1. Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
2. The address of the indoor unit is assigned by adjusting MAIN(SW02) and RMC(SW01) rotary switches.
K1 K2 K3 K4
SW03
K5 K6 K7 K8
SW04
K9
K10
K11
K12
SW05
SW02 MAIN SW01 RMC
3. The MAIN address is for communication between the indoor unit and the outdoor unit.
Therefore, you must set it to operate the air conditioner properly.
4. It is required to set the RMC address if you install the wired remote controller and/or the centralized controller.
5. If you install optional accessories such as the wired remote controller, centralized controller, etc. see an appropriate
installation manual.
6. If an optional accessory is not installed, you do not have to set the RMC address. However, adjust K1 and K2 switches of
the SW03 DIP switch to "ON" position in this case.
7. Set the MAIN address by adjusting the rotary switch(SW02) from 0 to F. Each indoor unit connected to the same outdoor
unit must have different address.
7.
i. e. If an indoor unit does not have an optional accessory and its
MAIN address is "4".
K1 K2 K3 K4
K5 K6 K7 K8
K9
K10
K11
K12
SW03
SW04
SW05
SW02 MAIN
SW01 RMC
7Samsung Electronics
2-2 Additional Functions
K5 K6 K7 K8
K5 K6 K7 K8
K5 K6 K7 K8
■ Compensation for lost temperature in heating operation
■
• Reduces the difference between an actual room temperature and a sensed
■
• temperature by the air conditioner when heating.
Switch No.Switch ONSwitch OFF
K52°C compensation5°C compensation
■ Adjusting filter cleaning cycle
■
• You can adjust the cycle for filter sign indicator.
Switch No.Switch ONSwitch OFF
K61000 hours2000 hours
■ Hot water heater
■
• You must adjust the K7 when you install the hot water heater.
SW04
SW04
Switch No.Switch ONSwitch OFF
K7No use of hot water heater Use of hot water heater
SW04
Samsung Electronics8
2-3 Setting Up Option Switches
■ Option Switch
Display
Key
■ Rotary Switch
■
You should display that how many indoor units are connected to the
outdoor unit. Refer to the table below, then turn the arrow to appropriate
position.
Rotary Switch
Switch No.
0 or 1
2
3
4
5
6
7
8
Number of
indoor unit(s)
One
Two
Three
Four
Five
Six
Seven
Eight
Switch No.
9
A
B
C
D
E
F
-
Number of
indoor unit(s)
Nine
Ten
Eleven
Twelve
Thirteen
Fourteen
Fifteen
-
■ KEY■ Display
K1K2K3K4
RESETCHECK MODEDISPLAY
MODE
DIS 1
SEG 1 SEG 2SEG 3 SEG 4
DIS 2
9Samsung Electronics
Installation
■ Summary of KEY functions
Number
of press times
✳ Use the K1 only for heat pump models.
Function
(Displayed on SEG 3, 4)
1
2
3
4
K1
Adding refrigerant at
heating mode
Test operation at
heating mode
End
-
■ Reading data indicated on the display
KEY
K1
Number of
press
1
2
3
Adding refrigerant for heat pump models
Test operation for heat pump models
End
(Displayed on SEG 3, 4)
K2
Adding refrigerant at
cooling mode
Test operation at
cooling mode
Pump Down for recovery
of refrigerant
End
Item
(Displayed on SEG 3, 4)
K3
Reset
-
-
-
DisplayMeaning
(Displayed on SEG 3, 4)
K4
Displays data
-
-
-
Example
K2
K3
K4
1
2
3
4
1
2
3(1)
4(2)
5(3)
6(4)
7(5)
8(6)
Adding refrigerant for cooling only models
Test operation for cooling only models
Pump Down for recovery of refrigerant
End
Reset
Discharge temperature of compressor
Temperature of outdoor heat exchanger
Outdoor temperature
Step of electronic expansion valve
● If an error occurs during the operation, an LED flickers and the operation is stopped except the LED.
● If you re-operate the air conditioner, it operates normally at first, then detect an error again.
4-1 LED Display on the receiver & display unit
■ LED Display
Indicators
Concealed Type
Abnormal conditions
Power reset
Error of temperature sensor in indoor unit
(OPEN/SHORT)
Error of heat exchanger sensor in indoor
unit(OPEN/SHORT)
Error of outdoor temperature sensor
Error of COND sensor
Error of DISCHARGE sensor
(OPEN/SHORT)
1. No communication for 2 minutes between
indoor unit and outdoor unit
(communication error for more than
2 minutes)
2. Indoor unit receiving the communication
error from outdoor unit
3. Outdoor unit tracking 3 minute error
4. When sending the communication error from
outdoor unit the mismatching of the
communication numbers and installed
numbers after completion of tracking. (communication error for more than 2 minutes)
Blue
Red
Standard Type
Operating
Displayed on appropriate indoor unit
which is operating
Displayed on appropriate indoor unit
which is operating
Displayed on appropriate indoor unit
which is operating
Displayed on outdoor unit
1. Error of indoor unit: Displayed on
the indoor unit regardless of
operation
2. Error of outdoor unit: Displayed on
the indoor unit which is operating
1. Communication error between indoors
(Communication error for more than
2 minutes)
2. Slave of indoor unit tracking error
-
If you turn off the air conditioner when the LED is flickering, the LED is also turned off.: On : Flickering : Off
-
If you re-operate the air conditioner, it operates normally at first, then detect an error again.
Error of indoor unit: Displayed on the
indoor unit regardless of operation
Samsung Electronics12
■ LED Display(cont.)
Troubleshooting
Indicators
Concealed Type
Abnormal conditions
Blue
Red
Operating
Standard Type
1. 2nd detection of high temperature COND
2. 2nd detection of high temperature
DISCHARGE
Displayed on appropriate indoor
unit which is operating
Displayed on outdoor unit
3. Error of reverse phase
Error of float switch
Error of setting option switches for optional
accessories
EEPROM error
EEPROM option error
-
If you turn off the air conditioner when the LED is flickering, the LED is also turned off.: On : Flickering : Off
-
If you re-operate the air conditioner, it operates normally at first, then detect an error again.
13Samsung Electronics
4-2 Outdoor Unit
If an error occurs during the operation, it is displayed on the outdoor unit PCB.
Display
Explanation
High temperature of Discharge (Protection control)
High temperature of outdoor heat exchanger (Protection control)
COMP DOWN to protect being frozen
Error of momentary power failure (disappears when the unit is Off/On)
Error of OUT TEMP sensor (OPEN/SHORT)
Error of temperature sensor in outdoor heat exchanger (OPEN/SHORT)
Error of Discharge TEMP sensor (OPEN/SHORT)
System Down caused by communication error after completion of tracking
Mismatching of the indoor unit numbers set with those
communicated after completion of tracking
Error of float switch in indoor unit
Error of setting option switches for optional accessories
Remark
Error about protection
control of outdoor unit
Errors about outdoor unit
sensor (OPEN/SHORT)
Detection during the
operation of indoor unit
(Sensing and sending errors
into the communication data)
Communication and
indoor unit errors
Self-diagnosis of indoor and
outdoor unit (x:indoor unit
address)
x
x
Flicker
Flicker
K1, K2, K3, K4,
K5 Flicker
The order of priority : E1 → E2 → E4 → E5 → P0 → P1 → P5 → P6 → t1 → t2 → t3 → tu → to → G4 → G5 → E3 → qx → rx → vx →
The order of priority : - In case that the same error displays from multi-indoor units, the one having the faster address has the priority.
OPEN/SHORT error of room sensor in indoor unit
OPEN/SHORT error of eva in sensor in indoor unit
EEPROM option error
x
Error of fan starting
x
Open error of electronic expansion valve in outdoor unit
(Detected once or more times)
Close error of electronic expansion valve in outdoor unit
(Detected once or more times)
Below -5°C when cooling (Outdoor temperature)
Over 30°C when heating (Outdoor temperature)
K1, K2, K3, K4, K5
Displays of operating status
Samsung Electronics14