Sanyo 12XS71 User Manual

Split System Submittal Data
Print Form
System: 12XS71 Indoor/Outdoor: XS1271/C1271 Grille: PNR-XS1872 Ceiling Recessed Air Conditioner
Job Name: Location: Engineer: Submitted to: Submitted by: Reference:
General Data (at 115V)
Power V/PH/Hz 115/1/60
Circuit Ampacity Fuse Size, Max.
Compressor DC Rotary Inverter
No. used R.L. Amps - L.R.
Outdoor Unit
Fan type Dia. (in.) - No. Speeds Type Drive - No. Speeds No. Poles No. Motors CFM F.L. Amps
(A) 20 (A) 20
(A) 12.6-20
Propeller
15-3/4-1
DC Motor
(RPM) 8-750
(W) 50-1
(HIGH)) 1059
(A) 0.6
Approval: Date: Construction: Unit #: Drawing #:
Refrigerant
Lbs. - R410a (outdoor unit) Control
1
Connection Line Length, Max (ft.) Lift Difference, Max (ft.) Line Size Line Size
Dimensions
Indoor Unit
Outdoor Unit
R410A
2.43
Electric Expansion Valve
Flare
65 23
(in O.D. Dishcharge) 1/4”
(in O.D. Suction) 3/8”
(in.) H x W x D
(uncrated) 11-1/16 x 22-5/8 x 22-5/8
(crated) 11-13/32 x 24-13/16 x 28-1/8
(uncrated) 21-9/16 x 28-11/32 x 10-1/16
(crated) 23-5/8 x 33-11/16 x 14-1/4
Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size
Indoor Unit
Fan type Dia. & Length (in.) - No. Speeds No. Speeds No. Poles No. Motors CFM Indoor Sound Rating F.L. Amps
Coil Type Fin Type - Pipe Type Rows - F.P.I. Face Area Tube Size Drain Connection Size
Aluminum Fin and Copper Pipe
Corrugated Plate-Inner Rifl ed
2-18.1
(sq.ft.)) 3.95
(in.) 5/16”
Turbo
12-5/8/5-3/4-1
3+Auto
(RPM, High)) 8-470
(W) 30-1
(Hi/Med/Low) 235/206/194
(Hi) (dB-A) 34
(A) .346
Aluminum Plate Fin & Copper Tube
Slit Plate & Inner Rifl ed
2-18.1
(sq.ft.)) 2.94
(in.) 9-32” (in.) 23/32”
Weight Indoor Outdoor
Net Shipping
Shipping Volume
Performance Data @ ARI Standard Conditions (115V)
Cooling
Total Capacity Sensible Capacity Latent Capacity SEER Dehumidification Amps Power Inputs Outdoor Sound Rating
(lbs.) 35.3 77.2
(lbs.) 41.9 83.8
(cu.ft.) 4.59 6.35
(BTU/H) 11,900 (3,000-11,900)
(BTU/H) 7,200
(BTU/H) 4,700
(Pints/H) 4.26
(A) 12.6 (2.5-12.6) (W) 1260 (250-1260)
(dB-A) 47
16
Dimensions
3. DIMENSIONAL DAT A
Indoor Unit XHS1271 & PNR-XS1872
XHS1872 & PNR-XS1872
6-5/16 6-11/16
1-3/16 (30)
4-19/32
1-25/32
1-25/32
2-3/32
8-15/32
22-5/8 (575)
11-5/32 (283)
3
6
5
Less than 31/32 Less than 31/32
3-5/8
22-5/8 (575)
12-7/8
Suspension bolt pitch
Suspension bolt pitch
21-1/32 (534)
21-1/32
(534)
12-7/16
23-5/8 (600)
Ceiling opening dimensions
23-5/8 (600)
Ceiling opening dimensions
7
Center of panel
24-19/32 (625)
24-19/32 (625)
13-5/32 (334)
14-3/32 (358)
1
2
2
2
2
7-11/16
4-29/32
A View
8
1-3/16
21/32
3-1/8
The length of the suspension bolts should be selected so that there is a gap of 1-3/16" or the ceiling (21/32" or more below the lower surface of the main unit), as shown in the figure at right. If the suspension bolts is too long, it will contact the ceiling panel and the unit cannot be installed.
AA
Air intake
Discharge outlet
Refrigerant tubing
(liquid tube)
dia.
1/4" (flared)
Refrigerant tubing
(gas tube)
dia. 1/2"
(flared)
Drain tube connection port VP20 (outer dia. 1")
Power supply port
Suspension bolt hole (4 - 1/2" x 1-1/8" hole)
Fresh air intake duct connection port (dia. 3-7/8")
1
2 3 4
5 6 7
8
7-23/32
1-27/32 1-3/32
2-3/32
2-3/4 1-9/32
5-9/16
25/32
10-13/16
3-19/32
ID:23/32
4-ID:15/16
21-3/16
6-3/32
4-9/32 2-5/32
Narrow tube service valve dia.1/4" (6.35)
Wide tube service valve dia.3/8" (9.52)
3-19/32
15/32
10-7/16 (265)
11-13/32
12-7/16
Outdoor Unit CH1271
28-11/32 (720) 2-1/8
21-9/16 (548)
5/8
Features
Controls Remote Controller Temperature Control Timer Night Setback Air Louver
(Horizontal) Manual
(Vertical) Automatic
Power Failure Automatic Restart Self-Diagnosis Air Filter Air Clean Apatite Filter Quiet Operation Ion Generator
Microprocessor
LCD Wireless Type, Temp. Sensor Built In
IC Thermostat
24 Hr Program; 1HR ON/OFF
Built-In
Built-In Built-In
Washable, Anti-Mold
Standard
Built-In Built-In
Options
Refrigerant Line Set Fresh Air Intake Airduct Extension Condensate Drain Pump Hard Wired Remote Controller Non-Removeable Locking Remo-con Bracket
Available
Knock-out
N/A
Standard
Available Available
Operating Range
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 95F DB/71F WB 115F DB Minimum 67F DB/57F WB 50F DB
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com
Loading...