Samsung DVM S VRF Technical Data Book User guide

Page 1
VRF
Technical
Data Book
DVM S for Europe
(R410A, 50Hz, HP)
Model : Premium (Compact / Energy Efficiency) Type
Standard Type
Page 2
2History
Version Modification Date Remark
Ver. 1.0 Release DVM S 30 HP High EER TDB for Europe (R410A, 50 Hz, HP) 15.12.30
Ver. 1.1 Add Sound Pressure Spec for Modules (At cooling mode / P.15 to 58) 16.01.06
Modify Electric Diagram Mapping (For AM160KXVGGH** Model/P.65 to 66)
Ver. 1.2
Ver. 2.0 Update all contents including installation 16.07.07
Ver. 2.01 Modify the Accessory Compatibility table for MCU kit(P163) 17.09.13
Line-up Name (Standard → Premium Compact, High Effi. → Premium High Efficiency / P. 4, 5)
16.01.13
Page 3
Nomenclature
Outdoor Unit
Model Name
(1) (2) (3) (4) (5) (6) (7) (8)
(1) Classification
AM DVM
(2) Capacity
x 1/10 HP (3 digits)
(3) Version
F 2013
H 2014
J 2015
K 2016
Buyer
(5) Feature 1
V Inverter
M DVM S Eco
(6) Feature 2
A Standard + General Temp.+ Module H High EER + Low Temp + Module G High EER + General Temp + Module
(7) Rating Voltage
E 1Ø, 220~240V, 50Hz G 3Ø, 380~415V, 50Hz
(4) Product Type
X Outdoor Unit N Indoor Unit
(8) Mode
H Heat Pump R Heat Recovery
3
Page 4
4Features & Benefits
Samsung’s VRF system air conditioners offer instant temperature control, user-friendly installation and advanced functionality, along with smart power usage. Our flagship VRF-based Samsung DVM S is a highly innovative system that adopts the new third-generation Samsung Scroll Compressor (SSC) technology with Dual Digital Inverter DVM S provides world-class energy efficiency and the most powerful cooling and heating performance available on the market. This ideal air conditioning system accomodates all variable environments, including large commercial or residential buildings.
.
Samsung DVM S offers innovative features to benefit the indoor comfort as well operational coasts of the system through technological advances such as:
The world’s largest capacity
Capacities of the outdoor units offer up to 30 HP rooftop space savings as well as lowering the installations and transportation costs.
High seasonal energy efficiency
Samsung DVM S adopts a dual inverter scroll compressor that upgrades refrigerant flow and the motor’s operating performance. It makes ESEER of DVM S is up to 8.00.
Superior Heating Performance & Wide Operating Temperature Range with Flash injection
Increase refrigerant flow by 32%, extend heating operation range at -25°C, thanks to Flash Injection technology, extended compressor reliability range and control compression ratio.
Page 5
Features & Benefits
Intelligent Defrosting Logic
DVM S Intelligent Defrost Control logic keeps the unit in the heating mode for up to 40% longer through out the heating season compared to conventional model by monitoring the air resistance through the heat exchanger.
Optimised Heat Exchanger
Combination of optimised coil path and different types of fin design for upper and lower parts of the condenser evens out the airflow profile to optimise the heat transfer process.
Extended Piping Length Limits
Allows extended piping length of up to 220 m, and units will still give a great performance over wide areas. With this technology, installation is available with a maximum height level of 110 m, which is equivalent to 20 stories (each story is considered 5 m high).
Smart management
Further improves system’s energy efficiency due to precise indoor climate control. Web-based remote monitoring and management system allows quick and easy HVAC control and breakdown alert.
Eurovent Certified Performance
Samsung DVM S had become the 1st VRF Product to be certified by Eurovent, the European Committee of HVAC&R, in March 2014.
5
Page 6
6Contents
1. Combination table 7
2. Specifications 15
3. Electrical Characteristics 95
4. Dimensional drawing 98
5. Center of gravity 101
6. Electrical wiring diagrams 104
7. Sound Data 106
8. Operation range 120
9. Piping diagram 122
10. Installation 129
11. Accessory 156
Page 7
1. Combination Table: Outdoor units
Premium Compact
System Model Capacity of Single Unit (HP)
Capa Code No. of Modules 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP
8HP
AM080JXVHGH/EU 1 1 10HP AM100JXVHGH/EU 1 1 12HP AM120JXVHGH/EU 1 1 14HP AM140KXVGGH/EU 1 1 16HP AM160KXVGGH/EU 1 1 18HP AM180KXVGGH/EU 1 1 20HP AM200KXVGGH/EU 1 1 22HP AM220KXVGGH/EU 1 1 24HP AM240KXVGGH/EU 1 1 26HP AM260KXVGGH/EU 1 1 28HP AM280KXVGGH/EU 1 1 30HP AM300KXVAGH/EU 1 1 32HP AM320KXVGGH1EU 2 1 1 34HP AM340KXVGGH1EU 2 1 1 36HP AM360KXVGGH1EU 2 1 1 38HP AM380KXVGGH1EU 2 1 1 40HP AM400KXVGGH1EU 2 1 1 42HP AM420KXVGGH1EU 2 1 1 44HP AM440KXVGGH1EU 2 1 1 46HP AM460KXVGGH1EU 2 1 1 48HP AM480KXVGGH1EU 2 1 1 50HP AM500KXVGGH1EU 2 1 1 52HP AM520KXVGGH1EU 2 1 1 54HP AM540KXVGGH1EU 2 1 1 56HP AM560KXVGGH1EU 2 1 1 58HP AM580KXVGGH1EU 2 1 1 60HP AM600KXVGGH1EU 2 2 62HP AM620KXVGGH1EU 3 1 1 1 64HP AM640KXVGGH1EU 3 1 1 1 66HP AM660KXVGGH1EU 3 1 1 1 68HP AM680KXVGGH1EU 3 1 1 1 70HP AM700KXVGGH1EU 3 1 1 1 72HP AM720KXVGGH1EU 3 1 1 1 74HP AM740KXVGGH1EU 3 2 1 76HP AM760KXVGGH1EU 3 1 1 1 78HP AM780KXVGGH1EU 3 1 1 1
80HP AM800KXVGGH1EU 3 1 1 1 82HP AM820KXVGGH1EU 3 1 2 84HP AM840KXVGGH1EU 3 1 2 86HP AM860KXVGGH1EU 3 1 2 88HP AM880KXVGGH1EU 3 1 2 90HP AM900KXVGGH1EU 3 3
NOTE
• Make sure to
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
• In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit and deciding on piping length in accordance with design of the building.
use an indoor unit that is compatible with DVM S.
7
Page 8
1. Combination Table: Outdoor units
Premium Energy Efficiency
System Model Capacity of Single Unit (HP)
Capa Code No. of Modules 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP
8HP AM080JXVHGH/EU 1 10HP AM100JXVHGH/EU 1 12HP AM120JXVHGH/EU 1 14HP AM140KXVGGH/EU 1 16HP AM160KXVGGH/EU 1 18HP AM180KXVGGH/EU 1 1
20HP AM200KXVGGH/EU 1 1
22HP AM220KXVGGH2EU 2 24HP AM240KXVGGH2EU 2 2 26HP AM260KXVGGH2EU 2
28HP AM280KXVGGH2EU 2 30HP AM300KXVGGH2EU 2 32HP AM320KXVGGH2EU 2 34HP AM340KXVGGH2EU 3 36HP AM360KXVGGH2EU 2 2 38HP AM380KXVGGH2EU 2 1 40HP AM400KXVGGH2EU 3 42HP AM420KXVGGH2EU 3 44HP AM440KXVGGH2EU 3 1 2 46HP AM460KXVGGH2EU 3 1 48HP AM480KXVGGH2EU 3 1 50HP AM500KXVGGH2EU 3
52HP AM520KXVGGH2EU 3 1
54HP AM540KXVGGH2EU 3 56HP AM560KXVGGH2EU 3 58HP AM580KXVGGH2EU 3 1 60HP AM600KXVGGH2EU 3 2 62HP AM620KXVGGH2EU 4 1 64HP AM640KXVGGH2EU 4 66HP AM660KXVGGH2EU 4 68HP AM680KXVGGH2EU 4
70HP AM700KXVGGH2EU 4 72HP AM720KXVGGH2EU 4 4 74HP AM740KXVGGH2EU 4 3 76HP AM760KXVGGH2EU 4 2 78HP AM780KXVGGH2EU 4 1 3
80HP AM800KXVGGH2EU 4 3 82HP AM820KXVGGH2EU 4 2 1 84HP AM840KXVGGH2EU 4 1 86HP AM860KXVGGH2EU 4 1 1 88HP AM880KXVGGH2EU 4 1 1 90HP AM900KXVGGH2EU 4 1 1 2
1
1
1
1
1
1 1
1 1 1 1
1
1 1
2
1 1 1 1
1
1 1 1
1
1
1
1
1
1
1
1
1
1
1
1
2 2 1 1
1 1
1
1 3 2
1 3 3 2
1
2
2
1
1
1
1
1 1 1 1 1
NOTE
• Make sure to
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
• In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit and deciding on piping length in accordance with design of the building.
8
use an indoor unit that is compatible with DVM S.
Page 9
1. Combination Table: Outdoor units
Standard
System Model Capacity of Single Unit (HP)
Capa Code No. of Modules 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP
8HP AM080JXVAGH/EU 1
10HP AM100JXVAGH/EU 1
12HP AM120JXVAGH/EU 1 14HP AM140KXVAGH/EU 1 16HP AM160KXVAGH/EU 1
18HP AM180KXVAGH/EU 1 1 20HP AM200KXVAGH/EU 1 1 22HP AM220KXVAGH/EU 1 24HP AM240KXVAGH/EU 1 26HP AM260KXVAGH/EU 1 28HP AM280KXVAGH/EU 1 30HP AM300KXVAGH/EU 1 32HP AM320KXVAGH/EU 2 34HP AM340KXVAGH/EU 2 36HP AM360KXVAGH/EU 2 38HP AM380KXVAGH/EU 2 40HP AM400KXVAGH/EU 2 42HP AM420KXVAGH/EU 2 44HP AM440KXVAGH/EU 2 2 46HP AM460KXVAGH/EU 2 48HP AM480KXVAGH/EU 2 50HP AM500KXVAGH/EU 2 52HP AM520KXVAGH/EU 2 54HP AM540KXVAGH/EU 2 56HP AM560KXVAGH/EU 2 58HP AM580KXVAGH/EU 2 60HP AM600KXVAGH/EU 2 2 62HP AM620KXVAGH/EU 3 64HP AM640KXVAGH/EU 3 66HP AM660KXVAGH/EU 3 68HP AM680KXVAGH/EU 3 70HP AM700KXVAGH/EU 3
72HP AM720KXVAGH/EU 3
74HP AM740KXVAGH/EU 3 2 1
76HP AM760KXVAGH/EU 3 1 78HP AM780KXVAGH/EU 3 1 80HP AM800KXVAGH/EU 3 1 82HP AM820KXVAGH/EU 3 1 2 84HP AM840KXVAGH/EU 3 86HP AM860KXVAGH/EU 3 88HP AM880KXVAGH/EU 3 90HP AM900KXVAGH/EU 3 3
1
1
1
1
1
1 1
1
1
1
1 1
1 1
1
1
1
1
1
1
1
1 1 1
1
1
1
1
1
1
1
1
1
1 1 1 1 1 1 1 1
1
1 1
1
1
1
1
1
1
1
1
1
1 1 1 1 1 1
1
1 1 1
2 2 2
NOTE
• Make sure to
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
• In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit and deciding on piping length in accordance with design of the building.
use an indoor unit that is compatible with DVM S.
9
Page 10
1. Combination Table: Indoor units
Model
JSF-0
1Way
JSF-1
CST
JSF-2
2Way CST
4Way CST
360 CST
Floor
Standing
Unit
4Way CST S
(600X600)
Capacity (kW)
1.5 1.7 2.2 2.8 3.2 3.6 4.5 5.6 6.0 7.1 8.2 9.0 11.2 12.8 14.0 16.0
Duct S
(MSP)
Slim Duct
MSP Duct
Ceiling
Console
Boracay
Boracay
(with EEV)
AR5000
AR5000
(with EEV)
10
Page 11
1. Combination Table: Indoor units
Model
1.5 1.7 2.2 2.8 3.2 3.6 4.5 5.6 6.0 7.1 8.2 9.0 11.2 12.8 14.0 16.0
HSP Duct
OAP Duct
Big Duct
Hydro
Unit HE
Hydro
Unit HT
ERV Plus
Capacity (kW)
NOTE
• Make sure to use an indoor unit that is compatible with DVM S.
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
11
Page 12
1. Combination Table: External Appearance
Premium compact
Capa [HP] Model Nane Model Capa [HP] Model Nane Model
AM140KXVGGH/EU
8 10 12
24 26 28 30
36 38 40 42
54 56 58 60
AM080JXVHGH/EU AM100JXVHGH/EU
AM120JXVHGH/EU
AM240KXVGGH/EU AM260KXVGGH/EU AM280KXVGGH/EU AM300KXVAGH/EU
AM360KXVGGH1EU AM380KXVGGH1EU AM400KXVGGH1EU AM420KXVGGH1EU
AM540KXVGGH1EU AM560KXVGGH1EU AM580KXVGGH1EU AM600KXVGGH1EU
14 16 18 20 22
32 34
44 46 48 50 52
62 64
AM160KXVGGH/EU AM180KXVGGH/EU AM200KXVGGH/EU AM220KXVGGH/EU
AM320KXVGGH1EU AM340KXVGGH1EU
AM440KXVGGH1EU AM460KXVGGH1EU AM480KXVGGH1EU AM500KXVGGH1EU AM520KXVGGH1EU
AM620KXVGGH1EU AM640KXVGGH1EU
66 68 70 72 74
84 86 88 90
AM660KXVGGH1EU AM680KXVGGH1EU AM700KXVGGH1EU AM720KXVGGH1EU AM740KXVGGH1EU
AM840KXVGGH1EU AM860KXVGGH1EU AM880KXVGGH1EU AM900KXVGGH1EU
76 78 80 82
AM760KXVGGH1EU AM780KXVGGH1EU AM800KXVGGH1EU AM820KXVGGH1EU
12
Page 13
1. Combination Table: External Appearance
Premium Energy Efficiency
Capa [HP] Model Nane Model Capa [HP] Model Nane Model
AM140KXVGGH/EU
8 10 12
22 24
32 36 38
40 42 44 46 48
AM080JXVHGH/EU AM100JXVHGH/EU
AM120JXVHGH/EU
AM220KXVGGH2EU AM240KXVGGH2EU
AM320KXVGGH2EU AM360KXVGGH2EU AM380KXVGGH2EU
AM400KXVGGH2EU AM420KXVGGH2EU AM440KXVGGH2EU AM460KXVGGH2EU AM480KXVGGH2EU
14
AM160KXVGGH/EU
16
AM180KXVGGH/EU
18
AM200KXVGGH/EU
20
AM260KXVGGH2EU
26
AM280KXVGGH2EU
28
AM300KXVAGH2EU
30
34 AM340KXVGGH2EU
50 AM500KXVGGH2EU
AM520KXVGGH2EU
52
AM540KXVGGH2EU
54
AM560KXVGGH2EU
56
60 AM600KXVGGH2EU
AM680KXVGGH2EU
68
AM720KXVGGH2EU
72
AM740KXVGGH2EU
74
AM760KXVGGH2EU
76
AM780KXVGGH2EU
78
AM800KXVGGH2EU
80
AM820KXVGGH2EU
82
AM840KXVGGH2EU
84
AM860KXVGGH2EU
86
58 AM580KXVGGH2EU
AM620KXVGGH2EU
62
AM640KXVGGH2EU
64
AM660KXVGGH2EU
66
70 AM700KXVGGH2EU
88 90AM880KXVGGH2EU
AM900KXVGGH2EU
13
Page 14
1. Combination Table: External Appearance
Standard
Capa [HP] Model Nane Model Capa [HP] Model Nane Model
AM140KXVAGH/EU
14 16 18 20 22
AM160KXVAGH/EU AM180KXVAGH/EU AM200KXVAGH/EU AM220KXVAGH/EU
10 12
8
AM080JXVAGH/EU AM100JXVAGH/EU
AM120JXVAGH/EU
24 26 28
30
36 38
40
42 44
54 56 58
60
66 68 70 72 74
84
86 88 90
AM240KXVAGH/EU AM260KXVAGH/EU AM280KXVAGH/EU AM300KXVAGH/EU
AM360KXVAGH/EU AM380KXVAGH/EU AM400KXVAGH/EU AM420KXVAGH/EU AM440KXVAGH/EU
AM540KXVAGH/EU AM560KXVAGH/EU AM580KXVAGH/EU AM600KXVAGH/EU
AM660KXVAGH/EU AM680KXVAGH/EU AM700KXVAGH/EU AM720KXVAGH/EU AM740KXVAGH/EU
AM840KXVAGH/EU AM860KXVAGH/EU AM880KXVAGH/EU AM900KXVAGH/EU
32 34
46 48 50 52
62 64
76 78 80 82
AM320KXVAGH/EU AM340KXVAGH/EU
AM460KXVAGH/EU AM480KXVAGH/EU AM500KXVAGH/EU AM520KXVAGH/EU
AM620KXVAGH/EU AM640KXVAGH/EU
AM760KXVAGH/EU AM780KXVAGH/EU AM800KXVAGH/EU AM820KXVAGH/EU
14
Page 15
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type ­Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S
AM080JXVHGH/EU AM100JXVHGH/EU AM120JXVHGH/EU
- - -
- - -
- - -
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
8 10 12
22.4 28.0 33.6
76,400 95,500 114,600
25.2 31.5 37.8
86,000 107,500 129,000
14 18 21
11.2 14.0 16.8
29.1 36.4 43.7
4.59 6.22 7. 5 7
4.59 5.89 7. 5 6
7. 4 0 10.00 12.10
7. 4 0 9.40 12.10
3.1 4.6 5.3
18.0 2 1.1 25.0 25 32 32
4.88 4.50 4.44
5.49 5.35 5.00
8.00 7. 4 3 7. 2 3
EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS-GB052FAVBSG x 1 DS-GB066FAVBSG x 1 DS-GB066FAVBSG x 1
5.18 x 1 6.39 x 1 6.39 x 1 PVE PVE PVE
1,100 x 1 1,100 x 1 1,100 x 1
Propeller Propeller Propeller
Top Top Top
1 1 1
170 170 220
2,833 2,833 3,667
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
830 x 1 830 x 1 830 x 1
Braze connection Braze connection Braze connection
9.52 (3/8) 9.52 (3/8) 12.70 (1/2)
Braze connection Braze connection Braze connection
19.05 (3/4) 22.22 (7/8) 28.58 (1-1/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
15
Page 16
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
6.5 6.5 6.5 57 58 62 59 60 64 77 79 81
195.5 195.5 195.5
211.5 211.5 211.5
880 x 1,695 x 765 880 x 1,695 x 765 880 x 1,695 x 765
948 x 1,887 x 832 948 x 1,887 x 832 948 x 1,887 x 832
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
16
Page 17
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type ­Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S
AM140KXVGGH/EU AM160KXVGGH/EU AM180KXVGGH/EU
- - -
- - -
- - -
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
14 16 18
40.0 45.0 50.4
136,500 153,500 172,000
45.0 50.4 56.7
153,500 172,000 193,500
26 29 32
20.0 22.5 25.2
52.0 58.5 65.5
8.89 10.9 2 10.68
9.6 2 10.75 10.52
14.30 17.50 17.10
15.40 17.20 16.90
5.4 7. 2 8.8
25.0 32.0 39.2 32 40 50
4.50 4 .12 4.72
4.68 4.69 5.39
7. 7 8 7. 3 8 7. 2 5 EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS-GB066FAVB x 1 DS4GJ5080FVA x 1 DS-GB066FAVB x 2
6.39 x 1 7.81 x 1 6.39 x 2 PVE PVE PVE
1,100 x 1 1,400 x 1 1,100 x 2
Propeller Propeller Propeller
Top Top Top
2 2 2
255 255 290
4,250 4,250 4,833
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
620 x 2 620 x 2 620 x 2
Braze connection Braze connection Braze connection
12.70 (1/2) 12.70 (1/2) 15.88 (5/8)
Braze connection Braze connection Braze connection
28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
17
Page 18
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
9.4 8.4 8.4 61 63 65 63 65 67 81 83 89
241.0 255.0 285.0
261.0 275.0 305.0
1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765
1,363 x 1,887 x 832 1,363 x 1,887 x 832 1,363 x 1,887 x 832
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
18
Page 19
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type ­Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S
AM200KXVGGH/EU AM220KXVGGH/EU AM240KXVGGH/EU
- - -
- - -
- - -
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
20 22 24
56.0 61.6 6 7. 2
191,100 210,200 229,300
63.0 69. 3 75.6
215,000 236,500 258,000
36 40 43
28.0 30.8 33.6
72.8 8 0.1 8 7. 4
12.50 15.75 16.00
12.75 15.86 15.43
20.00 25.30 25.70
20.50 25.40 24.70
8.1 8.6 12.5
42.0 44.6 55.0 63 63 63
4.48 3.91 4.20
4.94 4.37 4.90
6.82 6.43 7.1 8
EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS-GB066FAVB x 2 DS-GB066FAVB x 2 DS-GB070FAVA x 2
6.39 x 2 6.39 x 2 6.76 x 2 PVE PVE PVE
1,100 x 2 1,100 x 2 1,100 x 2
Propeller Propeller Propeller
Top Top Top
2 2 2
290 290 340
4,833 4,833 5,667
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
620 x 2 620 x 2 620 x 2
Braze connection Braze connection Braze connection
15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
Braze connection Braze connection Braze connection
28.58 (1-1/8) 28.58 (1-1/8) 34.92 (1-3/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
19
Page 20
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
8.4 8.4 14.0 65 65 69 67 67 71 89 89 90
285.0 285.0 342.0
305.0 305.0 364.0 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,795 x 765 1,363 x 1,887 x 832 1,363 x 1,887 x 832 1,363 x 1,987 x 832
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
20
Page 21
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type ­Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S
AM260KXVGGH/EU AM280KXVGGH/EU AM300KXVAGH/EU
- - -
- - -
- - -
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
26 28 30
72.8 78.6 84.0
248,400 268,200 286,600
81.9 88.2 94.5
279,500 301,000 322,400
47 51 54
36.4 39. 3 42.0
94.6 102.2 109.2
17.33 19.65 22.70
17.06 18.77 20.59
27.80 31.50 36.40 2 7. 4 0 30.10 33.00
12.2 13.6 14.8
60.0 6 7. 0 73.0 75 75 80
4.20 4.00 3.70
4.80 4.70 4.59
7.1 7 6.86 6.65 EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS4GJ5080FVA x 2 DS4GJ5080FVA x 2 DS4GJ5080FVA x 2
7.81 x 2 7.81 x 2 7.81 x 2 PVE PVE PVE
1,400 x 2 1,400 x 2 1,400 x 2 Propeller Propeller Propeller
Top Top Top
2 2 2
340 340 340
5,667 5,667 5,667
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
620 x 2 620 x 2 620 x 2
Braze connection Braze connection Braze connection
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Braze connection Braze connection Braze connection
34.92 (1-3/8) 34.92 (1-3/8) 34.92 (1-3/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
21
Page 22
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
14.0 14.0 14.0 69 69 69
71 71 71
90 90 90
350.0 350.0 350.0
372.0 372.0 372.0
1,295 x 1,795 x 765 1,295 x 1,795 x 765 1,295 x 1,795 x 765
1,363 x 1,987 x 832 1,363 x 1,987 x 832 1,363 x 1,987 x 832
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
22
Page 23
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type ­Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S
AM320KXVGGH1EU AM340KXVGGH1EU AM360KXVGGH1EU
AM120JXVHGH/EU AM120JXVHGH/EU AM140KXVGGH/EU
AM200KXVGGH/EU AM220KXVGGH/EU AM220KXVGGH/EU
- - -
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
32 34 36
89. 6 95.2 101.6
305,700 324,800 346,700
100.8 1 0 7. 1 114.3
343,900 365,400 390,000
58 61 64
44.8 4 7. 6 50.8
116.5 123.8 132.1
20.07 23.32 24.64
20.31 23.42 25.48
32.10 3 7. 4 0 39.6 0
32.60 37.50 40.80
13.4 13.9 14 67 69. 6 69. 6
80 80 80
4.46 4.08 4.12
4.96 4.57 4.49
6.97 6.71 6.96
EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion DS-GB066FAVB x 2 + DSGB066FAVBSG x 1
DS-GB066FAVB x 2 + DSGB066FAVBSG x 1
DS-GB066FAVB x 3
(6.39 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1
PVE PVE PVE
(1,100 x 1) x 1 + (1,100 x 2) x 1 (1,100 x 1) x 1 + (1,100 x 2) x 1 (1,100 x 1) x 1 + (1,100 x 2) x 1
Propeller Propeller Propeller
Top Top Top
3 3 4
220 x 1 + 290 x 1 220 x 1 + 290 x 1 255 x 1 + 290 x 1
3,667 x 1 + 4,833 x 1 3,667 x 1 + 4,833 x 1 4,250 x 1 + 4,833 x 1
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(830 x 1) x 1 +
(620 x 2) x 1
(830 x 1) x 1 +
(620 x 2) x 1
(620 x 2) x 2
Braze connection Braze connection Braze connection
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Braze connection Braze connection Braze connection
34.92 (1-3/8) 34.92 (1-3/8) 41.28 (1-5/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
23
Page 24
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
6.5 x 1 + 8.4 x 1 6.5 x 1 + 8.4 x 1 9.4 x 1 + 8.4 x 1 67 67 66 69 69 68 90 90 90
195.5 x 1 + 285.0 x 1 195.5 x 1 + 285.0 x 1 241.0 x 1 + 285.0 x 1
211.5 x 1 + 305.0 x 1 211.5 x 1 + 305.0 x 1 261.0 x 1 + 305.0 x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 1
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 1
(1,295 x 1,695 x 765) x 2
(1,363 x 1,887 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
24
Page 25
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type -
Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S AM380KXVGGH1EU AM400KXVGGH1EU AM420KXVGGH1EU AM160KXVGGH/EU AM180KXVGGH/EU AM200KXVGGH/EU AM220KXVGGH/EU AM220KXVGGH/EU AM220KXVGGH/EU
- - -
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
38 40 42
106.6 112.0 117.6
363,700 382,200 401,300
119.7 126.0 132.3
408,400 429,900 451,400
64 64 64
53.3 56.0 58.8
138.6 145.6 152.9
26.67 26.43 28.25
26.61 26.38 28.61
42.80 42.40 45.30
42.60 42.30 45.90
15.8 1 7. 4 16.7
76.6 83.8 86.6 90 100 100
4.00 4.24 4.16
4.50 4.78 4.62
6.83 6.80 6.62
EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS4GJ5080FVA x 1 +
DSGB066FAVB x 2
DS-GB066FAVB x 4 DS-GB066FAVB x 4
(7.81 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 2) x 2 (6.39 x 2) x 2
PVE PVE PVE
(1,400 x 1) x 1 +
(1,100 x 2) x 1
(1,100 x 2) x 2 (1,100 x 2) x 2
Propeller Propeller Propeller
Top Top Top
4 4 4
255 x 1 + 290 x 1 290 x 2 290 x 2
4,250 x 1 + 4,833 x 1 4,833 x 2 4,833 x 2
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
Braze connection Braze connection Braze connection
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Braze connection Braze connection Braze connection
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
25
Page 26
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
8.4 x 2 8.4 x 2 8.4 x 2 67 68 68 69 70 70 90 92 92
255.0 x 1 + 285.0 x 1 285.0 x 2 285.0 x 2
275.0 x 1 + 305.0 x 1 305.0 x 2 305.0 x 2 (1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2 (1,363 x 1,887 x 832) x 2 (1,363 x 1,887 x 832) x 2 (1,363 x 1,887 x 832) x 2
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
26
Page 27
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type -
Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S AM440KXVGGH1EU AM460KXVGGH1EU AM480KXVGGH1EU AM140KXVGGH/EU AM160KXVGGH/EU AM180KXVGGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU
- - -
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
44 46 48
124.0 1 29.0 134.4
423,100 440,200 458,600
139.5 144.9 151.2
476,000 494,400 515,900
64 64 64
62.0 64.5 6 7. 2
161.2 167.7 174.7
31.59 33.62 33.38
30.21 31.34 31.11
50.70 53.90 53.50
48.40 50.20 49.90
20.2 22 23.6 98 105 112.2
125 125 125
3.93 3.84 4.03
4.62 4.62 4.86
7. 0 1 6.90 6.88 EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS-GB066FAVB x 1 +
DS4GJ5080FVA x 2
DS4GJ5080FVA x 3
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 2
(6.39 x 1) x 1 + (7.81 x 2) x 1 (7.81 x 1) x 1 + (7.81 x 2) x 1 (6.39 x 2) x 1 + (7.81 x 2) x 1
PVE PVE PVE
(1,100 x 1) x 1 +
(1,400 x 2) x 1
(1,400 x 1) x 1 +
(1,400 x 2) x 1
(1,100 x 2) x 1 +
(1,400 x 2) x 1
Propeller Propeller Propeller
Top Top Top
4 4 4
255 x 1 + 340 x 1 255 x 1 + 340 x 1 290 x 1 + 340 x 1
4,250 x 1 + 5,667 x 1 4,250 x 1 + 5,667 x 1 4,833 x 1 + 5,667 x 1
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
Braze connection Braze connection Braze connection
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Braze connection Braze connection Braze connection
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
27
Page 28
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
9.4 x 1 + 14.0 x 1 8.4 x 1 + 14.0 x 1 8.4 x 1 + 14.0 x 1 70 70 70
72 72 72 91 91 93
241.0 x 1 + 350.0 x 1 255.0 x 1 + 350.0 x 1 285.0 x 1 + 350.0 x 1
261.0 x 1 + 372.0 x 1 275.0 x 1 + 372.0 x 1 305.0 x 1 + 372.0 x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
28
Page 29
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type ­Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S AM500KXVGGH1EU AM520KXVGGH1EU AM540KXVGGH1EU AM200KXVGGH/EU AM220KXVGGH/EU AM240KXVGGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU
- - -
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
50 52 54
140.0 145.6 151.2
477,700 496,800 515,900
1 5 7. 5 163.8 17 0.1
537,400 558,900 580,400
64 64 64
70.0 72.8 75.6
182.0 189.3 196.6
35.20 38.45 38.70
33.34 36.45 36.02
56.40 61.70 62.10
53.50 58.40 57.70
22.9 23.4 2 7. 3 115 117.6 128
150 150 150
3.98 3.79 3.91
4.72 4.49 4.72
6.72 6.56 6.89
EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 2
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 2
DS-GB070FAVA x 2 +
DS4GJ5080FVA x 2
(6.39 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 2) x 1 + (7.81 x 2) x 1 (6.76 x 2) x 1 + (7.81 x 2) x 1
PVE PVE PVE
(1,100 x 2) x 1 + (1,400 x 2) x 1 (1,100 x 2) x 1 + (1,400 x 2) x 1 (1,100 x 2) x 1 + (1,400 x 2) x 1
Propeller Propeller Propeller
Top Top Top
4 4 4
290 x 1 + 340 x 1 290 x 1 + 340 x 1 340 x 2
4,833 x 1 + 5,667 x 1 4,833 x 1 + 5,667 x 1 5,667 x 2
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
Braze connection Braze connection Braze connection
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Braze connection Braze connection Braze connection
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
29
Page 30
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling Heating
2
(1,363 x 1,887 x 832) x 1 +
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
8.4 x 1 + 14.0 x 1 8.4 x 1 + 14.0 x 1 14.0 x 2 70 70 72 72 72 74 93 93 93
285.0 x 1 + 350.0 x 1 285.0 x 1 + 350.0 x 1 342.0 x 1 + 350.0 x 1
305.0 x 1 + 372.0 x 1 305.0 x 1 + 372.0 x 1 364.0 x 1 + 372.0 x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
30
Page 31
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type ­Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S AM560KXVGGH1EU AM580KXVGGH1EU AM600KXVGGH1EU AM260KXVGGH/EU AM280KXVGGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU
- - -
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
56 58 60
156.8 162.6 168.0
535,000 554,800 573,200
176.4 182.7 189.0
601,900 623,400 644,900
64 64 64
78.4 81.3 84.0
203.8 211.4 218.4
40.03 42.35 45.40
37.65 3 9.36 4 1.18
64.20 67.90 72.80
60.40 63.10 66.00 27 28.4 29.6
133 140 146 150 175 175
3.92 3.84 3.70
4.69 4.64 4.59
6.89 6.75 6.65 EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS4GJ5080FVA x 4 DS4GJ5080FVA x 4 DS4GJ5080FVA x 4
(7.81 x 2) x 2 (7.81 x 2) x 2 (7.81 x 2) x 2
PVE PVE PVE
(1,400 x 2) x 2 (1,400 x 2) x 2 (1,400 x 2) x 2
Propeller Propeller Propeller
Top Top Top
4 4 4
340 x 2 340 x 2 340 x 2
5,667 x 2 5,667 x 2 5,667 x 2
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
Braze connection Braze connection Braze connection
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Braze connection Braze connection Braze connection
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
31
Page 32
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
14.0 x 2 14.0 x 2 14.0 x 2 72 72 72 74 74 74
93 93 93
350.0 x 2 350.0 x 2 350.0 x 2
372.0 x 2 372.0 x 2 372.0 x 2
(1,295 x 1,795 x 765) x 2 (1,295 x 1,795 x 765) x 2 (1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2 (1,363 x 1,987 x 832) x 2 (1,363 x 1,987 x 832) x 2
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
32
Page 33
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type -
Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S
AM620KXVGGH1EU AM640KXVGGH1EU AM660KXVGGH1EU
AM120JXVHGH/EU AM120JXVHGH/EU AM140KXVGGH/EU AM200KXVGGH/EU AM220KXVGGH/EU AM220KXVGGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
62 64 66
173.6 1 79.2 185.6
592,300 611,500 633,300
195.3 201.6 208.8
666,400 687,900 712,500
64 64 64
86.8 8 9.6 92.8
225.7 233.0 241.3
42.77 46.02 4 7. 3 4
40.9 0 44.01 46.07
68.50 73.80 76.00
65.60 70.50 73.80
28.2 28.7 28.8 140 142.6 142.6 175 175 175
4.06 3.89 3.92
4.78 4.58 4.53
6.82 6.68 6.82
EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion DS-GB066FAVB x 2 + DS4GJ5080FVA x 2 + DSGB066FAVBSG x 1
DS-GB066FAVB x 2 + DS4GJ5080FVA x 2 +
DSGB066FAVBSG x 1
DS-GB066FAVB x 3 +
DS4GJ5080FVA x 2
(6.39 x 1) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1
PVE PVE PVE
(1,100 x 1) x 1 +
(1,100 x 2) x 1 + (1,400 x 2) x 1
(1,100 x 1) x 1 +
(1,100 x 2) x 1 + (1,400 x 2) x 1
(1,100 x 1) x 1 +
(1,100 x 2) x 1 + (1,400 x 2) x 1
Propeller Propeller Propeller
Top Top Top
5 5 6
220 x 1 + 290 x 1 + 340 x 1 220 x 1 + 290 x 1 + 340 x 1 255 x 1 + 290 x 1 + 340 x 1
3,667 x 1 + 4,833 x 1 + 5,667 x 1 3,667 x 1 + 4,833 x 1 + 5,667 x 1 4,250 x 1 + 4,833 x 1 + 5,667 x 1
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(830 x 1) x 1 + (620 x 2) x 2 (830 x 1) x 1 + (620 x 2) x 2 (620 x 2) x 3
Braze connection Braze connection Braze connection
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Braze connection Braze connection Braze connection
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
33
Page 34
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A)
Net Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
6.5 x 1 + 8.4 x 1 + 14.0 x 1 6.5 x 1 + 8.4 x 1 + 14.0 x 1 9.4 x 1 + 8.4 x 1 + 14.0 x 1 71 71 71 73 73 73 93 93 93
195.5 x 1 + 285.0 x 1 +
350.0 x 1
211.5 x 1 + 305.0 x 1 +
372.0 x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1 (948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
195.5 x 1 + 285.0 x 1 +
350.0 x 1
211.5 x 1 + 305.0 x 1 +
372.0 x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
241.0 x 1 + 285.0 x 1 +
350.0 x 1
261.0 x 1 + 305.0 x 1 +
372.0 x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
34
Page 35
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type -
Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S AM680KXVGGH1EU AM700KXVGGH1EU AM720KXVGGH1EU AM160KXVGGH/EU AM180KXVGGH/EU AM200KXVGGH/EU AM220KXVGGH/EU AM220KXVGGH/EU AM220KXVGGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
68 70 72
190.6 196.0 201.6
650,400 668,800 687,900
214.2 220.5 226.8
730,900 752,400 773,900
64 64 64
95.3 98.0 100.8
2 4 7.8 254.8 26 2.1
49.37 49.1 3 50.95 4 7. 2 0 46.97 49. 20
79. 20 78.80 81.70
75.60 75.30 78.90
30.6 32.2 31.5
149.6 156.8 1 59.6 175 175 175
3.86 3.99 3.96
4.54 4.69 4.61
6.75 6.74 6.63 EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS4GJ5080FVA x 3 +
DSGB066FAVB x 2
(7.81 x 1) x 1 + (6.39 x 2) x 1 +
(7.81 x 2) x 1
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 2
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 2
(6.39 x 2) x 2 + (7.81 x 2) x 1 (6.39 x 2) x 2 + (7.81 x 2) x 1
PVE PVE PVE
(1,400 x 1) x 1 +
(1,100 x 2) x 1 + (1,400 x 2) x 1
(1,100 x 2) x 2 +
(1,400 x 2) x 1
(1,100 x 2) x 2 +
(1,400 x 2) x 1
Propeller Propeller Propeller
Top Top Top
6 6 6
255 x 1 + 290 x 1 + 340 x 1 290 x 2 + 340 x 1 290 x 2 + 340 x 1
4,250 x 1 + 4,833 x 1 + 5,667 x 1 4,833 x 2 + 5,667 x 1 4,833 x 2 + 5,667 x 1
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 3
Braze connection Braze connection Braze connection
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Braze connection Braze connection Braze connection
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
35
Page 36
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A)
Net Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
8.4 x 2 + 14.0 x 1 8.4 x 2 + 14.0 x 1 8.4 x 2 + 14.0 x 1 71 72 72
73 74 74 93 94 94
255.0 x 1 + 285.0 x 1 +
350.0 x 1
275.0 x 1 + 305.0 x 1 +
372.0 x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
285.0 x 2 + 350.0 x 1 285.0 x 2 + 350.0 x 1
305.0 x 2 + 372.0 x 1 305.0 x 2 + 372.0 x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
36
Page 37
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type ­Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S AM740KXVGGH1EU AM760KXVGGH1EU AM780KXVGGH1EU AM220KXVGGH/EU AM240KXVGGH/EU AM260KXVGGH/EU AM220KXVGGH/EU AM220KXVGGH/EU AM220KXVGGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
74 76 78
2 0 7. 2 212.8 218.4
707,000 726,100 745,200
233.1 239. 4 245.7
795,400 816,900 838,400
64 64 64
103.6 106.4 109.2
269. 4 276.6 283.9
54.20 54.45 55.78
52.31 51.88 53.51
87.00 8 7. 4 0 89.50
83.80 83.10 85.80 32 3 5.9 35.6
162.2 172.6 1 7 7. 6 200 200 200
3.82 3.9 1 3 .92
4.46 4.61 4.59
6.52 6.75 6.76
EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 2
(6.39 x 2) x 2 +
(7.81 x 2) x 1
DS-GB066FAVB x 2 +
DSGB070FAVA x 2 +
DS4GJ5080FVA x 2
(6.76 x 2) x 1 +
(6.39 x 2) x 1 + (7.81 x 2) x 1
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 4
(7.81 x 2) x 1 + (6.39 x 2) x 1 +
(7.81 x 2) x 1
PVE PVE PVE
(1,100 x 2) x 2 + (1,400 x 2) x 1 (1,100 x 2) x 2 + (1,400 x 2) x 1
(1,400 x 2) x 1 + (1,100 x 2) x 1 + (1,400 x 2) x 1
Propeller Propeller Propeller
Top Top Top
6 6 6
290 x 2 + 340 x 1 340 x 1 + 290 x 1 + 340 x 1 340 x 1 + 290 x 1 + 340 x 1
4,833 x 2 + 5,667 x 1 5,667 x 1 + 4,833 x 1 + 5,667 x 1 5,667 x 1 + 4,833 x 1 + 5,667 x 1
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 3
Braze connection Braze connection Braze connection
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Braze connection Braze connection Braze connection
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
37
Page 38
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type -
Factory Charging kg
Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A)
Net Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
8.4 x 2 + 14.0 x 1
72 73 73 74 75 75 94 94 94
285.0 x 2 + 350.0 x 1
305.0 x 2 + 372.0 x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
14.0 x 1 + 8.4 x 1 +
14.0 x 1
342.0 x 1 + 285.0 x 1 +
350.0 x 1
364.0 x 1 + 305.0 x 1 +
372.0 x 1 (1,295 x 1,795 x 765) x 1 + (1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1 (1,363 x 1,987 x 832) x 1 + (1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
14.0 x 1 + 8.4 x 1 +
14.0 x 1
350.0 x 1 + 285.0 x 1 +
350.0 x 1
372.0 x 1 + 305.0 x 1 +
372.0 x 1 (1,295 x 1,795 x 765) x 1 + (1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1 (1,363 x 1,987 x 832) x 1 + (1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
38
Page 39
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type -
Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S AM800KXVGGH1EU AM820KXVGGH1EU AM840KXVGGH1EU AM280KXVGGH/EU AM300KXVAGH/EU AM240KXVGGH/EU AM220KXVGGH/EU AM220KXVGGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
80 82 84
224.2 2 29.6 235.2
765,000 783,400 802,500
252.0 258.3 264.6
859,900 881,400 902,900
64 64 64
112.1 114.8 117.6
291.5 298.5 305.8
58.10 61.15 61.40
55.22 5 7. 0 4 56.61
93.20 98.10 98.50
88.50 91.40 90.70 37 38.2 42 .1
184.6 190.6 201 225 225 225
3.86 3.75 3.83
4.56 4.53 4.67
6.66 6.59 6.80 EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 4
(7.81 x 2) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1 (7.81 x 2) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 4
DS-GB070FAVA x 2 +
DS4GJ5080FVA x 4
(6.76 x 2) x 1 + (7.81 x 2) x 2
PVE PVE PVE
(1,400 x 2) x 1 +
(1,100 x 2) x 1 + (1,400 x 2) x 1
(1,400 x 2) x 1 +
(1,100 x 2) x 1 + (1,400 x 2) x 1
(1,100 x 2) x 1 +
(1,400 x 2) x 2
Propeller Propeller Propeller
Top Top Top
6 6 6
340 x 1 + 290 x 1 + 340 x 1 340 x 1 + 290 x 1 + 340 x 1 340 x 3
5,667 x 1 + 4,833 x 1 + 5,667 x 1 5,667 x 1 + 4,833 x 1 + 5,667 x 1 5,667 x 3
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 3
Braze connection Braze connection Braze connection
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Braze connection Braze connection Braze connection
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
39
Page 40
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
40
Transmission Cable mm Remark ­Power supply intake ­Type -
Factory Charging kg
Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A)
Net Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
14.0 x 1 + 8.4 x 1 +
14.0 x 1 73 73 74 75 75 76 94 94 95
350.0 x 1 + 285.0 x 1 +
350.0 x 1
372.0 x 1 + 305.0 x 1 +
372.0 x 1 (1,295 x 1,795 x 765) x 1 + (1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1 (1,363 x 1,987 x 832) x 1 + (1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
14.0 x 1 + 8.4 x 1 +
14.0 x 1
350.0 x 1 + 285.0 x 1 +
350.0 x 1
372.0 x 1 + 305.0 x 1 +
372.0 x 1 (1,295 x 1,795 x 765) x 1 + (1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1 (1,363 x 1,987 x 832) x 1 + (1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
14.0 x 3
342.0 x 1 + 350.0 x 2
364.0 x 1 + 372.0 x 2
(1,295 x 1,795 x 765) x 3
(1,363 x 1,987 x 832) x 3
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
Page 41
2. Specifications
Premium Compact
Type Model Name
Outdoor unit module 1 Outdoor unit module 2 Outdoor unit module 3
Outdoor unit module 4 Power Supply Ø, #, V, Hz Mode -
HP HP
Perfor­mance
Maximum number of connectable indoor units EA Total capacity of the connected Indoor Units Min. kW Total capacity of the connected Indoor Units Max. kW
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W
COP (Nominal)
ESEER W/ W
Type -
Material
Fin Treatment -
Model Name -
Output kW x n
Oil
Type -
Discharge direction -
Quantity EA
Air Flow Rate
External Static Pressure Max.
Type -
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation -
Piping length (ODU-IDU)
Piping length (1st Branch-IDU) Max. m
Total piping length (System) Max. m
Level difference (ODU in highest position)
Level difference (IDU in highest position) Max. m
Level difference (IDU-IDU) Max. m
Cooling
Heating
Cooling kW Heating kW Cooling A Heating A Minimum Ssc MCA A MFA A
Heating
Body ­Base -
Fin ­Tube -
Type ­Initial charge
Max. [Equiv.]
Max. m
kW
Btu/h
kW
Btu/h
MVA
W/ W
cc x n
5
m
/min
l/s
mmAq
Pa
Type
Φ, mm (inch)
Type
Φ, mm (inch)
Type
Φ, mm (inch)
m
DVM S DVM S DVM S AM860KXVGGH1EU AM880KXVGGH1EU AM900KXVGGH1EU AM260KXVGGH/EU AM280KXVGGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU
- - -
3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50
HEAT PUMP HEAT PUMP HEAT PUMP
86 88 90
240.8 246.6 252.0
821,600 841,400 859,900
270.9 2 7 7. 2 283.5
924,300 945,800 967,300
64 64 64
120.4 123.3 126.0
313.0 320.6 327.6
62.73 65.05 68.10
58.24 59.95 61.77
100.60 104.30 109.20
93.40 9 6.10 99.00
41.8 43.2 44.4 206 213 219
250 250 250
3.84 3.79 3.70
4.65 4.62 4.59
6.81 6.72 6.65 EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin & Tube Fin & Tube Fin & Tube
Al Al Al
Cu Cu Cu
Anti-corrosion Anti-corrosion Anti-corrosion
DS4GJ5080FVA x 6 DS4GJ5080FVA x 6 DS4GJ5080FVA x 6
(7.81 x 2) x 3 (7.81 x 2) x 3 (7.81 x 2) x 3
PVE PVE PVE
(1,400 x 2) x 3 (1,400 x 2) x 3 (1,400 x 2) x 3
Propeller Propeller Propeller
Top Top Top
6 6 6
340 x 3 340 x 3 340 x 3
5,667 x 3 5,667 x 3 5,667 x 3
8 8 8
78.45 78.45 78.45
BLDC Motor BLDC Motor BLDC Motor
(620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 3
Braze connection Braze connection Braze connection
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Braze connection Braze connection Braze connection
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
- - -
Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
200 [220] 200 [220] 200 [220]
90 90 90
1,000 1,000 1,000
110 110 110 110 110 110
50 50 50
41
Page 42
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark ­Power supply intake ­Type ­Factory Charging kg Sound Pressure Cooling dB(A) Sound Pressure Heating dB(A) Sound Power dB(A) Net Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm Shipping Dimensions (WxHxD) mm Cooling Heating
2
0.75 0.75 0.75
F1, F2 F1, F2 F1, F2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
R410A R410A R410A
14.0 x 3 14.0 x 3 14.0 x 3 74 74 74 76 76 76
95 95 95
350.0 x 3 350.0 x 3 350.0 x 3
372.0 x 3 372.0 x 3 372.0 x 3
(1,295 x 1,795 x 765) x 3 (1,295 x 1,795 x 765) x 3 (1,295 x 1,795 x 765) x 3
(1,363 x 1,987 x 832) x 3 (1,363 x 1,987 x 832) x 3 (1,363 x 1,987 x 832) x 3
-5 ~ 48 -5 ~ 48 -5 ~ 48
-25 ~ 24 -25 ~ 24 -25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
42
Page 43
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM220KXVGGH2EU AM240KXVGGH2EU AM260KXVGGH2EU
Outdoor unit module 1 AM100JXVHGH/EU AM120JXVHGH/EU AM080JXVHGH/EU Outdoor unit module 2 AM120JXVHGH/EU AM120JXVHGH/EU AM180KXVGGH/EU Outdoor unit module 3 - - -
Outdoor unit module 4 - - ­Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 22 24 26
Performance
Maximum number of connectable indoor units EA 40 43 47 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 3 2 7. 2 3 7. 4 8
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name - DS-GB066FAVBSG x 2 DS-GB066FAVBSG x 2
Output kW x n (6.39 x 1) x 2 (6.39 x 1) x 2 (5.18 x 1) x 1 + (6.39 x 2) x 1
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 2 2 3
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n (830 x 1) x 2 (830 x 1) x 2 (830 x 1) x 1 + (620 x 2) x 1
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 61.6 6 7. 2 72.8
Btu/h 210,200 229,300 248,400
kW 69. 3 75.6 81.9
Btu/h 236,500 258,000 279,500
kW 30.8 33.6 36.4 kW 8 0.1 8 7. 4 94.6 kW 13.79 15.14 15.27 kW 13.45 15.12 15.11
A 22.10 24.20 24.50 A 21.50 24.20 24.30
MVA 9.8 10.6 11.9
A 46.1 50 5 7. 2
A 63 63 63 W/ W 4.47 4.44 4.77 W/ W 5 .15 5.00 5.42
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 2 +
DSGB052FAVBSG x 1
- PVE PVE PVE
cc x n
2
m
/min 170 x 1 + 220 x 1 220 x 2 170 x 1 + 290 x 1
l/s 2,833 x 1 + 3,667 x 1 3,667 x 2 2,833 x 1 + 4,833 x 1
mmAq 8 8 8
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
(1,100 x 1) x 2 (1,100 x 1) x 2 (1,100 x 1) x 1 + (1,100 x 2) x 1
15.88 (5/8) 15.88 (5/8) 19.05 (3/4)
28.58 (1-1/8) 34.92 (1-3/8) 34.92 (1-3/8)
- - -
43
Page 44
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 63 65 66 dB(A) 65 67 68
0.75 0.75 0.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 6.5 x 2 6.5 x 2 6.5 x 1 + 8.4 x 1 Sound Pressure Sound Pressure Sound Power dB(A) 83 84 89 Net Weight kg 195.5 x 2 195.5 x 2 195.5 x 1 + 285.0 x 1 Shipping Weight kg 211.5 x 2 211.5 x 2 211.5 x 1 + 305.0 x 1
Net Dimensions (WxHxD) mm (880 x 1,695 x 765) x 2 (880 x 1,695 x 765) x 2
Shipping Dimensions (WxHxD) mm (948 x 1,887 x 832) x 2 (948 x 1,887 x 832) x 2
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
44
Page 45
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM280KXVGGH2EU AM300KXVGGH2EU AM320KXVGGH2EU
Outdoor unit module 1 AM080JXVHGH/EU AM120JXVHGH/EU AM140KXVGGH/EU Outdoor unit module 2 AM200KXVGGH/EU AM180KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 3 - - -
Outdoor unit module 4 - - ­Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 28 30 32
Performance
Maximum number of connectable indoor units EA 51 54 58 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 1 6 7. 2 4 7. 4 8
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 3 3 4
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n (830 x 1) x 1 + (620 x 2) x 1 (830 x 1) x 1 + (620 x 2) x 1 (620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 78.4 84.0 90.4
Btu/h 267,500 286,600 308,500
kW 88.2 94.5 101.7
Btu/h 301,000 322,400 347,000
kW 39. 2 42.0 45.2 kW 101.9 109.2 117.5 kW 17.09 18.25 19. 57 kW 17.34 18.08 20.14
A 2 7. 4 0 29. 20 31.40 A 27.90 29.00 32.30
MVA 11.2 1 4.1 14.2
A 60 64.2 64.2
A 75 75 75 W/ W 4.59 4.60 4.62 W/ W 5.09 5.23 5.05
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 2 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1
- PVE PVE PVE
cc x n
m
mmAq 8 8 8
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 1) x 1 + (1,100 x 2) x 1 (1,100 x 1) x 1 + (1,100 x 2) x 1 (1,100 x 1) x 1 + (1,100 x 2) x 1
2
/min 170 x 1 + 290 x 1 220 x 1 + 290 x 1 255 x 1 + 290 x 1
l/s 2,833 x 1 + 4,833 x 1 3,667 x 1 + 4,833 x 1 4,250 x 1 + 4,833 x 1
Pa 78.45 78.45 78.45
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
34.92 (1-3/8) 34.92 (1-3/8) 34.92 (1-3/8)
- - -
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
DS-GB066FAVB x 2 + DSGB066FAVBSG x 1
DS-GB066FAVB x 3
45
Page 46
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 66 67 66 dB(A) 68 69 68
0.75 0.75 0.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 1
(1,295 x 1,695 x 765) x 2
(1,363 x 1,887 x 832) x 2
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 6.5 x 1 + 8.4 x 1 6.5 x 1 + 8.4 x 1 9.4 x 1 + 8.4 x 1 Sound Pressure Sound Pressure Sound Power dB(A) 89 90 90 Net Weight kg 195.5 x 1 + 285.0 x 1 195.5 x 1 + 285.0 x 1 241.0 x 1 + 285.0 x 1 Shipping Weight kg 211.5 x 1 + 305.0 x 1 211.5 x 1 + 305.0 x 1 261.0 x 1 + 305.0 x 1
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
46
Page 47
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM340KXVGGH2EU AM360KXVGGH2EU AM380KXVGGH2EU
Outdoor unit module 1 AM080JXVHGH/EU AM180KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 2 AM080JXVHGH/EU AM180KXVGGH/EU AM200KXVGGH/EU Outdoor unit module 3 AM180KXVGGH/EU - -
Outdoor unit module 4 - - ­Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 34 36 38
Performance
Maximum number of connectable indoor units EA 61 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 6 0 7. 2 5 7. 0 2
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 4 4 4
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n (830 x 1) x 2 + (620 x 2) x 1 (620 x 2) x 2 (620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 95.2 100.8 106.4
Btu/h 324,800 343,900 363,100
kW 1 0 7.1 113.4 119.7
Btu/h 365,400 386,900 408,400
kW 4 7. 6 50.4 53.2 kW 123.8 131.0 138.3 kW 19.86 21.36 23.18 kW 19.70 21.04 23.27
A 31.90 34.20 37.10 A 31.70 33.80 3 7. 4 0
MVA 15 1 7. 6 1 6.9
A 75.2 78.4 81.2
A 90 90 90 W/ W 4.79 4.72 4.59 W/ W 5.44 5.39 5.1 4
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 2 + DSGB052FAVBSG x 2
(5.18 x 1) x 2 + (6.39 x 2) x 1 (6.39 x 2) x 2 (6.39 x 2) x 2
- PVE PVE PVE
cc x n
m
mmAq 8 8 8
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 1) x 2 + (1,100 x 2) x 1 (1,100 x 2) x 2 (1,100 x 2) x 2
2
/min 170 x 2 + 290 x 1 290 x 2 290 x 2
l/s 2,833 x 2 + 4,833 x 1 4,833 x 2 4,833 x 2
Pa 78.45 78.45 78.45
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
34.92 (1-3/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
DS-GB066FAVB x 4 DS-GB066FAVB x 4
47
Page 48
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 66 68 68 dB(A) 68 70 70
(880 x 1,695 x 765) x 2 +
(948 x 1,887 x 832) x 2 +
0.75 0.75 0.75
(1,295 x 1,695 x 765) x 1
(1,363 x 1,887 x 832) x 1
(1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2
(1,363 x 1,887 x 832) x 2 (1,363 x 1,887 x 832) x 2
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 6.5 x 2 + 8.4 x 1 8.4 x 2 8.4 x 2 Sound Pressure Sound Pressure Sound Power dB(A) 90 92 92 Net Weight kg 195.5 x 2 + 285.0 x 1 285.0 x 2 285.0 x 2 Shipping Weight kg 211.5 x 2 + 305.0 x 1 305.0 x 2 305.0 x 2
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
48
Page 49
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM400KXVGGH2EU AM420KXVGGH2EU AM440KXVGGH2EU
Outdoor unit module 1 AM080JXVHGH/EU AM080JXVHGH/EU AM080JXVHGH/EU Outdoor unit module 2 AM140KXVGGH/EU AM140KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 3 AM180KXVGGH/EU AM200KXVGGH/EU AM180KXVGGH/EU
Outdoor unit module 4 - - ­Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 40 42 44
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 5 9 7. 3 6 7. 3 9
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 5 5 5
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n (830 x 1) x 1 + (620 x 2) x 2 (830 x 1) x 1 + (620 x 2) x 2 (830 x 1) x 1 + (620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 112.8 118.4 123.2
Btu/h 384,900 404,000 420,400
kW 126.9 133.2 138.6
Btu/h 433,000 454,500 472,900
kW 56.4 59. 2 61.6 kW 146.6 153.9 160.2 kW 24.1 6 25.98 25.95 kW 24.73 26.96 25.63
A 38.80 41.70 41.60 A 39.70 43.30 41.20
MVA 1 7. 3 16.6 20.7
A 82.2 85 96.4
A 90 100 125 W/ W 4.67 4.56 4.75 W/ W 5 .13 4.94 5.41
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 3 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 1) x 1 +
(6.39 x 2) x 1
- PVE PVE PVE
cc x n
m
mmAq 8 8 8
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 1) x 2 + (1,100 x 2) x 1 (1,100 x 1) x 2 + (1,100 x 2) x 1 (1,100 x 1) x 1 + (1,100 x 2) x 2
2
/min 170 x 1 + 255 x 1 + 290 x 1 170 x 1 + 255 x 1 + 290 x 1 170 x 1 + 290 x 2
l/s
2,833 x 1 + 4,250 x 1 + 4,833 x 1 2,833 x 1 + 4,250 x 1 + 4,833 x 1 2,833 x 1 + 4,833 x 2
Pa 78.45 78.45 78.45
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
DS-GB066FAVB x 3 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 1) x 1 +
(6.39 x 2) x 1
DS-GB066FAVB x 4 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 2) x 2
49
Page 50
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 67 67 68 dB(A) 69 69 70
0.75 0.75 0.75
195.5 x 1 + 241.0 x 1 +
285.0 x 1
211.5 x 1 + 261.0 x 1 +
305.0 x 1 (880 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 2 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 2
195.5 x 1 + 241.0 x 1 +
285.0 x 1
211.5 x 1 + 261.0 x 1 +
305.0 x 1 (880 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 2 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 2
195.5 x 1 + 285.0 x 2
211.5 x 1 + 305.0 x 2
(880 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 2 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 2
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 6.5 x 1 + 9.4 x 1 + 8.4 x 1 6.5 x 1 + 9.4 x 1 + 8.4 x 1 6.5 x 1 + 8.4 x 2 Sound Pressure Sound Pressure Sound Power dB(A) 90 90 92
Net Weight kg
Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
50
Page 51
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM460KXVGGH2EU AM480KXVGGH2EU AM500KXVGGH2EU
Outdoor unit module 1 AM080JXVHGH/EU AM080JXVHGH/EU AM140KXVGGH/EU Outdoor unit module 2 AM180KXVGGH/EU AM200KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 3 AM200KXVGGH/EU AM200KXVGGH/EU AM180KXVGGH/EU
Outdoor unit module 4 - - ­Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 46 48 50
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 1 9 7. 0 2 7. 4 0
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 5 5 6
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n (830 x 1) x 1 + (620 x 2) x 2 (830 x 1) x 1 + (620 x 2) x 2 (620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 128.8 134.4 140.8
Btu/h 439,500 458,600 480,400
kW 144.9 151.2 158.4
Btu/h 494,400 515,900 540,500
kW 64.4 6 7. 2 70.4 kW 167.4 174.7 183.0 kW 2 7. 7 7 29. 59 30.25 kW 27.86 30.09 30.66
A 44.50 47.40 48.50 A 44.80 48.40 49.20
MVA 20 19. 3 23
A 99.2 102 103.4
A 125 125 125 W/ W 4.64 4.54 4.65 W/ W 5.20 5.02 5.1 7
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 4 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 2) x 2 (5.18 x 1) x 1 + (6.39 x 2) x 2 (6.39 x 1) x 1 + (6.39 x 2) x 2
- PVE PVE PVE
cc x n
m
mmAq 8 8 8
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 1) x 1 + (1,100 x 2) x 2 (1,100 x 1) x 1 + (1,100 x 2) x 2 (1,100 x 1) x 1 + (1,100 x 2) x 2
2
/min 170 x 1 + 290 x 2 170 x 1 + 290 x 2 255 x 1 + 290 x 2
l/s
Pa 78.45 78.45 78.45
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
2,833 x 1 + 4,833 x 2 2,833 x 1 + 4,833 x 2 4,250 x 1 + 4,833 x 2
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
DS-GB066FAVB x 4 +
DSGB052FAVBSG x 1
DS-GB066FAVB x 5
51
Page 52
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 68 68 69 dB(A) 70 70 71
0.75 0.75 0.75
(880 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 2 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 2
(880 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 2 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 2
(1,295 x 1,695 x 765) x 3
(1,363 x 1,887 x 832) x 3
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 6.5 x 1 + 8.4 x 2 6.5 x 1 + 8.4 x 2 9.4 x 1 + 8.4 x 2 Sound Pressure Sound Pressure Sound Power dB(A) 92 92 92 Net Weight kg 195.5 x 1 + 285.0 x 2 195.5 x 1 + 285.0 x 2 241.0 x 1 + 285.0 x 2 Shipping Weight kg 211.5 x 1 + 305.0 x 2 211.5 x 1 + 305.0 x 2 261.0 x 1 + 305.0 x 2
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
52
Page 53
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM520KXVGGH2EU AM540KXVGGH2EU AM560KXVGGH2EU
Outdoor unit module 1 AM080JXVHGH/EU AM080JXVHGH/EU AM120JXVHGH/EU Outdoor unit module 2 AM180KXVGGH/EU AM200KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 3 AM260KXVGGH/EU AM260KXVGGH/EU AM260KXVGGH/EU
Outdoor unit module 4 - - ­Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 52 54 56
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 3 3 7.1 6 7. 2 1
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 5 5 5
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n (830 x 1) x 1 + (620 x 2) x 2 (830 x 1) x 1 + (620 x 2) x 2 (830 x 1) x 1 + (620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type
Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 145.6 151.2 156.8
Btu/h 496,800 515,900 535,000
kW 163.8 17 0.1 176.4
Btu/h 558,900 580,400 601,900
kW 72.8 75.6 78.4 kW 189.3 196.6 203.8 kW 32.60 34.42 35.58 kW 32.17 34.40 35.14
A 52.30 55.20 5 7. 0 0 A 51.70 55.30 56.40
MVA 2 4.1 23.4 26.3
A 117.2 120 124.2
A 150 150 150 W/ W 4.47 4.39 4.41 W/ W 5.09 4.94 5.02
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 2 + DS4GJ5080FVA x 2 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1 (5.18 x 1) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1
- PVE PVE PVE
cc x n
m
mmAq 8 8 8
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 1) x 1 + (1,100 x 2) x 1 +
(1,400 x 2) x 1
2
/min 170 x 1 + 290 x 1 + 340 x 1 170 x 1 + 290 x 1 + 340 x 1 220 x 1 + 290 x 1 + 340 x 1
l/s
2,833 x 1 + 4,833 x 1 + 5,667 x 1 2,833 x 1 + 4,833 x 1 + 5,667 x 1 3,667 x 1 + 4,833 x 1 + 5,667 x 1
Pa 78.45 78.45 78.45
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
DS-GB066FAVB x 2 + DS4GJ5080FVA x 2 +
DSGB052FAVBSG x 1
(1,100 x 1) x 1 + (1,100 x 2) x 1 +
(1,400 x 2) x 1
DS-GB066FAVB x 2 + DS4GJ5080FVA x 2 +
DSGB066FAVBSG x 1
(1,100 x 1) x 1 + (1,100 x 2) x 1 +
(1,400 x 2) x 1
53
Page 54
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 71 71 71 dB(A) 73 73 73
195.5 x 1 + 285.0 x 1 + 350.0 x 1 195.5 x 1 + 285.0 x 1 + 350.0 x 1 195.5 x 1 + 285.0 x 1 + 350.0 x 1
211.5 x 1 + 305.0 x 1 + 372.0 x 1 211.5 x 1 + 305.0 x 1 + 372.0 x 1 211.5 x 1 + 305.0 x 1 + 372.0 x 1
(1,295 x 1,695 x 765) x 1 +
(1,363 x 1,887 x 832) x 1 +
0.75 0.75 0.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 6.5 x 1 + 8.4 x 1 + 14.0 x 1 6.5 x 1 + 8.4 x 1 + 14.0 x 1 6.5 x 1 + 8.4 x 1 + 14.0 x 1 Sound Pressure Sound Pressure Sound Power dB(A) 93 93 93 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
54
Page 55
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM580KXVGGH2EU AM600KXVGGH2EU AM620KXVGGH2EU
Outdoor unit module 1 AM080JXVHGH/EU AM180KXVGGH/EU AM080JXVHGH/EU Outdoor unit module 2 AM240KXVGGH/EU AM180KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 3 AM260KXVGGH/EU AM240KXVGGH/EU AM180KXVGGH/EU
Outdoor unit module 4 - - AM180KXVGGH/EU Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 58 60 62
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 2 9 7. 2 2 7. 3 5
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 5 6 7
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n (830 x 1) x 1 + (620 x 2) x 2 (620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type
Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 162.4 168.0 173.6
Btu/h 554,100 573,200 592,300
kW 182.7 189.0 195.3
Btu/h 623,400 644,900 666,400
kW 81.2 84.0 86.8 kW 211.1 218.4 225.7 kW 3 7. 9 2 37.36 36.63 kW 37.08 36.47 36.15
A 60.90 59.9 0 58.70 A 5 9.50 58.50 58.10
MVA 27.8 3 0.1 29. 5
A 133 133.4 135.6
A 150 150 150 W/ W 4.28 4.50 4.74 W/ W 4.9 3 5 .18 5.40
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB070FAVA x 2 + DS4GJ5080FVA x 2 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.76 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 2) x 2 + (6.76 x 2) x 1
- PVE PVE PVE
cc x n
m
mmAq 8 8 8
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 1) x 1 + (1,100 x 2) x 1 +
(1,400 x 2) x 1
2
/min 170 x 1 + 340 x 2 290 x 2 + 340 x 1 170 x 1 + 290 x 3
l/s
Pa 78.45 78.45 78.45
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
2,833 x 1 + 5,667 x 2 4,833 x 2 + 5,667 x 1 2,833 x 1 + 4,833 x 3
19.05 (3/4) 19.05 (3/4) 22.22 (7/8)
41.28 (1-5/8) 41.28 (1-5/8) 53.98 (2-1/8)
- - -
DS-GB066FAVB x 4 +
DSGB070FAVA x 2
(1,100 x 2) x 3 (1,100 x 1) x 1 + (1,100 x 2) x 3
DS-GB066FAVB x 6 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 2) x 3
(830 x 1) x 1 + (620 x 2) x 3
55
Page 56
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 72 72 70 dB(A) 74 74 72
195.5 x 1 + 342.0 x 1 + 350.0 x 1 285.0 x 2 + 342.0 x 1 195.5 x 1 + 285.0 x 3
211.5 x 1 + 364.0 x 1 + 372.0 x 1 305.0 x 2 + 364.0 x 1 211.5 x 1 + 305.0 x 3
0.75 0.75 0.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 2 (948 x 1,887 x 832) x 1 + (1,363 x 1,987 x 832) x 2
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
(880 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 3 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 3
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 6.5 x 1 + 14.0 x 2 8.4 x 2 + 14.0 x 1 6.5 x 1 + 8.4 x 3 Sound Pressure Sound Pressure Sound Power dB(A) 93 94 94 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
56
Page 57
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM640KXVGGH2EU AM660KXVGGH2EU AM680KXVGGH2EU
Outdoor unit module 1 AM080JXVHGH/EU AM120JXVHGH/EU AM140KXVGGH/EU Outdoor unit module 2 AM180KXVGGH/EU AM180KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 3 AM180KXVGGH/EU AM180KXVGGH/EU AM180KXVGGH/EU
Outdoor unit module 4 AM200KXVGGH/EU AM180KXVGGH/EU AM180KXVGGH/EU Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 64 66 68
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 2 1 7. 2 5 7. 3 6
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 7 7 8
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 1 79.2 184.8 191.2
Btu/h 611,500 630,600 652,400
kW 201.6 2 0 7.9 215.1
Btu/h 687,900 709,400 734,000
kW 89. 6 92.4 95.6 kW 233.0 240.2 248.6 kW 38.45 39.61 40.93 kW 38.38 3 9.12 4 1.18
A 61.60 63.40 65.60 A 61.70 62.80 66.10
MVA 28.8 31.7 31.8
A 138.4 142.6 142.6
A 175 175 175 W/ W 4.66 4.67 4.67 W/ W 5.25 5.31 5.22
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 6 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 2) x 3 (6.39 x 1) x 1 + (6.39 x 2) x 3 (6.39 x 1) x 1 + (6.39 x 2) x 3
- PVE PVE PVE
cc x n
m
mmAq 8 8 8
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 1) x 1 + (1,100 x 2) x 3 (1,100 x 1) x 1 + (1,100 x 2) x 3 (1,100 x 1) x 1 + (1,100 x 2) x 3
2
/min 170 x 1 + 290 x 3 220 x 1 + 290 x 3 255 x 1 + 290 x 3
l/s
Pa 78.45 78.45 78.45
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
2,833 x 1 + 4,833 x 3 3,667 x 1 + 4,833 x 3 4,250 x 1 + 4,833 x 3
(830 x 1) x 1 +
(620 x 2) x 3
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
DS-GB066FAVB x 6 +
DSGB066FAVBSG x 1
(830 x 1) x 1 +
(620 x 2) x 3
DS-GB066FAVB x 7
(620 x 2) x 4
57
Page 58
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 70 70 70 dB(A) 72 72 72
0.75 0.75 0.75
195.5 x 1 + 285.0 x 3 195.5 x 1 + 285.0 x 3 241.0 x 1 + 285.0 x 3
211.5 x 1 + 305.0 x 3 211.5 x 1 + 305.0 x 3 261.0 x 1 + 305.0 x 3 (880 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 3 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 3
(880 x 1,695 x 765) x 1 + (1,295 x 1,695 x 765) x 3 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 3
(1,295 x 1,695 x 765) x 4
(1,363 x 1,887 x 832) x 4
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 6.5 x 1 + 8.4 x 3 6.5 x 1 + 8.4 x 3 9.4 x 1 + 8.4 x 3 Sound Pressure Sound Pressure Sound Power dB(A) 94 94 94 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
58
Page 59
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM700KXVGGH2EU AM720KXVGGH2EU AM740KXVGGH2EU
Outdoor unit module 1 AM080JXVHGH/EU AM180KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 2 AM180KXVGGH/EU AM180KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 3 AM180KXVGGH/EU AM180KXVGGH/EU AM180KXVGGH/EU
Outdoor unit module 4 AM260KXVGGH/EU AM180KXVGGH/EU AM200KXVGGH/EU Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 70 72 74
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 3 1 7. 2 5 7. 1 3
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 7 8 8
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type
Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 196.0 201.6 2 0 7. 2
Btu/h 668,800 687,900 707,000
kW 220.5 226.8 233.1
Btu/h 752,400 773,900 795,400
kW 98.0 100.8 103.6 kW 254.8 2 62.1 269.4 kW 43.28 42.72 44.54 kW 42.69 42.08 44.31
A 6 9.40 68.40 71.30 A 68.60 67.60 71.20
MVA 32.9 35.2 34.5
A 156.4 156.8 159.6
A 175 175 200 W/ W 4.53 4.72 4.65 W/ W 5 .17 5.39 5.26
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 4 + DS4GJ5080FVA x 2 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 2) x 2 + (7.81 x 2) x 1
- PVE PVE PVE
cc x n
m
mmAq 8 8 8
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 1) x 1 + (1,100 x 2) x 2 +
(1,400 x 2) x 1
2
/min 170 x 1 + 290 x 2 + 340 x 1 290 x 4 290 x 4
l/s
2,833 x 1 + 4,833 x 2 + 5,667 x 1 4,833 x 4 4,833 x 4
Pa 78.45 78.45 78.45
(830 x 1) x 1 + (620 x 2) x 3 (620 x 2) x 4 (620 x 2) x 4
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
DS-GB066FAVB x 8 DS-GB066FAVB x 8
(6.39 x 2) x 4 (6.39 x 2) x 4
(1,100 x 2) x 4 (1,100 x 2) x 4
59
Page 60
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 72 71 71 dB(A) 74 73 73
195.5 x 1 + 285.0 x 2 + 350.0 x 1 285.0 x 4 285.0 x 4
211.5 x 1 + 305.0 x 2 + 372.0 x 1 305.0 x 4 305.0 x 4
(1,295 x 1,695 x 765) x 2 +
(1,363 x 1,887 x 832) x 2 +
0.75 0.75 0.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 4 (1,295 x 1,695 x 765) x 4
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 4 (1,363 x 1,887 x 832) x 4
(1,363 x 1,987 x 832) x 1
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 6.5 x 1 + 8.4 x 2 + 14.0 x 1 8.4 x 4 8.4 x 4 Sound Pressure Sound Pressure Sound Power dB(A) 94 95 95 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
60
Page 61
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM760KXVGGH2EU AM780KXVGGH2EU AM800KXVGGH2EU
Outdoor unit module 1 AM180KXVGGH/EU AM180KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 2 AM180KXVGGH/EU AM200KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 3 AM200KXVGGH/EU AM200KXVGGH/EU AM180KXVGGH/EU
Outdoor unit module 4 AM200KXVGGH/EU AM200KXVGGH/EU AM260KXVGGH/EU Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 76 78 80
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 0 2 6.92 7. 2 2
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name - DS-GB066FAVB x 8 DS-GB066FAVB x 8
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 8 8 8
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 212.8 218.4 224.0
Btu/h 726,100 745,200 764,300
kW 239. 4 245.7 252.0
Btu/h 816,900 838,400 859,900
kW 106.4 109.2 112.0 kW 276.6 283.9 291.2 kW 46.36 48.18 49.3 7 kW 46.54 48.77 48.62
A 74.20 7 7. 1 0 79.10 A 74.80 78.40 78.10
MVA 33.8 33 .1 38.6
A 162.4 165.2 1 7 7. 6
A 200 200 200 W/ W 4.59 4.53 4.54 W/ W 5.14 5.04 5 .18
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 6 +
DS4GJ5080FVA x 2
(6.39 x 2) x 4 (6.39 x 2) x 4 (6.39 x 2) x 3 + (7.81 x 2) x 1
- PVE PVE PVE
cc x n
2
m
/min 290 x 4 290 x 4 290 x 3 + 340 x 1
l/s
mmAq 8 8 8
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
(1,100 x 2) x 4 (1,100 x 2) x 4 (1,100 x 2) x 3 + (1,400 x 2) x 1
4,833 x 4 4,833 x 4 4,833 x 3 + 5,667 x 1
(620 x 2) x 4 (620 x 2) x 4 (620 x 2) x 4
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
61
Page 62
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 71 71 72 dB(A) 73 73 74
0.75 0.75 0.75
285.0 x 4 285.0 x 4 285.0 x 3 + 350.0 x 1
305.0 x 4 305.0 x 4 305.0 x 3 + 372.0 x 1 (1,295 x 1,695 x 765) x 3 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 3 +
(1,363 x 1,987 x 832) x 1
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 8.4 x 4 8.4 x 4 8.4 x 3 + 14.0 x 1 Sound Pressure Sound Pressure Sound Power dB(A) 95 95 95 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm (1,295 x 1,695 x 765) x 4 (1,295 x 1,695 x 765) x 4
Shipping Dimensions (WxHxD) mm (1,363 x 1,887 x 832) x 4 (1,363 x 1,887 x 832) x 4
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
62
Page 63
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S DVM S Model Name AM820KXVGGH2EU AM840KXVGGH2EU AM860KXVGGH2EU
Outdoor unit module 1 AM180KXVGGH/EU AM180KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 2 AM180KXVGGH/EU AM200KXVGGH/EU AM200KXVGGH/EU Outdoor unit module 3 AM200KXVGGH/EU AM200KXVGGH/EU AM220KXVGGH/EU
Outdoor unit module 4 AM260KXVGGH/EU AM260KXVGGH/EU AM260KXVGGH/EU Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
HP HP 82 84 86
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7. 1 2 7. 0 2 6.92
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller
Discharge direction - To p To p To p
Quantity EA 8 8 8
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 229.6 235.2 240.8
Btu/h 783,400 802,500 821,600
kW 258.3 264.6 2 70.9
Btu/h 881,400 902,900 924,300
kW 114.8 117.6 120.4 kW 298.5 305.8 313.0 kW 51.19 53.01 56.26 kW 50.85 53.08 56.19
A 82.00 84.90 90.20 A 81.70 85.30 90.20
MVA 3 7.9 3 7. 2 3 7. 7
A 180.4 183.2 185.8
A 200 225 225 W/ W 4.49 4.44 4.28 W/ W 5.08 4.98 4.82
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate EGI Steel Plate
- Al Al Al
- Cu Cu Cu
DS-GB066FAVB x 6 +
DS4GJ5080FVA x 2
(6.39 x 2) x 3 + (7.81 x 2) x 1 (6.39 x 2) x 3 + (7.81 x 2) x 1 (6.39 x 2) x 3 + (7.81 x 2) x 1
- PVE PVE PVE
cc x n
m
mmAq 8 8 8
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 2) x 3 + (1,400 x 2) x 1 (1,100 x 2) x 3 + (1,400 x 2) x 1 (1,100 x 2) x 3 + (1,400 x 2) x 1
2
/min 290 x 3 + 340 x 1 290 x 3 + 340 x 1 290 x 3 + 340 x 1
l/s
Pa 78.45 78.45 78.45
m 200 [220] 200 [220] 200 [220] m 90 90 90 m 1,000 1,000 1,000 m 110 110 110 m 110 110 110 m 50 50 50
4,833 x 3 + 5,667 x 1 4,833 x 3 + 5,667 x 1 4,833 x 3 + 5,667 x 1
(620 x 2) x 4 (620 x 2) x 4 (620 x 2) x 4
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
DS-GB066FAVB x 6 +
DS4GJ5080FVA x 2
DS-GB066FAVB x 6 +
DS4GJ5080FVA x 2
63
Page 64
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 72 72 72 dB(A) 74 74 74
(1,295 x 1,695 x 765) x 3 +
(1,363 x 1,887 x 832) x 3 +
0.75 0.75 0.75
285.0 x 3 + 350.0 x 1 285.0 x 3 + 350.0 x 1 285.0 x 3 + 350.0 x 1
305.0 x 3 + 372.0 x 1 305.0 x 3 + 372.0 x 1 305.0 x 3 + 372.0 x 1
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 3 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 3 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 3 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 3 +
(1,363 x 1,987 x 832) x 1
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 8.4 x 3 + 14.0 x 1 8.4 x 3 + 14.0 x 1 8.4 x 3 + 14.0 x 1 Sound Pressure Sound Pressure Sound Power dB(A) 95 95 95 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
64
Page 65
2. Specifications
Premium Energy Efficiency
Type DVM S DVM S Model Name AM880KXVGGH2EU AM900KXVGGH2EU
Outdoor unit module 1 AM180KXVGGH/EU AM180KXVGGH/EU Outdoor unit module 2 AM200KXVGGH/EU AM200KXVGGH/EU Outdoor unit module 3 AM240KXVGGH/EU AM260KXVGGH/EU
Outdoor unit module 4 AM260KXVGGH/EU AM260KXVGGH/EU Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP
HP HP 88 90
Performance
Maximum number of connectable indoor units EA 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEER W/ W 7.1 1 7.1 1
Type - Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller
Discharge direction - To p To p
Quantity EA 8 8
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor
Output W x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Cooling
Heating
Min. Max. Cooling Heating Cooling Heating Minimum Ssc MCA MFA Cooling Heating
Body Base
Fin Tube
Type Initial charge
Max.
Max. [Equiv.] Max. Max. Max. Max. Max.
kW 246.4 252.0
Btu/h 840,800 859,900
kW 27 7. 2 283.5
Btu/h 945,800 967,300
kW 123.2 126.0 kW 320.3 327.6 kW 56.51 57.84 kW 55.76 5 7. 3 9
A 90.60 92.70 A 89.50 92.20
MVA 41.6 41.3
A 196.2 201.2
A 225 225 W/ W 4.36 4.36 W/ W 4.97 4.94
- EGI Steel Plate EGI Steel Plate
- EGI Steel Plate EGI Steel Plate
- Al Al
- Cu Cu
DS-GB066FAVB x 4 +
DSGB070FAVA x 2 + DS4GJ5080FVA x 2
(6.39 x 2) x 2 + (6.76 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 2) x 2 + (7.81 x 2) x 2
- PVE PVE
cc x n
2
m
/min 290 x 2 + 340 x 2 290 x 2 + 340 x 2
l/s
mmAq 8 8
Pa 78.45 78.45
Type Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection
Φ, mm (inch)
Type - -
Φ, mm (inch)
m 200 [220] 200 [220] m 90 90 m 1,000 1,000 m 110 110 m 110 110 m 50 50
(1,100 x 2) x 3 + (1,400 x 2) x 1 (1,100 x 2) x 2 + (1,400 x 2) x 2
4,833 x 2 + 5,667 x 2 4,833 x 2 + 5,667 x 2
(620 x 2) x 4 (620 x 2) x 4
22.22 (7/8) 22.22 (7/8)
53.98 (2-1/8) 53.98 (2-1/8)
- -
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 4
65
Page 66
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit
dB(A) 73 73 dB(A) 75 75
285.0 x 2 + 342.0 x 1 + 350.0 x 1 285.0 x 2 + 350.0 x 2
305.0 x 2 + 364.0 x 1 + 372.0 x 1 305.0 x 2 + 372.0 x 2 (1,295 x 1,695 x 765) x 2 +
(1,363 x 1,887 x 832) x 2 +
0.75 0.75
(1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 2
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 2
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 Power supply intake ­Type - R410A R410A Factory Charging kg 8.4 x 2 + 14.0 x 2 8.4 x 2 + 14.0 x 2 Sound Pressure Sound Pressure Sound Power dB(A) 96 96 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24
Cooling Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
66
Page 67
2. Specifications
Standard
Type DVM S DVM S DVM S
AM080JXVAGH/EU AM100JXVAGH/EU AM120JXVAGH/EU
Outdoor unit module 1 - - -
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 14 18 21 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 - - ­Outdoor unit module 3 - - ­Outdoor unit module 4 - - -
HP HP 8 10 12
Cooling
Capacity (Nominal)
Heating
Min. kW 11.2 14.0 16.8 Max. kW 2 9.1 36.4 43.7
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 4.48 4.09 4 .12 COP (Nominal) Heating W/W 4.94 4.74 4.71 ESEER W/ W 7.85 7. 2 5 7. 0 3
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion Model Name - DS-GA046FAVADO x 1 DS-GB066FAVB x 1 DS-GB066FAVB x 1 Output kW x n 4.39 x 1 6.39 x 1 6.39 x 1
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 1 1 1
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n 830 x 1 830 x 1 830 x 1
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 5.00 6.85 8.16 Heating kW 5.10 6.65 8.03 Cooling A 8.00 11.00 13.10 Heating A 8.20 10.70 12.90 Minimum Ssc MCA A 18.0 2 1.1 25.0 MFA A 25 32 32
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 22.4 28.0 33.6
Btu/h 76,400 95,500 114,600
kW 25.2 31.5 37.8
Btu/h 86,000 107,500 129,000
MVA 3 .1 4.5 5.3
cc x n 900 x 1 1,100 x 1 1,100 x 1
2
m
/min 170 170 220
l/s 2,833 2,833 3,667
mmAq 8 8 8
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
9.52 (3/8) 9.52 (3/8) 12.70 (1/2)
19.05 (3/4) 22.22 (7/8) 28.58 (1-1/8)
- - -
67
Page 68
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 5.5 5.5 6.5 Sound Pressure Cooling dB(A) 57 58 62 Sound Pressure Heating dB(A) 59 60 64 Sound Power dB(A) 77 79 81 Net Weight kg 186.0 1 9 7. 0 210.0 Shipping Weight kg 202.0 213.0 226.0 Net Dimensions (WxHxD) mm 880 x 1,695 x 765 880 x 1,695 x 765 880 x 1,695 x 765 Shipping Dimensions (WxHxD) mm 948 x 1,887 x 832 948 x 1,887 x 832 948 x 1,887 x 832 Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.75 0.75 0.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
68
Page 69
2. Specifications
Standard
Type DVM S DVM S DVM S
AM140KXVAGH/EU AM160KXVAGH/EU AM180KXVAGH/EU
Outdoor unit module 1 - - -
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 26 29 32 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 - - ­Outdoor unit module 3 - - ­Outdoor unit module 4 - - -
HP HP 14 16 18
Cooling
Capacity (Nominal)
Heating
Min. kW 20.0 22.5 25.2 Max. kW 52.0 58.5 65.5
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.66 3.72 4.00 COP (Nominal) Heating W/W 4.43 4.34 4.76 ESEER W/ W 7. 0 2 6.81 6.61
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion Model Name - DS-GB066FAVB x 1 DS4GJ5080FVA x 1 DS4G J5080FVA x 1 Output kW x n 6.39 x 1 7.81 x 1 7.81 x 1
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 2 2 2
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n 620 x 2 620 x 2 620 x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 10.93 12.10 12.60 Heating kW 10.16 11.61 11.91 Cooling A 17.50 1 9.40 20.20 Heating A 16.30 18.60 19.10 Minimum Ssc MCA A 25.0 32.0 39. 2 MFA A 32 40 50
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 40.0 45.0 50.4
Btu/h 136,500 153,500 172,000
kW 45.0 50.4 56.7
Btu/h 153,500 172,000 193,500
MVA 5.4 7. 2 8.8
cc x n 1,100 x 1 1,400 x 1 1,400 x 1
2
m
/min 255 255 290
l/s 4,250 4,250 4,833
mmAq 8 8 8
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
12.70 (1/2) 12.70 (1/2) 15.88 (5/8)
28.58 (1-1/8) 28.58 (1-1/8) 28.58 (1-1/8)
- - -
69
Page 70
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 7. 7 8.4 8.4 Sound Pressure Cooling dB(A) 61 63 64 Sound Pressure Heating dB(A) 63 65 66 Sound Power dB(A) 81 83 84 Net Weight kg 226.0 253.0 255.0 Shipping Weight kg 246.0 273.0 275.0 Net Dimensions (WxHxD) mm 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,695 x 765 Shipping Dimensions (WxHxD) mm 1,363 x 1,887 x 832 1,363 x 1,887 x 832 1,363 x 1,887 x 832 Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.75 0.75 0.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
70
Page 71
2. Specifications
Standard
Type DVM S DVM S DVM S
AM200KXVAGH/EU AM220KXVAGH/EU AM240KXVAGH/EU
Outdoor unit module 1 - - -
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 36 40 43 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 - - ­Outdoor unit module 3 - - ­Outdoor unit module 4 - - -
HP HP 20 22 24
Cooling
Capacity (Nominal)
Heating
Min. kW 28.0 30.8 33.6 Max. kW 72.8 80.1 8 7. 4
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.95 3.55 3.93 COP (Nominal) Heating W/W 4.53 4 .15 4.34 ESEER W/ W 6.56 6.25 7. 0 6
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion Model Name - DS-GB052FAVB x 2 DS-GB066FAVB x 2 DS-GB066FAVB x 2 Output kW x n 6.39 x 2 6.39 x 2 6.39 x 2
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 2 2 2
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n 620 x 2 620 x 2 620 x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 14.18 17.35 17.10 Heating kW 13.91 16.70 17.42 Cooling A 22.70 27.80 2 7. 4 0 Heating A 22.30 26.80 27.90 Minimum Ssc MCA A 42.0 44.6 55.0 MFA A 63 63 63
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 56.0 61.6 6 7. 2
Btu/h 191,100 210,200 229,300
kW 63.0 69. 3 75.6
Btu/h 215,000 236,500 258,000
MVA 8 .1 8.6 12.5
cc x n 1,100 x 2 1,100 x 2 1,100 x 2
2
m
/min 290 290 340
l/s 4,833 4,833 5,667
mmAq 8 8 8
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
15.88 (5/8) 15.88 (5/8) 15.88 (5/8)
28.58 (1-1/8) 28.58 (1-1/8) 34.92 (1-3/8)
- - -
71
Page 72
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 8.4 8.4 12.5 Sound Pressure Cooling dB(A) 65 65 66 Sound Pressure Heating dB(A) 67 67 68 Sound Power dB(A) 87 89 89 Net Weight kg 2 7 7. 0 285.0 333.0 Shipping Weight kg 297.0 305.0 355.0 Net Dimensions (WxHxD) mm 1,295 x 1,695 x 765 1,295 x 1,695 x 765 1,295 x 1,795 x 765 Shipping Dimensions (WxHxD) mm 1,363 x 1,887 x 832 1,363 x 1,887 x 832 1,363 x 1,987 x 832 Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.75 0.75 0.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
72
Page 73
2. Specifications
Standard
Type DVM S DVM S DVM S
AM260KXVAGH/EU AM280KXVAGH/EU AM300KXVAGH/EU
Outdoor unit module 1 - - -
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 47 51 54 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 - - ­Outdoor unit module 3 - - ­Outdoor unit module 4 - - -
HP HP 26 28 30
Cooling
Capacity (Nominal)
Heating
Min. kW 36.4 39. 3 42.0 Max. kW 94.6 102.2 109.2
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.85 3.80 3.70 COP (Nominal) Heating W/W 4.55 4.37 4.59 ESEER W/ W 6.92 6.83 6.65
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion Model Name - DS-GB066FAVB x 2 DS-GB070FAVA x 2 DS4GJ5080FVA x 2 Output kW x n 6.39 x 2 6.76 x 2 7.81 x 2
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 2 2 2
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n 620 x 2 620 x 2 620 x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 18.91 20.68 22.70 Heating kW 18.00 20.18 20.59 Cooling A 30.30 33.20 36.40 Heating A 28.90 32.40 33.00 Minimum Ssc MCA A 60.0 6 7. 0 73.0 MFA A 75 75 80
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 72.8 78.6 84.0
Btu/h 248,400 268,200 286,600
kW 81.9 88.2 94.5
Btu/h 279,500 301,000 322,400
MVA 12.2 13.6 14.8
cc x n 1,100 x 2 1,100 x 2 1,400 x 2
2
m
/min 340 340 340
l/s 5,667 5,667 5,667
mmAq 8 8 8
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
34.92 (1-3/8) 34.92 (1-3/8) 34.92 (1-3/8)
- - -
73
Page 74
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 12.5 14.0 14.0 Sound Pressure Cooling dB(A) 66 69 69 Sound Pressure Heating dB(A) 68 71 71 Sound Power dB(A) 89 90 90 Net Weight kg 333.0 342.0 350.0 Shipping Weight kg 355.0 364.0 372.0 Net Dimensions (WxHxD) mm 1,295 x 1,795 x 765 1,295 x 1,795 x 765 1,295 x 1,795 x 765 Shipping Dimensions (WxHxD) mm 1,363 x 1,987 x 832 1,363 x 1,987 x 832 1,363 x 1,987 x 832 Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.75 0.75 0.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
74
Page 75
2. Specifications
Standard
Type DVM S DVM S DVM S
AM320KXVAGH/EU AM340KXVAGH/EU AM360KXVAGH/EU
Outdoor unit module 1 AM100JXVAGH/EU AM120JXVAGH/EU AM140KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 58 61 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM220KXVAGH/EU AM220KXVAGH/EU AM220KXVAGH/EU Outdoor unit module 3 - - ­Outdoor unit module 4 - - -
HP HP 32 34 36
Cooling
Capacity (Nominal)
Heating
Min. kW 44.8 4 7. 6 50.8 Max. kW 116.5 123.8 132.1
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.70 3.73 3.59 COP (Nominal) Heating W/W 4.32 4.33 4.26 ESEER W/ W 6.56 6.53 6.55
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion Model Name - DS-GB066FAVB x 3 DS-GB066FAVB x 3 DS-GB066FAVB x 3 Output kW x n (6.39 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 3 3 4
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (830 x 1) x 1 + (620 x 2) x 1 (830 x 1) x 1 + (620 x 2) x 1 (620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 24.20 25.51 28.28 Heating kW 23.35 24.73 26.86 Cooling A 38.80 4 0.90 45.30 Heating A 37.50 39.70 43.10 Minimum Ssc MCA A 65.7 69.6 6 9.6 MFA A 80 80 80
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 89.6 95.2 101.6
Btu/h 305,700 324,800 346,700
kW 100.8 1 07. 1 114.3
Btu/h 343,900 365,400 390,000
MVA 1 3.1 13.9 14
cc x n
m
mmAq 8 8 8
Φ, mm (inch)
Φ, mm (inch)
Φ, mm (inch)
(1,100 x 1) x 1 + (1,100 x 2) x 1 (1,100 x 1) x 1 + (1,100 x 2) x 1 (1,100 x 1) x 1 + (1,100 x 2) x 1
2
/min 170 x 1 + 290 x 1 220 x 1 + 290 x 1 255 x 1 + 290 x 1
l/s 2,833 x 1 + 4,833 x 1 3,667 x 1 + 4,833 x 1 4,250 x 1 + 4,833 x 1
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Type Braze connection Braze connection Braze connection
34.92 (1-3/8) 34.92 (1-3/8) 41.28 (1-5/8)
Type - - -
- - -
75
Page 76
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 5.5 x 1 + 8.4 x 1 6.5 x 1 + 8.4 x 1 7.7 x 1 + 8.4 x 1 Sound Pressure Cooling dB(A) 66 67 66 Sound Pressure Heating dB(A) 68 69 68 Sound Power dB(A) 89 90 90 Net Weight kg 197.0 x 1 + 285.0 x 1 210.0 x 1 + 285.0 x 1 226.0 x 1 + 285.0 x 1 Shipping Weight kg 213.0 x 1 + 305.0 x 1 226.0 x 1 + 305.0 x 1 246.0 x 1 + 305.0 x 1
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.75 0.75 0.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 (948 x 1,887 x 832) x 1 + (1,363 x 1,887 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1
(1,295 x 1,695 x 765) x 2
(1,363 x 1,887 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
76
Page 77
2. Specifications
Standard
Type DVM S DVM S DVM S
AM380KXVAGH/EU AM400KXVAGH/EU AM420KXVAGH/EU
Outdoor unit module 1 AM160KXVAGH/EU AM180KXVAGH/EU AM200KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM220KXVAGH/EU AM220KXVAGH/EU AM220KXVAGH/EU Outdoor unit module 3 - - ­Outdoor unit module 4 - - -
HP HP 38 40 42
Cooling
Capacity (Nominal)
Heating
Min. kW 53.3 56.0 58.8 Max. kW 138.6 145.6 152.9
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.62 3.74 3.73 COP (Nominal) Heating W/W 4.23 4.40 4.32 ESEER W/ W 6.49 6.41 6.40
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n (7.81 x 1) x 1 + (6.39 x 2) x 1 (7.81 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 2) x 2
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 4 4 4
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 29.45 29.95 31.53 Heating kW 28.31 28.61 30.61 Cooling A 4 7. 2 0 48.00 50.50 Heating A 45.40 45.90 49.10 Minimum Ssc MCA A 76.6 83.8 86.6 MFA A 90 100 100
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 106.6 112.0 117.6
Btu/h 363,700 382,200 401,300
kW 119.7 126.0 132.3
Btu/h 408,400 429,900 451,400
MVA 15.8 1 7. 4 16.7
DS4GJ5080FVA x 1 +
DSGB066FAVB x 2
cc x n
m
mmAq 8 8 8
Φ, mm (inch)
Φ, mm (inch)
Φ, mm (inch)
(1,400 x 1) x 1 + (1,100 x 2) x 1 (1,400 x 1) x 1 + (1,100 x 2) x 1 (1,100 x 2) x 2
2
/min 255 x 1 + 290 x 1 290 x 2 290 x 2
l/s 4,250 x 1 + 4,833 x 1 4,833 x 2 4,833 x 2
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
Type Braze connection Braze connection Braze connection
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
Type - - -
- - -
DS4GJ5080FVA x 1 +
DSGB066FAVB x 2
DS-GB052FAVBx2 +
DSGB066FAVBx2
77
Page 78
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 8.4 x 2 8.4 x 2 8.4 x 2 Sound Pressure Cooling dB(A) 67 68 68 Sound Pressure Heating dB(A) 69 70 70 Sound Power dB(A) 90 90 91 Net Weight kg 253.0 x 1 + 285.0 x 1 255.0 x 1 + 285.0 x 1 277.0 x 1 + 285.0 x 1 Shipping Weight kg 273.0 x 1 + 305.0 x 1 275.0 x 1 + 305.0 x 1 297.0 x 1 + 305.0 x 1 Net Dimensions (WxHxD) mm (1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2 Shipping Dimensions (WxHxD) mm (1,363 x 1,887 x 832) x 2 (1,363 x 1,887 x 832) x 2 (1,363 x 1,887 x 832) x 2 Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.75 0.75 0.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
78
Page 79
2. Specifications
Standard
Type DVM S DVM S DVM S
AM440KXVAGH/EU AM460KXVAGH/EU AM480KXVAGH/EU
Outdoor unit module 1 AM220KXVAGH/EU AM160KXVAGH/EU AM180KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM220KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 3 - - ­Outdoor unit module 4 - - -
HP HP 44 46 48
Cooling
Capacity (Nominal)
Heating
Min. kW 61.6 64.5 6 7. 2 Max. kW 160.2 167.7 174.7
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.55 3.71 3.81 COP (Nominal) Heating W/W 4.1 5 4.50 4.65 ESEER W/ W 6.25 6.71 6.64
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion Model Name - DS-GB066FAVBx4 DS4GJ5080FVA x 3 DS4GJ5080FVA x 3 Output kW x n (6.39 x 2) x 2 (7.81 x 1) x 1 + (7.81 x 2) x 1 (7.81 x 1) x 1 + (7.81 x 2) x 1
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 4 4 4
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 34.70 34.80 35.30 Heating kW 33.40 32.20 32.50 Cooling A 55.60 55.80 56.60 Heating A 53.60 51.60 52.10 Minimum Ssc MCA A 8 9.2 105 112.2 MFA A 100 125 125
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 123.2 129.0 134.4
Btu/h 420,400 440,200 458,600
kW 138.6 144.9 151.2
Btu/h 472,900 494,400 515,900
MVA 1 7. 2 22 23.6
cc x n
2
m
/min 290 x 2 255 x 1 + 340 x 1 290 x 1 + 340 x 1
l/s 4,833 x 2 4,250 x 1 + 5,667 x 1 4,833 x 1 + 5,667 x 1
mmAq 8 8 8
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,100 x 2) x 2 (1,400 x 1) x 1 + (1,400 x 2) x 1 (1,400 x 1) x 1 + (1,400 x 2) x 1
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
79
Page 80
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 8.4 x 2 8.4 x 1 + 14.0 x 1 8.4 x 1 + 14.0 x 1 Sound Pressure Cooling dB(A) 68 70 70 Sound Pressure Heating dB(A) 70 72 72 Sound Power dB(A) 92 91 91 Net Weight kg 285.0 x 2 253.0 x 1 + 350.0 x 1 255.0 x 1 + 350.0 x 1 Shipping Weight kg 305.0 x 2 273.0 x 1 + 372.0 x 1 275.0 x 1 + 372.0 x 1
Net Dimensions (WxHxD) mm (1,295 x 1,695 x 765) x 2
Shipping Dimensions (WxHxD) mm (1,363 x 1,887 x 832) x 2
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.75 0.75 0.75
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
80
Page 81
2. Specifications
Standard
Type DVM S DVM S DVM S
AM500KXVAGH/EU AM520KXVAGH/EU AM540KXVAGH/EU
Outdoor unit module 1 AM200KXVAGH/EU AM220KXVAGH/EU AM240KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 3 - - ­Outdoor unit module 4 - - -
HP HP 50 52 54
Cooling
Capacity (Nominal)
Heating
Min. kW 70.0 72.8 75.6 Max. kW 182.0 189.3 196.6
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.80 3.64 3.80 COP (Nominal) Heating W/W 4.57 4.39 4.48 ESEER W/ W 6.61 6.48 6.83
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n (6.39 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 2) x 1 + (7.81 x 2) x 1
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 4 4 4
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 36.88 40.05 39.80 Heating kW 34.50 3 7. 2 9 38.01 Cooling A 5 9.10 64.20 63.80 Heating A 55.30 59.80 60.90 Minimum Ssc MCA A 115 117.6 128 MFA A 150 150 150
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 140.0 145.6 151.2
Btu/h 477,700 496,800 515,900
kW 1 5 7. 5 163.8 1 70.1
Btu/h 537,400 558,900 580,400
MVA 22 .9 23.4 2 7. 3
DS-GB052FAVB x 2 +
DS4GJ5080FVA x 2
cc x n
(1,100 x 2) x 1 + (1,400 x 2) x 1 (1,100 x 2) x 1 + (1,400 x 2) x 1 (1,100 x 2) x 1 + (1,400 x 2) x 1
2
m
/min 290 x 1 + 340 x 1 290 x 1 + 340 x 1 340 x 2
l/s 4,833 x 1 + 5,667 x 1 4,833 x 1 + 5,667 x 1 5,667 x 2
mmAq 8 8 8
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 2
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 2
81
Page 82
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 8.4 x 1 + 14.0 x 1 8.4 x 1 + 14.0 x 1 12.5 x 1 + 14.0 x 1 Sound Pressure Cooling dB(A) 70 70 71 Sound Pressure Heating dB(A) 72 72 73 Sound Power dB(A) 92 93 93 Net Weight kg 277.0 x 1 + 350.0 x 1 285.0 x 1 + 350.0 x 1 333.0 x 1 + 350.0 x 1 Shipping Weight kg 297.0 x 1 + 372.0 x 1 305.0 x 1 + 372.0 x 1 355.0 x 1 + 372.0 x 1
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
(1,295 x 1,695 x 765) x 1 +
(1,363 x 1,887 x 832) x 1 +
0.75 0.75 0.75
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
82
Page 83
2. Specifications
Standard
Type DVM S DVM S DVM S
AM560KXVAGH/EU AM580KXVAGH/EU AM600KXVAGH/EU
Outdoor unit module 1 AM260KXVAGH/EU AM280KXVAGH/EU AM300KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 3 - - ­Outdoor unit module 4 - - -
HP HP 56 58 60
Cooling
Capacity (Nominal)
Heating
Min. kW 78.4 81.3 84.0 Max. kW 203.8 211.4 218.4
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.77 3.75 3.70 COP (Nominal) Heating W/W 4.57 4.48 4.59 ESEER W/ W 6.78 6.74 6.65
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 4 4 4
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (620 x 2) x 2 (620 x 2) x 2 (620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 41.61 43.38 45.40 Heating kW 38.59 40.77 4 1.18 Cooling A 66.70 69.6 0 72.80 Heating A 61.90 65.40 66.00 Minimum Ssc MCA A 133 140 146 MFA A 150 175 175
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 156.8 162.6 168.0
Btu/h 535,000 554,800 573,200
kW 176.4 182.7 189.0
Btu/h 601,900 623,400 644,900
MVA 27 28.4 29. 6
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 2
(6.39 x 2) x 1 + (7.81 x 2) x 1 (6.76 x 2) x 1 + (7.81 x 2) x 1 (7.81 x 2) x 2
cc x n
m
mmAq 8 8 8
Φ, mm (inch)
Φ, mm (inch)
Φ, mm (inch)
(1,100 x 2) x 1 + (1,400 x 2) x 1 (1,100 x 2) x 1 + (1,400 x 2) x 1 (1,400 x 2) x 2
2
/min 340 x 2 340 x 2 340 x 2
l/s
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Type Braze connection Braze connection Braze connection
Type - - -
5,667 x 2 5,667 x 2 5,667 x 2
19.05 (3/4) 19.05 (3/4) 19.05 (3/4)
41.28 (1-5/8) 41.28 (1-5/8) 41.28 (1-5/8)
- - -
DS-GB070FAVA x 2 +
DS4GJ5080FVA x 2
DS4GJ5080FVA x 4
83
Page 84
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 12.5 x 1 + 14.0 x 1 14.0 x 2 14.0 x 2 Sound Pressure Cooling dB(A) 71 72 72 Sound Pressure Heating dB(A) 73 74 74 Sound Power dB(A) 93 93 93 Net Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm (1,295 x 1,795 x 765) x 2 (1,295 x 1,795 x 765) x 2 (1,295 x 1,795 x 765) x 2 Shipping Dimensions (WxHxD) mm (1,363 x 1,987 x 832) x 2 (1,363 x 1,987 x 832) x 2 (1,363 x 1,987 x 832) x 2 Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.75 0.75 0.75
333.0 x 1 + 350.0 x 1 342.0 x 1 + 350.0 x 1 350.0 x 2
355.0 x 1 + 372.0 x 1 364.0 x 1 + 372.0 x 1 372.0 x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
84
Page 85
2. Specifications
Standard
Type DVM S DVM S DVM S
AM620KXVAGH/EU AM640KXVAGH/EU AM660KXVAGH/EU
Outdoor unit module 1 AM100JXVAGH/EU AM120JXVAGH/EU AM140KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM220KXVAGH/EU AM220KXVAGH/EU AM220KXVAGH/EU Outdoor unit module 3 AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 4 - - -
HP HP 62 64 66
Cooling
Capacity (Nominal)
Heating
Min. kW 86.8 8 9.6 92.8 Max. kW 225.7 233.0 241.3
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.70 3.72 3.64 COP (Nominal) Heating W/W 4.44 4.45 4.40 ESEER W/ W 6.60 6.58 6.60
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 5 5 6
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (830 x 1) x 1 + (620 x 2) x 2 (830 x 1) x 1 + (620 x 2) x 2 (620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 46.90 48.21 50.98 Heating kW 43.94 45.32 47.45 Cooling A 75.20 7 7. 3 0 81.70 Heating A 70.50 72.70 76 .10 Minimum Ssc MCA A 138.7 142.6 142.6 MFA A 175 175 175
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE
Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 173.6 1 79.2 185.6
Btu/h 592,300 611,500 633,300
kW 195.3 201.6 208.8
Btu/h 666,400 687,900 712,500
MVA 2 7.9 28.7 28.8
DS-GB066FAVB x 3 +
DS4GJ5080FVA x 2
(6.39 x 1) x 1 + (6.39 x 2) x 1 +
(7.81 x 2) x 1
cc x n
m
mmAq 8 8 8
Φ, mm (inch)
Φ, mm (inch)
Φ, mm (inch)
(1,100 x 1) x 1 + (1,100 x 2) x 1 +
(1,400 x 2) x 1
2
/min 170 x 1 + 290 x 1 + 340 x 1 220 x 1 + 290 x 1 + 340 x 1 255 x 1 + 290 x 1 + 340 x 1
l/s
2,833 x 1 + 4,833 x 1 + 5,667 x 1 3,667 x 1 + 4,833 x 1 + 5,667 x 1 4,250 x 1 + 4,833 x 1 + 5,667 x 1
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
Type Braze connection Braze connection Braze connection
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
Type - - -
- - -
DS-GB066FAVB x 3 +
DS4GJ5080FVA x 2
(6.39 x 1) x 1 + (6.39 x 2) x 1 +
(7.81 x 2) x 1
(1,100 x 1) x 1 + (1,100 x 2) x 1 +
(1,400 x 2) x 1
DS-GB066FAVB x 3 +
DS4GJ5080FVA x 2
(6.39 x 1) x 1 + (6.39 x 2) x 1 +
(7.81 x 2) x 1
(1,100 x 1) x 1 + (1,100 x 2) x 1 +
(1,400 x 2) x 1
85
Page 86
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 5.5 x 1 + 8.4 x 1 + 14.0 x 1 6.5 x 1 + 8.4 x 1 + 14.0 x 1 7.7 x 1 + 8.4 x 1 + 14.0 x 1 Sound Pressure Cooling dB(A) 71 71 71 Sound Pressure Heating dB(A) 73 73 73 Sound Power dB(A) 93 93 93 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
197.0 x 1 + 285.0 x 1 + 350.0 x 1 210.0 x 1 + 285.0 x 1 + 350.0 x 1 226.0 x 1 + 285.0 x 1 + 350.0 x 1
213.0 x 1 + 305.0 x 1 + 372.0 x 1 226.0 x 1 + 305.0 x 1 + 372.0 x 1 246.0 x 1 + 305.0 x 1 + 372.0 x 1
(1,295 x 1,695 x 765) x 1 +
(1,363 x 1,887 x 832) x 1 +
0.75 0.75 0.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
86
Page 87
2. Specifications
Standard
Type DVM S DVM S DVM S
AM680KXVAGH/EU AM700KXVAGH/EU AM720KXVAGH/EU
Outdoor unit module 1 AM160KXVAGH/EU AM180KXVAGH/EU AM200KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM220KXVAGH/EU AM220KXVAGH/EU AM220KXVAGH/EU Outdoor unit module 3 AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 4 - - -
HP HP 68 70 72
Cooling
Capacity (Nominal)
Heating
Min. kW 95.3 98.0 100.8 Max. kW 2 4 7. 8 254.8 2 62.1
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.65 3.72 3.72 COP (Nominal) Heating W/W 4.38 4.48 4.43 ESEER W/ W 6.56 6.51 6.50
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 6 6 6
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 52.15 52.65 54.23 Heating kW 48.90 49.20 51.20 Cooling A 83.60 84.40 86.90 Heating A 78.40 78.90 82.10 Minimum Ssc MCA A 149.6 156.8 159. 6 MFA A 175 175 175
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE
Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 190.6 196.0 201.6
Btu/h 650,400 668,800 687,900
kW 214.2 220.5 226.8
Btu/h 730,900 752,400 773,900
MVA 30.6 32.2 31.5
DS4GJ5080FVA x 3 +
DSGB066FAVB x 2
(7.81 x 1) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1 (7.81 x 1) x 1 + (6.39 x 2) x 1 + (7.81 x 2) x 1
(1,400 x 1) x 1 + (1,100 x 2) x 1 +
cc x n
2
m
/min 255 x 1 + 290 x 1 + 340 x 1 290 x 2 + 340 x 1 290 x 2 + 340 x 1
l/s
mmAq 8 8 8
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type Braze connection Braze connection Braze connection
Φ, mm (inch)
Type - - -
Φ, mm (inch)
(1,400 x 2) x 1
4,250 x 1 + 4,833 x 1 + 5,667 x 1 4,833 x 2 + 5,667 x 1 4,833 x 2 + 5,667 x 1
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
DS4GJ5080FVA x 3 +
DSGB066FAVB x 2
(1,400 x 1) x 1 + (1,100 x 2) x 1 +
(1,400 x 2) x 1
DS-GB052FAVB x 2 +
DSGB066FAVB x 2 +
DS4GJ5080FVA x 2
(6.39 x 2) x 2 + (7.81 x 2) x 1
(1,100 x 2) x 2 + (1,400 x 2) x 1
87
Page 88
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 8.4 x 2 + 14.0 x 1 8.4 x 2 + 14.0 x 1 8.4 x 2 + 14.0 x 1 Sound Pressure Cooling dB(A) 71 71 72 Sound Pressure Heating dB(A) 73 73 74 Sound Power dB(A) 93 93 94 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
253.0 x 1 + 285.0 x 1 + 350.0 x 1 255.0 x 1 + 285.0 x 1 + 350.0 x 1 277.0 x 1 + 285.0 x 1 + 350.0 x 1
273.0 x 1 + 305.0 x 1 + 372.0 x 1 275.0 x 1 + 305.0 x 1 + 372.0 x 1 297.0 x 1 + 305.0 x 1 + 372.0 x 1 (1,295 x 1,695 x 765) x 2 +
(1,363 x 1,887 x 832) x 2 +
0.75 0.75 0.75
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
88
Page 89
2. Specifications
Standard
Type DVM S DVM S DVM S
AM740KXVAGH/EU AM760KXVAGH/EU AM780KXVAGH/EU
Outdoor unit module 1 AM220KXVAGH/EU AM220KXVAGH/EU AM220KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM220KXVAGH/EU AM240KXVAGH/EU AM260KXVAGH/EU Outdoor unit module 3 AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 4 - - -
HP HP 74 76 78
Cooling
Capacity (Nominal)
Heating
Min. kW 103.6 106.4 109.2 Max. kW 26 9.4 276.6 283.9
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.61 3.72 3.70 COP (Nominal) Heating W/W 4.32 4.38 4.44 ESEER W/ W 6.41 6.66 6.63
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 6 6 6
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 57.40 5 7. 1 5 58.96 Heating kW 53.99 54.71 55.29 Cooling A 92.00 91.60 94.50 Heating A 86.60 87.70 88.70 Minimum Ssc MCA A 162.2 172.6 1 7 7. 6 MFA A 200 200 200
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 2 0 7. 2 212.8 218.4
Btu/h 707,000 726,100 745,200
kW 233.1 2 39.4 245.7
Btu/h 795,400 816,900 838,400
MVA 32 35.9 35.6
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 2
(6.39 x 2) x 2 + (7.81 x 2) x 1 (6.39 x 2) x 2 + (7.81 x 2) x 1 (6.39 x 2) x 2 + (7.81 x 2) x 1
cc x n
m
mmAq 8 8 8
Φ, mm (inch)
Φ, mm (inch)
Φ, mm (inch)
(1,100 x 2) x 2 + (1,400 x 2) x 1 (1,100 x 2) x 2 + (1,400 x 2) x 1 (1,100 x 2) x 2 + (1,400 x 2) x 1
2
/min 290 x 2 + 340 x 1 290 x 1 + 340 x 2 290 x 1 + 340 x 2
l/s
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Type Braze connection Braze connection Braze connection
Type - - -
4,833 x 2 + 5,667 x 1 4,833 x 1 + 5,667 x 2 4,833 x 1 + 5,667 x 2
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 2
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 2
89
Page 90
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 8.4 x 2 + 14.0 x 1 8.4 x 1 + 12.5 x 1 + 14.0 x 1 8.4 x 1 + 12.5 x 1 + 14.0 x 1 Sound Pressure Cooling dB(A) 72 72 72 Sound Pressure Heating dB(A) 74 74 74 Sound Power dB(A) 94 94 94 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
(1,295 x 1,695 x 765) x 2 +
(1,363 x 1,887 x 832) x 2 +
0.75 0.75 0.75
285.0 x 2 + 350.0 x 1 285.0 x 1 + 333.0 x 1 + 350.0 x 1 285.0 x 1 + 333.0 x 1 + 350.0 x 1
305.0 x 2 + 372.0 x 1 305.0 x 1 + 355.0 x 1 + 372.0 x 1 305.0 x 1 + 355.0 x 1 + 372.0 x 1
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 2
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 2
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 2
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
90
Page 91
2. Specifications
Standard
Type DVM S DVM S DVM S
AM800KXVAGH/EU AM820KXVAGH/EU AM840KXVAGH/EU
Outdoor unit module 1 AM220KXVAGH/EU AM220KXVAGH/EU AM240KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM280KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 3 AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 4 - - -
HP HP 80 82 84
Cooling
Capacity (Nominal)
Heating
Min. kW 112.1 114.8 117.6 Max. kW 291.5 298.5 305.8
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.69 3.66 3.76 COP (Nominal) Heating W/W 4.38 4.46 4.52 ESEER W/ W 6.60 6.54 6.77
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 6 6 6
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 60.73 62.75 62.50 Heating kW 57.47 57.88 58.60 Cooling A 97.40 100.60 100.20 Heating A 92.20 92.80 93.90 Minimum Ssc MCA A 184.6 190.6 201 MFA A 225 225 225
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 224.2 2 29.6 235.2
Btu/h 765,000 783,400 802,500
kW 252.0 258.3 264.6
Btu/h 859,900 881,400 902,900
MVA 37 38.2 4 2.1
DS-GB066FAVB x 2 +
DSGB070FAVA x 2 +
DS4GJ5080FVA x 2
(6.39 x 2) x 1 + (6.76 x 2) x 1 +
(7.81 x 2) x 1
cc x n
m
mmAq 8 8 8
Φ, mm (inch)
Φ, mm (inch)
Φ, mm (inch)
(1,100 x 2) x 2 + (1,400 x 2) x 1 (1,100 x 2) x 1 + (1,400 x 2) x 2 (1,100 x 2) x 1 + (1,400 x 2) x 2
2
/min 290 x 1 + 340 x 2 290 x 1 + 340 x 2 340 x 3
l/s
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Type Braze connection Braze connection Braze connection
Type - - -
4,833 x 1 + 5,667 x 2 4,833 x 1 + 5,667 x 2 5,667 x 3
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 4
(6.39 x 2) x 1 + (7.81 x 2) x 2 (6.39 x 2) x 1 + (7.81 x 2) x 2
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 4
91
Page 92
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 8.4 x 1 + 14.0 x 2 8.4 x 1 + 14.0 x 2 12.5 x 1 + 14.0 x 2 Sound Pressure Cooling dB(A) 73 73 73 Sound Pressure Heating dB(A) 75 75 75 Sound Power dB(A) 94 94 94 Net Weight kg Shipping Weight kg
Net Dimensions (WxHxD) mm
Shipping Dimensions (WxHxD) mm
Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
285.0 x 1 + 342.0 x 1 + 350.0 x 1 285.0 x 1 + 350.0 x 2 333.0 x 1 + 350.0 x 2
305.0 x 1 + 364.0 x 1 + 372.0 x 1 305.0 x 1 + 372.0 x 2 355.0 x 1 + 372.0 x 2 (1,295 x 1,695 x 765) x 1 +
(1,363 x 1,887 x 832) x 1 +
0.75 0.75 0.75
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2
(1,295 x 1,795 x 765) x 2
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 2
(1,295 x 1,795 x 765) x 3
(1,363 x 1,987 x 832) x 3
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
92
Page 93
2. Specifications
Standard
Type DVM S DVM S DVM S
AM860KXVAGH/EU AM880KXVAGH/EU AM900KXVAGH/EU
Outdoor unit module 1 AM260KXVAGH/EU AM280KXVAGH/EU AM300KXVAGH/EU
Model Name
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 3, 4, 380-415, 50 3, 4, 380-415, 50 Mode - HEAT PUMP HEAT PUMP HEAT PUMP
Performance
Maximum number of connectable indoor units EA 64 64 64 Total capacity of the connected Indoor Units Total capacity of the connected Indoor Units
Power
Efficiency
Casing Material
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connec­tions
Outdoor unit module 2 AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 3 AM300KXVAGH/EU AM300KXVAGH/EU AM300KXVAGH/EU Outdoor unit module 4 - - -
HP HP 86 88 90
Cooling
Capacity (Nominal)
Heating
Min. kW 120.4 123.3 126.0 Max. kW 313.0 320.6 327.6
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal) Cooling W/ W 3.74 3.73 3.70 COP (Nominal) Heating W/W 4.58 4.52 4.59 ESEER W/ W 6.73 6.71 6.65
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin Treatment - Anti-corrosion Anti-corrosion Anti-corrosion
Model Name -
Output kW x n
Oil
Type - Propeller Propeller Propeller Discharge direction - Top Top To p Quantity EA 6 6 6
Air Flow Rate
External Static Pressure
Type - BLDC Motor BLDC Motor BLDC Motor Output W x n (620 x 2) x 3 (620 x 2) x 3 (620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation - Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes Piping length (ODU-IDU) Piping length (1st Branch-IDU) Total piping length (System) Level difference (ODU in highest position) Level difference (IDU in highest position) Level difference (IDU-IDU)
Cooling kW 64.31 66.08 68.10 Heating kW 59.1 8 61.36 61.77 Cooling A 103.10 106.00 109.20 Heating A 94.90 98.40 99.00 Minimum Ssc MCA A 206 213 219 MFA A 250 250 250
Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate Base - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Fin - Al Al Al Tube - Cu Cu Cu
Type - PVE PVE PVE Initial charge
Max.
Max. [Equiv.] m 200 [220] 200 [220] 200 [220] Max. m 90 90 90 Max. m 1,000 1,000 1,000 Max. m 110 110 110 Max. m 110 110 110 Max. m 50 50 50
kW 240.8 246.6 252.0
Btu/h 821,600 841,400 859,900
kW 270.9 2 7 7. 2 283.5
Btu/h 924,300 945,800 967,300
MVA 41.8 43.2 44.4
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 4
(6.39 x 2) x 1 + (7.81 x 2) x 2 (6.76 x 2) x 1 + (7.81 x 2) x 2 (7.81 x 2) x 3
cc x n
m
mmAq 8 8 8
Φ, mm (inch)
Φ, mm (inch)
Φ, mm (inch)
(1,100 x 2) x 1 + (1,400 x 2) x 2 (1,100 x 2) x 1 + (1,400 x 2) x 2 (1,400 x 2) x 3
2
/min 340 x 3 340 x 3 340 x 3
l/s
Pa 78.45 78.45 78.45
Type Braze connection Braze connection Braze connection
Type Braze connection Braze connection Braze connection
Type - - -
5,667 x 3 5,667 x 3 5,667 x 3
22.22 (7/8) 22.22 (7/8) 22.22 (7/8)
53.98 (2-1/8) 53.98 (2-1/8) 53.98 (2-1/8)
- - -
DS-GB070FAVA x 2 +
DS4GJ5080FVA x 4
DS4GJ5080FVA x 6
93
Page 94
2. Specifications
Wiring connections
Refrigerant
Sound
External Dimension
Operating Temp. Range
Transmission Cable mm Remark - F1, F2 F1, F2 F1, F2 Power supply intake ­Type - R410A R410A R410A Factory Charging kg 12.5 x 1 + 14.0 x 2 14.0 x 3 14.0 x 3 Sound Pressure Cooling dB(A) 73 74 74 Sound Pressure Heating dB(A) 75 76 76 Sound Power dB(A) 94 95 95 Net Weight kg Shipping Weight kg Net Dimensions (WxHxD) mm (1,295 x 1,795 x 765) x 3 (1,295 x 1,795 x 765) x 3 (1,295 x 1,795 x 765) x 3 Shipping Dimensions (WxHxD) mm (1,363 x 1,987 x 832) x 3 (1,363 x 1,987 x 832) x 3 (1,363 x 1,987 x 832) x 3 Cooling -5 ~ 48 -5 ~ 48 -5 ~ 48 Heating -25 ~ 24 -25 ~ 24 -25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.75 0.75 0.75
333.0 x 1 + 350.0 x 2 342.0 x 1 + 350.0 x 2 350.0 x 3
355.0 x 1 + 372.0 x 2 364.0 x 1 + 372.0 x 2 372.0 x 3
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is 50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under. (If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
94
Page 95
3. Electrical Characteristics
Premium Compact
Capacity
8 22.40 AM080JXVHGH/EU 50 380-415 342 456 7. 4 0 7. 4 0 18.0 25.0 19.8 0.83 2.4 10 28.00 AM100JXVHGH/EU 50 380-415 342 456 10.00 9. 40 2 1.1 32.0 23.2 0.83 2.4 12 33.60 AM120JXVHGH/EU 50 380-415 342 456 12.10 12.10 25.0 32.0 27.5 0.83 2.4 14 39. 20 AM140KXVGGH/EU 50 380-415 342 456 14.30 15.40 25.0 32.0 27.5 1.24 3.8 16 44.80 AM160KXVGGH/EU 50 380-415 342 456 17.50 17.20 32.0 40.0 35.2 1.24 3.8 18 50.40 AM180KXVGGH/EU 50 380-415 342 456 17.10 16.90 39. 2 50.0 4 3.1 1.24 3.8
20 56.00 AM200KXVGGH/EU 50 380-415 342 456 20.00 20.50 42.0 63.0 46.2 1.24 3.8
22 61.60 AM220KXVGGH/EU 50 380-415 342 456 25.30 25.40 44.6 63.0 49.1 1.24 3.8 24 67.20 AM240KXVGGH/EU 50 380-415 342 456 25.70 24.70 55.0 63.0 60.5 1.24 3.8 26 72.80 AM260KXVGGH/EU 50 380-415 342 456 27.80 27. 4 0 60.0 75.0 66.0 1.24 3.8 28 78.40 AM280KXVGGH/EU 50 380-415 342 456 31.50 30.10 67. 0 75.0 73.7 1.24 3.8
30 84.00 AM300KXVAGH/EU 50 380-415 342 456 36.40 33.00 73.0 80.0 80.3 1.24 3.8
32 89.60 AM320KXVGGH1EU 50 380-415 342 456 32.10 32.60 6 7.0 80.0 73.7 2.07 6.2 34 95.20 AM340KXVGGH1EU 50 380-415 342 456 3 7. 40 37.50 69.6 80.0 76.6 2.07 6.2 36 100.80 AM360KXVGGH1EU 50 380-415 342 456 39. 60 40.80 69.6 80.0 76.6 2.48 7. 6 38 106.40 AM380KXVGGH1EU 50 380-415 342 456 42.80 42.60 76.6 90.0 84.3 2.48 7. 6
40 112.00 AM400KXVGGH1EU 50 380-415 342 456 42.40 42.30 83.8 100.0 92.2 2.48 7.6
42 117.60 AM420KXVGGH1EU 50 380-415 342 456 45.30 45.90 86.6 100.0 95.3 2.48 7.6 44 123.20 AM440KXVGGH1EU 50 380-415 342 456 50.70 48.40 98.0 125.0 107.8 2.48 7.6 46 128.80 AM460KXVGGH1EU 50 380-415 342 456 53.90 50.20 105.0 125.0 115.5 2.48 7. 6 48 134.40 AM480KXVGGH1EU 50 380-415 342 456 53.50 49.9 0 112.2 125.0 123.4 2.48 7.6 50 140.00 AM500KXVGGH1EU 50 380-415 342 456 56.40 53.50 115.0 150.0 126.5 2.48 7.6 52 145.60 AM520KXVGGH1EU 50 380-415 342 456 61.70 58.40 117.6 150.0 129.4 2.48 7.6 54 151.20 AM540KXVGGH1EU 50 380-415 342 456 62.10 57.70 128.0 150.0 140.8 2.48 7. 6 56 156.80 AM560KXVGGH1EU 50 380-415 342 456 64.20 60.40 133.0 150.0 146.3 2.48 7. 6 58 162.40 AM580KXVGGH1EU 50 380-415 342 456 67.90 63.10 140.0 175.0 154.0 2.48 7.6 60 168.00 AM600KXVGGH1EU 50 380-415 342 456 72.80 66.00 146.0 175.0
62 173.60 AM620KXVGGH1EU 50 380-415 342 456 68.50 65.60 140.0 175.0 154.0 3.31 10.0 64 179.20 AM640KXVGGH1EU 50 380-415 342 456 73.80 70.50 142.6 175.0 156.9 3.31 10.0 66 184.80 AM660KXVGGH1EU 50 380-415 342 456 76.00 73.80 142.6 175.0 156.9 3.72 11.4 68 190.40 AM680KXVGGH1EU 50 380-415 342 456 79. 20 75.60 1 49. 6 175.0 164.6 3.72 11.4 70 196.00 AM700KXVGGH1EU 50 380-415 342 456 78.80 75.30 156.8 175.0 172.5 3.72 11.4 72 201.60 AM720KXVGGH1EU 50 380-415 342 456 81.70 78.90 159. 6 175.0 175.6 3.72 11.4 74 207.20 AM740KXVGGH1EU 50 380-415 342 456 87.00 83.80 162.2 200.0 178.4 3.72 11.4 76 212.80 AM760KXVGGH1EU 50 380-415 342 456 8 7. 4 0 83.10 172.6 200.0 189.9 3.72 11.4 78 218.40 AM780KXVGGH1EU 50 380-415 342 456 89.50 85.80 1 77. 6 200.0 195.4 3.72 11.4
80 224.00 AM800KXVGGH1EU 50 380-415 342 456 93.20 88.50 184.6 225.0 203.1 3.72 11.4
82 229.60 AM820KXVGGH1EU 50 380-415 342 456 98.10 91.40 190.6 225.0 209.7 3.72 11.4 84 235.20 AM840KXVGGH1EU 50 380-415 342 456 98.50 90.70 201.0 225.0 221.1 3.72 11.4 86 240.80 AM860KXVGGH1EU 50 380-415 342 456 100.60 93.40 206.0 250.0 226.6 3.72 11.4
88 246.40 AM880KXVGGH1EU 50 380-415 342 456 104.30 96 .10 213.0 250.0 234.3 3.72 11.4 90 252.00 AM900KXVGGH1EU 50 380-415 342 456 109.20 99.00 219.0 250.0 240.9 3.72 11.4
Model
Power Supply Voltage Range Nominal Running
Hz Voltage
Min.
(-10%)
Max.
(+10%)HP kW Cooling Heating MCA MFA TOCA kW FLA [A]
Current [A]
Current [A] ODU Fan Motor
160.6 2.48 7.6
NOTE
• MCA : Mimium circuit amperes
• MFA : Maximum fuse amperes
• TOCA : Total over current amperes
• FLA : Full load amperes
• MSC : Maximum starting current.
DVM S uses inverter compress. Starting current is always ≤ TOCA.
95
Page 96
3. Electrical Characteristics
Premium Energy Efficiency
Capacity
8 22.40 AM080JXVHGH/EU 50 380-415 342 456 7. 4 0 7. 4 0 18.0 25.0 19.8 0.83 2.4 10 28.00 AM100JXVHGH/EU 50 380-415 342 456 10.00 9.4 0 2 1.1 32.0 23.2 0.83 2.4 12 33.60 AM120JXVHGH/EU 50 380-415 342 456 12.10 12.10 25.0 32.0 27.5 0.83 2.4 14 39. 20 AM140KXVGGH/EU 50 380-415 342 456 14.30 15.40 25.0 32.0 27.5 1.24 3.8 16 44.80 AM160KXVGGH/EU 50 380-415 342 456 17.50 17.20 32.0 40.0 35.2 1.24 3.8 18 50.40 AM180KXVGGH/EU 50 380-415 342 456 17.10 16.90 39. 2 50.0 4 3.1 1.24 3.8 20 56.00 AM200KXVGGH/EU 50 380-415 342 456 20.00 20.50 42.0 63.0 46.2 1.24 3.8 22 61.60 AM220KXVGGH2EU 50 380-415 342 456 22.10 21.50 46.1 63.0 49.6 1.66 4.8 24 67.20 AM240KXVGGH2EU 50 380-415 342 456 24.20 24. 20 50.0 63.0 49.6 1.66 4.8 26 72.80 AM260KXVGGH2EU 50 380-415 342 456 24.50 24.30 5 7.2 63.0 74.4 2.07 6.2 28 78.40 AM280KXVGGH2EU 50 380-415 342 456 2 7. 4 0 27.90 60.0 75.0 74.4 2.07 6.2 30 84.00 AM300KXVGGH2EU 50 380-415 342 456 29. 20 29.00 64.2 75.0 74.4 2.07 6.2 32 89.60 AM320KXVGGH2EU 50 380-415 342 456 31.40 32.30 64.2 75.0 74.4 2.48 7. 6 34 95.20 AM340KXVGGH2EU 50 380-415 342 456 31.90 31.70 75.2 90.0 99.2 2.90 8.6 36 100.80 AM360KXVGGH2EU 50 380-415 342 456 34.20 33.80 78.4 90.0 99. 2 2.48 7.6 38 106.40 AM380KXVGGH2EU 50 380-415 342 456 37.10 3 7.4 0 81. 2 90.0 9 9. 2 2.48 7.6 40 112.00 AM400KXVGGH2EU 50 380-415 342 456 38.80 39.70 82.2 90.0 99.2 3.31 10.0 42 117.60 AM420KXVGGH2EU 50 380-415 342 456 41.70 43.30 85.0 100.0 99.2 3.31 10.0 44 123.20 AM440KXVGGH2EU 50 380-415 342 456 41.60 41.20 96.4 125.0 9 9. 2 3.31 10.0 46 128.80 AM460KXVGGH2EU 50 380-415 342 456 44.50 44.80 9 9.2 125.0 124.0 3.31 10.0 48 134.40 AM480KXVGGH2EU 50 380-415 342 456 47.40 48.40 102.0 125.0 124.0 3.31 10.0 50 140.00 AM500KXVGGH2EU 50 380-415 342 456 48.50 4 9.20 103.4 125.0 124.0 3.72 11.4 52 145.60 AM520KXVGGH2EU 50 380-415 342 456 52.30 51.70 117.2 150.0 124.0 3.31 7. 6 54 151.20 AM540KXVGGH2EU 50 380-415 342 456 55.20 55.30 120.0 150.0 124.0 3.31 7.6 56 156.80 AM560KXVGGH2EU 50 380-415 342 456 5 7. 0 0 56.40 124.2 150.0 124.0 3.31 7. 6 58 162.40 AM580KXVGGH2EU 50 380-415 342 456 60.90 59.50 133.0 150.0 142.4 3.31 10.0 60 168.00 AM600KXVGGH2EU 50 380-415 342 456 5 9.90 58.50 133.4 150.0
62 173.60 AM620KXVGGH2EU 50 380-415 342 456 58.70 58.10 135.6 150.0 173.6 4.55 13.8 64 179.20 AM640KXVGGH2EU 50 380-415 342 456 61.60 61.70 138.4 175.0 173.6 4.55 13.8 66 184.80 AM660KXVGGH2EU 50 380-415 342 456 63.40 62.80 142.6 175.0 173.6 4.55 11.4 68 190.40 AM680KXVGGH2EU 50 380-415 342 456 65.60 66.10 142.6 175.0 173.6 4.96 15.2 70 196.00 AM700KXVGGH2EU 50 380-415 342 456 6 9.40 68.60 156.4 175.0 173.6 4.55 13.8 72 201.60 AM720KXVGGH2EU 50 380-415 342 456 68.40 67.60 156.8 175.0 198.4 4.96 15.2 74 207.20 AM740KXVGGH2EU 50 380-415 342 456 71.30 71.20 15 9.6 200.0 198.4 4.96 15.2 76 212.80 AM760KXVGGH2EU 50 380-415 342 456 74.20 74.80 162.4 200.0 198.4 4.96 15.2 78 218.40 AM780KXVGGH2EU 50 380-415 342 456 7 7. 1 0 78.40 165.2 200.0 198.4 4.96 15.2 80 224.00 AM800KXVGGH2EU 50 380-415 342 456 7 9.10 78.10 17 7.6 200.0 198.4 4.96 15.2 82 229.60 AM820KXVGGH2EU 50 380-415 342 456 82.00 81.70 180.4 200.0 198.4 4.96 15.2 84 235.20 AM840KXVGGH2EU 50 380-415 342 456 84.90 85.30 183.2 225.0 198.4 4.96 15.2 86 240.80 AM860KXVGGH2EU 50 380-415 342 456 90.20 90.20 185.8 225.0 198.4 4.96 15.2 88 246.40 AM880KXVGGH2EU 50 380-415 342 456 90.60 89.50 196.2 225.0 216.8 4.96 15.2 90 252.00 AM900KXVGGH2EU 50 380-415 342 456 92.70 92.20 201.2 225.0 198.4 4.96 15.2
Model
Power Supply Voltage Range Nominal Running
Hz Voltage
Min.
(-10%)
Max.
(+10%)HP kW Cooling Heating MCA MFA TOCA kW FLA [A]
Current [A]
Current [A] ODU Fan Motor
167.2 3.72 11.4
96
NOTE
• MCA : Mimium circuit amperes
• MFA : Maximum fuse amperes
• TOCA : Total over current amperes
• FLA : Full load amperes
• MSC : Maximum starting current.
DVM S uses inverter compress. Starting current is always ≤ TOCA.
Page 97
3. Electrical Characteristics
Standard
Capacity
8 22.40 AM080JXVAGH/EU 50 380-415 342 456 8.00 8.20 18.0 25.0 18.9 0.83 2.4 10 28.00 AM100JXVAGH/EU 50 380-415 342 456 11.00 10.70 2 1.1 32.0 22.2 0.83 2.4 12 33.60 AM120JXVAGH/EU 50 380-415 342 456 13.10 12.90 25.0 32.0 26.3 0.83 2.4 14 39. 20 AM140KXVAGH/EU 50 380-415 342 456 17.50 16.30 25.0 32.0 26.3 1. 24 3.8 16 44.80 AM160KXVAGH/EU 50 380-415 342 456 19.40 18.60 32.0 40.0 33.6 1.24 3.8 18 50.40 AM180KXVAGH/EU 50 380-415 342 456 20.20 19.10 39.2 50.0 41.2 1.24 3.8
20 56.00 AM200KXVAGH/EU 50 380-415 342 456 22.70 22.30 42.0 63.0 44 .1 1.24 3.8
22 61.60 AM220KXVAGH/EU 50 380-415 342 456 27.80 26.80 44.6 63.0 46.8 1.24 3.8 24 67.20 AM240KXVAGH/EU 50 380-415 342 456 2 7.4 0 27.90 55.0 63.0 5 7.8 1.24 3.8 26 72.80 AM260KXVAGH/EU 50 380-415 342 456 30.30 28.90 60.0 75.0 63.0 1.24 3.8 28 78.40 AM280KXVAGH/EU 50 380-415 342 456 33.20 32.40 67. 0 75.0 70.4 1.24 3.8
30 84.00 AM300KXVAGH/EU 50 380-415 342 456 36.40 33.00 73.0 80.0 76.7 1.24 3.8
32 89.60 AM320KXVAGH/EU 50 380-415 342 456 38.80 37.50 65.7 80.0 69.0 2.07 6.2 34 95.20 AM340KXVAGH/EU 50 380-415 342 456 40.90 39.70 69.6 80.0 73.1 2.07 6.2 36 100.80 AM360KXVAGH/EU 50 380-415 342 456 45.30 43.10 69.6 80.0 73.1 2.48 7.6 38 106.40 AM380KXVAGH/EU 50 380-415 342 456 4 7.2 0 45.40 76.6 90.0 80.4 2.48 7.6
40 112.00 AM400KXVAGH/EU 50 380-415 342 456 48.00 45.90 83.8 100.0 88.0 2.48 7. 6
42 117.60 AM420KXVAGH/EU 50 380-415 342 456 50.50 49.10 86.6 100.0 90.9 2.48 7.6 44 123.20 AM440KXVAGH/EU 50 380-415 342 456 55.60 53.60 89. 2 100.0 93.7 2.48 7.6 46 128.80 AM460KXVAGH/EU 50 380-415 342 456 55.80 51.60 105.0 125.0 110.3 2.48 7. 6 48 134.40 AM480KXVAGH/EU 50 380-415 342 456 56.60 52.10 112.2 125.0 117.8 2.48 7. 6 50 140.00 AM500KXVAGH/EU 50 380-415 342 456 59.10 55.30 115.0 150.0 120.8 2.48 7. 6 52 145.60 AM520KXVAGH/EU 50 380-415 342 456 64.20 59.80 117.6 150.0 123.5 2.48 7.6 54 151.20 AM540KXVAGH/EU 50 380-415 342 456 63.80 60.90 128.0 150.0 134.4 2.48 7.6 56 156.80 AM560KXVAGH/EU 50 380-415 342 456 66.70 61.90 133.0 150.0 139.7 2.48 7.6 58 162.40 AM580KXVAGH/EU 50 380-415 342 456 69.6 0 65.40 140.0 175.0 1 4 7. 0 2.48 7. 6 60 168.00 AM600KXVAGH/EU 50 380-415 342 456 72.80 66.00 146.0 175.0
62 173.60 AM620KXVAGH/EU 50 380-415 342 456 75.20 70.50 138.7 175.0 145.6 3.31 10.0 64 179.20 AM640KXVAGH/EU 50 380-415 342 456 77.30 72.70 142.6 175.0 149.7 3.31 10.0 66 184.80 AM660KXVAGH/EU 50 380-415 342 456 81.70 76.1 0 142.6 175.0 149.7 3.72 11.4 68 190.40 AM680KXVAGH/EU 50 380-415 342 456 83.60 78.40 149.6 175.0 15 7.1 3.72 11.4 70 196.00 AM700KXVAGH/EU 50 380-415 342 456 84.40 78.90 156.8 175.0 164.6 3.72 11.4 72 201.60 AM720KXVAGH/EU 50 380-415 342 456 86.90 82.10 159. 6 175.0 167.6 3.72 11.4 74 207.20 AM740KXVAGH/EU 50 380-415 342 456 92.00 86.60 162.2 200.0 170.3 3.72 11.4 76 212.80 AM760KXVAGH/EU 50 380-415 342 456 91.60 87.70 172.6 200.0 181.2 3.72 11.4 78 218.40 AM780KXVAGH/EU 50 380-415 342 456 94.50 88.70 17 7.6 200.0 186.5 3.72 11.4
80 224.00 AM800KXVAGH/EU 50 380-415 342 456 97.40 92.20 184.6 225.0 193.8 3.72 11.4
82 229.60 AM820KXVAGH/EU 50 380-415 342 456 100.60 92.80 190.6 225.0 200.1 3.72 11.4
84 235.20 AM840KXVAGH/EU 50 380-415 342 456 100.20 93.90 201.0 225.0 211.1 3.72 11.4 86 240.80 AM860KXVAGH/EU 50 380-415 342 456 103.10 94.9 0 206.0 250.0 216.3 3.72 11.4 88 246.40 AM880KXVAGH/EU 50 380-415 342 456 106.00 98.40 213.0 250.0 223.7 3.72 11.4 90 252.00 AM900KXVAGH/EU 50 380-415 342 456 109.20 99.00 219.0 250.0 230.0 3.72 11.4
Model
Power Supply Voltage Range Nominal Running
Hz Voltage
Min.
(-10%)
Max.
(+10%)HP kW Cooling Heating MCA MFA TOCA kW FLA [A]
Current [A]
Current [A] ODU Fan Motor
153.3 2.48 7. 6
NOTE
• MCA : Mimium circuit amperes
• MFA : Maximum fuse amperes
• TOCA : Total over current amperes
• FLA : Full load amperes
• MSC : Maximum starting current.
DVM S uses inverter compress. Starting current is always ≤ TOCA.
97
Page 98
4. Dimensional Drawing
Outdoor unit
• AM080JXVHGH/EU, AM100JXVHGH/EU, AM120JXVHGH/EU, AM080JXVAGH/EU, AM100JXVAGH/EU, AM120JXVAGH/EU
[2'-6"]
Pitch of foundation bolt holes
740
[2’-5”]
761
[2’-6”]
Pitch of foundation bolt holes
4-20 x 12 SLOT HOLE
Foundation bolt holes
765
1695
75
[3”]
55 [2 1/4”]
[5’-6 3/4”]
[2 1/4”]
[3 3/4”]
[2 1/2”]
120
55
95
65
Units : mm [inches]
118
[4 3/4”]
[4 3/4”]
239
[9 1/2”]
381
[1’-3”]
40
[1 1/2”]
616 [2’-1/4”]
625
[2’ -1/2”]
803
[2’-7 1/2”]
[3 1/2”]
87
65 [2 1/2”]
107 [4 1/4”]
[3 3/4”]
[3 1/2”]
[2 1/2”]
241
[9 1/2”]
89
202
[3 1/2”]
[8”]
653
[2’-1 3/4”]
880
[2’-10 3/4”]
192
60
[7 1/2”]
95
90
74
[3”]
[7”]
179
115
[4 1/2”]
[2’-6”]
492
47
[1 3/4”]
65
[2 1/2”]
107
[4 1/4”]
NO Table of descriptions NO Table of descriptions
1 Gas Ref. pipe See note 4. 5 Power wiring conduit Φ22 2 Liquid Ref. pipe See note 4. 6 Communication wiring conduit Φ44 3 Power wiring conduit Φ34 7 Knock-out Hole for Ref. Piping (bottom) 4 Communication wiring conduit Φ44 8 Knock-out Hole for Ref. Piping (front)
98
Page 99
4. Dimensional Drawing
Outdoor unit
• AM140KXVGGH/EU, AM160KXVGGH/EU, AM180KXVGGH/EU, AM200KXVGGH/EU, AM220KXVGGH/EU, AM140KXVAGH/EU, AM160KXVAGH/EU, AM180KXVAGH/EU, AM200KXVAGH/EU, AM220KXVAGH/EU
Pitch of foundation bolt holes
1150
[3’ - 9 1/4 ”]
761
[2’ - 6”]
Units : mm [inches]
765
[2'-6"]
625
[2’ -1/2”]
803
[2’-7 1/2”]
75 [3”]
[3 1/2”]
Pitch of foundation bolt holes
4-20 x 12 SLOT HOLE
Foundation bolt holes
1695
[5'-6 3/4"]
55 [2 1/4”]
616 [2’-1/4”]
87
65 [2 1/2”]
107 [4 1/4”]
241
[9 1/2”]
202
119
[8”]
[4 3/4”]
1069
[3’ - 6”]
1295
[4’ - 3”]
74 [3”]
[7”]
179
115
[4 1/2”]
[2 1/4”]
[3 3/4”]
[2 1/2”]
[2’-6”]
118
120
[4 3/4”]
[4 3/4”]
344
[1'-1 1/2"]
486
[1'-7 1/4"]
40
[1 1/2”]
55
95
65
492
47
[1 3/4”]
65
[2 1/2”]
107
[4 1/4”]
250
45
[9 3/4”]
[1 3/4”]
89
[3 1/2”]
90
[3 1/2”]
NO Table of descriptions NO Table of descriptions
1 Gas Ref. pipe See note 4. 5 Power wiring conduit Φ22 2 Liquid Ref. pipe See note 4. 6 Communication wiring conduit Φ44 3 Power wiring conduit Φ34 7 Knock-out Hole for Ref. Piping (bottom) 4 Communication wiring conduit Φ44 8 Knock-out Hole for Ref. Piping (front)
99
Page 100
4. Dimensional Drawing
Outdoor unit
• AM240KXVGGH/EU, AM260KXVGGH/EU, AM280KXVGGH/EU, AM300KXVAGH/EU, AM240KXVAGH/EU, AM260KXVAGH/EU, AM280KXVAGH/EU
Pitch of foundation bolt holes
1150
[3’ - 9 1/4 ”]
761
[2’ - 6”]
Units : mm [inches]
765
[2'-6"]
625
[2’-1/2”]
803
[2’ -7 1/2”]
Pitch of foundation bolt holes
4-20 x 12 SLOT HOLE
Foundation bolt holes
1795
[5’-10 3/4”]
241
[9 1/2”]
202
110
[8”]
[4 1/4”]
622
[2’ - 1/2”]
74 [3”]
[4’ - 3”]
1295
[7”]
179
115
[4 1/2”]
123
116
[4 3/4”]
[4 1/2”]
156
[6 1/4”]
243
[9 1/2”]
86
192
[8 1/4”]
[3 1/4”]
86
[3 1/4”]
88
[3 1/2”]
NO Table of descriptions NO Table of descriptions
1 Gas Ref. pipe See note 4. 4 Communication wiring conduit Φ44 2 Liquid Ref. pipe See note 4. 5 Knock-out Hole for Ref. Piping (bottom) 3 Power wiring conduit Φ34 6 Knock-out Hole for Ref. Piping (front)
100