Sanyo 12RLS11, 12RS11 User Manual

SANYO AIR CONDITIONING PRODUCTS

DUCTLESS SPLIT SYSTEM AIR CO NDITIONERS & HEA T PUMPS

SPECIFICATIONS - SECTION 15700
Covers Sanyo System Models > 12RS11, 12RLS11 (See plans for specified models & details)
DUCTLESS SPLIT SYSTEM AIR CONDITIONERS - RECESSED CEILING MOUNT
1) GENERAL SPECIFICATIONS
Matching indoor & outdoor sections shall be connected by deoxidized, annealed refrigerant copper tubing, type “L”, cleaned & capped. All systems shall have flared refrigeration connections on both indoor & outdoor sections. Size & insulate tubing according to manufacturer’s specifications.
System(s) indoor & outdoor sections shall be completely factory assembled & wired, with a pre­charge of refrigerant. A single power source shall provide voltage to both the outdoor & indoor units. Electrical wire & connections to outdoor section, and between indoor & outdoor section(s), shall be sized, installed & grounded by the installer in conformance with the National Electrical Code (N.E.C.), local codes, as well as, manufacturer’s instructions.
System(s) shall be equipped with a microprocessor control system, utilizing an infrared remote controller with LCD display that provides access to all system functions, and transmits room conditions & programs to the indoor microprocessor every 3 minutes. Infrared remote controller shall be capable of operating system mounted up to 26’ from the indoor section, according to manufacturer’s recommendations & instructions. System(s) shall have the capability of continuous operation in the case of a lost or damaged remote controller, utilizing a factory installed, integral manual switch in conjunction with the system microprocessor.
System Infrared Remote Controller Functions will include: system mode selection, programmable temperature control, 24 hour programmable timer, automatic thr ee (3) spe ed indoor fan speed control, constant fan speed selection, night setback mode, user selectable room temperature sensor located on either infrared remote controller or indoor unit, multiple system control using a single controller.
System Features will include: Sanyo high efficiency, rotary compressor, with suction line accumulator, a strainer, cap tube refrigerant control, indoor coil freeze protection, built-in auto restart after power failure, short cycle time delay, low ambient cooling operation to zero degrees
-
1-
outdoor air temperature (selected systems), automatic indoor fan speed determined by system microprocessor, washable anti-mold poly filters, indoor mounted operation selector & lamp showing operation, standby & timer modes, with start up test mode & manual on/off switch.
Low Ambient Systems shall be capable of operating in tne cooling mode down to zero (0) degrees F. outdoor temperature.

1B) INSTALLATION

System(s) shall be installed according to manufacturer’s instruct ions & recommendations, as well as, all governing local & national codes. System(s), as well as the infrared remote controller, shall be mounted & placed as shown on plans within all minimum clearances as specified by manufacturer’s instructions, & secured to provide for safe operation. Refriger ant tubing size shall not vary from manufacturer’s specifications, and shall be properly secured & insulated. Installer shall insulate both liquid & suction lines individually. Electrical wiring shall be sized & installed according to manufacturer’s instructions & in conformance with the National Electric Code (N.E.C.). Outdoor condensers shall be mounted & secured to accommodate for extreme weather conditions. Distance between indoor & outdoor unit(s) shall not exceed manufacturer’s specifications.
2) OUTDOOR CONDENSING SECTIONSANYO MODELSC1211, CL1211 Outdoor condensing section(s) shall be factory assembled, wired, piped & pre-charged with a start
up amount of R-22 refrigerant. Unit(s) shall be constructed of G90 galvannealed steel with corrosion inhibiting, acrylic, baked-on enamel finish. Unit(s) shall be furnished with a high efficiency, Sanyo rotary compressor with internal overload protection, securely mounted with vibration isolators to reduce noise & vibration. Condenser coil heat ex chan ger shall be constru cted of nonferrous, rifled copper tubing with enhanced aluminum slit fins mechanically bonded to the copper. A suction line accumulator, a coil temperature sensor & cap tube metering device shall be factory installed. Fan motor(s) shall be direct drive with internal overload protection, permanent lubrication, with propeller type fan(s), mounted for horizontal air discharge. Brass valves with refrigeration flare connections & flare nuts, & servic e ports shall be factory mounted, externally for easy access. The unit(s) shall be test started by the manufacturer at their factory prior to shipment for installation.
Low Ambient outdoor section(s) shall contain a printed circuit board, factory mounted & wired, to assist in control of low ambient operation. Unit(s) shall be able to operate in the A/C mode down to zero (0) degrees Fahrenheit outdoor temperature. A factory installed 20 watt crankcase heater shall provide additional compressor protection.
3) INDOOR EVAPORATOR SECTION – SANYO MODELS – RS1211
Indoor section(s) shall be recessed ceiling mount type, with single direction airflow, factory assembled & wired. Ceiling mounting diagram shall be included with each system. Unit(s) shall contain an evaporator heat exchanger constructed of nonferrous, rifled copper tubing with enhanced aluminum slit fins, mechanically bonded to the copper. A single centrifugal blower wheel, statically & dynamicall y balanced shal l be attached to a single direct dri ve, P SC fan mo tor, with overload protection, permanent lubrication & multi-speed capability. Unit(s) shall contain a Printed Circuit Board (PCB) with a control circuit fuse & microprocessor, factory mounted &
-
2-
Loading...
+ 1 hidden pages