PACKAGED AIR CONDITIONER
INDOOR UNIT |
OUTDOOR UNIT |
KFH28PV2 |
KRH28PV2 |
SERVICE Manual
AIR CONDITIONER |
|
CONTENTS |
1. |
Precautions |
|
2. |
Product Specifications |
|
3. |
Operating Instructions and |
|
|
|
Installation |
4. |
Disassembly and Reassembly |
|
5. |
Troubleshooting |
|
6. |
Exploded Views and Parts List |
|
7. |
Block Diagrams |
|
8. |
PCB Diagrams |
|
9. |
Wiring Diagrams |
|
10. |
Schematic Diagrams |
©Samsung Electronics Co., Ltd. MAR. 1999. Printed in Korea.
Code No. DB81-00071A(1)
1. Precautions
1)Turn off the the power.
Be sure to turn off the power before attempting to repair the unit such as the disassembly of the unit.
2)Be careful of electric shock
When checking the circuit with the power connected in unavoidable circumstances, take special care not to touch the live parts. There is a danger of electric shock.
3)Use of appropriate parts
Be sure to use the genuine parts of the relevant model when it is necessary to replace parts. (Replace parts instead of repairing with regard to the malfunctioning of electric contact areas. Never attempt to modify the unit. It is extremely dangerous for the consumer to attempt to repair the unit on his(her) own.)
4)Use of proper tools
Use appropriate tools for repair, and use measuring equipment after accurate calibration. Using worn tools may result in problems, including poor contact and poor connection.
5)Avoid damage to electric wire or electric cord.
Check the electric cord or electric wire for any damage during repair.
Be sure to replace it if damaged.
6)Avoid intermediate connection of the electric cord.
Never attempt to make an intermediate connection by cutting the middle area of the electric cord or make a connection to the power receptacle as it is very dangerous, causing problems or fire.
7)Checking of insulation
Be sure to check the insulation resistance after completion of the assembly work.
(Check whether the insulation resistance of the electric wire and grounding terminal is over 30MΩ by using the insulation resistance tester, and then connect the power source.)
8)Checking of grounding
Check the grounding condition, and perform repair if poorly grounded.
9)Checking of installation condition
Check the installation condition of the unit, and perform repair if there is any defective area.
If the unit remains in an unstable installing condition, install it at a new site.
10)Be careful of children
As the repair of the unit involves a lot of dangerous elements, do not allow children to approach nearby during repair work.
Cleaning
Turn off the sub power switch separately installed.
No connection with the power receptacle
Upon completion of the repair, clean the air conditioner and surrounding area, and
inform the customer of completion of the repair.
1-1
M E M O
1-2
2. Product Specifications
2-1 Table
|
|
|
|
|
|
|
Model |
|
KFH28PV2 |
Item |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Size |
Indoor unit |
|
|
Unit |
Width x Height x Depth |
mm |
500 x 1835 x 330 |
||
|
|
|
|
|
|
||||
|
|
Packed |
Width x Height x Depth |
mm |
574 x 1945 x 409 |
||||
|
|
|
|
||||||
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
Outdoor unit |
|
|
Unit |
Width x Height x Depth |
mm |
880 x 790 x 310 |
||
|
|
|
|
|
|
|
|
||
|
|
|
Packed |
Width x Height x Depth |
mm |
1023 x 851 x 413 |
|||
|
|
|
|
|
|||||
|
Piping |
|
|
Packed |
Width x Height x Depth |
mm |
640 x 130 x 640 |
||
|
|
|
|
|
|
|
|
|
|
Weight |
Indoor unit |
|
|
|
Unit |
|
kg |
42 |
|
|
|
|
Packed |
|
kg |
49 |
|||
|
|
|
|
|
|
||||
|
Outdoor unit |
|
|
Unit |
|
kg |
67 |
||
|
|
|
|
|
|
|
|
||
|
|
Packed |
|
kg |
75 |
||||
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|||
|
Piping |
|
|
Packed |
|
kg |
12 |
||
Electric |
1. Cooling capacity/Heating Capacity |
|
BTU/h |
25,800 / 29,800 |
|||||
|
|
|
|
|
|
|
|||
characteristics |
2. Power consumption(Cooling/Heating) |
|
W |
2,700 / 2.900 |
|||||
|
3. Current consuption(Cooling/Heating) |
|
A |
12.5 / 13.5 |
|||||
|
5. Noise |
|
Indoor unit |
Turbo |
dB |
50 / 48 |
|||
|
(Cooling/ |
|
|
|
High |
dB |
48 |
||
|
Heating) |
|
|
|
Medium |
dB |
45 |
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low |
dB |
43 |
|
|
|
|
|
Outdoor unit |
|
dB |
59 |
|
|
|
|
|
|
|
|
|
||
Indoor unit |
1. Evaporator |
|
|
Construction |
Row x Step |
3 x 26 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fin |
|
WAVE 1.4 |
|
|
|
|
|
|
|
Capillary tube |
|
ø1.3 x L x 4 |
|
2. Blower motor |
|
|
No. of polarities |
|
6P |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Capacitor |
|
450VAC 4.5µF |
|
|
|
|
|
|
|
RPM |
Turbo |
750 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
High |
650 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Medium |
600 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low |
550 |
|
|
|
|
|
|
|
|
||
|
3. Blower |
|
|
Type |
|
SIROCCO |
|||
|
4. Motor swing |
|
|
|
|
220V/3W |
|||
|
5. Fuse |
|
|
|
V/A |
250V 3.15A |
|||
Outdoor unit |
1. Condenser |
|
|
Construction |
Row x Step |
2 x 30 |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fin |
|
WAVE 1.7 |
|
2. Refrigerant volume |
|
|
R-22 |
g |
2,500 |
|||
|
3. Compressor |
|
|
Maker |
|
COPELAND |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Model |
|
ZR34K3-PFJ |
|
|
|
|
|
|
|
Type |
|
SCROLL |
|
|
|
|
|
|
|
Capacitor |
|
450VAC 50µF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OLP |
|
- |
|
|
|
|
|
|
|
|
||
|
4. Fan motor |
|
|
No. of polarities |
|
6P |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Capacitor |
|
450VAC 4.0µF |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
RPM |
|
840 |
|
|
|
|
|
|
|
|
||
|
5. Fan |
|
|
Type |
|
PROPELLER |
|||
|
6. Service v/v |
|
|
High pressure side |
|
3/8 inch |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low pressure side |
|
5/8 inch |
|
|
|
|
|
|
|
|
|
|
2-1
2-2 Dimensions
unit : mm
Indoor Unit
Outdoor Unit
330
2-2
3. Operating Instructions and Installation
3-1 Operating Instructions
3-1-1 Control System Chart
Operation |
|
|
Main switch operation |
|
Auto, Cool, Dry, Fan, Heat operation |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Remote control operation |
|
Turbo, Mild, Auto, Cool, Dry, Fan, Heat, Timer operation |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
Operation selector mode |
|
Auto mode |
|
||
|
|
|
Cool mode
Dry mode
Fan mode
Heat mode
In this mode, operation mode(COOL, HEAT) is selected automatically by room temperature of initial operation
Chaos output step fan motor control (Cooling:NATURAL, Heating:AUTO)
Indoor temperature control according to the set temperature.
Decide the dry cycle by the difference in room temperature and set temperature.
Operation of the indoor fan motor only.
Indoor temperature control according to the set temperature
Fan speed selector mode |
|
|
Manual 3-step |
|
High, Medium, Low |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Natural |
|
Automatic decision of High, Medium, and Low step by chaos operation. |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Auto |
|
Automatic decision of High, Medium, and Low step by chaos operation. |
|
|
|
|
||
|
|
|
|
||
|
|
|
|
|
|
Airflow selector mode |
|
|
Right and left turn |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
UP and Down Turn |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Timer operation mode |
|
|
ON time |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
OFF time |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Convenience function |
|
|
Turbo opertion |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Mild operation |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Q.timer |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Self-diagnosis function |
|
|
“E1” |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
“E2” |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
“E5” |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
“E6” |
|
|
|
|
|
|
|
|
|
|
|
Only use by remote control.
Continuously operating compressor & powerful operating fan motor(30 minutes). In case of heating operation, prevention against cold wind function is given priority before turbo operation. (Cooling:TURBO, Heating:HIGH)
Set off after opertion for one hour in medium mode, and two hours in low mode.
Reserve function which is off after on time of 30 minutes, 1,2,3, and 5 hours.
Displayed at the time of indoor temperature sensor open or short.
Displayed when the panel shutter opening/closing is not sensed.
Displayed at the time of EVAP. Sensor open or short. (Heating mode)
Displayed at the time of COND. Sensor open or short. (Heating mode)
3-1
Operating Instructions and Installation
|
|
|
|
|
|
|
|
|
VFD display function |
|
|
Selection of operation mode |
|
Auto, Cool, Dry, Fan Heat Display |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Selection of fan speed |
|
Auto, natural, high, medium, and low fan speed Display |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Current temperature |
|
Temperature display |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fan speed diagram |
|
Turbo, high, medium, and low airflow Display |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Timer function |
|
Timer Display |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Convenience function |
|
Timer, turbo lamp, mild Dispaly |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Airflow function |
|
Up/Down, Left/Right Display |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Others |
|
CHECK Display, Operation Display, Defrost Display |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3-2
Operating Instructions and Installation
3-1-2 Main Controller Function
3-1-2(a) Auto Operation
1. In this mode, operation mode(COOL, HEAT) is selected automatically by the room temperature of initial operation.
Room Temp. |
Operation Type |
|
|
Tr ³ 21˚C + DT |
Cool operation (Set Temp.:24˚C + DT) |
|
|
Tr < 21˚C + DT |
Heat operation (Set Temp.:22˚C + DT) |
|
|
DT=-1˚C, -2˚C, 0˚C, +1˚C, +2˚C
DT is controlled by setting temperature TEMP. SET Key of remote controller.
2. In Auto mode, the optimum fan speed is selected automatically and cannot be changed. · Set the "Auto" for heating.
· Set the "NATURAL" for cooling.
3-1-2(b) Cool Operation
1.The compressor is automatically turned on/off by the difference between the current temperature and desired temperature.
2.By selecting the fan speed , the operation of "low", "medium", "high", "natural", "auto" mode is selected.
3.The compressor is turned on/off by the change of the current temperature.
•The compressor is turned off when the current temperature is equal to the desired temperature.
•The compressor is turned on when the current temperature is +1˚C of the desired temperature.
4.Desired temperature setting range : 18˚C ~ 30˚C it can be changed by the unit of 1˚C.
5.Three minutes delay operation of the compressor.
ON |
|
|
|
|
|
• Three minutes delay setting condition |
|
|
|
|
|
|
|||
OFF |
|
|
|
1 |
After power reset |
||
|
|
|
|||||
|
|
|
|
|
|
On again after compressor off |
|
|
2 |
||||||
|
|
|
|
|
|
|
|
Three minutes delay
3-1-2(c) Heat Operation
1.The compressor is automatically turned on/off by the difference between the current temperature and desired temperature.
2.By selecting the fan speed , the operation of "low", "medium", "high", "auto" mode is selected.
3.The compressor is turned on/off by the change of the current temperature.
•The compressor is turned off when the current temperature is +1˚C of the desired temperature.
•The compressor is turned on when the current temperature is -1˚C of the desired temperature.
4.Desired temperature setting range : 16˚C ~ 30˚C it can be changed by the unit of 1˚C.
5.Delay operation of the compressor.
•Delay setting condition
ON |
|
|
|
|
|
|
1 |
After power reset or shut down |
|
|
|
|
|
|
|
||||
OFF |
|
|
|
|
|
|
|
|
compressor by control the desired |
|
|
|
|
|
|
|
|
||
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
temperature:3minutes. |
|
|
|
|
|
|
After deice:40sec. |
|||
|
|
|
40sec-3minutes. |
2 |
|||||
|
|
|
|
|
|
3 |
After shut down compressor or 4-way |
||
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
valve:1/2minutes |
3-3
Operating Instructions and Installation
3-1-2(d) Turbo Operation
Indoor fan speed
Compressor control
set fan speed |
turbo fan speed(high speed) |
set fan speed |
|
(note) |
opertion mode of (note)area |
|
|
|
Time,(t) |
start of turbo |
end of turbo |
operation |
operation |
Operating condition
1.The turbo operation is available only in auto, cool, mild and heat mode.
2.The turbo operation is performed for 30 minutes when the turbo button is pressed. (including three minutes delay time)
3.Control of the indoor fan motor and compressor during turbo operation •Indoor fan motor = Heating High
Cooling Turbo(fan speed one step higher than “high”) •Compressor : continued on regardless of room temperature.
4.After an elapse of 30 minutes from the start of turbo operaiton, the turbo operation is ended, and the unit returns to the previous mode.
5.When you press the turbo key again during the turbo operation, the turbo operation mode is canceled, and the unit returns to the previous mode.
3-1-2(e) Fan Speed Auto
1. Cooling operation
Desired temperature +5 |
|
|
Desired temperature +4 |
Desired temperature +4˚C |
|
High speed area |
|
|
Desired temperature +3 |
|
|
Medium speed area |
|
|
Desired temperature +2 |
Desired temperature +2˚C |
|
Medium speed area |
|
|
Desired temperature +1 |
|
|
Low speed area |
• The indoor fan motor speed is |
|
Low speed area |
||
automatically controlled |
||
Desired temperature +0 |
||
|
according to the difference |
|
|
between the indoor temperature |
|
2. Heating operation |
and the desired temperature. |
Desired temperature +1˚C
Desired temperature +0˚C
Desired temperature -1˚C
Desired temperature -2˚C
Low speed area |
|
Medium speed area |
Desired temperature -1˚C |
|
|
High speed area |
Desired temperature -3˚C |
|
3-4
Operating Instructions and Installation
3-1-2(f) |
Dry Operation |
|
|
|
|
|
|
|
|
|
||||
|
Room temperature[˚C] |
|
|
|
|
|
|
|
|
|
||||
Ts+4 |
|
|
A - MODE |
|
|
|
A - MODE |
|
|
|||||
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
B - MODE |
|
|
|||||||
Ts+3 |
|
|
|
|
|
|
|
|
|
|||||
Ts+2 |
|
|
B - MODE |
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
C - MODE |
|
|
|||||||
Ts+1 |
|
|
C - MODE |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Temperature down |
|
Temperature up |
|
|||||||
|
|
Ts=desired temperature |
|
|
|
|
|
|
|
|||||
1. On/off time by dry operation mode |
|
|||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor |
|
|
|
|
|
Operating mode |
|
||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
A - MODE |
|
|
B - MODE |
C - MODE |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ON time |
|
6 min. |
|
|
5 min |
3 min. |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OFF time |
|
4 min |
|
|
5 min. |
6 min. |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
•The indoor fan motor operation is fixed at a Low Speed
2.The dry operation mode is determined depending upon the difference between the indoor temperature (Ta) and desired temperature (Ts).
3.The unit is operated with the compressor on, and an indoor fan motor at a Low Speed for an initial six minutes (including a three-minute delay) after setting up the dry operation mode.
3-5
Operating Instructions and Installation
3-1-3 Key Types and Functions
3-1-3(a) Panel Key Types and Functions
KEY NAME |
KEY OPERATING FUNCTION |
KEY TYPE |
|
|
|
|
Start and end of operation |
TACT |
ON/OFF |
- ON one time = operation start, ON again = operation end |
|
|
- No continued operation |
|
|
|
|
|
Change of the operation mode |
TACT |
Mode selection |
-Each time the button is pressed (ON), the mode is changed in the following order ; |
|
"COOL → DRY → FAN → HEAT → AUTO → COOL" (standard = AUTO) |
|
|
|
|
|
|
-No continued operation |
|
|
|
|
|
Setting of the indoor fan motor speed. |
TACT |
Fan speed |
-Eacn time the button is pressed (ON), the mode is changed in the following order; |
|
selection |
COOL:"LOW → MEDIUM → HIGH → NATURAL → AUTO → LOW" (standard = AUTO) |
|
|
HEAT:"LOW → MEDIUM → HIGH → AUTO → LOW" (standard = AUTO) |
|
|
|
|
|
Increase the desired temperature display. |
JOG SHUTTLE |
Temperature |
-When turning the jog dial clock-wise, it displays the desired temperature and |
DIAL |
holding the jog dial continuously, the desired temperature is increased by the unit of 1˚C |
|
|
setting (up) |
|
|
(COOL:18˚C → 30˚C, HEAT:16˚C → 30˚C) |
|
|
|
|
|
|
-One short, and continued operation. |
|
|
|
|
|
Decrease the desired temperature display. |
JOG SHUTTLE |
Temperature |
-When turning the jog dial counter clock-wise, it displays the desired temperature and |
DIAL |
setting |
holding the jog dial continuously, the desired temperature is decreased by the unit of 1˚C |
|
(down) |
(COOL:30°C → 18°C, HEAT:30°C → 16°C) |
|
|
-One short, and continued operation. |
|
|
|
|
3-6
Operating Instructions and Installation
3-1-3(b) V.F. Display Operating Spec
|
|
|
|
DISPLAY |
|
|
|
|
OPERATING SPEC |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• When the compressor is activated (outdoor power relay on) : ON |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• When the compressor is stopped (outdoor power relay off) :OFF |
|
|
|
|
OPERATING |
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• During the defrost operation : ON |
|
|
|
|
|
DEFROST |
|
|
|
• The defrost operation ended : OFF |
|||||||||
|
|
|
|
|
|
|
|
|
|||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
HEAT |
|
|
|
COOL |
|
|
|
• |
Display the selected "operation selection mode" |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AUTO, COOL, DRY, FAN, HEAT |
|||
DRY |
|
|
AUTO |
|
|
|
FAN |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TEMP. |
|
|
|
|
|
|
|
|
|
˚C |
• |
When the ON/OFF is ON, the indoor temperature is displayed. |
|||
|
SET TEMP. |
|
|
|
|
|
|
|
|
|
|
|
• |
When changing the desired temperature, the indoor room temperature is displayed |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
after displaying the desired for 5 senconds |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
CHECK |
|
|
|
|
|
|
|
|
|
|
|
• The trouble is occured by self - diagnosis funtion :ON |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
• The troubleshooting is completed : OFF |
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TIMER |
|
|
|
• During reservation : ON |
|||||
|
|
|
|
|
|
|
|
|
|
|
• Reservation ended or canceled : OFF |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• Display the selected "fan speed selection mode" |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LOW, MEDIUM, HIGH, NATURAL, AUTO |
|
|
AUTO |
|
|
|
|
NATURAL |
• |
Display operation of the indoor fan motor |
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LOW, MEDIUM, HIGH, TURBO |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• During turbo operation : ON |
|
|
|
|
|
|
TURBO |
|
|
|
|
• Turbo operation ended or canceled : OFF |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
• During mild operation : ON |
|
|
|
|
|
|
|
MILD |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
• Mild operation ended or canceled : OFF |
|||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AIR |
|
|
|
|
|
|
|
|
|
|
|
• When [the right and left turn] is on by the remote control, it displays |
||||
|
SWING |
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
AIR |
|
|
|
|
|
|
|
|
|
|
|
• |
When [the up and down turn] is on by the remote control, it displays |
|||
|
SWING |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3-7
3-2 Installationn
3-2-1 Selection of Installation Place
3-2-1(a) Indoor Unit
•Install the unit at a place close to the wall facing the outside as it is necessary to perform piping connection with the outdoor unit.
-It is effective to install the unit at a window side to ensure uniform distribution of indoor temperature.
•Install the unit at a place where there is no obstacle against the wind around the air inlet and air outlet.
•Install the unit horizontally at a stable, rigid place.
(When installing the unit at a place subjected to vibration, noise may occur.)
•Avoid a place near the door which is frequented by people.
•Avoid a place subject to direct sunlight.
3-2-1(b) Outdoor Unit
•place free from the risk of combustible gas leakage.
•place which can bear the weight of the unit.
•place which can bear the fixing strength of the outdoor unit.
•Avoid a place subject to oil(including machine oil).
•Avoid a saline place
•Avoid a place subject to sulfide gas(hot spring zone).
(When installing the unit at such special environmental conditions, it may cause machine trouble. When it is unavoidable to use such places. It requires special maintenance.)
•A place where the discharge air and noise of the outdoor unit do not disturb the neighborhood.
(Take special care not to cause any inconvenience to your neighbors when installing the unit on the borderline with your neighborhood.)
•A place where strong wind does not head against the air outlet of the outdoor unit.
(If a strong wind heads directly against the air outlet at the time of cool operation, a safety device can be operated.)
•Do not install the outdoor unit at an unstable place such as outer wall of an apartment or building.
The outdoor unit may fall down, causing severe personal or property damage or loss.
•If there is any unavoidable reason to install the unit at such a place, take the following measures against the wind;
1.When installing the unit at a roadside concentrated with buildings, install it parallel with the road.
2.Install the unit so that the air outlet faces toward the wall at a place such as rooftop, which may be subjected to strong wind.
Top view
•Good method for using space more efficiency.
Side view
Above 50cm
Above 100cm
Wall |
Strong wind |
|
|
|
Roof top |
* Be sure to install the outdoor unit with consideration of service space.
Above 10cm |
|
Above 50cm |
|
Above 50cm |
|
Space for pip- |
|
|
ing and wiring |
||
Space for piping |
|
||
Above 10cm |
Above 30cm |
||
and wiring |
|||
Above 10cm |
|
|
|
The air inlet faces toward the wall. |
The air outlet faces toward the wall. |
||
|
|
|
3-8
Operating Instructions and Installation
3-2-2 Electrical Work
The electrical work should be performed by a specialist qualified for the work.
•Use the single phase power supply, and be sure to install the sub power distributing board for exclusive use with the unit(separately purchased by the user).
•Avoid octopus-type wiring as it can cause a drop in voltage, thus resulting in poor performance of the automatic control circuit.
•Be sure to install the earth leakage circuit breaker (separately purchased by the user).
•Be sure to connect the grounding wire.
Electric power spec |
|
|
|
Connecting wire & PCB fuse spec |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
SPEC |
|
|
|
TYPE |
SPEC |
|
||
|
Power |
Single phase 220V-240V~, 50Hz |
|
|
Power cable |
H07RN-F |
3G 2.5mm2 |
450-750V~ |
|
|
|
Sub switch |
30 A |
|
|
Connecting wire |
H07RN-F |
5G 1.0mm2 |
450-750V~ |
|
|
|
Fuse |
30 A |
|
|
|
H05RN-F |
2G 0.75mm2 |
300-500V~ |
|
|
|
Electric wire Below 20m |
3.5 mm2 |
|
|
Sensor cable |
H05RN-F |
2G 0.75mm2 |
300-500V~ |
|
|
|
Allowable voltage |
198V ~ 264V |
|
|
PCB fuse |
50T |
250V~, 3.5A |
|
||
|
|
|
|
|
|
|
F2L |
250V~, 2A |
|
|
Indoor and Outdoor Connection Wiring |
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
•When connecting the connecting wire between the indoor and outdoor unit, be sure to align the terminal block number with the connecting wire number.
•When the connecting wire is not properly connected, it may cause trouble.
Be careful not to allow connecting wires and power lines to get in contact with service valve or the pipe without an insulator.
Color of connecting wire |
Model name |
No. |
1 |
2 |
3 |
4 |
5 |
|
|
|
|
|
|
|
|
|
KRH28PV2 |
|
BRN |
SKY |
Thin BRN |
BLK |
Thin SKY |
Outdoor side
Terminal plate
Cable clamp
Cover control
Electric
panel board
Cable cover
Holder cable
Base control
Terminal block |
|
Earth |
1.Connect the connecting wire to the terminal block and connect the earth wire to the bracket earth.
2.Close the cover control.
3.As following the figure, firmly fix connecting wire with the holder cable.
A |
Wire of sensor |
B |
Earth |
C |
Power cable |
Electrical Wiring
1.Connect it to the terminal board N and L for power supply to the outdoor unit.
In so doing, peel off the end of the power cord by about 5mm, and press the cord to the ring terminal for hooking.
2.Perform the power grounding using the screw for exclusive use with the outdoor unit.
3-9
Operating Instructions and Installation
3-2-3 Installation Method
3-2-3(a) Indoor Unit
This unit is greater in height compared to its width, and thus it may fall down.
Therefore, be sure to fix the unit to the wall and floor surfaces securely to prevent the unit from falling down.
Fixing to the wall
•Fix the unit using the fixing holders separately supplied.
•Select a direction (right or left) according to a place of being installed.
•The fixing holder “B” was decided on a direction (front or rear) according to a condition of being installed.
1.Fix the fixing holder “B” using the screw at a rear side groove.
2.Put the fixing holder “A” on the fixing holder “B”, then fix holders using the nut, washer and bolt to direction you want.
3.Fix the fixing holder “A” to the wall.
3-2-3(b) Outdoor Unit
When using the anchor bolt
1.Fix the unit on a flat, rigid floor using the anchor bolt.
(Anchor bolt : M10 x 4 points - separately purchased)
When using the leg holder of the outdoor unit
1.Insert the foot holder (4EA, optional).
2.Remove the nut fastened to the leg holder, and then insert the leg holder into the hole of the outdoor unit leg.
3.Fix the unit securely with the nut.
Anchor bolt fixing dimensions
Unit:mm
A |
B |
660 335
Nut
Outdoor unit leg
Leg holder
Foot holder
3-10
Operating Instructions and Installation
3-2-3(c) Installation Procedures
1 Open the inlet grille, and remove the flare nut.
2.Bend the connection pipe to an appropriate length using the spring bender depending upon the installation place.
-Allowable pipe length : Maximum 25m
-Allowable pipe drop distance : Maximum 15m
-Make no more than ten bending points on the pipe
•When the pipe length is in excess of the standard pipe length of 5m, add the refrigerant
(R-22) of 50g for each additional 1m.
Caution
•If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened. Therefore, the pipe length should be as short as possible (less then 15m).
3.Install the high pressure pipe to the heat exchanger liquid pipe, and the low pressure pipe to the heat exchanger gas pipe respectively using the flare nut, taking care not to cause any leakage of refrigerant.
4.Be sure to insulate the pipe with appropriate insulation material.
5.Insert the drain hose into the drain pipe, and connect them by tying them to the cable tie to prevent any water leakage.
6.After completion of the installation, check the connecting area for any gas leakage.
7.Wind a finish tape when the wiring of the refrigerant pipe, the unit, and the drain piping are completed.
|
Outdoor unit |
Indoor unit |
checking area |
checking area |
|
3-11
Operating Instructions and Installation
3-2-3(d) Connection of refrigerant pipe
Flare Processing
1. Cut the pipe using the pipe cutter.
Oblique |
Roughness |
Burr |
2. Insert the flare nut into the pipe, and then perform the flare processing.
Outer Diameter |
A |
|
|
ø 6.35 mm |
1.3 |
|
|
ø 9.52 mm |
1.8 |
|
|
ø 15.8 mm |
2.0 |
|
|
Pipe Bending
|
1. |
Perform bending of the pipe using the bender which has |
|
Spring |
|||
|
a specified bending radius. |
||
|
2. |
Be sure to take full care to perform bending of the pipe |
|
|
|
successfully at one time. Bending and unbending the pipe |
|
|
|
more than twice makes the bending work increasingly |
|
|
|
||
|
|
difficult. |
|
3. |
You may use the spring inserted into the gas pipe instead |
||
|
|
of the bender to bend the pipe. |
|
4. |
When you bend the pipe using the spring, hold the pipe |
||
|
|
with both hands to prevent any distortion, and secure a |
|
|
|
minimum bending radius of more than 100mm. |
Tightening of Connection Parts
•Align the center of the connection piping, and tighten the flare nut by turning it with hand. Then tighten it again using the spanner in the direction as shown in the figure.
Outer Diameter |
Tightening Torque |
Final Torque |
Remarks |
ø 6.35mm |
160 kg • cm |
200kg • cm |
|
ø 9.52mm |
400 kg • cm |
450 kg • cm |
|
ø 15.8mm |
700 kg • cm |
750 kg • cm |
|
3-12