SAMSUNG KFH28PV20K_KLM.GR017.1.16 Service Manual

PACKAGED AIR CONDITIONER

INDOOR UNIT

OUTDOOR UNIT

KFH28PV2

KRH28PV2

SERVICE Manual

AIR CONDITIONER

 

CONTENTS

1.

Precautions

2.

Product Specifications

3.

Operating Instructions and

 

 

Installation

4.

Disassembly and Reassembly

5.

Troubleshooting

6.

Exploded Views and Parts List

7.

Block Diagrams

8.

PCB Diagrams

9.

Wiring Diagrams

10.

Schematic Diagrams

©Samsung Electronics Co., Ltd. MAR. 1999. Printed in Korea.

Code No. DB81-00071A(1)

1. Precautions

1)Turn off the the power.

Be sure to turn off the power before attempting to repair the unit such as the disassembly of the unit.

2)Be careful of electric shock

When checking the circuit with the power connected in unavoidable circumstances, take special care not to touch the live parts. There is a danger of electric shock.

3)Use of appropriate parts

Be sure to use the genuine parts of the relevant model when it is necessary to replace parts. (Replace parts instead of repairing with regard to the malfunctioning of electric contact areas. Never attempt to modify the unit. It is extremely dangerous for the consumer to attempt to repair the unit on his(her) own.)

4)Use of proper tools

Use appropriate tools for repair, and use measuring equipment after accurate calibration. Using worn tools may result in problems, including poor contact and poor connection.

5)Avoid damage to electric wire or electric cord.

Check the electric cord or electric wire for any damage during repair.

Be sure to replace it if damaged.

6)Avoid intermediate connection of the electric cord.

Never attempt to make an intermediate connection by cutting the middle area of the electric cord or make a connection to the power receptacle as it is very dangerous, causing problems or fire.

7)Checking of insulation

Be sure to check the insulation resistance after completion of the assembly work.

(Check whether the insulation resistance of the electric wire and grounding terminal is over 30MΩ by using the insulation resistance tester, and then connect the power source.)

8)Checking of grounding

Check the grounding condition, and perform repair if poorly grounded.

9)Checking of installation condition

Check the installation condition of the unit, and perform repair if there is any defective area.

If the unit remains in an unstable installing condition, install it at a new site.

10)Be careful of children

As the repair of the unit involves a lot of dangerous elements, do not allow children to approach nearby during repair work.

Cleaning

Turn off the sub power switch separately installed.

No connection with the power receptacle

Upon completion of the repair, clean the air conditioner and surrounding area, and

inform the customer of completion of the repair.

1-1

M E M O

1-2

2. Product Specifications

2-1 Table

 

 

 

 

 

 

 

Model

 

KFH28PV2

Item

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Size

Indoor unit

 

 

Unit

Width x Height x Depth

mm

500 x 1835 x 330

 

 

 

 

 

 

 

 

Packed

Width x Height x Depth

mm

574 x 1945 x 409

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

Unit

Width x Height x Depth

mm

880 x 790 x 310

 

 

 

 

 

 

 

 

 

 

 

Packed

Width x Height x Depth

mm

1023 x 851 x 413

 

 

 

 

 

 

Piping

 

 

Packed

Width x Height x Depth

mm

640 x 130 x 640

 

 

 

 

 

 

 

 

 

Weight

Indoor unit

 

 

 

Unit

 

kg

42

 

 

 

Packed

 

kg

49

 

 

 

 

 

 

 

Outdoor unit

 

 

Unit

 

kg

67

 

 

 

 

 

 

 

 

 

 

Packed

 

kg

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Piping

 

 

Packed

 

kg

12

Electric

1. Cooling capacity/Heating Capacity

 

BTU/h

25,800 / 29,800

 

 

 

 

 

 

 

characteristics

2. Power consumption(Cooling/Heating)

 

W

2,700 / 2.900

 

3. Current consuption(Cooling/Heating)

 

A

12.5 / 13.5

 

5. Noise

 

Indoor unit

Turbo

dB

50 / 48

 

(Cooling/

 

 

 

High

dB

48

 

Heating)

 

 

 

Medium

dB

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

dB

43

 

 

 

 

 

Outdoor unit

 

dB

59

 

 

 

 

 

 

 

 

Indoor unit

1. Evaporator

 

 

Construction

Row x Step

3 x 26

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin

 

WAVE 1.4

 

 

 

 

 

 

 

Capillary tube

 

ø1.3 x L x 4

 

2. Blower motor

 

 

No. of polarities

 

6P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacitor

 

450VAC 4.5µF

 

 

 

 

 

 

 

RPM

Turbo

750

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

650

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Medium

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low

550

 

 

 

 

 

 

 

 

 

3. Blower

 

 

Type

 

SIROCCO

 

4. Motor swing

 

 

 

 

220V/3W

 

5. Fuse

 

 

 

V/A

250V 3.15A

Outdoor unit

1. Condenser

 

 

Construction

Row x Step

2 x 30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fin

 

WAVE 1.7

 

2. Refrigerant volume

 

 

R-22

g

2,500

 

3. Compressor

 

 

Maker

 

COPELAND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

ZR34K3-PFJ

 

 

 

 

 

 

 

Type

 

SCROLL

 

 

 

 

 

 

 

Capacitor

 

450VAC 50µF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OLP

 

-

 

 

 

 

 

 

 

 

 

4. Fan motor

 

 

No. of polarities

 

6P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacitor

 

450VAC 4.0µF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RPM

 

840

 

 

 

 

 

 

 

 

 

5. Fan

 

 

Type

 

PROPELLER

 

6. Service v/v

 

 

High pressure side

 

3/8 inch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low pressure side

 

5/8 inch

 

 

 

 

 

 

 

 

 

 

2-1

2-2 Dimensions

unit : mm

Indoor Unit

Outdoor Unit

330

2-2

SAMSUNG KFH28PV20K_KLM.GR017.1.16 Service Manual

3. Operating Instructions and Installation

3-1 Operating Instructions

3-1-1 Control System Chart

Operation

 

 

Main switch operation

 

Auto, Cool, Dry, Fan, Heat operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote control operation

 

Turbo, Mild, Auto, Cool, Dry, Fan, Heat, Timer operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation selector mode

 

Auto mode

 

 

 

 

Cool mode

Dry mode

Fan mode

Heat mode

In this mode, operation mode(COOL, HEAT) is selected automatically by room temperature of initial operation

Chaos output step fan motor control (Cooling:NATURAL, Heating:AUTO)

Indoor temperature control according to the set temperature.

Decide the dry cycle by the difference in room temperature and set temperature.

Operation of the indoor fan motor only.

Indoor temperature control according to the set temperature

Fan speed selector mode

 

 

Manual 3-step

 

High, Medium, Low

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Natural

 

Automatic decision of High, Medium, and Low step by chaos operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto

 

Automatic decision of High, Medium, and Low step by chaos operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow selector mode

 

 

Right and left turn

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UP and Down Turn

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timer operation mode

 

 

ON time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Convenience function

 

 

Turbo opertion

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mild operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q.timer

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Self-diagnosis function

 

 

“E1”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“E2”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“E5”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“E6”

 

 

 

 

 

 

 

 

 

 

Only use by remote control.

Continuously operating compressor & powerful operating fan motor(30 minutes). In case of heating operation, prevention against cold wind function is given priority before turbo operation. (Cooling:TURBO, Heating:HIGH)

Set off after opertion for one hour in medium mode, and two hours in low mode.

Reserve function which is off after on time of 30 minutes, 1,2,3, and 5 hours.

Displayed at the time of indoor temperature sensor open or short.

Displayed when the panel shutter opening/closing is not sensed.

Displayed at the time of EVAP. Sensor open or short. (Heating mode)

Displayed at the time of COND. Sensor open or short. (Heating mode)

3-1

Operating Instructions and Installation

 

 

 

 

 

 

 

 

 

VFD display function

 

 

Selection of operation mode

 

Auto, Cool, Dry, Fan Heat Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selection of fan speed

 

Auto, natural, high, medium, and low fan speed Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Current temperature

 

Temperature display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan speed diagram

 

Turbo, high, medium, and low airflow Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timer function

 

Timer Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Convenience function

 

Timer, turbo lamp, mild Dispaly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow function

 

Up/Down, Left/Right Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Others

 

CHECK Display, Operation Display, Defrost Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-2

Operating Instructions and Installation

3-1-2 Main Controller Function

3-1-2(a) Auto Operation

1. In this mode, operation mode(COOL, HEAT) is selected automatically by the room temperature of initial operation.

Room Temp.

Operation Type

 

 

Tr ³ 21˚C + DT

Cool operation (Set Temp.:24˚C + DT)

 

 

Tr < 21˚C + DT

Heat operation (Set Temp.:22˚C + DT)

 

 

DT=-1˚C, -2˚C, 0˚C, +1˚C, +2˚C

DT is controlled by setting temperature TEMP. SET Key of remote controller.

2. In Auto mode, the optimum fan speed is selected automatically and cannot be changed. · Set the "Auto" for heating.

· Set the "NATURAL" for cooling.

3-1-2(b) Cool Operation

1.The compressor is automatically turned on/off by the difference between the current temperature and desired temperature.

2.By selecting the fan speed , the operation of "low", "medium", "high", "natural", "auto" mode is selected.

3.The compressor is turned on/off by the change of the current temperature.

The compressor is turned off when the current temperature is equal to the desired temperature.

The compressor is turned on when the current temperature is +1˚C of the desired temperature.

4.Desired temperature setting range : 18˚C ~ 30˚C it can be changed by the unit of 1˚C.

5.Three minutes delay operation of the compressor.

ON

 

 

 

 

 

• Three minutes delay setting condition

 

 

 

 

 

OFF

 

 

 

1

After power reset

 

 

 

 

 

 

 

 

 

On again after compressor off

 

2

 

 

 

 

 

 

 

 

Three minutes delay

3-1-2(c) Heat Operation

1.The compressor is automatically turned on/off by the difference between the current temperature and desired temperature.

2.By selecting the fan speed , the operation of "low", "medium", "high", "auto" mode is selected.

3.The compressor is turned on/off by the change of the current temperature.

The compressor is turned off when the current temperature is +1˚C of the desired temperature.

The compressor is turned on when the current temperature is -1˚C of the desired temperature.

4.Desired temperature setting range : 16˚C ~ 30˚C it can be changed by the unit of 1˚C.

5.Delay operation of the compressor.

Delay setting condition

ON

 

 

 

 

 

 

1

After power reset or shut down

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

compressor by control the desired

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature:3minutes.

 

 

 

 

 

 

After deice:40sec.

 

 

 

40sec-3minutes.

2

 

 

 

 

 

 

3

After shut down compressor or 4-way

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

valve:1/2minutes

3-3

Operating Instructions and Installation

3-1-2(d) Turbo Operation

Indoor fan speed

Compressor control

set fan speed

turbo fan speed(high speed)

set fan speed

(note)

opertion mode of (note)area

 

 

Time,(t)

start of turbo

end of turbo

operation

operation

Operating condition

1.The turbo operation is available only in auto, cool, mild and heat mode.

2.The turbo operation is performed for 30 minutes when the turbo button is pressed. (including three minutes delay time)

3.Control of the indoor fan motor and compressor during turbo operation •Indoor fan motor = Heating High

Cooling Turbo(fan speed one step higher than “high”) •Compressor : continued on regardless of room temperature.

4.After an elapse of 30 minutes from the start of turbo operaiton, the turbo operation is ended, and the unit returns to the previous mode.

5.When you press the turbo key again during the turbo operation, the turbo operation mode is canceled, and the unit returns to the previous mode.

3-1-2(e) Fan Speed Auto

1. Cooling operation

Desired temperature +5

 

Desired temperature +4

Desired temperature +4˚C

High speed area

 

Desired temperature +3

 

Medium speed area

 

Desired temperature +2

Desired temperature +2˚C

Medium speed area

 

Desired temperature +1

 

Low speed area

The indoor fan motor speed is

Low speed area

automatically controlled

Desired temperature +0

 

according to the difference

 

between the indoor temperature

2. Heating operation

and the desired temperature.

Desired temperature +1˚C

Desired temperature +0˚C

Desired temperature -1˚C

Desired temperature -2˚C

Low speed area

 

Medium speed area

Desired temperature -1˚C

 

High speed area

Desired temperature -3˚C

 

3-4

Operating Instructions and Installation

3-1-2(f)

Dry Operation

 

 

 

 

 

 

 

 

 

 

Room temperature[˚C]

 

 

 

 

 

 

 

 

 

Ts+4

 

 

A - MODE

 

 

 

A - MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B - MODE

 

 

Ts+3

 

 

 

 

 

 

 

 

 

Ts+2

 

 

B - MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C - MODE

 

 

Ts+1

 

 

C - MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature down

 

Temperature up

 

 

 

Ts=desired temperature

 

 

 

 

 

 

 

1. On/off time by dry operation mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

Operating mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A - MODE

 

 

B - MODE

C - MODE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON time

 

6 min.

 

 

5 min

3 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF time

 

4 min

 

 

5 min.

6 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The indoor fan motor operation is fixed at a Low Speed

2.The dry operation mode is determined depending upon the difference between the indoor temperature (Ta) and desired temperature (Ts).

3.The unit is operated with the compressor on, and an indoor fan motor at a Low Speed for an initial six minutes (including a three-minute delay) after setting up the dry operation mode.

3-5

Operating Instructions and Installation

3-1-3 Key Types and Functions

3-1-3(a) Panel Key Types and Functions

KEY NAME

KEY OPERATING FUNCTION

KEY TYPE

 

 

 

 

Start and end of operation

TACT

ON/OFF

- ON one time = operation start, ON again = operation end

 

 

- No continued operation

 

 

 

 

 

Change of the operation mode

TACT

Mode selection

-Each time the button is pressed (ON), the mode is changed in the following order ;

 

"COOL DRY FAN HEAT AUTO COOL" (standard = AUTO)

 

 

 

 

-No continued operation

 

 

 

 

 

Setting of the indoor fan motor speed.

TACT

Fan speed

-Eacn time the button is pressed (ON), the mode is changed in the following order;

 

selection

COOL:"LOW MEDIUM HIGH NATURAL AUTO LOW" (standard = AUTO)

 

 

HEAT:"LOW MEDIUM HIGH AUTO LOW" (standard = AUTO)

 

 

 

 

 

Increase the desired temperature display.

JOG SHUTTLE

Temperature

-When turning the jog dial clock-wise, it displays the desired temperature and

DIAL

holding the jog dial continuously, the desired temperature is increased by the unit of 1˚C

 

setting (up)

 

(COOL:18˚C 30˚C, HEAT:16˚C 30˚C)

 

 

 

 

-One short, and continued operation.

 

 

 

 

 

Decrease the desired temperature display.

JOG SHUTTLE

Temperature

-When turning the jog dial counter clock-wise, it displays the desired temperature and

DIAL

setting

holding the jog dial continuously, the desired temperature is decreased by the unit of 1˚C

 

(down)

(COOL:30°C 18°C, HEAT:30°C 16°C)

 

 

-One short, and continued operation.

 

 

 

 

3-6

Operating Instructions and Installation

3-1-3(b) V.F. Display Operating Spec

 

 

 

 

DISPLAY

 

 

 

 

OPERATING SPEC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• When the compressor is activated (outdoor power relay on) : ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• When the compressor is stopped (outdoor power relay off) :OFF

 

 

 

OPERATING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• During the defrost operation : ON

 

 

 

 

DEFROST

 

 

 

• The defrost operation ended : OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT

 

 

 

COOL

 

 

 

Display the selected "operation selection mode"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUTO, COOL, DRY, FAN, HEAT

DRY

 

 

AUTO

 

 

 

FAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMP.

 

 

 

 

 

 

 

 

 

˚C

When the ON/OFF is ON, the indoor temperature is displayed.

 

SET TEMP.

 

 

 

 

 

 

 

 

 

 

 

When changing the desired temperature, the indoor room temperature is displayed

 

 

 

 

 

 

 

 

 

 

 

 

 

after displaying the desired for 5 senconds

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CHECK

 

 

 

 

 

 

 

 

 

 

 

• The trouble is occured by self - diagnosis funtion :ON

 

 

 

 

 

 

 

 

 

 

 

 

 

• The troubleshooting is completed : OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TIMER

 

 

 

• During reservation : ON

 

 

 

 

 

 

 

 

 

 

 

• Reservation ended or canceled : OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Display the selected "fan speed selection mode"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW, MEDIUM, HIGH, NATURAL, AUTO

 

 

AUTO

 

 

 

 

NATURAL

Display operation of the indoor fan motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW, MEDIUM, HIGH, TURBO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• During turbo operation : ON

 

 

 

 

 

TURBO

 

 

 

 

• Turbo operation ended or canceled : OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• During mild operation : ON

 

 

 

 

 

 

MILD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Mild operation ended or canceled : OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

• When [the right and left turn] is on by the remote control, it displays

 

SWING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR

 

 

 

 

 

 

 

 

 

 

 

When [the up and down turn] is on by the remote control, it displays

 

SWING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-7

3-2 Installationn

3-2-1 Selection of Installation Place

3-2-1(a) Indoor Unit

Install the unit at a place close to the wall facing the outside as it is necessary to perform piping connection with the outdoor unit.

-It is effective to install the unit at a window side to ensure uniform distribution of indoor temperature.

Install the unit at a place where there is no obstacle against the wind around the air inlet and air outlet.

Install the unit horizontally at a stable, rigid place.

(When installing the unit at a place subjected to vibration, noise may occur.)

Avoid a place near the door which is frequented by people.

Avoid a place subject to direct sunlight.

3-2-1(b) Outdoor Unit

place free from the risk of combustible gas leakage.

place which can bear the weight of the unit.

place which can bear the fixing strength of the outdoor unit.

Avoid a place subject to oil(including machine oil).

Avoid a saline place

Avoid a place subject to sulfide gas(hot spring zone).

(When installing the unit at such special environmental conditions, it may cause machine trouble. When it is unavoidable to use such places. It requires special maintenance.)

A place where the discharge air and noise of the outdoor unit do not disturb the neighborhood.

(Take special care not to cause any inconvenience to your neighbors when installing the unit on the borderline with your neighborhood.)

A place where strong wind does not head against the air outlet of the outdoor unit.

(If a strong wind heads directly against the air outlet at the time of cool operation, a safety device can be operated.)

Do not install the outdoor unit at an unstable place such as outer wall of an apartment or building.

The outdoor unit may fall down, causing severe personal or property damage or loss.

If there is any unavoidable reason to install the unit at such a place, take the following measures against the wind;

1.When installing the unit at a roadside concentrated with buildings, install it parallel with the road.

2.Install the unit so that the air outlet faces toward the wall at a place such as rooftop, which may be subjected to strong wind.

Top view

•Good method for using space more efficiency.

Side view

Above 50cm

Above 100cm

Wall

Strong wind

 

 

Roof top

* Be sure to install the outdoor unit with consideration of service space.

Above 10cm

 

Above 50cm

Above 50cm

 

Space for pip-

 

ing and wiring

Space for piping

 

Above 10cm

Above 30cm

and wiring

Above 10cm

 

 

The air inlet faces toward the wall.

The air outlet faces toward the wall.

 

 

 

3-8

Operating Instructions and Installation

3-2-2 Electrical Work

The electrical work should be performed by a specialist qualified for the work.

Use the single phase power supply, and be sure to install the sub power distributing board for exclusive use with the unit(separately purchased by the user).

Avoid octopus-type wiring as it can cause a drop in voltage, thus resulting in poor performance of the automatic control circuit.

Be sure to install the earth leakage circuit breaker (separately purchased by the user).

Be sure to connect the grounding wire.

Electric power spec

 

 

 

Connecting wire & PCB fuse spec

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPEC

 

 

 

TYPE

SPEC

 

 

Power

Single phase 220V-240V~, 50Hz

 

 

Power cable

H07RN-F

3G 2.5mm2

450-750V~

 

 

Sub switch

30 A

 

 

Connecting wire

H07RN-F

5G 1.0mm2

450-750V~

 

 

Fuse

30 A

 

 

 

H05RN-F

2G 0.75mm2

300-500V~

 

 

Electric wire Below 20m

3.5 mm2

 

 

Sensor cable

H05RN-F

2G 0.75mm2

300-500V~

 

 

Allowable voltage

198V ~ 264V

 

 

PCB fuse

50T

250V~, 3.5A

 

 

 

 

 

 

 

 

F2L

250V~, 2A

 

Indoor and Outdoor Connection Wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When connecting the connecting wire between the indoor and outdoor unit, be sure to align the terminal block number with the connecting wire number.

When the connecting wire is not properly connected, it may cause trouble.

Be careful not to allow connecting wires and power lines to get in contact with service valve or the pipe without an insulator.

Color of connecting wire

Model name

No.

1

2

3

4

5

 

 

 

 

 

 

 

 

KRH28PV2

 

BRN

SKY

Thin BRN

BLK

Thin SKY

Outdoor side

Terminal plate

Cable clamp

Cover control

Electric

panel board

Cable cover

Holder cable

Base control

Terminal block

 

Earth

1.Connect the connecting wire to the terminal block and connect the earth wire to the bracket earth.

2.Close the cover control.

3.As following the figure, firmly fix connecting wire with the holder cable.

A

Wire of sensor

B

Earth

C

Power cable

Electrical Wiring

1.Connect it to the terminal board N and L for power supply to the outdoor unit.

In so doing, peel off the end of the power cord by about 5mm, and press the cord to the ring terminal for hooking.

2.Perform the power grounding using the screw for exclusive use with the outdoor unit.

3-9

Operating Instructions and Installation

3-2-3 Installation Method

3-2-3(a) Indoor Unit

This unit is greater in height compared to its width, and thus it may fall down.

Therefore, be sure to fix the unit to the wall and floor surfaces securely to prevent the unit from falling down.

Fixing to the wall

Fix the unit using the fixing holders separately supplied.

Select a direction (right or left) according to a place of being installed.

The fixing holder “B” was decided on a direction (front or rear) according to a condition of being installed.

1.Fix the fixing holder “B” using the screw at a rear side groove.

2.Put the fixing holder “A” on the fixing holder “B”, then fix holders using the nut, washer and bolt to direction you want.

3.Fix the fixing holder “A” to the wall.

3-2-3(b) Outdoor Unit

When using the anchor bolt

1.Fix the unit on a flat, rigid floor using the anchor bolt.

(Anchor bolt : M10 x 4 points - separately purchased)

When using the leg holder of the outdoor unit

1.Insert the foot holder (4EA, optional).

2.Remove the nut fastened to the leg holder, and then insert the leg holder into the hole of the outdoor unit leg.

3.Fix the unit securely with the nut.

Anchor bolt fixing dimensions

Unit:mm

A

B

660 335

Nut

Outdoor unit leg

Leg holder

Foot holder

3-10

Operating Instructions and Installation

3-2-3(c) Installation Procedures

1 Open the inlet grille, and remove the flare nut.

2.Bend the connection pipe to an appropriate length using the spring bender depending upon the installation place.

-Allowable pipe length : Maximum 25m

-Allowable pipe drop distance : Maximum 15m

-Make no more than ten bending points on the pipe

When the pipe length is in excess of the standard pipe length of 5m, add the refrigerant

(R-22) of 50g for each additional 1m.

Caution

If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, the pipe length should be as short as possible (less then 15m).

3.Install the high pressure pipe to the heat exchanger liquid pipe, and the low pressure pipe to the heat exchanger gas pipe respectively using the flare nut, taking care not to cause any leakage of refrigerant.

4.Be sure to insulate the pipe with appropriate insulation material.

5.Insert the drain hose into the drain pipe, and connect them by tying them to the cable tie to prevent any water leakage.

6.After completion of the installation, check the connecting area for any gas leakage.

7.Wind a finish tape when the wiring of the refrigerant pipe, the unit, and the drain piping are completed.

 

Outdoor unit

Indoor unit

checking area

checking area

 

3-11

Operating Instructions and Installation

3-2-3(d) Connection of refrigerant pipe

Flare Processing

1. Cut the pipe using the pipe cutter.

Oblique

Roughness

Burr

2. Insert the flare nut into the pipe, and then perform the flare processing.

Outer Diameter

A

 

 

ø 6.35 mm

1.3

 

 

ø 9.52 mm

1.8

 

 

ø 15.8 mm

2.0

 

 

Pipe Bending

 

1.

Perform bending of the pipe using the bender which has

Spring

 

a specified bending radius.

 

2.

Be sure to take full care to perform bending of the pipe

 

 

successfully at one time. Bending and unbending the pipe

 

 

more than twice makes the bending work increasingly

 

 

 

 

difficult.

3.

You may use the spring inserted into the gas pipe instead

 

 

of the bender to bend the pipe.

4.

When you bend the pipe using the spring, hold the pipe

 

 

with both hands to prevent any distortion, and secure a

 

 

minimum bending radius of more than 100mm.

Tightening of Connection Parts

Align the center of the connection piping, and tighten the flare nut by turning it with hand. Then tighten it again using the spanner in the direction as shown in the figure.

Outer Diameter

Tightening Torque

Final Torque

Remarks

ø 6.35mm

160 kg cm

200kg cm

 

ø 9.52mm

400 kg cm

450 kg cm

 

ø 15.8mm

700 kg cm

750 kg cm

 

3-12