Stop operation of the air conditioner and remove the power cord before repairing the unit.
2-1 Indoor Unit
NoPartsProcedureRemark
1Electrical
Part
1) Open the grille by pressing 3 position.
(center and both side)
2) Detach the air inlet grille.
3) Open the cover of component electrical
box by removing 3 screws.
(center and both side)
5Samsung Electronics
Disassembly and Reassembly
NoPartsProcedureRemark
2Fan & Motor
1) Detach the screw and untie earth
wire of motor.
2) Disconnect of housing of motor wire.
3) Disconnect the capacitor wire.
Samsung Electronics6
Disassembly and Reassembly
NoPartsProcedureRemark
4) Loosen the guard safety by removing
6 screws.
5) Detach the upper case of fan. (2EA)
6) Loosen the 4 screws what is fix the motor.
7) Detach the fan and motor assembly.
7Samsung Electronics
Disassembly and Reassembly
NoPartsProcedureRemark
8) Loosen the set fixing bolts.
(with a M3 wrench)
9) Detach the fan.
3Drain Pan
1) Disconnect the display pcb wire as shown
in picture. (white housing)
2) Disconnect the step motor wire as shown
in picture. (blue housing)
3) Disassemble the hanger bracket by
removing the 1 screw.
Samsung Electronics8
Disassembly and Reassembly
NoPartsProcedureRemark
4) Loosen the 3 screws of front side.
5) Disassemble the assembly front
cover part.
6) Disconnect the step motor wire as
shown in picture.
7) Detach the wire clamp fixed in base part.
8) Detach the front cover assembly
completely.
9Samsung Electronics
Disassembly and Reassembly
NoPartsProcedureRemark
9) Loosen the screw what is fix with base
part and drain pan. (upper side:2EA)
10) Loosen the screw what is fix with base
part and drain pan.
(lower side:2EA)
11) Detach the drain pan completely.
Samsung Electronics10
Disassembly and Reassembly
NoPartsProcedureRemark
4Evaporator
1) Disconnect the thermistor wire as
shown in picture. (white housing)
2) Loosen the 2 screws shown in picture.
3) Loosen the 2 screws shown in picture
and remove plastic part. (white)
4) Loosen the 2 screws shown in picture
and remove steel bracket.
5) Disassemble the 4 screws steel plate in
rear side of the unit.
11Samsung Electronics
Disassembly and Reassembly
NoPartsProcedureRemark
6) Loosen the 2 screws as shown in picture.
7) Detach the plastic cover as shown in
picture.
8) Detach the evaporator assembly.
Samsung Electronics12
Disassembly and Reassembly
NoPartsProcedureRemark
5
Stepping Motor
1) Loosen the 4 screws in rear side of front
cover assembly as shown in picture.
2) Loosen the 2 screws as shown in picture.
3) Disassemble the blade and stepping
motor assembly and remove the 2 screws
stepping motor.
6
Display PCB
1) Loosen the 3 screws in rear side of front
cover assembly as shown in picture.
2) Disassemble display PCB assembly
and disconnect wire.
3) Disassemble the display PCB.
13Samsung Electronics
2-2 Outdoor Unit
NoPartsProcedureRemark
1
2
Cabinet
Fan Motor
&
Propeller Fan
1) Turn off the unit and remove the power
cable.
2) Detach the top cover.
3) Detach the control box cover.
4) Unplug the ass'y cable.
5) Detach the cabi-side.
6) Detach the cabi-front.
● Cautions
When you assemble the parts, check if the
each parts and component electric box are
fixed firmly.
1) Loosen the indicating bolt screw.
2) Disassemble the propeller fan.
Samsung Electronics14
3. Refrigerating Cycle Diagram
Indoor UnitOutdoor Unit
❋
Allowable pipe length : Max. 30m
❋
Allowable drop distance : Max. 15m
2-way valve
Capillary tube
Heat
exchanger
(Evaporator)
Cooling
Heating
Gas leak check point
Liquid pipe
Gas pipe
3-way valve
FilterFilter
Expansion
valve
AccumulatorMuffler
Compressor
Heat
exchanger
(Condensor)
4-way valve
15Samsung Electronics
4. Set Up the Model Option
4-1 Setting Option Setup Method
Option No. :
Step 1 : Enter the Option Setup mode.
st
1
Take out the batteries of remote control.
nd
2
Press the temperature button simultaneously and
insert the battery again.
rd
3
Make sure the remocon display shown as .
Step 2 : Enter the Option Setup mode and select your option according to the following procedure.
1
The default value is .
Otherwise, push the button to .
Every time you push the button, the display panel reads or
repeatedly.
1
2
3
4
5
6
2
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
3
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
repeatedly.
repeatedly.
4
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
repeatedly.
✳ Setting is not required if you must
a value which has a default.
5
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
6
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
repeatedly.
repeatedly.
Samsung Electronics16
7
8
9
10
11
12
7
The default value is .
Otherwise, push the button to .
Every time you push the button, the display panel reads or
repeatedly.
8
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
9
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
10
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
Set Up the Model Option
repeatedly.
repeatedly.
repeatedly.
11
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
✳ Setting is not required if you must
a value which has a default.
12
Push the button to set the display panel to .
Every time you push the button, the display panel reads
. . .
Step 3 : Upon completion of the selection, check you made right selections.
Press the Mode Selection key,to set the display part to and check the display part.
The display part shows.
Press the Mode Selection key,to set the display part to and check the display part.
The display part shows.
Step 4 : Pressthe ON/OFF button.
When pressing the operation ON/OFF key with the direction of remote controller for unit, the sound “Ding” or “Diriring” is
heard and the OPERATION LED lamp is flickering at the same time, then the input of option is completed.
(If the diriring sound isn’t heard, try again pressing the ON/OFF button.)
Step 5 : Unit operation test-run
First, Remove the battery from the remote controller.
Second, Re-insert the battery into the remote controller.
Third, Press ON/OFF button() with the direction of remote controller for set.
Compressor stop due to frozen evaporator of indoor unit
(every times)
Error of momentary power failure(Disappears when the
unit is Off/On)
During the defrosting operation
(Heat pump model only)
Outdoor temperature SENSOR ERROR
(OPEN/SHORT)
Condensor temperature SENSOR ERROR
(OPEN/SHORT)
Discharge temperature SENSOR ERROR
(OPEN/SHORT)
DescriptionRemarks
Outdoor protection control
related error
Outdoor sensor related error 1
- The whole outdoor unit sensor
error detection should be done
during the indoor unit operation
only.(But ,transferring to communication data by sensing is
allowed at any time.)
10
11
12
13
14
15
16
17
or
flickering
Display priority order at overlapping error : E1→E4→P0 →P1 →P5→P6 →t1→t2→t3 →tu →to →G4→G5→E3→qx→rx→K1, 2, 3, 4, 5
- If several indoor unit report the same error, the fast address is priority.
After tracking completion, system down due to
communication error
To mismatch the indoor unit number communicated
with setting indoor unit after 5 times tracking
completion
Floating switch error from indoor unit
Indoor unit room temperature sensor open/short error
Indoor unit evaporator temperature sensor
open/short error
Outdoor unit electronic valve opening error
(Detecting over 1 time)
Outdoor unit electronic valve closing error
(Detecting over I time)
(below -5˚C at cooling),
(over 30˚C at heating)
Communication and indoor unit
error related
Indoor/Outdoor unit self
diagnosis related
Operation status display
23Samsung Electronics
5-3 Sequence for trouble diagnosis
5-3-1 Outdoor temperature sensor(OPEN/SHORT)
Outdoor unit display
Indoor unit display
How to determine
Reason of error
Is not separated the out
temperature sensor connector from
To measure the resistance value
between two terminals after
separating the out temperature sensor
connector from PCB
At this time, Is not largely
deviate the resistance value from side
Er → t1 (Outdoor temperature sensor OPEN/SHORT error)
(Operation) (Timer) (Airflow) (Filter)
Disconnection and short of outdoor temperature sensor
Disconnection or leak of applied sensor
No
PCB?(CN41)
Yes
Yes
table value?
Reoperation
after connection to
connector PCB
No
Temperature
(˚C)
70
60
50
40
30
20
10
0
-10
Resistance
(kΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Yes
To check the out temperature
sensor is normal or not by use of
out data display part
➞ To check the temperature data is
normal or not after pressing K4 3 times.
At this time, is occurred the difference
between the out temperature and data?
Yes
Reoperation after PCB exchange
Outdoor unit thermistor
self badness (exchange)
No
PCB and sensor are normal.
To perform the test
operation by use of K2
Samsung Electronics24
5-3-2 Outdoor heat exchanger temperature sensor error(OPEN/SHORT)
Control Specification & Troubleshooting
Outdoor unit display
Indoor unit display
How to determine
Reason of error
Is not separated the out
heat exchanger temperature sensor
connector from PCB?(CN41)
To measure the resistance value
between two terminals after separating
the out heat exchanger temperature
sensor connector from PCB
At this time, Is not largely
deviate the resistance value from side
Er → t2 (Outdoor heat exchanger temperature sensor error(OPEN/SHORT)
(Operation) (Timer) (Airflow) (Filter)
Disconnection and short of outdoor heat exchanger temperature sensor
Disconnection or leak of Applied sensor
No
Yes
Yes
No
table value?
Reoperation
after connection to
connector PCB
Temperature
(˚C)
70
60
50
40
30
20
10
0
-10
Resistance
(kΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Yes
To check the out temperature
sensor is normal or not by use of
out data display part
➞ To check the temperature data is
normal or not after pressing K4 2 times.
At this time, is occurred the difference
between the out temperature and data?
Yes
Reoperation after PCB exchange
Outdoor heat exchanger
temperature self badness
(exchange)
No
PCB and sensor are
normal.
25Samsung Electronics
Control Specification & Troubleshooting
5-3-3 Outdoor discharge temperature sensor error(OPEN/SHORT)
Outdoor unit display
Er → t3 (Outdoor discharge temperature sensor OPEN/SHORT error)
Indoor unit display
How to determine
Reason of error
Is not separated the outdoor
discharge temperature sensor connector
from PCB?(CN42)
To measure the resistance value
between two terminals after separating
the outdoor discharge temperature
sensor connector from PCB
At this time, Is not largely
deviate the resistance value from
side table value?
To check the out temperature
sensor is normal or not by use of out
data display part
➞ To check the temperature data is
normal or not after pressing K4 1 times.
At this time, is occurred the difference
between the out temperature and data?
Disconnection and short of outdoor heat exchanger temperature sensor
Disconnection or leak of Applied sensor
Yes
Yes
Yes
Yes
(Operation) (Timer) (Airflow) (Filter)
No
Re-operation
after connection to
connector PCB
No
Outdoor heat exchanger
temperature self badness
(exchange)
No
PCB and sensor are normal.
To perform the test
operation by use of K2
Temperature
(˚C)
130
120
100
80
60
25
20
10
0
-10
Resistance
(kΩ)
8.9
11.2
18.5
32
59
200
242
362
553
Re-operation after PCB exchange
Samsung Electronics26
5-3-4 Communication error during the operation
+0.7V
-0.7V
Good
Bad
Control Specification & Troubleshooting
Outdoor unit display
Indoor unit display
Disconnection
and short of
communication lines
Reason of error
To check the display after
pressing the reset key on outdoor PCB
When tracking, is there any
indoor answer from display part?
To measure the 2 lines of outdoor side
by scope after removing the
communication line connecting from
outdoor unit to indoor unit.
Er → E1 (Communication error during the operation)
(Operation) (Timer) (Airflow) (Filter)
Disconnection and short of outdoor heat exchanger temperature sensor
Disconnection or leak of Applied sensor
Multi type
After 2 minutes, to check if PCB address
setting of indoor unit displayed th
No
Yes
communication error among indoor units is
overlapped or not.
(If the indoor unit address is overlapped, the
communication error is occurred.)
- In this case, the communication error is
occurred to over two indoor units set
wrong.
If address is no fault,
to exchange the indoor unit PCB after
communication line check.
between lines spherical wave over DC ±0.7V
At this time, is the voltage
like below figure?
Yes
After connecting again the communication
line connecting from outdoor unit to indoor unit,
to remove the communication
connector on indoor unit PCB, and find the
indoor unit preventing communication
through connecting the communication
connectors each by each, and then exchange
the indoor unit PCB after line check.
No
To exchange PCB after checking
the outdoor unit communication line
and connector
27Samsung Electronics
Control Specification & Troubleshooting
5-3-5 Communication error between indoor and outdoor after initial power input.
Outdoor unit display
Indoor unit display
How to determine
Reason of error
To check the setting value of
indoor unit installation number setting
switch of outdoor PCB and actual indoor unit
installation numbers
Is equal indoor unit actual
installation number and installation
number setting switch?
To press the reset key K3 of outdoor unit
PCB and check the display to check the
number of indoor units answering to the
Er → E2 (Tracking error)
(Operation) (Timer) (Airflow) (Filter)
Mismatching the communicating indoor unit and setting switch indoor numbers When outdoor tracking
Communication error between the indoor unit and outdoor unit, and installation number switch
setting miss
Yes
tracking
If the indoor unit number installed is one, set the
outdoor unit switch forward to "0", "1"
➞ "0" and "1" spell the connection of an indoor unit.
No
After setting the indoor unit installation setting
number switch correctly, Re-perform the
tracking by pressing the reset key K3 of
outdoor unit PCB
When tracking, is there any
indoor answer from display part?
Yes
To measure the 2 lines of outdoor unit side by
use of scope after removing the communication
line connecting from outdoor unit to indoor unit
At this time, is the voltage
between lines spherical wave over
DC ±0.7V ?
Yes
After connecting again the communication line
connecting from outdoor unit to indoor unit,
to check this communication is reverse or not,
and if there is no fault, to find the indoor unit
preventing communication through connecting
indoor units each by each, and then
exchange the indoor unit PCB after line check
No
Multi type
After 2 minutes, to check if PCB address setting
of indoor unit displayed the communication error
among indoor units is overlapped or not .
(If the indoor unit address is overlapped, the
communication error is occurred.)
- In this case, the communication error is
occurred to over two indoor units set wrong
If address is no fault,
to exchange the indoor unit PCB after
communication line check.
Samsung Electronics28
5-3-6 Indoor floating switching error
Control Specification & Troubleshooting
Outdoor unit display
Er → E3 (Indoor floating switching error )
Indoor unit display
How to determine
Reason of error
Is the indoor unit
error occurred cassette type?
Is the resistance value ∞
when measuring the resistance value
of two terminal after taking out the floating
switch connector connected to indoor
unit PCB? (Open status)
The status continues over 1 minute that indoor unit floating switch is opened.
The rising of water level of drain pan due to the disorder of indoor unit drain pump,
the badness of detection sensor
Yes
Yes
(Operation) (Timer) (Airflow) (Filter)
No
Refer to the drain pump
option in the next page.
No
To re-assembly the floating switch
connector and perform the reset of
outdoor power(Required the reset of
indoor unit power)
Is the same error occurred?
No
Is much the water of drain pan ?
Yes
To reset the indoor unit power
and check the drain pump operation
Is operated the drain pump?
Yes
Is lowing the water level?
Yes
Normal operation
To exchange the indoor unit PCB
No
No
Is the terminal voltage
of drain pump PCB about
No
To exchange the drain pump
To exchange the drain pump
Yes
Normal operation
To determine the floating switch
bad To reset the indoor unit
power after exchange
No
AC 220V?
Yes
To exchange the indoor unit PCB
❋ Note : E3 error should be released when
indoor unit power is reset.
29Samsung Electronics
14
7
43
37
29
4
23
18
6
41
40
36
34
32
1
38
19
20
16
24
42
13
15
39
30
26
28
27
3
25
33
44
11 12
22
21
17
8
31
35
2
5
9 10
45
45-6
45-1
45-2
45-8
45-7
45-3
45-4
45-5
6. Exploded Views and Parts List
6-1 Indoor Unit
You can search for the updated part code
number through the ITSELF.
Use this page to keep any special servicing information. (Service Bulletin, etc.)
If only parts number changes, Just change parts number directly on parts list.
And if you need more information, please see the service website.
By Samsung Electronics Co., Ltd.
All rights reserved.
This manual may not, in whole or in part, be
copied, photocopied, reproduced, translated, or
converted to any electronic or machine readable
from without prior written permission of
Samsung Electronics Co., Ltd.
ELECTRONICS
This Service Manual is a property of Samsung Electronics Co., Ltd.
Any unauthorized use of Manual can be punished under applicable
International and/or domestic law.