This air conditioning system meets strict safety and operating
standards. As the installer or service person, it is an important
part of your job to install or service the system so it operates
safely and efficiently.
For safe installation and trouble-free operation, you must :
● Carefully read this instruction booklet before beginning.
● Follow each installation or repair step exactly as shown.
● Observe all local, state, and national electrical codes.
● Pay close attention to all warning and caution notices
given in this manual.
This symbol refers to a hazard or
unsafe practice which can result
in severe personal injury or death.
This symbol refers to a hazard or
CAUTION
unsafe practice which can result
in personal injury or product or
property damage.
If Necessary, Get Help
These instructions are all you need for most installation sites
and maintenance conditions. If you require help for a special
problem, contact our sales/service outlet or your certified
dealer for additional instructions.
In Case of Improper Installation
The manufacturer shall in no way be responsible for improper
installation or maintenance service, including failure to follow
the instructions in this document.
SPECIAL PRECAUTIONS
When Wiring
……………………………………………………………………
ELECTRICAL SHOCK CAN CAUSE SEVERE
PERSONAL INJURY OR DEATH. ONLY A
QUALIFIED, EXPERIENCED ELECTRICIAN
SHOULD ATTEMPT TO WIRE THIS SYSTEM.
• Do not supply power to the unit until all wiring and tubing are
completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system.
Carefully refer to the wiring diagram and these instructions
when wiring. Improper connections and inadequate
grounding can cause accidentaly injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
When Transporting
……………………………………………………………………
Be careful when picking up and moving the indoor and outdoor
units. Get a partner to help, and bend your knees when lifting
to reduce strain on your back. Sharp edges or thin aluminum
fins on the air conditioner can cut your fingers.
When Installing
……………………………………………………………………
…In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to walls
and floors.
…In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide a
solid, level foundation for the outdoor unit. This prevents water
damage and abnormal vibration.
…In an area with High Winds
Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
…In a Snowy Area (for Heat Pump-type Sys-tems)
Install the outdoor unit on a raised platform that is higher than
drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
……………………………………………………………………
• Ventilate the room well, in the event that refrigerant gas
leaks during the installation. Be careful not to allow contact
of the refrigerant gas with a flame as this will cause the
generation of poisonous gas.
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Apply refrigerant lubricant to the matching surfaces of the
flare and union tubes before connecting them, then tighten
the nut with a torque wrench for a leak-free connection.
• Check carefully for leaks before starting the test run.
NOTE
Depending on the system type, liquid and gas lines may be
either narrow or wide. Therefore, to avoid confusion the
refrigerant tubing for your particular model is specified as either
“narrow” or “wide” rather than as “liquid” or “gas”.
When Servicing
……………………………………………………………………
• Turn the power OFF at the main power box (mains) before
opening the unit to check or repair electrical parts and
wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site when installation is finished. Check that no
metal scraps or bits of wiring have been left inside the unit.
CAUTION
• Ventilate any enclosed areas when installing or testing the
refrigeration system. Contact of refrigerant gas with fire or
heat can produce poisonous gas.
• Confirm after installation that no refrigerant gas is leaking. If
the gas comes in contact with a burning stove, gas water
heater, electric room heater or other heat source, it can
cause the generation of poisonous gas.
i
SM830082
WHO SHOULD USE THIS MANUAL
This service manual is made to assist the service technician apply his knowledge and training
to this model air conditioner. This manual is written both for experienced service persons
and those who are new to air conditioning service. To help those with less experience or
who are new to this kind of unit we have included more explanations of basic procedures in
simple language than is usual in some service manuals. The experienced technician will of
course find he knows many of these things already and can go directly to the procedures and
information he needs; the less experienced technician will better understand what to do even
before he arrives on the job, and therefore be better able to work by himself as well as assist
the more experienced technician.
TABLE OF CONTENTS
1. SPECIFICATIONS............................................................................................ I - 1
Air circulation (H / M / L)230 V
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA11.211.611.712.3
Power input*W2,4502,3502,5002,450
Maximum overcurrent protectionA25
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / Vertical— / Automatic
Air filterWashable, easy access, long life fiter (2,500 hr)
Operation soundIndoor - Hi / Me / LodB - A38 / 35 / 31
Refrigerant controlElectronic Expansion Control Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)1 / 4 (6.35)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)12-1/8(380)28-15/16(735)
Net weightlbs. (kg)49(22)157(71)
Indoor grille dimensionsHeightin. (mm)3-1/16(78)—
PNR-XHS2432Widthin. (mm)33-27/32(860)—
Net weightlbs. (kg)11(5)—
Indoor / Outdoor unitHeightin. (mm)13-5/16(338)32-17/32(826)
Air circulation (H / M / L)230 V
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA15.415.818.219.3
Power input*W3,3503,2003,8503,750
Maximum overcurrent protectionA40
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / Vertical— / Automatic
Air filterWashable, easy access, long life fiter (2,500 hr)
Operation soundIndoor - Hi / Me / LodB - A44 / 37 / 33
Refrigerant controlElectronic Expansion Control Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)3 / 8 (9.52)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)14-1/2(368)48-5/8(1,235)
Net weightlbs. (kg)60(27)203(92)
Indoor grille dimensionsHeightin. (mm)3-1/16(78)—
PNR-XHS2432Widthin. (mm)45-9/32(1,150)—
Net weightlbs. (kg)15(7)—
Indoor / Outdoor unitHeightin. (mm)14-1/2(368)52-7/32(1,326)
Air circulation (H / M / L)230 V
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA20.621.021.722.2
Power input*W4,2004,1004,4504,350
Maximum overcurrent protectionA45
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / Vertical— / Automatic
Air filterWashable, easy access, long life fiter (2,500 hr)
Operation soundIndoor - Hi / Me / LodB - A45 / 38 / 34
Refrigerant controlElectronic Expansion Control Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)3 / 8 (9.52)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)14-1/2(368)48-5/8(1,235)
Net weightlbs. (kg)60(27)203(92)
Indoor grille dimensionsHeightin. (mm)3-1/16(78)—
PNR-XHS2432Widthin. (mm)45-9/32(1,150)—
Net weightlbs. (kg)15(7)—
Indoor / Outdoor unitHeightin. (mm)14-1/2(368)52-7/32(1,326)
Air circulation (H / M / L)230 V
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA10.711.311.712.9
Power input*W2,3502,2802,5502,500
Maximum overcurrent protectionA25
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / VerticalManual / Automatic
Air filterWashable, easy access
Operation soundIndoor - Hi / Me / LodB - A40 / 38 / 36
Refrigerant controlElectronic Expansion Control Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)1 / 4 (6.35)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)7-15/32(190)28-15/16(735)
Air circulation (H / M / L)230 V
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA15.115.718.219.6
Power input*W3,3503,1703,9503,890
Maximum overcurrent protectionA40
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / VerticalManual / Automatic
Air filterWashable, easy access
Operation soundIndoor - Hi / Me / LodB - A46 / 42 / 37
Refrigerant controlElectronic Expansion Control Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)3 / 8 (9.52)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)9-7/16(240)48-5/8(1,235)
Air circulation (H / M / L)230 V
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA20.621.321.722.5
Power input*W4,3004,2004,4504,350
Maximum overcurrent protectionA45
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / VerticalManual / Automatic
Air filterWashable, easy access
Operation soundIndoor - Hi / Me / LodB - A47 / 43 / 38
Refrigerant controlElectronic Expansion Control Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)3 / 8 (9.52)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)9-7/16(240)48-5/8(1,235)
Air circulation (H / M / L)230 V
External Static Pressurein.Aq (Pa)0.2 (49) : at shipment / 0.4 (100) : using jumper cable
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA11.512.112.012.5
Power input*W2,5502,4802,6502,550
Maximum overcurrent protectionA25
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / Vertical— / —
Air filterOptional
Operation soundIndoor - Hi / Me / LodB - A34 / 30 / 27 : at shipment / 38 / 34 / 30 : using jumper cable
Refrigerant controlElectronic Expansion Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)1 / 4 (6.35)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)12-7/32(310)28-15/16(735)
Net weightibs. (kg)1-1/4(32)32-17/32(826)
Package dimensionsHeightin. (mm)14-3/32(358)40(1,016)
Air circulation (H / M / L)230 V
External Static Pressurein.Aq (Pa)0.24 (59) : at shipment / 0.38 (94) : using jumper cable
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA15.115.718.219.6
Power input*W3,3503,1703,7803,760
Maximum overcurrent protectionA40
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-SH80UA. WL / RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / Vertical— / —
Air filterOptional
Operation soundIndoor - Hi / Me / LodB - A38 / 33 / 31 : at shipment / 42 / 38 / 33 : using jumper cable
Refrigerant controlElectronic Expansion Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)3 / 8 (9.52)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)12-7/32(310)48-5/8(1,235)
Air circulation (H / M / L)230 V
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA10.310.911.312.2
Power input*W2,3002,2202,5002,430
Maximum overcurrent protectionA25
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / VerticalManual / Automatic
Air filterWashable, easy access
Operation soundIndoor - Hi / Me / LodB - A45 / 42 / 40
Refrigerant controlElectronic Expansion Control Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)1 / 4 (6.35)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)14-9/16(370)28-15/16(735)
Air circulation (H / M / L)230 V
S.E.E.R. (H.S.P.F.)
ELECTRICAL RATINGS
Voltage ratingVAC230208230208
Available voltage rangeVAC187 - 253
Running amperesA14.915.517.819.1
Power input*W3,2903,1203,8603,810
Maximum overcurrent protectionA40
FEATURES
ControlsMicroprocessor
Low ambient controlBuilt-in 0°F
Fan speeds Indoor / Outdoor3 and Automatic control / 3 (Auto)
Optional Wired Remote Controller (Timer)RCS-SH80UG (72-hour ON / OFF)
Optional Wireless Remote Controller (Timer)RCS-BH80UA. WL (72-hour ON / OFF)
Air deflectionHorizontal / VerticalManual / Automatic
Air filterWashable, easy access
Operation soundIndoor - Hi / Me / LodB - A48 / 44 / 40
Refrigerant controlElectronic Expansion Control Valve
REFRIGERANT PIPING
Limit of piping lengthft.(m)165 (50)
Limit of piping length at shipmentft.(m)100 (30)
Limit of elevation differenceft.(m)Outdoor unit is higher than indoor unit: 165 (50)
between the two unitsOutdoor unit is lower than indoor unit: 100 (30)
Refrigerant pipingNarrow pipein. (mm)3 / 8 (9.52)
Flare typeWide pipein. (mm)3 / 4 (19.05)
DIMENSIONS & WEIGHTIndoor unitOutdoor unit
Unit dimensionsHeightin. (mm)14-9/16(370)48-5/8(1,235)
MODEL No.XH2442
Source230 - 208 VAC / 1 phase / 60 Hz
Remote controller (Option)RCS - SH80UA, WL
Controller P. C. B Ass'yCR - TH2442
Control circuit fuse250 VAC, 3 A
Fan (Number … diameter)in.(mm)Turbo (1…17-7/16 (443))
Fan motor
ModelSFG6X - 41D6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm6 … 464
Nominal outputW40
Coil resistanceΩBRW - WHT: 170.3,ORG - YEL:43.2
(Ambient temperature 68 °F)WHT - VLT:18.1,WHT - PNK:83.5
CoilAluminum plate fin / Copper tube
Rows … Fins per inch2 … 14.9
Face areaft.
Panel
Model No.PNR - XH2442
Auto louver motorMT8 - 3C
Auto louver motor … RatedV, W,rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16.430 Ω± 8 %
2
(m2)3.69 (0.343)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
4
5
I - 12
SM830082
1. Specifications
1-2Major Component Specifications
(A) Indoor Unit
MODEL No.XH3642
Source230 - 208 VAC / 1 phase / 60 Hz
Remote controller (Option)RCS - SH80UA, WL
Controller P. C. B Ass'yCR - TH2442
Control circuit fuse250 VAC, 3 A
Fan (Number … diameter)in.(mm)Turbo (1…17-7/16 (443))
Fan motor
ModelSFG6X - 81A6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm6 … 467
Nominal outputW60
Coil resistanceΩBRW - WHT:75.1,ORG - YEL:27.4
(Ambient temperature 68 °F)WHT - VLT:6.7,VLT - PNK:42.7
CoilAluminum plate fin / Copper tube
Rows … Fins per inch2 … 14.9
Face areaft.
Panel
Model No.PNR - XH3642
Auto louver motorMT8 - 3C
Auto louver motor … RatedV, W,rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16.430 Ω± 8 %
2
(m2)8.20 (0.762)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1
2
3
I - 13
4
5
SM830082
1
2
3
1. Specifications
1-2Major Component Specifications
(A) Indoor Unit
MODEL No.XH4242
Source230 - 208 VAC / 1 phase / 60 Hz
Remote controller (Option)RCS - SH80UA, WL
Controller P. C. B Ass'yCR - TH2442
Control circuit fuse250 VAC, 3 A
Fan (Number … diameter)in.(mm)Turbo (1…17-7/16 (443))
Fan motor
ModelSFG6X - 81A6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm6 … 506
Nominal outputW60
Coil resistanceΩBRW - WHT:75.1,ORG - YEL:27.4
(Ambient temperature 68 °F)WHT - VLT:6.7,VLT - PNK:42.7
CoilAluminum plate fin / Copper tube
Rows … Fins per inch2 … 14.9
Face areaft.
Panel
Model No.PNR - XH3642
Auto louver motorMT8 - 3C
Auto louver motor … RatedV, W,rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16.430 Ω± 8 %
2
(m2)8.20 (0.762)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
4
5
I - 14
SM830082
1. Specifications
1-2Major Component Specifications
(A) Indoor Unit
MODEL No.TH2442
Source230 - 208 V / 1 phase / 60 Hz
Remote controller (Option)RCS - SH80UA, WL
Controller P. C. B Ass'yCR - TH2442
Control circuit fuse250 V, 3 A
Fan (Number … diameter)in.(mm)Centrifugal (4 ... 5-1/8(130))
Fan motor
ModelSR4X - 51A6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm1,179
Nominal outputW31
Coil resistanceΩBRW - WHT: 111.0,ORG - YEL:16.7
(Ambient temperature 68 °F)WHT - VLT:35.4,BLK - PNK:23.9
VLT - ORG:13.4,YEL - BLK: 136.6
Safety device
Operating temperatureOpen°F266± 14.4
Close°F174.2 ± 27
Run capacitorVAC,µF440 V , 1.5 µF
Electronic refrigerant control valve
Solenoid control modelDKV - MOZS582E0
Coil resistanceΩORG - GRY:46,YEL - GRY:46
(Ambient temperature 68 °F)RED - GRY:46,BLK - GRY:46
Solenoid control valve modelIKV - 24D18
Heat exchanger
CoilAluminum plate fin / Copper tube
Rows … Fins per inch3 … 14.9
Face areaft.
Auto louver motor
Model No.MT8 - 3C
Auto louver motor … RatedV, W, rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16,430 Ω± 8 %
2
(m2)1.81 (0.168)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1
2
3
I - 15
4
5
SM830082
1
2
3
1. Specifications
1-2Major Component Specifications
(A) Indoor Unit
MODEL No.TH3642
Source230 - 208 V / 1 phase / 60 Hz
Remote controller (Option)RCS - SH80UA, WL
Controller P. C. B Ass'yCR - TH2442
Control circuit fuse250 V, 3 A
Fan (Number … diameter)in.(mm)Centrifugal (4 ... 5-29/32(150))
Fan motor
ModelKFG4X - 101C6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm4 ... 1,040
Nominal outputW100
Coil resistanceΩBRW - WHT:61.05,ORG - YEL:13.23
(Ambient temperature 68 °F)WHT - VLT:9.955 ,YEL - BLK:19.25
CoilAluminum plate fin / Copper tube
Rows … Fins per inch3 … 14.9
Face areaft.
Auto louver motor
Model No.MT8 - 3C
Auto louver motor … RatedV, W, rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16,430 Ω± 8 %
2
(m2)3.51 (0.326)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
4
5
I - 16
SM830082
1. Specifications
1-2Major Component Specifications
(A) Indoor Unit
MODEL No.TH4242
Source230 - 208 V / 1 phase / 60 Hz
Remote controller (Option)RCS - SH80UA, WL
Controller P. C. B Ass'yCR - TH2442
Control circuit fuse250 V, 3 A
Fan (Number … diameter)in.(mm)Centrifugal (4 ... 5-29/32(150))
Fan motor
ModelKFG4X - 101C6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm4 ... 1,099
Nominal outputW100
Coil resistanceΩBRW - WHT:61.05,ORG - YEL:13.23
(Ambient temperature 68 °F)WHT - VLT:9.955 ,YEL - BLK:19.25
CoilAluminum plate fin / Copper tube
Rows … Fins per inch3 … 14.9
Face areaft.
Auto louver motor
Model No.MT8 - 3C
Auto louver motor … RatedV, W, rpm240 VAC , 3 W , 3 rpm
Coil resistance (Ambient temperature 77 °F)Ω16,430 Ω± 8 %
2
(m2)3.51 (0.326)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
1
2
3
I - 17
4
5
SM830082
1
2
3
1. Specifications
1-2Major Component Specifications
(A) Indoor Unit
MODEL No.UH2442
Source230 - 208 V / 1 phase / 60 Hz
Remote controller (Option)RCS - BH80UA, WL
Controller P. C. B Ass'yCR - TH2442
Control circuit fuse250 V, 3 A
Fan (Number … diameter)in.(mm)Centrifugal (4 ... 5-29/32(150))
Fan motor
ModelKFG4X - 71B6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm4 ... 920
Nominal outputW100
Coil resistanceΩBRW - WHT:74.7,ORG - YEL:9.59
(Ambient temperature 68 °F)WHT - VLT:19.1,YEL - BLK:10.52
CoilAluminum plate fin / Copper tube
Rows … Fins per inch3 … 14.9
Face areaft.
2
(m2)2.03 (0.189)
DATA SUBJECT TO CHANGE WITHOUT NOTICE
4
5
I - 18
SM830082
1. Specifications
1-2Major Component Specifications
(A) Indoor Unit
MODEL No.UH3642
Source230 - 208 V / 1 phase / 60 Hz
Remote controller (Option)RCS - BH80UA, WL
Controller P. C. B Ass'yCR - TH2442
Control circuit fuse250 V, 3 A
Fan (Number … diameter)in.(mm)Centrifugal (4 ... 5-29/32(150))
Fan motor
ModelKFG4X - 141A6P
Source230 - 208 V / 1 phase / 60 Hz
No. of pole … r.p.m. (230 V, High)rpm4 ... 940
Nominal outputW100
Coil resistanceΩBRW - WHT:39.9,ORG - YEL:9.37
(Ambient temperature 68 °F)WHT - VLT:6.91,YEL - BLK:8.86