % 95.5 S.E.E.R 13.0 Max. starting amperes A 61
FEATURES
Controls Microprocessor Timer 1-hour OFF, ON/OFF 12-hours & Program Fan speed Indoor / Outdoor 3 and Automatic control / 3 (Auto) Air deflection Horizontal / Vertical – / Automatic Air filter Washable, easy access Remote controller (Accessory) RCS - 1PS4U - G Refrigerant control Capillary tube Refrigerant tubing connections Flare type Compressor Scroll Operation sound
REFRIGERANT TUBING
Limit of tubing length ft. (m) Limit of tubing length at shipment 23 ( 7 ) Limit of elevation difference between the two units Refrigerant tube Narrow tube 3 / 8 (9.52) outer diameter Wide tube 3 / 4 (19.05) Refrigerant amount at shipment lbs. (kg) R410A - 6.6 (3)
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height in. (mm)
Package dimensions Height
Net weight lbs. (kg) Shipping weight Shipping volume
Cooling:
Rating conditions (*) : Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 95 °F DB / 75°F WB Full load conditions (**):Indoor air temperature 80 °F DB / 67 °F WB, Outdoor air temperature 115°F DB
Indoor - Hi/Me/Lo Outdoor - Hi
Width Depth
Width Depth
BTU / h
kW
Cu.ft. / min.
VAC
BTU / Wh
dB - A 48 / 42 / 38 dB - A 55
ft. (m) ft. (m)
in. (mm) in. (mm)
in. (mm) in. (mm) in. (mm) in. (mm) in. (mm)
lbs. (kg)
cu. ft.(m )
3
27,000
7.912 559
230
13 (330) 44-7/8 (1,140) 8-31/32 (228) 12-25/32 (325) 48-15/32 (406) 15-31/32 (406) 40 (18) 44 (20)
5.7 (0.162)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
KS2462R
26,000
7.619 519
6.4
208
10.9
13.5
2,200
97.0
13.0 61
132 ( 40 )
50 ( 15 )
36-5/8 (930) 37 (940) 13-3/8 (340) 39-3/4 (1,010) 39-3/8 (1,000) 15-3/4 (400) 150 (68) 190 (86.5)
14.1 (0.40)
– 6 –
SM830092
2. SPECIFICATIONS
(2) Major Component Specifications
(A) Indoor Unit
MODEL No. KS2462R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Accessory) RCS - 1PS4U - G Controller P. C. B Ass'y CR - KS2462R
Control circuit fuse 250 V, 3 A
Fan Type Cross-flow Number ... Dia. and length in. (mm) 1 ... O.D. 4 (100), L33-3/8 (847) Fan motor
Model KFG4X - 31B6P-S Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m. (230 V, High) rpm 4 … 1,365 Nominal output W 30 Coil resistance BRW - WHT : 161.2 , ORG - YEL : 26.9 (Ambient temperature 68 °F) WHT - VLT : 11.6 , YEL - BLK : 22.8
VLT - ORG : 68.7 , BLK - PNK : 115.2
Safety device Internal
Operating temperature Open °F 266 ± 9
Close °F 181 ± 27
Run capacitor VAC, µF 440 V , 1.5 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube Rows … Fins per inch 2 … 19.5 Face area ft.
Flap Motor
Type Stepping motor Model ... Q’ty MP24GA2 ... 2 Step angle 5.625 deg / step Rating V DC 12 V Coil resistance (Ambient temperature 77 °F) 400 ± 7 %
2
(m2) 2.30 (0.214)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
– 7 –
SM830092
2. SPECIFICATIONS
(2) Major Component Specifications
(B) Outdoor Unit
MODEL No. C2462R Source 230 - 208 V / 1 phase / 60 Hz Compressor Scroll (Hermetic)
Model ZP23K3E Source 230 - 208 V / 1 phase / 60 Hz Nominal output W 2,400 Compressor oil cc 1,120 Coil resistance (Ambient temperature 77 °F) C - R : 2.28 , C - S : 1.01 Safety device Internal type
Overload relay models — Operating temperature Open °F 284 ± 9
Close °F
Operating ampere (at 77 °F) A
Run capacitor VAC, µF 400 V, 40 µF
Refrigerant amount charged at shipment lbs. (kg) R410A : 6.6 (3) High pressure switch ACB - 1UB24W
Set pressure OFF MPa 4.15
ON MPa 3.15 ± 0.3
Fan Propeller
Number...diameter in. (mm) 1 … 18-3/32 (460)
Fan speeds 2 (AUTO) Fan motor
Model KFC6T - 91D6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … rpm (230 V, High) rpm 6 … 879 Nominal output W 110 Coil resistance BRW – WHT : 67.14 , VLT – YEL : 11.42
(Ambient temperature 68 °F) Safety device
Operating temperature Open °F 248 ± 9
Close °F 171 ± 27
Run capacitor VAC, µF 440 V, 4 µF
Heat exchanger
Coil Aluminum plate fin / Copper tube Rows … Fins per inch 2 … 14.1 Face area ft.
2
(m2) 8.72 (0.81)
WHT – VLT : 64.85 , YEL – PNK : 10.60
DATA SUBJECT TO CHANGE WITHOUT NOTICE
156 189
+ 0 – 0.15
Internal
– 8 –
SM830092
2. SPECIFICATIONS
(2) Major Component Specifications
(B) Outdoor Unit
MODEL No. CL2462R Source 230 - 208 V / 1 phase / 60 Hz Controller P.C.B. Ass'y CR - CL2432 (Microprocessor)
Control circuit fuse 250 V, 3 A
Compressor Scroll (Hermetic)
Model ZP23K3E Source 230 - 208 V / 1 phase / 60 Hz Nominal output W 2,400 Compressor oil cc 1,120 Coil resistance (Ambient temperature 77 °F) C – R : 0.885 , C – S : 1.773
Safety device Internal type
Overload relay models — Operating temperature Open °F 284 ± 9
Close °F 156 189
Operating ampere (at 77 °F) A — Run capacitor VAC, µF 400 V, 40 µF Crank case heater V, W 230 V, 30 W
Refrigerant amount charged at shipment lbs. (kg) R410A : 6.6 (3) High pressure switch ACB-1UB24W
Set pressure OFF MPa 4.15
ON MPa 3.15 ± 0.3
Fan Propeller
Number...diameter in. (mm) 1 ... 18 - 3/32 (460)
Fan speeds 3 (AUTO) Fan motor
Model KFC6T - 91D6P Source 230 - 208 V / 1 phase / 60 Hz
No. of pole ..... rpm (230 V, High) 6 ... 879
Nominal output W 110 Coil resistance BRN – WHT : 67.14 , VLT – YEL : 11.42
(Ambient temperature 68 °F) WHT – VLT : 64.85 , YEL – PNK : 10.60 Safety device Internal
Operating temperature Open °F 248 ± 9
Close °F 171 ± 27
Run capacitor VAC, µF 440 V, 4 µF
Heat exchange
Coil Aluminum plate fin / Copper tube
Rows ..... Fins per inch 2 ... 14.1
2
Face area ft.
(m2) 8.72 (0.81)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
+ 0 – 0.15
– 9 –
SM830092
2. SPECIFICATIONS
(3) Other Component Specifications
(A) Indoor Unit
MODEL No. KS2462R Power Transformer ATR – T5
Rated Primary AC 230 V, 60 Hz
Secondary AC19 V, 0.5 A Capacity 9.5 VA
Coil resistance (Ambient temprature 77 °F) Secondary (BRN - BRN) : 3.9
Thermistor cut off temperature 277 °F
Thermistor (Coil sensor) DTN - TKS131B
Coil resistance k 32 °F : 15.0 ± 2 %
Thermistor (Room sensor) DTN - TKS128B
Coil resistance k 77 °F : 5.0 ± 3 %
Lamp Ass'y IND - K301AH Flap Motor MP24GA2
Primary (WHT - WHT) : 457.5
– 10 –
SM830092
2. SPECIFICATIONS
(3) Other Component Specifications
(A) Outdoor Unit
MODEL No. C2462R
Compressor Motor Magnetic Contactor FC - 1SUL
Coil rated AC 240 V, 60 Hz Coil resistance (at 68 °F) 587 ± 5 % Contact rated (Main) AC 240 V, 26 A Contact rated (Auxiliary) AC 240 V, 3 A
Power Relay HH62S
Coil rated AC 240 V, 60 Hz Coil resistance (at 68 °F) k 17.2 Contact rated AC 220 V, 5 A
Thermostat (Coil sensor) YTB - 4U305F
Operating Temperature °F 79 ± 3 OFF
75 ON
Contact rated 200 to 240 V, 1 A
+ 3 – 1
– 11 –
SM830092
2. SPECIFICATIONS
(3) Other Component Specifications
(B) Outdoor Unit
MODEL No. CL2462R Compressor Motor Magnetic Contactor FC - 1SUL
Coil rated AC 240 V, 60 Hz Coil resistance (at 77 °F) 587 ± 5 % Contact rated (Main) AC 240 V, 26 A Contact rated (Auxiliary) AC 240 V, 3 A
Power Relay HH62S
Coil rated AC 240 V, 60 Hz Coil resistance (at 77 °F) k 17.2 Contact rated AC 220 V, 5 A
Power Transformer ATR - I35B
Rated
Primary AC 220 V, 60 Hz
Secondary 14 V, 0.2 A Capacity 2.8 VAC Coil resistance (at 78 °F ) WHT – WHT : 482.5 , BRN – BRN : 3.95 Thermal cut off temperature °F 266
Thermistor (Outdoor Temp. sensor)
Coil resistance k 14 °F : 23.7 , 50 °F : 9.7
23 °F : 18.8 , 68 °F : 6.5 32 °F : 15.0 , 86 °F : 4.4 41 °F : 12.1 , 104 °F : 3.1
Solenoid control valve or coil
Solenoid control valve VPV - 202DQ50 Solenoid coil VPV - MOAQ517B1
PBC - 41E - S4
113 °F : 2.6
– 12 –
SM830092
3. DIMENSIONAL DATA
(1) Indoor Unit: KS2462R
44-7/8
13
1-7/8
6-27/32
Center of tubing hole (2 places)
Narrow tube 3/8"(ø9.52)
Drain hose O.D. 23/32"(ø18)
5-5/16
Wide tube 3/4"(ø19.05)
8-31/32
Remote control unit
6-7/32
1-7/8
2-13/32
Dimension : inch
25/32
2199_M_S
– 13 –
SM830092
3. DIMENSIONAL DATA
(2) Outdoor Unit: C2462R, CL2462R
13-3/8
36-5/8
6-23/32
1/2
25-31/32
37
1/21/2
1/2
4-3/8
25/323/4
15-15/16
14-31/32
18-1/16
16-7/8
5
4
Dimension : inch
Hole for anchor bolt (4-R1/4) Refrigerant tube joint (narrow tube) Flare connection 3/8 in (9.52 mm) Refrigerant tube joint (wide tube) Flare connection 3/4 in (19.05 mm) Refrigerant tubing inlet Power supply inlet
5
4
– 14 –
SM830092
4. COOLING CAPACITY
Indoor Unit: KS2462R Outdoor Unit: C2462R
1
• 230V / 1 phase / 60Hz
RATING CAPACITY : 27,000 BTU / h AIR FLOW RATE : 559 Cu.ft / min EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
TC
CI 1.66
72(22.2) SHC 18,460
59
(15.0)
63
(17.2)
67
(19.4)
71
(21.7)
75
(23.9)
76(24.4) SHC 20,150 80(26.7) SHC 21,930 84(28.9) SHC 23,620 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
76(24.4) 80(26.7) 84(28.9) 88(31.1)
SHC 25,320
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC
(23.9) (29.4) (35.0) (40.6) (46.1)
27,350
28,380
1.67 16,130 17,820
19,590 21,290 22,990 29,460
1.69 13,770 15,470
17,240 18,940 20,630 31,020
1.7 11,500 13,190
14,960 16,660 18,360 31,640
1.74 10,560 12,330
14,020
15,720
26,030
1.81 17,640 19,340 21,110 22,810 24,500 27,110
1.83 15,400 17,100 18,870 20,570 22,260 28,300
1.85 13,170 14,870 16,640 18,330 20,030 29,940
1.87 10,990 12,680 14,450 16,150 17,850 30,620
1.9 10,120 11,900 13,590 15,290
24,520
1.97 16,740 18,430 20,210 21,900 23,600 25,760
2 14,660 16,360 18,130 19,820 21,520
# 27,000
2.02 12,510 14,210 15,980 17,680 19,370 28,780
2.05 10,450 12,140 13,920 15,610 17,310 29,540
2.08
9,680 11,450 13,150 14,840
22,820
2.23 15,760 17,450
19,220 20,920 22,620 24,220
2.26 13,840 15,530
17,310 19,000 20,700 25,570
2.29 11,810 13,510
15,280 16,970 18,670 27,510
2.32
9,870
11,570
13,340 15,040 16,730 28,300
2.35
9,170 10,950 12,640 14,340
20,930
2.49 14,710 16,400 18,170 19,870 20,930 22,550
2.52 12,970 14,670 16,440 18,140 19,830 24,000
2.55 11,060 12,760 14,530 16,230 17,920 26,110
2.59
9,260 10,950 12,730 14,420 16,120 26,970
2.63
8,650 10,420 12,110 13,810
TC : Total Cooling Capacity (BTU / h) SHC : Sensible Heat Capacity (BTU / h) CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB : Indoor Unit Entering Air Temp. 80 °F DB / 67 °F WB
SM830092
– 15 –
4. COOLING CAPACITY
Indoor Unit: KS2462R Outdoor Unit: C2462R
1
• 208V / 1 phase / 60Hz
RATING CAPACITY : 26,000 BTU / h AIR FLOW RATE : 519 Cu.ft / min EVAPORATOR CONDENSER
ENT. TEMP. °F (°C) AMBIENT TEMP. °F (°C)
WB DB 75 85 95 105 115
TC
CI 1.64
72(22.2) SHC 17,760
59
(15.0)
63
(17.2)
67
(19.4)
71
(21.7)
75
(23.9)
76(24.4) SHC 19,360 80(26.7) SHC 21,030 84(28.9) SHC 22,630 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
72(22.2) 76(24.4) 80(26.7) 84(28.9) 88(31.1)
76(24.4) 80(26.7) 84(28.9) 88(31.1)
SHC 24,230
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC SHC
TC
CI SHC SHC SHC SHC
(23.9) (29.4) (35.0) (40.6) (46.1)
26,340
27,330
1.66 15,540 17,140 18,810 20,410 22,010 28,370
1.67 13,310 14,910 16,580 18,180 19,770 29,870
1.69 11,150 12,750 14,420 16,020 17,620 30,470
1.72 10,240 11,910 13,510 15,110
25,060
1.79 16,960 18,560 20,230 21,830 23,430 26,100
1.82 14,840 16,430 18,110 19,700 21,300 27,250
1.83 12,720 14,320 15,990 17,590 19,190 28,830
1.85 10,650 12,250 13,920 15,520 17,120 29,480
1.88
9,810 11,480 13,080 14,680
23,610
1.95 16,080 17,680 19,350 20,950 22,550 24,800
1.98 14,110 15,710 17,380 18,980 20,580
# 26,000
2 12,080 13,680 15,350 16,950 18,550 27,720
2.03 10,130 11,730 13,400 15,000 16,600 28,440
2.06
9,380 11,050 12,650 14,250
21,970
2.23 15,120 16,720 18,390 19,990 21,590 23,320
2.27 13,310 14,910 16,580 18,180 19,780 24,620
2.29 11,390 12,990 14,660 16,260 17,860 26,490
2.32
9,570 11,170 12,840 14,440 16,040 27,250
2.36
8,890 10,560 12,160 13,760
20,150
2.52 14,100 15,700 17,370 18,970 20,150 21,710
2.55 12,470 14,070 15,740 17,340 18,940 23,110
2.58 10,670 12,260 13,940 15,540 17,130 25,140
2.62
8,970 10,570 12,240 13,840 15,440 25,970
2.66
8,380 10,050 11,650 13,250
TC : Total Cooling Capacity (BTU / h) SHC : Sensible Heat Capacity (BTU / h) CI : Compressor Input (kW)
Rating conditions are
: Outdoor Ambient Temp. 95 °F DB : Indoor Unit Entering Air Temp. 80 °F DB / 67 °F WB
SM830092
– 16 –
5. PERFORMANCE CHARTS
(1) Operating Current
Indoor Unit: KS2462R Outdoor Unit: C2462R
1
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V
208V
Outdoor fan speed
Low
14 13 12 11 10
9 8
Operating current (A)
7
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
Outdoor fan speed
Low
14 13 12 11 10
9 8
Operating current (A)
7
High
High
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1061_X_S
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
59 68 77 86 95 104
(15) (20) (25) (30) (35) (40)
Outdoor ambient temp. °F (°C)
– 17 –
1062_X_S
SM830092
5. PERFORMANCE CHARTS
(1) Operating Current
Indoor Unit: KS2462R Outdoor Unit: CL2462R
2
Operating current characteristics versus outdoor ambient temperature and indoor temperature. (Indoor relative humidity: 50%, Indoor fan speed: High)
230V
Operating current (A)
208V
Operating current (A)
Outdoor fan speed
Low High
14 13 12 11 10
9 8
7
23 32 41 50
(–5) (0) (5) (10) (35) (40)
14 13 12 11 10
9 8 7
59 68 77 86 95 104
(15) (20) (25) (30)
Outdoor ambient temp. °F (°C)
Outdoor fan speed
Low High
Med
Med
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
1063_X_S
Indoor temp. °F (°C)
85 (30) 80 (27) 75 (24) 70 (21)
23 32 41 50
(–5) (0) (5) (10) (35) (40)
59 68 77 86 95 104
(15) (20) (25) (30)
Outdoor ambient temp. °F (°C)
– 18 –
1064_X_S
SM830092