1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Optional Copper Tubing Kit
1-4. Type of Copper Tube and Insulation Material
1-5. Additional Materials Required for Installation
2.INSTALLATION SITE SELECTION ................... 4
2-1. Indoor Unit
2-2. Outdoor Unit
2-3. Baffle Plate for the Outdoor Unit
3.HOW TO INSTALL THE INDOOR UNIT ........... 11
3-1. Preparation for Suspending
3-2. Suspending the Indoor Unit
3-3. Placing the Unit Inside the Ceiling
3-4. Installing the Drain Piping
3-5. Checking the Drainage
3-6. How to Install the Ceiling Panel
3-7. Wiring Instructions
3-8. Recommended Wire Length and Diameter
3-9. Wiring Instructions for Inter-unit Connections
5-1. Use of the Flaring Method
5-2. Flaring Procedure with a Flare Tool
5-3. Caution before Connecting Tubes Tightly
5-4. Connecting Tubing between Indoor and
Outdoor Units
5-5. Insulation of Refrigerant Tubing
5-6. Taping the Tubes
5-7. Finishing the Installation
SANYO Commercial SolutionsIn Canada
A Division of SANYO North America CorporationSANYO Canada Inc.
1300 Michael Drive, Suite A1-300 Applewood Crescent, Concord
Wood Dale, IL 60191, U.S.A.Ontario, L4K 5C7, Canada
COOL/ DRY Model
Model Combinations
Combine indoor and outdoor units only as listed
below.
Indoor UnitOutdoor Unit
XS1271C1271
CL1271
Power Source:
60 Hz, single-phase, 115 V
XS1872C1872
CL1872
Power Source:
60 Hz, single-phase, 230/208 V
Ceiling Panel
PNR-XS1872
Be sure to read the yellow instruction sheet
attached to the outdoor unit for models using the
new refrigerant R410A.
7.REMOTE CONTROL UNIT INSTALLATION
POSITION ......................................................... 26
The illustrations are based on the typical appearance of
a standard model. Consequently, the shape may differ
from that of the air conditioner that you are installing.
IMPORTANT!
WARNING
WARNING
CAUTION
CAUTION
Please Read Before Starting
This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
For safe installation and trouble-free operation, you
must:
G
Carefully read this instruction booklet before beginning.
G
Follow each installation or repair step exactly as shown.
G
Observe all local, state, and national electrical codes.
G
Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard
or unsafe practice which can
result in severe personal injury
or death.
This symbol refers to a hazard
or unsafe practice which can
result in personal injury or product or property damage.
If Necessary, Get Help
These instructions are all you need for most installation
sites and maintenance conditions. If you require help for a
special problem, contact our sales/service outlet or your
certified dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper installation or maintenance service, including failure to
follow the instructions in this document.
SPECIAL PRECAUTIONS
When Installing…
…In a Ceiling or Wall
Make sure the ceiling/wall is strong enough to hold the
unit’s weight. It may be necessary to construct a strong
wood or metal frame to provide added support.
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents
water damage and abnormal vibration.
…In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
• Check carefully for leaks before starting the test run.
When Servicing
• Do not supply power to the unit until all wiring and tubing
• Highly dangerous electrical voltages are used in this
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause over-
When Transporting
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and bend your knees when
lifting to reduce strain on your back. Sharp edges or thin aluminum fins on the air conditioner can cut your fingers.
When Wiring
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
are completed or reconnected and checked.
system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and
inadequate grounding can cause accidental injury or
death.
heating at connection points and a possible fire hazard.
• Turn the power OFF at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
• Keep your fingers and clothing away from any moving
parts.
• Clean up the site after you finish, remembering to check
that no metal scraps or bits of wiring have been left inside
the unit being serviced.
Others
• Ventilate any enclosed areas when installing or testing
the refrigeration system. Escaped refrigerant gas, on
contact with fire or heat, can produce dangerously
toxic gas.
• Confirm upon completing installation that no refrigerant
gas is leaking. If escaped gas comes in contact with a
stove, gas water heater, electric room heater or other heat
source, it can produce dangerously toxic gas.
2
Printed on
container box
For unit & PVC
tube connection
For drain hose
connection
RemarksQ’ty
For full-scale
installation
diagram
1
2
4
1
4
4
4
2
1
For temporarily
suspending indoor
unit from ceiling
Flare
insulation
For wide /
narrow tube
connection
For wide /
narrow tube /
flare nut connection
For flare / drain
insulating
connection
For drain tube
connection
Insulation tape
Vinyl tie
Drain hose
insulation
Washer
AAA alkaline
battery
Remote
control unit
Remote control
unit holder
PartsPartsFigureRemarksQ’tyFigure
Drain hose
Full-scale
installation
diagram
5-1/2"(L140)
Hose band
Truss head screw
Truss head screw
Hex wrench
Special screw
Cushion rubber
Tapping screw
8
2
set
2
8
1
1
1
2
1/8"(T3)
3/16"(T5)
13/32"(T10)
3/32"(T2)
Truss-head Phillips
5/32 5/8"
(4 16mm)
3/16 13/32"
(5 10mm)
5/32 15/32"
(4 12mm)
3/16 1-9/16"
(5 40mm)
Packed in the
outdoor unit
Packed in the
ceiling panel
Use M10 or 3/8" for suspension bolts.
Suspension bolts and nuts (locally purchased)
1. General
CAUTION
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning.
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Unit
Table 1
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the narrow and wide
tubing, fittings and insulation. Consult your nearest sales outlet or air conditioning workshop.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from a local source, you will need:
1.Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2.
2.Foamed polyethylene insulation for the specified copper tubes as required to precise length of tubing. Wall thickness
3.Use insulated copper wire for field wiring. Wire size varies with the total length of wiring. Refer to 3-7. Wiring
Table 2
Cut each tube to the appropriate lengths 1' to 1'4" (30 cm to 40 cm) to dampen vibration between units.
of the insulation should be not less than 5/16" (8 mm).
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.
1-5. Additional Materials Required for Installation
3.3 ft.
(1m)
(1m)
(1m)
3.3 ft.
(1m)
3.3 ft.
3.3 ft.
3.3 ft.
(1m)
Tubing length (L)
Elevation difference (H)
Outdoor unit
Indoor unit
WARNING
CAUTION
1.Refrigeration (armored) tape
2.Insulated staples or clamps for connecting wire
(See local codes)
3.Putty
4.Refrigeration lubricant
5.Clamps or saddles to secure refrigerant tubing
2. Installation Site Selection
2-1. Indoor Unit
To prevent abnormal heat generation and the possibility of fire, do
not place obstacles, enclosures
and grilles in front of or surrounding the air conditioner in a way
that may block air flow.
AVOID:
G direct sunlight.
G nearby heat sources that may affect performance of the unit.
G areas where leakage of flammable gas may be expected.
G places where large amounts of oil mist exist.
DO:
G select an appropriate position from which every corner of
the room can be uniformly cooled.
G select a location that will hold the weight of the unit.
G select a location where tubing and drain hose have the
shortest run to the outside.
G allow room for operation and maintenance as well as unre-
stricted air flow around the unit. (Fig. 1)
G install the unit within the maximum elevation difference (H)
above or below the outdoor unit and within a total tubing length
(L) from the outdoor unit as detailed in Table 3 and Fig. 2.
G install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for television,
radio, telephone, security system, or intercom. Electrical noise
from any of these sources may affect operation.
Fig. 1
Fig. 2
Air delivery will be degraded if the distance
from the floor to the ceiling is greater than
10 ft. (3 m).
Table 3
Max. Allowable Tubing Limit of TubingLimit of ElevationRequired Amount of
ModelLength at ShipmentLength (L)Difference (H)Additional Refrigerant
XS12712565230.16
XS18722598500.27
* If total tubing length becomes 25 to 65 ft. (Max.) or 25 to 98 ft. (Max.), charge additional refrigerant (R410A) by 0.16 or 0.27 oz./ft.
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.
(ft.)(ft.)(ft.)(oz./ft.)*
4
2-2. Outdoor Unit
Outdoor unit
Hot air
Heat source
Exhaust fan
NO
Min.
7' (2 m)
Min.
7' (2 m)
Ground
Obstacle
Obstacle above
Air discharge
Min. 4" (10 cm)
Air intake
AVOID:
G heat sources, exhaust fans, etc. (Fig. 3)
G damp, humid or uneven locations.
DO:
G choose a place as cool as possible.
G choose a place that is well ventilated.
G install in a location where at least two sides are unob-
structed, so that the flow of air at the intake port or
exhaust port is not blocked, and so that sufficient
space is ensured for maintenance to be carried out
without trouble. In general the top also must be unobstructed. (Figs. 4a and 4b)
G provide a solid base (level concrete pad, concrete
block, 4" × 1'4" (10 × 40 cm) beams or equal), a minimum of 4" (10 cm) above ground level to reduce
humidity and protect the unit against possible water
damage and decreased service life. (Fig. 5a)
G install cushion rubber under unit’s feet to reduce
vibration and noise. (Fig. 5b)
G use lug bolts or equal to bolt down unit, reducing
vibration and noise.
G install in a location where no antenna of a television
or radio exists within 10' (3 m).
(C1271, CL1271)
Air intakeMin. 2" (5 cm)
Min.
2" (5 cm)
Air discharge
(C1872, CL1872)
Fig. 3
Valve
side
Min. 10"
(25 cm)
Min.
8" (20 cm)
Fig. 4a
Obstacle above
Min.
7' (2 m)
Air discharge
Ground
Min. 2" (5 cm)
Air intake
Min.
7' (2 m)
Obstacle
Air intake
Concrete
or equal
Abou
t 1'4" (40 cm)
Anchor bolts
(4 pcs.)
Min. 4" (10 cm)
About 4" (10 cm)
Air intakeMin. 4" (10 cm)
Min.
2" (5 cm)
Air discharge
Valve
side
Min. 10"
(25 cm)
Min.
1'4" (40 cm)
Fig. 4b
Fig. 5aFig. 5b
Cushion rubber
5
2-3. Baffle Plate for the Outdoor Unit
(CLxx models only)
Air intake baffle
NOTE
It is recommended to use baffle plates for models
CL1271 and CL1872. The baffle plates are not normally
required for the other models.
When the outdoor unit is installed in a position exposed
to strong wind (such as seasonal winds with low air temperature in winter), baffle plates must be installed on the
outdoor unit. (Fig. 5c)
This unit is designed so that the fan of the outdoor unit
runs at low speed when the air conditioner is operated at
low outdoor air temperatures. When the outdoor unit is
exposed to strong wind, the system pressure drops
because of the freeze protector.
Install a pair of windbaffle plates at the front and back of
the outdoor unit if it will be subject to strong wind during
the winter. (Figs. 5c to 5k)
2. Remove the panel side L, and drill 2 holes of ø1/4 inch
(6.5 mm) at the prescribed position.
3. Install the windbaffle on the unit using field supply bolts
and nuts.
4. Recommended bolts to be used are 15/64" (M6 ISO
standard), and the recommended length of the bolts is
between 19/32 – 25/32 inch (15 – 20 mm).
5. Use washers and spring washers to tightly fasten the
windbaffle to the unit.
(2) Right side
1. Remove the front panel from the unit.
2. Use 2 preholes on the panel side R to install the baffle
plate.
3. Remove the panel side R from the unit by removing the
screws. These screws are used in step 4 below.
4. Put (sandwich) the windbaffle between the unit and the
panel side R, then install the windbaffle on the unit using
the above screws. Be careful not to damage the screw
holes.
2. Air Discharge Baffle
1. Remove the panels front, side L and R from the unit
and drill 4 holes of ø1/4 inch (6.5 mm) at the
prescribed positions.
2. Install the windbaffle on the unit using field supply
bolts and nuts.
3. Recommended bolts to be used are 15/64" (M6 ISO
standard), and the recommended length of the bolts
is between 13/32 – 19/32 inch (10 – 15 mm).
4. Use washers and spring washers to tightly fasten the
windbaffle to the unit.
Panel side R
Panel front
Panel side L
Fig. 5h
NOTE
G In order to prevent contact of the bolts and heat exchanger and other parts inside the unit, install the windbaffle using
Fig. 5i
bolts from inside the unit and fasten the bolts with nuts from outside the unit.
G When the windbaffle is installed on the unit, the unit has higher wind resistance. In order to prevent the unit from
falling over, anchor the legs of the unit using anchor bolts (or similar method).
9
Panel top
Panel front
Panel side R
Panel side L
Panel side R
Panel top
Panel front
Panel side L
I CL1872
1. Air Intake Baffle
(1) Left side
1. Remove the top panel from the unit.
2. Remove the panel side L, and drill 3 holes of ø1/4 inch
(6.5 mm) at the prescribed positions.
3. Install the windbaffle on the unit using field supply bolts
and nuts.
4. Recommended bolts to be used are 15/64" (M6 ISO
standard), and the recommended length of the bolts is
between 19/32 – 25/32 inch (15 – 20 mm).
5. Use washers and spring washers to tightly fasten the
windbaffle to the unit.
(2) Right side
1. Remove the top panel from the unit.
2. Use 2 preholes on the panel side R to install the baffle plate.
3. Remove the panel side R from the unit by removing the
screws. These screws are used in step 4 below.
4. Put (sandwich) the windbaffle between the unit and the
panel side R, then install the windbaffle on the unit using the
above screws. Be careful not to damage the screw holes.
2. Air Discharge Baffle
1. Remove the panels front, top, side L and R from the
unit and drill 4 holes of ø1/4 inch (6.5 mm) at the
prescribed positions.
2. Install the windbaffle on the unit using field supply
bolts and nuts.
3. Recommended bolts to be used are 15/64" (M6 ISO
standard), and the recommended length of the bolts
is between 13/32 – 19/32 inch (10 – 15 mm).
4. Use washers and spring washers to tightly fasten the
windbaffle to the unit.
G In order to prevent contact of the bolts and heat exchanger and other parts inside the unit, install the windbaffle using
G When the windbaffle is installed on the unit, the unit has higher wind resistance. In order to prevent the unit from
(4) Precautions for installation
1. Be sure not to damage painted surfaces.
2. Finish the edges of the windbaffle to avoid cuts or injury.
3. Drilling of holes must be carefully done so that no damage is caused to external or internal parts of the unit.
Fig. 5j
NOTE
bolts from inside the unit and fasten the bolts with nuts from outside the unit.
falling over, anchor the legs of the unit using anchor bolts (or similar method).
Particular care must be taken that drill chips do not drop into the unit.
10
Fig. 5k
Hole-in-anchor
ConcreteInsert
Suspension bolt (M10 or 3/8")
Hole-in-plug
(locally purchased)
1/2" — 23/32" (13~18
mm
)
Over 19/32" (15
mm
)
Supplied screw
Full-scale installation diagram
(printed on top of container box)
3. How to Install the Indoor Unit
Nuts and washers
(used for upper and lower)
Double nut
Notch
Suspension lug
Suspension bolt
1/2" — 23/32"
(13~18
mm
)
3-1. Preparation for Suspending
This unit uses a drain pump. Use a carpenter’s level to
check that the unit is level.
3-2. Suspending the Indoor Unit
(1) Fix the suspension bolts securely in the ceiling using
the method shown in the diagrams, by attaching
them to the ceiling support structure, or by any other
method that ensures that the unit will be securely
and safely suspended. (Fig. 6-1)
(2) Follow the diagram to make the holes in the ceiling.
Fig. 6-1
23-5/8"(600mm)
Ceiling opening dimensions
21-1/32"(534
Suspension bolt pitch
mm
)
(3) Determine the pitch of the suspension bolts using
the supplied full-scale installation diagram. The diagram shows the relationship between the positions
of the suspension fitting, unit, and panel. (Fig. 6-2)
3-3. Placing the Unit Inside the Ceiling
(1) Be sure to remove the fan protection (4pcs) for
transportation before hanging up the indoor unit.
(2) When placing the unit inside the ceiling, determine
the pitch of the suspension bolts using the supplied
full-scale installation diagram. (Fig. 6-3)
Tubing and wiring must be laid inside the ceiling
when suspending the unit. If the ceiling is already
constructed, lay the tubing and wiring into position
for connection to the unit before placing the unit
inside the ceiling.
(3) The length of suspension bolts must be appropriate
for a distance between the bottom of the bolt and the
bottom of the unit of more than 19/32" (15 mm) as
shown in the diagram. (Fig. 6-3)
Drain tube
connection port
(outer dia 1-1/32"( 26mm))
)
mm
)
mm
(215
8-15/32"
11-5/32"(283
)
mm
1-3/16"
(30
(4) Thread the 3 hexagonal nuts (locally purchased) and
2 supplied washers onto each of the 4 suspension
bolts as shown in the diagram. Use 1 nut and 1
washer for the upper side, and 2 nuts and 1 washer
for the lower side, so that the unit will not fall off the
suspension lugs. (Fig. 6-4)
(5) Adjust so that the distance between the unit and the
ceiling bottom is 1/2" (13 mm) to 23/32" (18 mm).
Tighten the nuts on the upper side and lower side of
the suspension lug. (Fig. 6-4)
Fig. 6-3
Fig. 6-4
11
Drain port
Twist tie
(4 vinyl ties, supplied)
Hard PVC pipe
Position to
Drain hose
(supplied)
Hose band
(2 bands, supplied)
3/16"
(5mm)
3/16"
(5mm)
15/16"
(25mm)
15/16"
(25mm)
5-1/2"(140
mm
)
Drain hose
(locally purchased)
bands
(supplied)
O.D. 1-1/32" (26mm))
fasten hose
insulation
(equivalent to
Unit
Air bleeder prohibited
Support
bracket
Uphill slope
3-4. Installing the Drain Piping
1 ft.(300mm) or less
0 - 45
2.78 ft.(850
mm
) or less
* Length of supplied drain hose = 5-1/2"(140
mm
)
CAUTION
CAUTION
CAUTION
(1) Prepare standard hard PVC pipe (locally purchased O.D.
1-1/32" (26 mm)) for the drain and use the supplied hose
band to prevent water leaks. (Fig. 6-5)
(2) To install the drain hose, first place 1 of the 2 hose bands
over the unit drain port and the other hose band over the
hard PVC pipe (not supplied). Then connect both ends of
the supplied drain hose. (Fig. 6-5)
(3) On the unit drain side, grasp the hose band with pliers
and insert the drain hose all the way to the base.
G If other commercially available hose bands are used, the
drain hose may become pinched or wrinkled and there is
danger of water leakage. Therefore be sure to use the
supplied hose bands. When sliding the hose bands, be
careful to avoid scratching the drain hose.
G Do not use adhesive when connecting the supplied drain
hose to the drain port (either on the main unit or the PVC
pipe).
Reasons:a) It may cause water to leak from the connec-
tion. Since the connection is slippery just
after the adhesive has been applied, the
pipe easily slips off.
b) The pipe cannot be removed when mainte-
nance is needed.
Fig. 6-5
G Attach so that the hose band
fastener is on the side of the
drain port.
G Attach the hose bands so that
each is approximately 3/16"
(5 mm) to 15/16" (25 mm) from
the end of the supplied drain
hose.
(4) Wrap the hose with the supplied drain hose insulation
and use the 4 twist ties so that the hose is insulated with
no gaps.
G Do not bend the supplied drain hose 90° or more. The
hose may slip off.
NOTE
Make sure the drain pipe has a downward gradient (1/100 or
more) and that there are no water traps.
G In cases where it is necessary to raise the height of the
drain piping, the drain piping can be raised to a maximum
height of 2.78 ft. (850 mm) above the bottom surface of
the ceiling. Under no conditions attempt to raise it higher
than 2.78 ft. (850 mm) above the bottom surface of the
ceiling. Doing so will result in water leakage. (Fig. 6-7)
G Do not use natural drainage.
G Do not install the pipe with an upward gradient from the
connection port. This will cause the drain water to flow
backward and leak when the unit is not operating.
G Do not apply force to the piping on the unit side when
(Fig. 6-8)
connecting the drain pipe. The pipe should not be
allowed to hang unsupported from its connection to the
unit. Fasten the pipe to a wall, frame, or other support as
close to the unit as possible. (Fig. 6-9)
G Provide insulation for any pipes that are run indoors.
Fig. 6-6
G Do not install an air bleeder as
this may cause water to spray
from the drain pipe outlet.
(Fig. 6-6)
Fig. 6-7
Fig. 6-8
Fig. 6-9
12
A
must be within the range of 1/2"(13mm) to 23/32"(18mm). (Fig. 6-11)
If not within this range, malfunction or other trouble may occur.
Ceiling opening
dimension
Ceiling side
A
Indoor unit
3-5. Checking the Drainage
CAUTION
CAUTION
2
1
Water drain
Control box
Drain pan outlet
Water
Plastic container
for water intake
Over 4"
(100
mm
)
(Approx. 16 ounces (500m ) )
Flap
NO
Latch
Air-intake grille
Ceiling panel
Air-intake grille hinge
1
1
FS
FLAP
Control box
RCIND
After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.
G Be sure to do the wiring between the units before installing the
ceiling panel. (Refer to 3-9. Wiring Instructions for Inter-unit
Connections)
(1) Turn on the power. (Here, “power” refers to the power supply
from the outdoor unit.)
(2) Slowly pour approx. 16 ounces (500 ml) of water into the drain
pan to check drainage. (Fig. 6-10a)
(3) Remove the 2 screws from the control box cover, then open
the cover. Be careful not to drop the cover at this time.
(4) Disconnect the FS 3P connector (red) on the control PCB and
operate the drain pump. (Fig. 6-10b) Check the water flow
through the transparent drain pipe and see if there is any
leakage.
(5) When the check of drainage is complete, reconnect the FS
3P connector and remount the control cover.
The drain pump will continue to
operate for a minimum of 6 minutes after the FS 3P connector is
reconnected.
Fig. 6-10a
Fig. 6-10b
3-6. How to Install the Ceiling Panel
Checking the unit position
(1) Check that the ceiling hole is 23-5/8" (600 mm) × 23-5/8"
(600 mm) (Fig. 6-11)
(2) Confirm that the position of the indoor unit and the ceiling
as shown in the diagram. If the positions of the ceiling surface and unit do not match, air leakage, water leakage, flap
operation failure, or other problems may occur. (Fig. 6-11)
G Never place the panel face-down. Neither hang it ver-
tically nor place it on top of a projecting object. Placing it face-down will damage the surface.
G Do not touch the flap or apply force to it. (This may
cause flap malfunction.) (Fig. 6-12)
3-6-1. Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the ceiling
panel.
a) Press on and slide the two latches of the air-intake grille
with your thumb in the direction shown by the arrow
to open the grille. (Figs. 6-13 and 6-14)
b) With the air-intake grille opened, remove the grille hinge
from the ceiling panel by sliding it in the direction shown
by the arrow . (Fig. 6-15)
Fig. 6-12
Fig. 6-14
Fig. 6-11
Fig. 6-13
2
Fig. 6-15
13
(2) Removing the corner cover and
CAUTION
latch
Temporary latches
Temporary
DRAIN mark
Ceiling panel
Special screws
Refrigerant tubing joint
Drainage check
REF.PIPE mark
Panel installation hole
(4 locations)
Indoor unit
Ceiling panel
Ceiling surface
Do not allo
w
gaps
indicator cover
a) While lightly pressing the cen-
ter of the corner cover, pull up
the tab for the screw hole.
Use the same procedure to
remove the indicator cover.
(Fig. 6-16)
Corner cover
1
Press
2
Pull up
Indicator cover
3-6-2. Installing the Ceiling Panel
(1) Hang the temporary latches on the inside of the ceil-
ing panel to the receptacle on the unit to temporarily
attach the ceiling panel in place. (Fig. 6-17)
G The ceiling panel must be installed in the correct
direction relative to the unit. Align the REF. PIPE and
DRAIN marks on the ceiling panel corner with the
correct positions on the unit.
(2) Align the panel installation holes and the unit screw
holes. (Fig. 6-18)
(3) Tighten the supplied special screws at the 4 panel
installation locations so that the panel is attached
tightly to the unit.
G Check that the wiring connectors are not caught
between the unit and the ceiling panel.
(4) Check that the panel is attached tightly to the ceiling.
(Fig. 6-19)
G At this time, make sure that there are no gaps
between the unit and the ceiling panel, or between
the ceiling panel and the ceiling surface.
G If there is a gap between the panel and the ceiling,
leave the ceiling panel attached and make fine
adjustments to the installation height of the unit to
eliminate the gap with the ceiling.
Fig. 6-16
Fig. 6-17
Fig. 6-18
If the screws are not sufficiently tightened,
trouble such as that shown in the figure
below may occur. Be sure to tighten
the screwssecurely.
Air leakage
Air leakage from
ceilingsurface
Staining
Condensation, water leakage
If a gap remains between the ceilingsurface and the ceiling panel even
after the screws are tightened,
adjust the height of the unit again.
Adjust so that there are no gaps.
Fig. 6-20
14
Fig. 6-19
The height of the unit can be adjusted from the ceiling
panel corner hole, with the ceiling panel attached, to
an extent that doesnot affect the unit levelness,
the drain hose, or other elements.
fit into the holes in the ceiling panel.
Place the corner cover so that the 3 tabs
Then fasten it in place with the supplied screws.
Pin
Hole for ceiling
panel hook
the grille from
dropping
Hook that prevents
Can be installed rotated 90
* The grille can be installed
with these hinges facing
in any of 4 directions.
3-6-3. Wiring the Ceiling Panel and the Indicator
FLAP
RCIND
Indicator
Indicator
7P IND and 4P RC wiring connector
7P IND and 4P RC
Ceiling panel
5P FLAP wiring connector
Clamps
Control box
Indoor unit
* Pass the wiring connectors through the clamps to fasten them in place,
as shown in the figure.
wiring connector
7P
4P
5P
5P FLAP
wiring connector
Control box
As to how to attach the indicator cover, refer to Fig.6-23.
Drain pipe side
Refrigerant tube side
Indicator cover
Power box
(1) Remove the 2 screws from the control box cover, then open
the cover. Be careful that the cover does not fall.
(2) Connect the 5P FLAP wiring connector from the ceiling
panel to the connector on the control PCB in the control box.
(Fig. 6-21)
(3) Connect the 7P IND and 4P RC wiring connector from the
indicator to the connectors on the control PCB in the control
box. (Fig. 6-21)
(4) Be sure to use the clamps to fasten the connector wires in
place. (Fig. 6-21)
(5) Tighten the 2 cover screws to
close the cover.
G Check that the wiring
connectors are not caught
between the electrical
component box and the cover.
G If the indicator connector is
not securely connected,
the remote controller
signal will not be
received.
G If the connectors are not
connected, the auto flap will not
operate. Be sure
to connect them securely.
Fig. 6-22
3-6-4. How to Attach the Corner Cover and Air-Intake Grille
A. Attaching the corner cover
(1) Check that the safety strap from the corner cover is fas-
(2) Use the supplied screws to attach the corner cover to the
B. Attaching the air-intake grille
G To install the air-intake grille, follow the steps for 3-6-1.
G When attaching the air-intake
G Be sure to attach the safety
tened to the ceiling panel pin, as shown in the figure.
(Fig. 6-23)
ceiling panel.
Before Installing the Ceiling Panel in the reverse order.
By rotating the air-intake grille, it is possible to attach the
grille onto the ceiling panel
from any of 4 directions.
(Fig. 6-25)
grille, be careful that the flap
and the indicator wiring do
not become caught.
cord that prevents the air-intake
grille from dropping off to the
ceiling panel unit as shown
in Fig. 6-24.
Fig. 6-24Fig. 6-25
Fig. 6-21
15
Fig. 6-23
3-6-5. Checking After Installation
G Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling sur-
face. Gaps may cause water leakage and condensation.
G Check that the wiring is securely connected.
If it is not securely connected, the auto flap will not operate. In addition, water leakage and condensation may occur.
3-6-6. When Removing the Ceiling Panel for Servicing
When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the flap and the indicator wiring connectors inside the control box, and then remove the 4 mounting screws.
3-6-7. Adjusting the Auto Flap
The air-direction flap on the ceiling panel outlet can be adjusted as follows.
G Adjust the flap to the desired angle using the remote controller. The flap also has an automatic air-sweeping mecha-
nism.
NOTE
G Never attempt to move the flap by hand.
G Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or
heating seems inadequate, try changing the direction of the air flow.
3-7. Wiring Instructions
General precautions on wiring
(1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate,
then carry out the wiring closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for each unit, with a power supply
disconnect and circuit breaker for overcurrent protection provided in the exclusive line.
(3) To prevent possible hazards due to insulation failure, the unit must be grounded.
(4) Each wiring connection must be done tightly and in accordance with the wiring
system diagram. Wrong wiring may cause the unit to misoperate or become
damaged.
(5) Do not allow wiring to touch the refrigerant tubing, compressor, or any moving
parts of the fan.
(6) Unauthorized changes in the internal wiring can be very dangerous. The manu-
facturer will accept no responsibility for any damage or misoperation that occurs
as a result of such unauthorized changes.
3-8. Recommended Wire Length and Diameter
Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local electrical codes. Carefully observe these regulations when carrying out the installation.
Table 4 lists recommended wire lengths and diameters for power supply systems.
NOTE
Refer to the wiring system diagram (Fig. 7a or Fig. 7b) for the meaning of (A), (B)
and (C) in Table 4.
Refer to your local codes or in the absence of local codes see the National Electric
Code: ANSI/NFPA70.
16
Table 4
WARNING
WARNING
CAUTION
CAUTION
Cross-Sectional(A)+(B)(A) Power Supply Wiring Length (ft)(C) Control
Area (AWG)
Model(#14)(#12)(#14)
C1271, CL1271131 (Max.)230 (Max.)65 (Max.)20A
C1872, CL1872131 (Max.)230 (Max.)98 (Max.)20A
(B) Power Line Length (ft)Line Length (ft)
# ... AWG (American Wire Gauge)
WIRING SYSTEM DIAGRAM
(C1271, CL1271)
G Be sure to comply with local codes on running the
wire from the indoor unit to the outdoor unit (size
of wire and wiring method, etc.).
G Each wire must be firmly connected.
G No wire should be allowed to touch refrigerant
tubing, the compressor, or any moving part.
G To avoid the risk of electric shock, each air con-
INDOOR
UNIT
Te r mi nalTerminal
1
2
3
Disconnect
*
switch
Field supply
(C)
ditioner unit must be grounded.
G For the installation of a grounding device,
please observe local electrical codes.
G Grounding is necessary, especially for units
using inverter circuits, in order to release
charged electricity and electrical noise caused
by high tension.
Otherwise, electrical shock may occur.
G Place a dedicated ground more than 7' (2 m)
away from other grounds and do not have it
INDOOR
UNIT
Te r mi nalTerminal
1
2
3
(C1872, CL1872)
Disconnect
*
switch
Field supply
(C)
shared with other electric appliances.
Fuse or Circuit
Breaker Capacity
115V
115V
115V
Grounding line
Fig. 7a
230/208V
230/208V
230/208V
Grounding line
(B)
(B)
(B)
(B)
OUTDOOR
UNIT
1
2
3
4
5
6
OUTDOOR
UNIT
1
2
3
4
5
6
Powe r supply
(A)
L
N
Grounding
line
Powe r supply
(A)
L
1
L
2
Single phase 115V 60HZ
Single phase 230/208V 60HZ
G Be sure to connect the power supply line to the
outdoor unit as shown in the wiring diagram. The
indoor unit draws its power from the outdoor unit.
G Do not run wiring for antenna, signal, or power
lines of television, radio, stereo, telephone, security system, or intercom any closer than 3'3" (1 m)
from the power cable and wires between the
indoor and outdoor units. Electrical noise may
affect the operation.
Fig. 7b
NOTE
*
A disconnect switch may be required by
national or local codes.
Always comply with national and local code
requirements.
17
Grounding
line
WARNING
1
32
Earth screw
Clamping strap
(Conduit)
Inter unit
Power wiring
(Locally purchased)
3-9. Wiring Instructions for Inter-unit Connections
(1) Remove the 1 screw from the terminal cover, then open the
cover. Be careful that the cover does not fall.
(2) Remove the 3 screws from the power box cover, then open
the cover. Be careful that the cover does not fall.
(3) Use the screw to securely fasten the ground wire from the
outdoor unit in place.
(4) Remove the transparent plastic cover from the 3P terminal
plate.
(5) While viewing the wiring diagram, connect the inter-unit and
power supply line to terminals 1, 2 and 3 on the 3P terminal
plate.
(6) Remount the transparent plastic cover onto the 3P terminal
plate.
(7) Be sure to use the clamping strap to fasten the wires in place.
(8) Tighten the screws to remount the terminal and the power
box cover.
Loose wiring may cause the terminal to overheat or result in unit
malfunction. A fire hazard may
also exist. Therefore, be sure all
wiring is tightly connected.
Fig. 8
When connecting each power wire to the corresponding terminal, follow the instructions “How to connect wiring to the terminal” and fasten
the wire securely tight with the fixing screw of the terminal plate.
How to connect wiring to the terminal
a) For Indoor Unit
(1) Cut the wire end with a cutting pliers, then strip the insulation to
expose the wire about 9/32" (7 mm). See the label (Fig. 9) near the
terminal plate.
(2) Using a screwdriver, loosen the terminal screw on the terminal
plate.
(3) Insert the wire and tighten the terminal screw completely using a
screwdriver.
b) For Outdoor Unit
I For solid core wiring (or F-cable)
(1) Cut the wire end with a cutting pliers, then strip the insulation to
expose the solid wire about 15/16" (25 mm). (Fig. 10)
(2) Using a screwdriver, remove the terminal screw(s) on the terminal
plate.
(3) Using the pliers, bend the solid wire to form a loop suitable for the
terminal screw.
(4) Shape the loop wire properly, place it on the terminal plate and fix
it securely with the removed terminal screw using a screwdriver.
9/32"
STRIP
SIZE
(7 mm)
Fig. 9
Solid wire
Strip 15/16" (25 mm)
Insulation
Fig. 10
(ACTUAL
SIZE)
Loop
18
I For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the insulation to expose the stranded wiring about 3/8" (10 mm) and
tightly twist the wire ends. (Figs. 11 and 12)
(2) Using a screwdriver, remove the terminal screw(s) on the terminal plate.
(3) Using a ring connector fastener or pliers, securely clamp each stripped wire end with a ring connector. (Fig. 11)
(4) Place the ring connector wire, and replace and tighten the removed terminal screw using a screwdriver. (Fig. 13)
Stranded wire
Ring
connector
Strip 3/8" (10 mm)
Fig. 11
Tw ist wire ends
Fig. 12
4. How to Install the Outdoor Unit
First refer to Section 2. Installation Site Selection.
4-1. Wiring Instructions for the Outdoor Unit
Regulations on wire size differ from locality to locality.
For field wiring requirements, please refer to your
local electrical codes. Make sure that the installation
fully complies with all local and national regulations.
Te r mi nal
block
Special
washer
Wire
Lock nut
Screw
Ring connector
Te r mi nal plate
Wire
Fig. 13
Cabinet
Screw and
special washer
Ring
connector
(1) Remove access panel “C”. (Fig. 14)
(2) Connect the inter-unit and power supply line
according to the drawing on the panel side.
(3) Be sure to size each wire allowing approx. 4"
(10 cm) longer than the required length for
wiring. Store excess wiring inside the cabinet.
(4) When connections are completed, check that all
connections are correct as shown in the wiring
system diagram on panel side.
(5) Be sure to ground the unit according to your
local codes.
Conduit
plate
Plug
Inter unit
(Conduit)
Access panel “C”
Power supply
(Conduit)
Fig. 14
19
5. Refrigerant Tubing
Flare nut
Union
Deburring
5-1. Use of the Flaring Method
Many of the conventional split system air conditioners
employ the flaring method to connect refrigerant tubes
which run between indoor and outdoor units. In this
method, the copper tubes are flared at each end and
connected with flare nuts.
5-2. Flaring Procedure with a Flare Tool
(1) Cut the copper tube to the required length with a
tube cutter. It is recommended to cut approx. 12" to
20" (30 to 50 cm) longer than the tubing length you
estimate.
(2) Remove burrs at the end of the copper tube with a
tube reamer or file. This process is important and
should be done carefully to make a good flare.
(Fig. 15)
NOTE
When reaming, hold the tube end downward and be
sure that no copper scraps fall into the tube. (Fig. 16)
Before
After
Fig. 15
Copper
tubing
Reamer
Fig. 16
(3) Remove the flare nut from the unit and be sure to
mount it on the copper tube.
(4) Make a flare at the end of copper tube with a flare
tool.* (Figs. 17 and 18)
(*Use “RIDGID” or equivalent.)
NOTE
A good flare should have the following characteristics:
G inside surface is glossy and smooth.
G edge is smooth.
G tapered sides are of uniform length.
5-3. Caution before Connecting Tubes Tightly
a) Be sure to apply a sealing cap or water-proof tape
to prevent dust or water from getting into the tubes
before they are used.
b) Be sure to apply refrigerant lubricant to the match-
ing surfaces of the flare and union before connecting them together. This is effective for reducing gas
leaks. (Fig. 19)
c)For proper connection, align the union tube and
flare tube straight with each other, then screw in the
flare nut lightly at first to obtain a smooth match.
(Fig. 20)
If the special R410A
flare tool is used:
0 to 0.0196"
(0 to 0.5 mm)
If the previous flare tool
(clutch-type) is used:
0.0472" (1.2 mm)
Adjust so that the amount of tube
protrusion is asshown in the figure.
Fig. 17
Flare nut
Copper
tubing
Flare tool
Fig. 18
Apply refrigerant
lubricant here and here
Fig. 19
Fig. 20
20
5-4. Connecting Tubing between Indoor and
IMPORTANT
CAUTION
Indoor unit
Outdoor unit
Spanner
Torque wrench
Insulation tape (supplied)
Flare insulation (3/16"(T5, supplied) )
Flare insulation (1/8"(T3, supplied) )
Tube insulation
(not supplied)
Vinyl tie (supplied)
Flare nut
The procedure used for installing
the insulation for both wide and
narrow tubes are the same.
Flare
insulation
Vinyl tie (supplied)
Insulation tape
Refrigerant tubing
and insulation
(not supplied)
Drain pipe and insulation
(not supplied)
Drain hose insulation
and vinyl tie
(supplied)
Drain hose
and hose band
(supplied)
Outdoor Units
a) Tightly connect the indoor side refrigerant tubing exten-
ded from the wall with the outdoor side tubing. (Fig. 21)
b) To fasten the flare nuts, apply specified torque as:
To prevent heat loss and wet floors due to dripping of condensation, both tubes must be well insulated with a
proper insulation material.
The thickness of the insulation should be a minimum 5/16"
(8 mm). (Fig. 22)
Min.
5/16"
(8 mm)
Fig. 21
Insulation
Thickness:
min. 5/16"
(8 mm)
Fig. 22
Taping the flare nuts
Wind the insulation tape around the flare nuts at the
tube connections. Secondly cover up the tubing connections with the flare insulation (1/8" (T3, supplied)). Then
wind the other flare insulation (3/16" (T5, supplied)).
Finally, fasten the insulation at both ends with the supplied vinyl ties. (Fig. 23)
Insulation material
The material used for insulation must have good insulation characteristics, be easy to use, be age resistant,
and must not easily absorb moisture.
After a tube has been insulated, never try to bend it into a
narrow curve because it can
cause the tube to break or
crack.
Fig. 23
Fig. 24
Never grasp the drain or refrigerant connecting outlets when moving the unit.
21
Insulated tubes
Drain hose
Clamp
5-6. Taping the Tubes
CAUTION
CAUTION
Apply putty here
Tubing
(1) At this time, the 2 refrigerant tubes (and electrical wire
if local codes permit) should be taped together with
armoring tape. The drain hose may also be included
and taped together as 1 bundle with the tubing.
(2) Wrap the armoring tape from the bottom of the outdoor
unit to the top of the tubing where it enters the wall. As
you wrap the tubing, overlap half of each previous tape
turn. (Fig. 25)
(3) Clamp the tubing bundle to wall, using 1 clamp approx.
every 47" (120 cm).
NOTE
Do not wind the armoring tape too tightly, since this will
decrease the heat insulation effect. Also, be sure the condensation drain hose splits away from the bundle and drips
clear of the unit and the tubing.
Fig. 25
5-7. Finishing the Installation
After finishing insulating and taping over the tubing, use
sealing putty to seal off the hole in the wall to prevent rain
and draft from entering. (Fig. 26)
6. Air Purging
Air and moisture remaining in the refrigerant system have
undesirable effects as indicated below. Therefore, they must
be purged completely.
G pressure in the system rises
G operating current rises
G cooling (or heating) efficiency drops
G moisture in the air may freeze and block capillary tubing
G water may lead to corrosion of parts in the refrigerant system
I Air Purging with a Vacuum Pump (for Test Run)
(1) Check that each tube (both narrow and wide tubes)
between the indoor and outdoor units have been properly connected and all wiring for the test run has been
completed. Note that both narrow and wide tube service
valves on the outdoor unit are kept closed at this stage.
(2) Using an adjustable wrench or box wrench, remove the
valve caps from the service valve on both narrow and
wide tubes.
(3) Connect a vacuum pump and a manifold valve (with
pressure gauges) to the service port on the wide tube
service valve. (Fig. 27)
Manifold valve
(Exclusively for R410A)
Pressure
gauge
Fig. 26
Indoor unit
Outdoor unit
HiLo
The service port on the wide tube service valve
uses a Schrader core valve to access the
refrigerant system. The valve core is similar to
those used in automobile tires. Therefore, be
sure to use a vacuum hose connector which
has a push-pin inside.
Be sure to use a manifold valve for air
purging. If it is not available, use a stop
valve (field supply) for this purpose. The
“Hi” knob of the manifold valve must
always be kept closed.
(4) With the “Lo” knob of the manifold valve open, run
CAUTION
CAUTION
the vacuum pump. The operation time for the vacuum pump varies with tubing length and the capacity
of the pump. The following table shows the amount
of time for evacuation:
Table 6
Required time for evacuation when
26.4 gal/h (100 liter/h) vacuum pump is used
If tubing length isIf tubing length is
less than 33 ft. (10 m)more than 33 ft. (10 m)
10 min. or more15 min. or more
(5) With the vacuum pump still running, close the “Lo”
knob of the manifold valve. Then stop the vacuum
pump.
(6) With the accessory hex wrench, turn the valve stem on
the narrow tube service valve counter-clockwise by 90
degrees (1/4 turn) for 10 seconds, and then turn the
stem clockwise to close it again. (Fig. 28)
NOTE
To prevent other refrigerants from being mistakenly
charged to units which use R410A, the size of the
charge port on the service valve is different from the
one for other refrigerant types. For servicing such as
recharging, the specified charging hose, manifold and
vacuum pump adapter (with reverse flow prevention)
for R410A must be used.
NOTE
The required time in Table 6 is calculated based on the
assumption that the ideal (or target) vacuum condition
is around 0.193 psi (10 mmHg abs.).
90° (1/4 turn)
Narrow tube
Hex wrench
Be sure to completely insert the hex
wrench before attempting to turn the valve.
(7) Leak test all joints at the tubing (both indoor and outdoors) with
soapy water. Bubbles indicate a leak. Tighten the joint more
when leaks, then check if there is no leak. Be sure to wipe off the
soap with a clean cloth.
(8) With the hex wrench, turn the wide tube service valve stem
counter-clockwise to fully open the valve.
(9) Turn the narrow tube service valve stem counter-clockwise to
fully open the valve.
(10) Loosen the vacuum hose connected to the wide tube service
port slightly to release the pressure. Then, remove the hose.
This may cause the refrigerant gas to
leak. In order to avoid this, take off the
hose quickly.
(11) Fasten the valve cap on the wide tube service port securely
with an adjustable wrench or box wrench. Next, mount the
valve cap on the service valve and tighten it to 170 lbs·in
(200 kgf·cm) with a torque wrench. This process is very
important to prevent gas from leaking from the system.
Wide tube
Valve cap
Vac uum hose to manifold valve
Fig. 28
(12) Test run the air conditioner. (See next page.)
(13) While the air conditioner is running, apply liquid soap to
check for any gas leaks around the service valves or caps.
(14) If there is no leakage, stop the air conditioner.
(15) Wipe off the soap on the tubing.
This completes air purging with a vacuum pump and the air conditioner is ready for actual operation.
23
How to Test Run the Air Conditioner
IMPORTANT
ACL
(Reset)
button
1HR.
TIMER
button
ON/OFF
operation
button
HIGH POWER
button
OPERATION lamp
TIMER lamp
HIGH POWER lamp
REMOTE CONTROL receiver
OPERATION button
After turning on the power of the air conditioner, use the
remote controller and follow the steps below to conduct
the test run.
(1) Set the remote controller in Test Run mode. (Fig. 29)
a)Press and hold the HIGH POWER button and the
1HR. TIMER button.
b)Then press and hold the ACL (Reset) button with
a pointed object such as the tip of a pen. After 5
seconds, release the ACL button first.
c) Then release the HIGH POWER and 1HR. TIMER
buttons.
d)appears and “oP-1” blinking in the remote con-
troller clock display area. (Fig. 30)
(2) Start Cooling mode test run by pressing the ON/OFF
operation button of the remote controller. (Fig. 29)
• This starts the fan producing uncooled forced air
with the 3 indicator lamps (OPERATION lamp,
TIMER lamp, and HIGH POWER lamp) on the
main unit blinking. (Fig. 31)
• After 3 minutes, the system shifts into cooling
operation, and cool air will start to be felt. Cooling
mode test run is unaffected by the room temperature.
(3) Press the ON/OFF operation button of the remote
controller again to stop the test run. (Fig. 29)
(4) Finally press the ACL (Reset) button of the remote
controller to release it from Test Run mode to return
to normal mode. (Fig. 29)
• “” and “oP-1” will disappear from the remote
controller clock display area.
Fig. 29
NOTE
Troubleshooting:
In the event that the green OPERATION lamp is blinking
upon powering up the system, an error condition exists.
In this case, refer to the self-diagnostics procedure
which can be seen by opening the air-intake grille.
After the test run is completed, be sure to press the ACL
(Reset) button to return to normal mode. The air conditioner will not operate correctly if this is not done.
Fig. 30
Fig. 31
24
I Basic Functions of the Service Valves
PUSH
Hose with push-pin
Service valve
Close
Hex
wrench
Open
CAUTION
The basic functions of the service valves are given in Table 7 below.
Table 7
Action
Shipping
Operating and
test running
the air conditioner
Measuring pressure
and gas charging
Air purging with
a vacuum pump
Narrow Tube Service
Valve (2-Way)
CLOSED
Fully OPEN
Fully OPEN
CLOSED
Wide Tube Service
Valve (3-Way)
O-ring
*
*
Valve cap
Stem
* The service port on the wide tube ser-
vice valve uses a Schrader core valve
to access the refrigerant system.
Therefore, be sure to use a hose connector which has a push-pin inside.
(Fig. 32)
I Pump Down
Pump down means collecting all refrigerant gas in the
system back into the outdoor unit without losing any of
the gas. Pump down is used when the unit is to be
moved or before servicing the refrigerant circuit.
Pump Down Procedure
Be sure to carry out pump down with the unit in
Cooling mode.
(1) Connect the Lo side charging hose of the manifold
When opening or closing the service valve
stem, use the accessory
hex wrench. Be sure to
fully seat the wrench
Fig. 33
before turning the valve.
valve to the service port on the wide tube service
valve.
NOTE
External diameter of service port
R410A: 5/16"
Fig. 32
(2) Using a hex wrench, turn the narrow tube service
valve clockwise all the way to close the service
valve. (Be sure to confirm that the wide tube service
valve is fully open.)
(3) Press the operation button and start cooling oper-
ation.
(4) When the low pressure gauge reading falls to 14.2 to
7.1 psi (1 to 0.5 kg/cm
2
), fully close the wide tube
valve stem. Then quickly stop the unit.
(5) Disconnect all gauges and hoses, and replace the
valve caps as they were before.
25
I Service Valve Connections
CAUTION
a) Temporary connection:
Screw in 3 – 5 turns by hand. (Fig. 34)
b) To fasten the flare nuts, apply specified torque
The remote control unit can be operated from either a
non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do
not install the remote control unit in the following places:
G In direct sunlight
G Behind a curtain or other place where it is covered
G More than 26' (8 m) away from the air conditioner
G In the path of the air conditioner’s airstream
G Where it may become extremely hot or cold
G Where it may be subject to electrical or magnetic
interference
G Where there is an obstacle between the remote con-
trol unit and the air conditioner (since a check signal
is sent from the remote control unit every 5 minutes)
Fig. 34
Torque wrench
Fig. 35
Be sure to tighten the flare nut
using the prescribed torque. If the
nut is over-tightened, refrigerant
leakage may occur.
7-1. Mounting on a Wall
Before mounting the remote control unit, press the
ON/OFF operation button at the mounting location to
make sure that the air conditioner operates from that
location. The indoor unit should make a beeping sound
to indicate that it has received the signal.
Remote control
unit mount
Mounting screws
5/32 5/8" (4 16 mm)
(included)
To take out the remote control unit, pull it forward.
Press
Set in
place
Fig. 36
Rear side
Hole
To prevent loss of the remote control
unit, you can connect the remote
control unit to the mount by passing
a string through the remote control
unit and attachment hole.
26
ACL
(Reset)
button
1HR.
TIMER
button
ON/OFF
operation
button
HIGH POWER
button
8. Address Switch
8-1. Address Setting of the Remote Control Unit
The address can be set in order to prevent interference between remote controllers when 2 indoor units
are installed near each other. The address is normally
set to “A.” To set a different address, it is necessary to
change the address on the second remote controller.
Ta b
NOTE
Once changed, you cannot restore the original
address setting of the air conditioner.
(1) Switch on the power source.
(2) Break the address-setting tab marked “A” on the
second remote controller to change the address
(Fig. 37). When the tab is removed, the address is
automatically set to B (Fig. 38).
(3) Press and hold the remote controller HIGH
POWER button and 1HR. TIMER button. Then,
press and hold the ACL (Reset) button with a
pointed object such as the tip of a pen. After 5
seconds, release the ACL button first, then
release the HIGH POWER and 1HR. TIMER buttons. “oP-1” (Test Run) appears, blinking in the
remote controller clock display area.
(4) Each time the 1HR. TIMER button is pressed, the
display changes as shown below. Press this button 2 times to change the display to “oP-7”
(Address setting). (Fig. 39)
Fig. 37
ACL button
Fig. 38
(5) “oP-7” has now been selected for address setting.
(6) Press the ON/OFF operation button on the remote
(7) Finally press the remote controller ACL (Reset)
Changing of the second remote controller address is
now completed.
Te st run mode
Self-diagnostic mode
Addresssetting mode
controller. (Fig. 39) Check that the “beep” signalreceived sound is heard from the second indoor
unit (approximately 5 times). The sound you hear
is the signal that the remote controller address
has been changed.
button to cancel the blinking “oP-7” display.
(Fig. 39)
Fig. 39
27
SETTING THE TIMER
1. How to set the present time
(Example) To set to 9:10 pm.
3. How to set the ON time
(Example) To start operation at 7:10 am.
ON TIMEPresent time
OperationIndication
1. Press the SET button once.The timer indication alone
2. • Press the HH button until
AM 7 is displayed.
• Press the MM button until
10 is displayed.
3. Press the ON/OFF button to
start the air conditioner.
4. Press the TIMER SELECT
button once to set ON time.
flashes and the previous settime is only displayed.
The display will change
automatically back to show the
present time after about 10 sec.
The present time is displayed.
The present time and are
displayed.
OperationIndication
1. Press the SET button three
times.
2. • Press the HH button until
PM 9 is displayed.
• Press the MM button until
10 is displayed.
The time indication alone
flashes.
The display will flash for 10 sec.
and automatically stop flashing
except for the “:” symbol.
2. How to set the OFF time
(Example) To stop the air conditioner at 11:30 pm.
OFF TIMEPresent time
OperationIndication
1. Press the SET button twice.The timer indication alone
2. • Press the HH button until
PM 11 is displayed.
• Press the MM button until
30 is displayed.
3. Press the ON/OFF button to
start the air conditioner.
4. Press the TIMER SELECT
button twice to set OFF time.
flashes and the previous settime is only displayed.
The display will change
automatically back to show the
present time after about 10 sec.
The present time is displayed.
The present time and are
displayed.
4. How to set daily ON/OFF repeat timer
(Example) To start operation at 7:10 am. and stop the air conditioner
at 11:30 pm.
Present timeOFF TIME
ON TIME
9:10 pm.
Present time
7:10 am.
ON
OperationIndication
1. Set the timer ON/OFF times
as shown in 2 and 3.
2. Press the ON/OFF button to
start the air conditioner.
3. Press the TIMER SELECT
button three times to set the
ON/OFF combination timer.
The present time PM 9:10 and
are displayed.
Programmed
daily ON / OFF
11:30 pm.
OFF
NOTE
You can check the timer ON/OFF times after you have set them by
pressing the SET button.
8
OI-119-8-EG
5. Cancellation of the time setting
You can cancel the time settings by pressing the TIMER SELECT
button.
The time settings cannot be canceled by pressing the ON/OFF
operation button or MODE selector button.
6. Backup function
Even if the main power supply (circuit breaker) is cut off, the
capacitor inside the remote control store the mode settings in the
memory for 3 hours after the power is off.
The mode settings are reset if the main power supply is off for 3
hours or more.
USING THE 1-HOUR OFF
TIMER
1. 1-Hour OFF Timer
ADJUSTING THE AIRFLOW
DIRECTION
The vertical airflow can be adjusted by moving the flap with the
remote control unit. Do not move the flap with your hands. Confirm
that the remote control unit has been turned on. Use the FLAP
button to set either the sweep function or one of the six airflow
direction settings.
A. Sweep function
The flap starts moving
up and down to deliver
air over the sweep
range.
This function causes the unit to operate for one hour and then
stop, regardless of whether the unit is on or off when this
button is pressed.
The indicator in the display indicates that this function is
operating.
Setting procedure:
Regardless of whether the unit is operating or stopped, press the 1
HR. TIMER button.
appears in the display.
Cancellation procedure:
Press the ON/OFF operation button to turn the unit off, wait for the
unit to stop operating, and then press the ON/OFF operation button
again.
The 1-Hour Timer function is now cancelled and the unit operates
normally.
NOTE
• If, while the 1-Hour Timer function is operating, the 1HR. TIMER
button is pressed once to cancel the function and then again, the
unit continues to operate for one hour from that point in time and
then stops.
• It is not possible to use the OFF Timer and 1-Hour OFF Timer
together. Whichever function is set last takes precedence. If the 1
HR. TIMER button is pressed while the TIMER OFF function
operates, the OFF Timer is cancelled and the unit will stop
operating one hour later.
B. Setting the airflow manually
Referring to the above
illustration, use the
FLAP button to set the
airflow direction within
the range used during
the heating, cooling, or
dehumidifying
operation.
COOL
DRY
SWEEP
SWEEP
HEAT
FAN
NOTE
• The flap automatically closes when the unit is off.
• During the heating operation, the fan speed will be very low and the
flap will be in the horizontal position (position ) until the air being
blown out of the unit begins to warm. Once the air warms up, the
flap position and fan speed change to the settings specified with
the remote control.
CAUTION
• Use the FLAP button on the remote control to adjust the
position of the flap. If you move the flap by hand, the flap
position according to the remote control and the actual flap
position may no longer match. If this should happen, shut off
the unit, wait for the flap to close, and then turn on the unit
again; the flap position will now be normal again.
• Do not have the flap pointed down during cooling operation.
Condensation may begin to form around the air vent and drip
down.
2. Operation together with the daily ON/OFF
repeat timer
The 1-Hour OFF Timer setting is given priority over the DAILY ON/
OFF REPEAT setting.
OI-119-9-EG
9
IMPORTANT
Q'tyQ'ty
1
Parts
Wired
remote
controller
Machine
screws
Tapping
screws
2
2
2
Spacers
1
Parts
1
1
Instruction
manual
FigureFigure
Installation
Instructions
Wire
harness
5/32
15/16"
5/32
15/16"
(4
25mm)
(4
25mm)
26.2 ft. (8m)
INSTALLATION INSTRUCTIONS
W
STK-RCS-7TWSU (Wired Remote Controller)
I Parts supplied with the remote controller
Table 1
See Table 1.
I Remote controller installation guidelines
Installation location
• Mount the remote controller 3.3 to 4.9 ft. (1 to 1.5
meters) off the floor where it can sense the average
temperature of the room.
• Do not mount the remote controller in a place exposed
to direct sunlight or where it is exposed to outside air
such as near a window.
• Do not mount the remote controller behind a curtain or
other object so that it is separated from the air circulation of the room.
• Mount the remote controller inside the room being air
conditioned.
Switching the room temperature sensor
Room temperature sensors are separately incorporated in both the indoor unit and the remote controller. Either sensor can
be used to sense the room temperature. The indoor unit sensor is usually used.
If you wish the remote controller to sense the room temperature, press the SENSOR button with a ballpoint pen or tool with
a small tip. (Refer to Fig. 9 on page 4 to locate the SENSOR button.)
I How to install the remote controller
• The remote controller is set to “Cool/Dry/Heat model” at
the time of shipment from the factory. If the purchased air
conditioner is a COOL/DRY model, follow the instructions
on the label and change the switch on the reverse side of
the remote controller unit to “Cool/Dry model”. (Fig. 1)
• The remote controller is also set to “Single” at the time of
shipment from the factory. For multiple use, set the switch
on the reverse side of the remote controller unit to “Multi”.
(Fig. 1)
• After all work is completed, if any switches have been
changed, then be sure to press the ACL (Reset) button.
(Refer to Fig. 9 on page 4 to locate the ACL (Reset) button.)
SANYO Commercial SolutionsIn Canada
A Division of SANYO North America CorporationSANYO Canada Inc.
1300 Michael Drive, Suite A1-300 Applewood Crescent, Concord
Wood Dale, IL 60191, U.S.A.Ontario, L4K 5C7, Canada
Fig. 1
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.