Model : Premium (Compact / Energy Efficiency) Type
Standard Type
Page 2
2History
VersionModificationDateRemark
Ver. 1.0Release DVM S 30 HP High EER TDB for Europe (R410A, 50 Hz, HP)15.12.30
Ver. 1.1Add Sound Pressure Spec for Modules (At cooling mode / P.15 to 58)16.01.06
Modify Electric Diagram Mapping (For AM160KXVGGH** Model/P.65 to 66)
Ver. 1.2
Ver. 2.0Update all contents including installation16.07.07
Ver. 2.01Modify the Accessory Compatibility table for MCU kit(P163)17.09.13
Line-up Name (Standard → Premium Compact, High Effi. →
Premium High Efficiency / P. 4, 5)
16.01.13
Page 3
Nomenclature
Outdoor Unit
Model Name
(1)(2)(3)(4)(5)(6)(7)(8)
(1) Classification
AMDVM
(2) Capacity
x 1/10 HP (3 digits)
(3) Version
F2013
H2014
J2015
K2016
Buyer
(5) Feature 1
VInverter
MDVM S Eco
(6) Feature 2
AStandard + General Temp.+ Module
HHigh EER + Low Temp + Module
GHigh EER + General Temp + Module
(7) Rating Voltage
E1Ø, 220~240V, 50Hz
G3Ø, 380~415V, 50Hz
(4) Product Type
XOutdoor Unit
NIndoor Unit
(8) Mode
HHeat Pump
RHeat Recovery
3
Page 4
4Features & Benefits
Samsung’s VRF system air conditioners offer instant temperature control, user-friendly installation and advanced
functionality, along with smart power usage. Our flagship VRF-based Samsung DVM S is a highly innovative system
that adopts the new third-generation Samsung Scroll Compressor (SSC) technology with Dual Digital Inverter
DVM S provides world-class energy efficiency and the most powerful cooling and heating performance available on
the market. This ideal air conditioning system accomodates all variable environments, including large commercial
or residential buildings.
.
Samsung DVM S offers innovative features to benefit the indoor comfort as well operational coasts of the system
through technological advances such as:
The world’s largest capacity
Capacities of the outdoor units offer up to 30 HP rooftop space savings as well as
lowering the installations and transportation costs.
High seasonal energy efficiency
Samsung DVM S adopts a dual inverter scroll compressor that upgrades refrigerant
flow and the motor’s operating performance. It makes ESEER of DVM S is up to 8.00.
Superior Heating Performance &
Wide Operating Temperature Range with Flash injection
Increase refrigerant flow by 32%, extend heating operation range at -25°C, thanks to
Flash Injection technology, extended compressor reliability range and control
compression ratio.
Page 5
Features & Benefits
Intelligent Defrosting Logic
DVM S Intelligent Defrost Control logic keeps the unit in the heating mode
for up to 40% longer through out the heating season compared to
conventional model by monitoring the air resistance through the heat
exchanger.
Optimised Heat Exchanger
Combination of optimised coil path and different types of fin design for upper and
lower parts of the condenser evens out the airflow profile to optimise the heat transfer
process.
Extended Piping Length Limits
Allows extended piping length of up to 220 m, and units will still give
a great performance over wide areas. With this technology,
installation is available with a maximum height level of 110 m, which
is equivalent to 20 stories (each story is considered 5 m high).
Smart management
Further improves system’s energy efficiency due to precise indoor
climate control. Web-based remote monitoring and management
system allows quick and easy HVAC control and breakdown alert.
Eurovent Certified Performance
Samsung DVM S had become the 1st VRF Product to be certified by
Eurovent, the European Committee of HVAC&R, in March 2014.
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
❇ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
❇ Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
• In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit
and deciding on piping length in accordance with design of the building.
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
❇ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
❇ Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
• In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit
and deciding on piping length in accordance with design of the building.
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
❇ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
❇ Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
• In case of combining modules more than 90 HP, please consult the manufacturer when connecting the indoor unit
and deciding on piping length in accordance with design of the building.
• Make sure to use an indoor unit that is compatible with DVM S.
• Indoor units can be connected within the range indicated in following table.
• If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
• Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 ×Σ (Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ (Outdoor unit capacity)
❇ You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
❇ Maximum 32 Wall-mount type indoor units with EEV (AM***FNQDEH***, AM***JNVDKH*) can be connected.
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
6.56.56.5
575862
596064
777981
195.5195.5195.5
211.5211.5211.5
880 x 1,695 x 765880 x 1,695 x 765880 x 1,695 x 765
948 x 1,887 x 832948 x 1,887 x 832948 x 1,887 x 832
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
16
Page 17
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
9.48.48.4
616365
636567
818389
241.0255.0285.0
261.0275.0305.0
1,295 x 1,695 x 7651,295 x 1,695 x 7651,295 x 1,695 x 765
1,363 x 1,887 x 8321,363 x 1,887 x 8321,363 x 1,887 x 832
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
18
Page 19
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
8.48.414.0
656569
676771
898990
285.0285.0342.0
305.0305.0364.0
1,295 x 1,695 x 7651,295 x 1,695 x 7651,295 x 1,795 x 765
1,363 x 1,887 x 8321,363 x 1,887 x 8321,363 x 1,987 x 832
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
20
Page 21
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
14.014.014.0
696969
717171
909090
350.0350.0350.0
372.0372.0372.0
1,295 x 1,795 x 7651,295 x 1,795 x 7651,295 x 1,795 x 765
1,363 x 1,987 x 8321,363 x 1,987 x 8321,363 x 1,987 x 832
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
22
Page 23
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
6.5 x 1 + 8.4 x 16.5 x 1 + 8.4 x 19.4 x 1 + 8.4 x 1
676766
696968
909090
195.5 x 1 + 285.0 x 1195.5 x 1 + 285.0 x 1241.0 x 1 + 285.0 x 1
211.5 x 1 + 305.0 x 1211.5 x 1 + 305.0 x 1261.0 x 1 + 305.0 x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1
(1,295 x 1,695 x 765) x 2
(1,363 x 1,887 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
24
Page 25
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
8.4 x 28.4 x 28.4 x 2
676868
697070
909292
255.0 x 1 + 285.0 x 1285.0 x 2285.0 x 2
275.0 x 1 + 305.0 x 1305.0 x 2305.0 x 2
(1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2 (1,295 x 1,695 x 765) x 2
(1,363 x 1,887 x 832) x 2 (1,363 x 1,887 x 832) x 2 (1,363 x 1,887 x 832) x 2
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
26
Page 27
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
9.4 x 1 + 14.0 x 18.4 x 1 + 14.0 x 18.4 x 1 + 14.0 x 1
707070
727272
919193
241.0 x 1 + 350.0 x 1255.0 x 1 + 350.0 x 1285.0 x 1 + 350.0 x 1
261.0 x 1 + 372.0 x 1275.0 x 1 + 372.0 x 1305.0 x 1 + 372.0 x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
28
Page 29
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
8.4 x 1 + 14.0 x 18.4 x 1 + 14.0 x 114.0 x 2
707072
727274
939393
285.0 x 1 + 350.0 x 1285.0 x 1 + 350.0 x 1342.0 x 1 + 350.0 x 1
305.0 x 1 + 372.0 x 1305.0 x 1 + 372.0 x 1364.0 x 1 + 372.0 x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
30
Page 31
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
14.0 x 214.0 x 214.0 x 2
727272
747474
939393
350.0 x 2350.0 x 2350.0 x 2
372.0 x 2372.0 x 2372.0 x 2
(1,295 x 1,795 x 765) x 2(1,295 x 1,795 x 765) x 2(1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2 (1,363 x 1,987 x 832) x 2 (1,363 x 1,987 x 832) x 2
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
32
Page 33
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
6.5 x 1 + 8.4 x 1 + 14.0 x 1 6.5 x 1 + 8.4 x 1 + 14.0 x 1 9.4 x 1 + 8.4 x 1 + 14.0 x 1
717171
737373
939393
195.5 x 1 + 285.0 x 1 +
350.0 x 1
211.5 x 1 + 305.0 x 1 +
372.0 x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
195.5 x 1 + 285.0 x 1 +
350.0 x 1
211.5 x 1 + 305.0 x 1 +
372.0 x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
241.0 x 1 + 285.0 x 1 +
350.0 x 1
261.0 x 1 + 305.0 x 1 +
372.0 x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
34
Page 35
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
8.4 x 2 + 14.0 x 18.4 x 2 + 14.0 x 18.4 x 2 + 14.0 x 1
717272
737474
939494
255.0 x 1 + 285.0 x 1 +
350.0 x 1
275.0 x 1 + 305.0 x 1 +
372.0 x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
285.0 x 2 + 350.0 x 1285.0 x 2 + 350.0 x 1
305.0 x 2 + 372.0 x 1305.0 x 2 + 372.0 x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
36
Page 37
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
8.4 x 2 + 14.0 x 1
727373
747575
949494
285.0 x 2 + 350.0 x 1
305.0 x 2 + 372.0 x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
14.0 x 1 + 8.4 x 1 +
14.0 x 1
342.0 x 1 + 285.0 x 1 +
350.0 x 1
364.0 x 1 + 305.0 x 1 +
372.0 x 1
(1,295 x 1,795 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
14.0 x 1 + 8.4 x 1 +
14.0 x 1
350.0 x 1 + 285.0 x 1 +
350.0 x 1
372.0 x 1 + 305.0 x 1 +
372.0 x 1
(1,295 x 1,795 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
38
Page 39
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
14.0 x 1 + 8.4 x 1 +
14.0 x 1
737374
757576
949495
350.0 x 1 + 285.0 x 1 +
350.0 x 1
372.0 x 1 + 305.0 x 1 +
372.0 x 1
(1,295 x 1,795 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
14.0 x 1 + 8.4 x 1 +
14.0 x 1
350.0 x 1 + 285.0 x 1 +
350.0 x 1
372.0 x 1 + 305.0 x 1 +
372.0 x 1
(1,295 x 1,795 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
14.0 x 3
342.0 x 1 + 350.0 x 2
364.0 x 1 + 372.0 x 2
(1,295 x 1,795 x 765) x 3
(1,363 x 1,987 x 832) x 3
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
Page 41
2. Specifications
Premium Compact
Type
Model Name
Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Outdoor unit module 4
Power SupplyØ, #, V, Hz
Mode-
HPHP
Performance
Maximum number of connectable indoor unitsEA
Total capacity of the connected Indoor UnitsMin.kW
Total capacity of the connected Indoor UnitsMax.kW
Both indoor and outdoor unitBoth indoor and outdoor unitBoth indoor and outdoor unit
R410AR410AR410A
14.0 x 314.0 x 314.0 x 3
747474
767676
959595
350.0 x 3350.0 x 3350.0 x 3
372.0 x 3372.0 x 3372.0 x 3
(1,295 x 1,795 x 765) x 3(1,295 x 1,795 x 765) x 3(1,295 x 1,795 x 765) x 3
(1,363 x 1,987 x 832) x 3 (1,363 x 1,987 x 832) x 3 (1,363 x 1,987 x 832) x 3
-5 ~ 48-5 ~ 48-5 ~ 48
-25 ~ 24-25 ~ 24-25 ~ 24
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
42
Page 43
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM220KXVGGH2EUAM240KXVGGH2EUAM260KXVGGH2EU
Outdoor unit module 1AM100JXVHGH/EUAM120JXVHGH/EUAM080JXVHGH/EU
Outdoor unit module 2AM120JXVHGH/EUAM120JXVHGH/EUAM180KXVGGH/EU
Outdoor unit module 3---
(1,100 x 1) x 2(1,100 x 1) x 2(1,100 x 1) x 1 + (1,100 x 2) x 1
15.88 (5/8)15.88 (5/8)19.05 (3/4)
28.58 (1-1/8)34.92 (1-3/8)34.92 (1-3/8)
---
43
Page 44
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)636566
dB(A)656768
0.750.750.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg6.5 x 26.5 x 26.5 x 1 + 8.4 x 1
Sound Pressure
Sound Pressure
Sound PowerdB(A)838489
Net Weightkg195.5 x 2195.5 x 2195.5 x 1 + 285.0 x 1
Shipping Weightkg211.5 x 2211.5 x 2211.5 x 1 + 305.0 x 1
Net Dimensions (WxHxD)mm(880 x 1,695 x 765) x 2(880 x 1,695 x 765) x 2
Shipping Dimensions (WxHxD)mm(948 x 1,887 x 832) x 2(948 x 1,887 x 832) x 2
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
44
Page 45
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM280KXVGGH2EUAM300KXVGGH2EUAM320KXVGGH2EU
Outdoor unit module 1AM080JXVHGH/EUAM120JXVHGH/EUAM140KXVGGH/EU
Outdoor unit module 2AM200KXVGGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 3---
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)666766
dB(A)686968
0.750.750.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1
(1,295 x 1,695 x 765) x 2
(1,363 x 1,887 x 832) x 2
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg6.5 x 1 + 8.4 x 16.5 x 1 + 8.4 x 19.4 x 1 + 8.4 x 1
Sound Pressure
Sound Pressure
Sound PowerdB(A)899090
Net Weightkg195.5 x 1 + 285.0 x 1195.5 x 1 + 285.0 x 1241.0 x 1 + 285.0 x 1
Shipping Weightkg211.5 x 1 + 305.0 x 1211.5 x 1 + 305.0 x 1261.0 x 1 + 305.0 x 1
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
46
Page 47
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM340KXVGGH2EUAM360KXVGGH2EUAM380KXVGGH2EU
Outdoor unit module 1AM080JXVHGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 2AM080JXVHGH/EUAM180KXVGGH/EUAM200KXVGGH/EU
Outdoor unit module 3AM180KXVGGH/EU--
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)666868
dB(A)687070
(880 x 1,695 x 765) x 2 +
(948 x 1,887 x 832) x 2 +
0.750.750.75
(1,295 x 1,695 x 765) x 1
(1,363 x 1,887 x 832) x 1
(1,295 x 1,695 x 765) x 2(1,295 x 1,695 x 765) x 2
(1,363 x 1,887 x 832) x 2(1,363 x 1,887 x 832) x 2
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg6.5 x 2 + 8.4 x 18.4 x 28.4 x 2
Sound Pressure
Sound Pressure
Sound PowerdB(A)909292
Net Weightkg195.5 x 2 + 285.0 x 1285.0 x 2285.0 x 2
Shipping Weightkg211.5 x 2 + 305.0 x 1305.0 x 2305.0 x 2
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
48
Page 49
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM400KXVGGH2EUAM420KXVGGH2EUAM440KXVGGH2EU
Outdoor unit module 1AM080JXVHGH/EUAM080JXVHGH/EUAM080JXVHGH/EU
Outdoor unit module 2AM140KXVGGH/EUAM140KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 3AM180KXVGGH/EUAM200KXVGGH/EUAM180KXVGGH/EU
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)676768
dB(A)696970
0.750.750.75
195.5 x 1 + 241.0 x 1 +
285.0 x 1
211.5 x 1 + 261.0 x 1 +
305.0 x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 2
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 2
195.5 x 1 + 241.0 x 1 +
285.0 x 1
211.5 x 1 + 261.0 x 1 +
305.0 x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 2
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 2
195.5 x 1 + 285.0 x 2
211.5 x 1 + 305.0 x 2
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 2
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 2
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg6.5 x 1 + 9.4 x 1 + 8.4 x 16.5 x 1 + 9.4 x 1 + 8.4 x 16.5 x 1 + 8.4 x 2
Sound Pressure
Sound Pressure
Sound PowerdB(A)909092
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
50
Page 51
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM460KXVGGH2EUAM480KXVGGH2EUAM500KXVGGH2EU
Outdoor unit module 1AM080JXVHGH/EUAM080JXVHGH/EUAM140KXVGGH/EU
Outdoor unit module 2AM180KXVGGH/EUAM200KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 3AM200KXVGGH/EUAM200KXVGGH/EUAM180KXVGGH/EU
2,833 x 1 + 4,833 x 22,833 x 1 + 4,833 x 24,250 x 1 + 4,833 x 2
19.05 (3/4)19.05 (3/4)19.05 (3/4)
41.28 (1-5/8)41.28 (1-5/8)41.28 (1-5/8)
---
DS-GB066FAVB x 4 +
DSGB052FAVBSG x 1
DS-GB066FAVB x 5
51
Page 52
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)686869
dB(A)707071
0.750.750.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 2
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 2
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 2
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 2
(1,295 x 1,695 x 765) x 3
(1,363 x 1,887 x 832) x 3
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg6.5 x 1 + 8.4 x 26.5 x 1 + 8.4 x 29.4 x 1 + 8.4 x 2
Sound Pressure
Sound Pressure
Sound PowerdB(A)929292
Net Weightkg195.5 x 1 + 285.0 x 2195.5 x 1 + 285.0 x 2241.0 x 1 + 285.0 x 2
Shipping Weightkg211.5 x 1 + 305.0 x 2211.5 x 1 + 305.0 x 2261.0 x 1 + 305.0 x 2
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
52
Page 53
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM520KXVGGH2EUAM540KXVGGH2EUAM560KXVGGH2EU
Outdoor unit module 1AM080JXVHGH/EUAM080JXVHGH/EUAM120JXVHGH/EU
Outdoor unit module 2AM180KXVGGH/EUAM200KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 3AM260KXVGGH/EUAM260KXVGGH/EUAM260KXVGGH/EU
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)717171
dB(A)737373
195.5 x 1 + 285.0 x 1 + 350.0 x 1 195.5 x 1 + 285.0 x 1 + 350.0 x 1 195.5 x 1 + 285.0 x 1 + 350.0 x 1
211.5 x 1 + 305.0 x 1 + 372.0 x 1 211.5 x 1 + 305.0 x 1 + 372.0 x 1 211.5 x 1 + 305.0 x 1 + 372.0 x 1
(1,295 x 1,695 x 765) x 1 +
(1,363 x 1,887 x 832) x 1 +
0.750.750.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg6.5 x 1 + 8.4 x 1 + 14.0 x 16.5 x 1 + 8.4 x 1 + 14.0 x 16.5 x 1 + 8.4 x 1 + 14.0 x 1
Sound Pressure
Sound Pressure
Sound PowerdB(A)939393
Net Weightkg
Shipping Weightkg
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
54
Page 55
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM580KXVGGH2EUAM600KXVGGH2EUAM620KXVGGH2EU
Outdoor unit module 1AM080JXVHGH/EUAM180KXVGGH/EUAM080JXVHGH/EU
Outdoor unit module 2AM240KXVGGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 3AM260KXVGGH/EUAM240KXVGGH/EUAM180KXVGGH/EU
2,833 x 1 + 5,667 x 24,833 x 2 + 5,667 x 12,833 x 1 + 4,833 x 3
19.05 (3/4)19.05 (3/4)22.22 (7/8)
41.28 (1-5/8)41.28 (1-5/8)53.98 (2-1/8)
---
DS-GB066FAVB x 4 +
DSGB070FAVA x 2
(1,100 x 2) x 3(1,100 x 1) x 1 + (1,100 x 2) x 3
DS-GB066FAVB x 6 +
DSGB052FAVBSG x 1
(5.18 x 1) x 1 + (6.39 x 2) x 3
(830 x 1) x 1 + (620 x 2) x 3
55
Page 56
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)727270
dB(A)747472
195.5 x 1 + 342.0 x 1 + 350.0 x 1285.0 x 2 + 342.0 x 1195.5 x 1 + 285.0 x 3
211.5 x 1 + 364.0 x 1 + 372.0 x 1305.0 x 2 + 364.0 x 1211.5 x 1 + 305.0 x 3
0.750.750.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 2
(948 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 2
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 3
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 3
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg6.5 x 1 + 14.0 x 28.4 x 2 + 14.0 x 16.5 x 1 + 8.4 x 3
Sound Pressure
Sound Pressure
Sound PowerdB(A)939494
Net Weightkg
Shipping Weightkg
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
56
Page 57
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM640KXVGGH2EUAM660KXVGGH2EUAM680KXVGGH2EU
Outdoor unit module 1AM080JXVHGH/EUAM120JXVHGH/EUAM140KXVGGH/EU
Outdoor unit module 2AM180KXVGGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 3AM180KXVGGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
2,833 x 1 + 4,833 x 33,667 x 1 + 4,833 x 34,250 x 1 + 4,833 x 3
(830 x 1) x 1 +
(620 x 2) x 3
22.22 (7/8)22.22 (7/8)22.22 (7/8)
53.98 (2-1/8)53.98 (2-1/8)53.98 (2-1/8)
---
DS-GB066FAVB x 6 +
DSGB066FAVBSG x 1
(830 x 1) x 1 +
(620 x 2) x 3
DS-GB066FAVB x 7
(620 x 2) x 4
57
Page 58
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)707070
dB(A)727272
0.750.750.75
195.5 x 1 + 285.0 x 3195.5 x 1 + 285.0 x 3241.0 x 1 + 285.0 x 3
211.5 x 1 + 305.0 x 3211.5 x 1 + 305.0 x 3261.0 x 1 + 305.0 x 3
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 3
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 3
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 3
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 3
(1,295 x 1,695 x 765) x 4
(1,363 x 1,887 x 832) x 4
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg6.5 x 1 + 8.4 x 36.5 x 1 + 8.4 x 39.4 x 1 + 8.4 x 3
Sound Pressure
Sound Pressure
Sound PowerdB(A)949494
Net Weightkg
Shipping Weightkg
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
58
Page 59
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM700KXVGGH2EUAM720KXVGGH2EUAM740KXVGGH2EU
Outdoor unit module 1AM080JXVHGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 2AM180KXVGGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 3AM180KXVGGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)727171
dB(A)747373
195.5 x 1 + 285.0 x 2 + 350.0 x 1285.0 x 4285.0 x 4
211.5 x 1 + 305.0 x 2 + 372.0 x 1305.0 x 4305.0 x 4
(1,295 x 1,695 x 765) x 2 +
(1,363 x 1,887 x 832) x 2 +
0.750.750.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 4(1,295 x 1,695 x 765) x 4
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 4(1,363 x 1,887 x 832) x 4
(1,363 x 1,987 x 832) x 1
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg6.5 x 1 + 8.4 x 2 + 14.0 x 18.4 x 48.4 x 4
Sound Pressure
Sound Pressure
Sound PowerdB(A)949595
Net Weightkg
Shipping Weightkg
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
60
Page 61
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM760KXVGGH2EUAM780KXVGGH2EUAM800KXVGGH2EU
Outdoor unit module 1AM180KXVGGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 2AM180KXVGGH/EUAM200KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 3AM200KXVGGH/EUAM200KXVGGH/EUAM180KXVGGH/EU
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
62
Page 63
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM SDVM S
Model NameAM820KXVGGH2EUAM840KXVGGH2EUAM860KXVGGH2EU
Outdoor unit module 1AM180KXVGGH/EUAM180KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 2AM180KXVGGH/EUAM200KXVGGH/EUAM200KXVGGH/EU
Outdoor unit module 3AM200KXVGGH/EUAM200KXVGGH/EUAM220KXVGGH/EU
4,833 x 3 + 5,667 x 14,833 x 3 + 5,667 x 14,833 x 3 + 5,667 x 1
(620 x 2) x 4(620 x 2) x 4(620 x 2) x 4
22.22 (7/8)22.22 (7/8)22.22 (7/8)
53.98 (2-1/8)53.98 (2-1/8)53.98 (2-1/8)
---
DS-GB066FAVB x 6 +
DS4GJ5080FVA x 2
DS-GB066FAVB x 6 +
DS4GJ5080FVA x 2
63
Page 64
2. Specifications
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
dB(A)727272
dB(A)747474
(1,295 x 1,695 x 765) x 3 +
(1,363 x 1,887 x 832) x 3 +
0.750.750.75
285.0 x 3 + 350.0 x 1285.0 x 3 + 350.0 x 1285.0 x 3 + 350.0 x 1
305.0 x 3 + 372.0 x 1305.0 x 3 + 372.0 x 1305.0 x 3 + 372.0 x 1
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 3 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 3 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 3 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 3 +
(1,363 x 1,987 x 832) x 1
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg8.4 x 3 + 14.0 x 18.4 x 3 + 14.0 x 18.4 x 3 + 14.0 x 1
Sound Pressure
Sound Pressure
Sound PowerdB(A)959595
Net Weightkg
Shipping Weightkg
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
64
Page 65
2. Specifications
Premium Energy Efficiency
TypeDVM SDVM S
Model NameAM880KXVGGH2EUAM900KXVGGH2EU
Outdoor unit module 1AM180KXVGGH/EUAM180KXVGGH/EU
Outdoor unit module 2AM200KXVGGH/EUAM200KXVGGH/EU
Outdoor unit module 3AM240KXVGGH/EUAM260KXVGGH/EU
Outdoor unit module 4AM260KXVGGH/EUAM260KXVGGH/EU
Power SupplyØ, #, V, Hz3, 4, 380-415, 503, 4, 380-415, 50
Mode-HEAT PUMPHEAT PUMP
HPHP8890
Performance
Maximum number of connectable indoor unitsEA6464
Total capacity of the connected Indoor Units
Total capacity of the connected Indoor Units
Power
Efficiency
CasingMaterial
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Capacity (Nominal)
Power Input (Nominal)
Current Input (Nominal)
Current
EER (Nominal)
COP (Nominal)
ESEERW/ W7.1 17.1 1
Type-Fin & TubeFin & Tube
Material
Fin Treatment-Anti-corrosionAnti-corrosion
Model Name-
OutputkW x n
Oil
Type-PropellerPropeller
Discharge direction-To pTo p
QuantityEA88
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC Motor
OutputW x n
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipesBoth liquid and gas pipes
(1,100 x 2) x 3 + (1,400 x 2) x 1(1,100 x 2) x 2 + (1,400 x 2) x 2
4,833 x 2 + 5,667 x 24,833 x 2 + 5,667 x 2
(620 x 2) x 4(620 x 2) x 4
22.22 (7/8)22.22 (7/8)
53.98 (2-1/8)53.98 (2-1/8)
--
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 4
65
Page 66
2. Specifications
2
Both indoor and outdoor unitBoth indoor and outdoor unit
dB(A)7373
dB(A)7575
285.0 x 2 + 342.0 x 1 + 350.0 x 1285.0 x 2 + 350.0 x 2
305.0 x 2 + 364.0 x 1 + 372.0 x 1305.0 x 2 + 372.0 x 2
(1,295 x 1,695 x 765) x 2 +
(1,363 x 1,887 x 832) x 2 +
0.750.75
(1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 2
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 2
Wiring connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2
Power supply intakeType-R410AR410A
Factory Chargingkg8.4 x 2 + 14.0 x 28.4 x 2 + 14.0 x 2
Sound Pressure
Sound Pressure
Sound PowerdB(A)9696
Net Weightkg
Shipping Weightkg
Net Dimensions (WxHxD)mm
Shipping Dimensions (WxHxD)mm
Cooling℃-5 ~ 48-5 ~ 48
Heating℃-25 ~ 24-25 ~ 24
Cooling
Heating
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-DS-GA046FAVADO x 1DS-GB066FAVB x 1DS-GB066FAVB x 1
OutputkW x n4.39 x 16.39 x 16.39 x 1
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA111
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n830 x 1830 x 1830 x 1
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg5.55.56.5
Sound PressureCoolingdB(A)575862
Sound PressureHeatingdB(A)596064
Sound PowerdB(A)777981
Net Weightkg186.01 9 7. 0210.0
Shipping Weightkg202.0213.0226.0
Net Dimensions (WxHxD)mm880 x 1,695 x 765880 x 1,695 x 765880 x 1,695 x 765
Shipping Dimensions (WxHxD)mm948 x 1,887 x 832948 x 1,887 x 832948 x 1,887 x 832
Cooling℃-5 ~ 48-5 ~ 48-5 ~ 48
Heating℃-25 ~ 24-25 ~ 24-25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.750.750.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-DS-GB066FAVB x 1DS4GJ5080FVA x 1DS4G J5080FVA x 1
OutputkW x n6.39 x 17.81 x 17.81 x 1
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA222
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n620 x 2620 x 2620 x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg7. 78.48.4
Sound PressureCoolingdB(A)616364
Sound PressureHeatingdB(A)636566
Sound PowerdB(A)818384
Net Weightkg226.0253.0255.0
Shipping Weightkg246.0273.0275.0
Net Dimensions (WxHxD)mm1,295 x 1,695 x 7651,295 x 1,695 x 7651,295 x 1,695 x 765
Shipping Dimensions (WxHxD)mm1,363 x 1,887 x 8321,363 x 1,887 x 8321,363 x 1,887 x 832
Cooling℃-5 ~ 48-5 ~ 48-5 ~ 48
Heating℃-25 ~ 24-25 ~ 24-25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.750.750.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-DS-GB052FAVB x 2DS-GB066FAVB x 2DS-GB066FAVB x 2
OutputkW x n6.39 x 26.39 x 26.39 x 2
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA222
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n620 x 2620 x 2620 x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg8.48.412.5
Sound PressureCoolingdB(A)656566
Sound PressureHeatingdB(A)676768
Sound PowerdB(A)878989
Net Weightkg2 7 7. 0285.0333.0
Shipping Weightkg297.0305.0355.0
Net Dimensions (WxHxD)mm1,295 x 1,695 x 7651,295 x 1,695 x 7651,295 x 1,795 x 765
Shipping Dimensions (WxHxD)mm1,363 x 1,887 x 8321,363 x 1,887 x 8321,363 x 1,987 x 832
Cooling℃-5 ~ 48-5 ~ 48-5 ~ 48
Heating℃-25 ~ 24-25 ~ 24-25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.750.750.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-DS-GB066FAVB x 2DS-GB070FAVA x 2DS4GJ5080FVA x 2
OutputkW x n6.39 x 26.76 x 27.81 x 2
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA222
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n620 x 2620 x 2620 x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg12.514.014.0
Sound PressureCoolingdB(A)666969
Sound PressureHeatingdB(A)687171
Sound PowerdB(A)899090
Net Weightkg333.0342.0350.0
Shipping Weightkg355.0364.0372.0
Net Dimensions (WxHxD)mm1,295 x 1,795 x 7651,295 x 1,795 x 7651,295 x 1,795 x 765
Shipping Dimensions (WxHxD)mm1,363 x 1,987 x 8321,363 x 1,987 x 8321,363 x 1,987 x 832
Cooling℃-5 ~ 48-5 ~ 48-5 ~ 48
Heating℃-25 ~ 24-25 ~ 24-25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.750.750.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
74
Page 75
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM320KXVAGH/EUAM340KXVAGH/EUAM360KXVAGH/EU
Outdoor unit module 1AM100JXVAGH/EUAM120JXVAGH/EUAM140KXVAGH/EU
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-DS-GB066FAVB x 3DS-GB066FAVB x 3DS-GB066FAVB x 3
OutputkW x n(6.39 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1 (6.39 x 1) x 1 + (6.39 x 2) x 1
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA334
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(830 x 1) x 1 + (620 x 2) x 1 (830 x 1) x 1 + (620 x 2) x 1(620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg5.5 x 1 + 8.4 x 16.5 x 1 + 8.4 x 17.7 x 1 + 8.4 x 1
Sound PressureCoolingdB(A)666766
Sound PressureHeatingdB(A)686968
Sound PowerdB(A)899090
Net Weightkg197.0 x 1 + 285.0 x 1210.0 x 1 + 285.0 x 1226.0 x 1 + 285.0 x 1
Shipping Weightkg213.0 x 1 + 305.0 x 1226.0 x 1 + 305.0 x 1246.0 x 1 + 305.0 x 1
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.750.750.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1
(1,295 x 1,695 x 765) x 2
(1,363 x 1,887 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
76
Page 77
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM380KXVAGH/EUAM400KXVAGH/EUAM420KXVAGH/EU
Outdoor unit module 1AM160KXVAGH/EUAM180KXVAGH/EUAM200KXVAGH/EU
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-
OutputkW x n(7.81 x 1) x 1 + (6.39 x 2) x 1 (7.81 x 1) x 1 + (6.39 x 2) x 1(6.39 x 2) x 2
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA444
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(620 x 2) x 2(620 x 2) x 2(620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg8.4 x 28.4 x 28.4 x 2
Sound PressureCoolingdB(A)676868
Sound PressureHeatingdB(A)697070
Sound PowerdB(A)909091
Net Weightkg253.0 x 1 + 285.0 x 1255.0 x 1 + 285.0 x 1277.0 x 1 + 285.0 x 1
Shipping Weightkg273.0 x 1 + 305.0 x 1275.0 x 1 + 305.0 x 1297.0 x 1 + 305.0 x 1
Net Dimensions (WxHxD)mm(1,295 x 1,695 x 765) x 2(1,295 x 1,695 x 765) x 2(1,295 x 1,695 x 765) x 2
Shipping Dimensions (WxHxD)mm(1,363 x 1,887 x 832) x 2(1,363 x 1,887 x 832) x 2(1,363 x 1,887 x 832) x 2
Cooling℃-5 ~ 48-5 ~ 48-5 ~ 48
Heating℃-25 ~ 24-25 ~ 24-25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.750.750.75
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
78
Page 79
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM440KXVAGH/EUAM460KXVAGH/EUAM480KXVAGH/EU
Outdoor unit module 1AM220KXVAGH/EUAM160KXVAGH/EUAM180KXVAGH/EU
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-DS-GB066FAVBx4DS4GJ5080FVA x 3DS4GJ5080FVA x 3
OutputkW x n(6.39 x 2) x 2(7.81 x 1) x 1 + (7.81 x 2) x 1 (7.81 x 1) x 1 + (7.81 x 2) x 1
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA444
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(620 x 2) x 2(620 x 2) x 2(620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
(1,100 x 2) x 2(1,400 x 1) x 1 + (1,400 x 2) x 1 (1,400 x 1) x 1 + (1,400 x 2) x 1
19.05 (3/4)19.05 (3/4)19.05 (3/4)
41.28 (1-5/8)41.28 (1-5/8)41.28 (1-5/8)
---
79
Page 80
2. Specifications
Wiring
connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg8.4 x 28.4 x 1 + 14.0 x 18.4 x 1 + 14.0 x 1
Sound PressureCoolingdB(A)687070
Sound PressureHeatingdB(A)707272
Sound PowerdB(A)929191
Net Weightkg285.0 x 2253.0 x 1 + 350.0 x 1255.0 x 1 + 350.0 x 1
Shipping Weightkg305.0 x 2273.0 x 1 + 372.0 x 1275.0 x 1 + 372.0 x 1
Net Dimensions (WxHxD)mm(1,295 x 1,695 x 765) x 2
Shipping Dimensions (WxHxD)mm(1,363 x 1,887 x 832) x 2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.750.750.75
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
80
Page 81
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM500KXVAGH/EUAM520KXVAGH/EUAM540KXVAGH/EU
Outdoor unit module 1AM200KXVAGH/EUAM220KXVAGH/EUAM240KXVAGH/EU
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-
OutputkW x n(6.39 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 2) x 1 + (7.81 x 2) x 1 (6.39 x 2) x 1 + (7.81 x 2) x 1
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA444
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(620 x 2) x 2(620 x 2) x 2(620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg8.4 x 1 + 14.0 x 18.4 x 1 + 14.0 x 112.5 x 1 + 14.0 x 1
Sound PressureCoolingdB(A)707071
Sound PressureHeatingdB(A)727273
Sound PowerdB(A)929393
Net Weightkg277.0 x 1 + 350.0 x 1285.0 x 1 + 350.0 x 1333.0 x 1 + 350.0 x 1
Shipping Weightkg297.0 x 1 + 372.0 x 1305.0 x 1 + 372.0 x 1355.0 x 1 + 372.0 x 1
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
(1,295 x 1,695 x 765) x 1 +
(1,363 x 1,887 x 832) x 1 +
0.750.750.75
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
82
Page 83
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM560KXVAGH/EUAM580KXVAGH/EUAM600KXVAGH/EU
Outdoor unit module 1AM260KXVAGH/EUAM280KXVAGH/EUAM300KXVAGH/EU
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-
OutputkW x n
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA444
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(620 x 2) x 2(620 x 2) x 2(620 x 2) x 2
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg12.5 x 1 + 14.0 x 114.0 x 214.0 x 2
Sound PressureCoolingdB(A)717272
Sound PressureHeatingdB(A)737474
Sound PowerdB(A)939393
Net Weightkg
Shipping Weightkg
Net Dimensions (WxHxD)mm(1,295 x 1,795 x 765) x 2(1,295 x 1,795 x 765) x 2(1,295 x 1,795 x 765) x 2
Shipping Dimensions (WxHxD)mm(1,363 x 1,987 x 832) x 2(1,363 x 1,987 x 832) x 2(1,363 x 1,987 x 832) x 2
Cooling℃-5 ~ 48-5 ~ 48-5 ~ 48
Heating℃-25 ~ 24-25 ~ 24-25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.750.750.75
333.0 x 1 + 350.0 x 1342.0 x 1 + 350.0 x 1350.0 x 2
355.0 x 1 + 372.0 x 1364.0 x 1 + 372.0 x 1372.0 x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
84
Page 85
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM620KXVAGH/EUAM640KXVAGH/EUAM660KXVAGH/EU
Outdoor unit module 1AM100JXVAGH/EUAM120JXVAGH/EUAM140KXVAGH/EU
Maximum number of connectable indoor unitsEA646464
Total capacity of the connected Indoor Units
Total capacity of the connected Indoor Units
Power
Efficiency
CasingMaterial
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Outdoor unit module 2AM220KXVAGH/EUAM220KXVAGH/EUAM220KXVAGH/EU
Outdoor unit module 3AM300KXVAGH/EUAM300KXVAGH/EUAM300KXVAGH/EU
Outdoor unit module 4---
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-
OutputkW x n
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA556
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(830 x 1) x 1 + (620 x 2) x 2 (830 x 1) x 1 + (620 x 2) x 2(620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg5.5 x 1 + 8.4 x 1 + 14.0 x 16.5 x 1 + 8.4 x 1 + 14.0 x 17.7 x 1 + 8.4 x 1 + 14.0 x 1
Sound PressureCoolingdB(A)717171
Sound PressureHeatingdB(A)737373
Sound PowerdB(A)939393
Net Weightkg
Shipping Weightkg
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
197.0 x 1 + 285.0 x 1 + 350.0 x 1 210.0 x 1 + 285.0 x 1 + 350.0 x 1 226.0 x 1 + 285.0 x 1 + 350.0 x 1
213.0 x 1 + 305.0 x 1 + 372.0 x 1 226.0 x 1 + 305.0 x 1 + 372.0 x 1 246.0 x 1 + 305.0 x 1 + 372.0 x 1
(1,295 x 1,695 x 765) x 1 +
(1,363 x 1,887 x 832) x 1 +
0.750.750.75
(880 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(880 x 1,695 x 765) x 1 +
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 1
(948 x 1,887 x 832) x 1 +
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
86
Page 87
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM680KXVAGH/EUAM700KXVAGH/EUAM720KXVAGH/EU
Outdoor unit module 1AM160KXVAGH/EUAM180KXVAGH/EUAM200KXVAGH/EU
Maximum number of connectable indoor unitsEA646464
Total capacity of the connected Indoor Units
Total capacity of the connected Indoor Units
Power
Efficiency
CasingMaterial
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Outdoor unit module 2AM220KXVAGH/EUAM220KXVAGH/EUAM220KXVAGH/EU
Outdoor unit module 3AM300KXVAGH/EUAM300KXVAGH/EUAM300KXVAGH/EU
Outdoor unit module 4---
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-
OutputkW x n
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA666
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(620 x 2) x 3(620 x 2) x 3(620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
4,250 x 1 + 4,833 x 1 + 5,667 x 14,833 x 2 + 5,667 x 14,833 x 2 + 5,667 x 1
22.22 (7/8)22.22 (7/8)22.22 (7/8)
53.98 (2-1/8)53.98 (2-1/8)53.98 (2-1/8)
---
DS4GJ5080FVA x 3 +
DSGB066FAVB x 2
(1,400 x 1) x 1 + (1,100 x 2) x 1 +
(1,400 x 2) x 1
DS-GB052FAVB x 2 +
DSGB066FAVB x 2 +
DS4GJ5080FVA x 2
(6.39 x 2) x 2 + (7.81 x 2) x 1
(1,100 x 2) x 2 + (1,400 x 2) x 1
87
Page 88
2. Specifications
Wiring
connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg8.4 x 2 + 14.0 x 18.4 x 2 + 14.0 x 18.4 x 2 + 14.0 x 1
Sound PressureCoolingdB(A)717172
Sound PressureHeatingdB(A)737374
Sound PowerdB(A)939394
Net Weightkg
Shipping Weightkg
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
253.0 x 1 + 285.0 x 1 + 350.0 x 1 255.0 x 1 + 285.0 x 1 + 350.0 x 1 277.0 x 1 + 285.0 x 1 + 350.0 x 1
273.0 x 1 + 305.0 x 1 + 372.0 x 1 275.0 x 1 + 305.0 x 1 + 372.0 x 1 297.0 x 1 + 305.0 x 1 + 372.0 x 1
(1,295 x 1,695 x 765) x 2 +
(1,363 x 1,887 x 832) x 2 +
0.750.750.75
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 2 +
(1,295 x 1,795 x 765) x 1
(1,363 x 1,887 x 832) x 2 +
(1,363 x 1,987 x 832) x 1
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
88
Page 89
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM740KXVAGH/EUAM760KXVAGH/EUAM780KXVAGH/EU
Outdoor unit module 1AM220KXVAGH/EUAM220KXVAGH/EUAM220KXVAGH/EU
Maximum number of connectable indoor unitsEA646464
Total capacity of the connected Indoor Units
Total capacity of the connected Indoor Units
Power
Efficiency
CasingMaterial
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Outdoor unit module 2AM220KXVAGH/EUAM240KXVAGH/EUAM260KXVAGH/EU
Outdoor unit module 3AM300KXVAGH/EUAM300KXVAGH/EUAM300KXVAGH/EU
Outdoor unit module 4---
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-
OutputkW x n
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA666
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(620 x 2) x 3(620 x 2) x 3(620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
4,833 x 2 + 5,667 x 14,833 x 1 + 5,667 x 24,833 x 1 + 5,667 x 2
22.22 (7/8)22.22 (7/8)22.22 (7/8)
53.98 (2-1/8)53.98 (2-1/8)53.98 (2-1/8)
---
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 2
DS-GB066FAVB x 4 +
DS4GJ5080FVA x 2
89
Page 90
2. Specifications
Wiring
connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg8.4 x 2 + 14.0 x 18.4 x 1 + 12.5 x 1 + 14.0 x 18.4 x 1 + 12.5 x 1 + 14.0 x 1
Sound PressureCoolingdB(A)727272
Sound PressureHeatingdB(A)747474
Sound PowerdB(A)949494
Net Weightkg
Shipping Weightkg
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
(1,295 x 1,695 x 765) x 2 +
(1,363 x 1,887 x 832) x 2 +
0.750.750.75
285.0 x 2 + 350.0 x 1285.0 x 1 + 333.0 x 1 + 350.0 x 1 285.0 x 1 + 333.0 x 1 + 350.0 x 1
305.0 x 2 + 372.0 x 1305.0 x 1 + 355.0 x 1 + 372.0 x 1 305.0 x 1 + 355.0 x 1 + 372.0 x 1
(1,295 x 1,795 x 765) x 1
(1,363 x 1,987 x 832) x 1
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 2
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 2
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 2
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 2
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
90
Page 91
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM800KXVAGH/EUAM820KXVAGH/EUAM840KXVAGH/EU
Outdoor unit module 1AM220KXVAGH/EUAM220KXVAGH/EUAM240KXVAGH/EU
Maximum number of connectable indoor unitsEA646464
Total capacity of the connected Indoor Units
Total capacity of the connected Indoor Units
Power
Efficiency
CasingMaterial
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Outdoor unit module 2AM280KXVAGH/EUAM300KXVAGH/EUAM300KXVAGH/EU
Outdoor unit module 3AM300KXVAGH/EUAM300KXVAGH/EUAM300KXVAGH/EU
Outdoor unit module 4---
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-
OutputkW x n
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA666
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(620 x 2) x 3(620 x 2) x 3(620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
4,833 x 1 + 5,667 x 24,833 x 1 + 5,667 x 25,667 x 3
22.22 (7/8)22.22 (7/8)22.22 (7/8)
53.98 (2-1/8)53.98 (2-1/8)53.98 (2-1/8)
---
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 4
(6.39 x 2) x 1 + (7.81 x 2) x 2(6.39 x 2) x 1 + (7.81 x 2) x 2
DS-GB066FAVB x 2 +
DS4GJ5080FVA x 4
91
Page 92
2. Specifications
Wiring
connections
Refrigerant
Sound
External
Dimension
Operating
Temp. Range
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg8.4 x 1 + 14.0 x 28.4 x 1 + 14.0 x 212.5 x 1 + 14.0 x 2
Sound PressureCoolingdB(A)737373
Sound PressureHeatingdB(A)757575
Sound PowerdB(A)949494
Net Weightkg
Shipping Weightkg
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
285.0 x 1 + 342.0 x 1 + 350.0 x 1285.0 x 1 + 350.0 x 2333.0 x 1 + 350.0 x 2
305.0 x 1 + 364.0 x 1 + 372.0 x 1305.0 x 1 + 372.0 x 2355.0 x 1 + 372.0 x 2
(1,295 x 1,695 x 765) x 1 +
(1,363 x 1,887 x 832) x 1 +
0.750.750.75
(1,295 x 1,695 x 765) x 1 +
(1,295 x 1,795 x 765) x 2
(1,363 x 1,987 x 832) x 2
(1,295 x 1,795 x 765) x 2
(1,363 x 1,887 x 832) x 1 +
(1,363 x 1,987 x 832) x 2
(1,295 x 1,795 x 765) x 3
(1,363 x 1,987 x 832) x 3
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.
92
Page 93
2. Specifications
Standard
TypeDVM SDVM SDVM S
AM860KXVAGH/EUAM880KXVAGH/EUAM900KXVAGH/EU
Outdoor unit module 1AM260KXVAGH/EUAM280KXVAGH/EUAM300KXVAGH/EU
Maximum number of connectable indoor unitsEA646464
Total capacity of the connected Indoor Units
Total capacity of the connected Indoor Units
Power
Efficiency
CasingMaterial
Heat Exchanger
Compressor
Fan
Fan Motor
Piping Connections
Outdoor unit module 2AM300KXVAGH/EUAM300KXVAGH/EUAM300KXVAGH/EU
Outdoor unit module 3AM300KXVAGH/EUAM300KXVAGH/EUAM300KXVAGH/EU
Outdoor unit module 4---
Fin Treatment-Anti-corrosionAnti-corrosionAnti-corrosion
Model Name-
OutputkW x n
Oil
Type-PropellerPropellerPropeller
Discharge direction-TopTopTo p
QuantityEA666
Air Flow Rate
External Static Pressure
Type-BLDC MotorBLDC MotorBLDC Motor
OutputW x n(620 x 2) x 3(620 x 2) x 3(620 x 2) x 3
Liquid Pipe
Gas Pipe
High pressure Gas Pipe(HR Only)
Heat Insulation-Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Piping length (ODU-IDU)
Piping length (1st Branch-IDU)
Total piping length (System)
Level difference (ODU in highest position)
Level difference (IDU in highest position)
Level difference (IDU-IDU)
Transmission Cablemm
Remark-F1, F2F1, F2F1, F2
Power supply intakeType-R410AR410AR410A
Factory Chargingkg12.5 x 1 + 14.0 x 214.0 x 314.0 x 3
Sound PressureCoolingdB(A)737474
Sound PressureHeatingdB(A)757676
Sound PowerdB(A)949595
Net Weightkg
Shipping Weightkg
Net Dimensions (WxHxD)mm(1,295 x 1,795 x 765) x 3(1,295 x 1,795 x 765) x 3(1,295 x 1,795 x 765) x 3
Shipping Dimensions (WxHxD)mm(1,363 x 1,987 x 832) x 3(1,363 x 1,987 x 832) x 3(1,363 x 1,987 x 832) x 3
Cooling℃-5 ~ 48-5 ~ 48-5 ~ 48
Heating℃-25 ~ 24-25 ~ 24-25 ~ 24
2
Both indoor and outdoor unit Both indoor and outdoor unit Both indoor and outdoor unit
0.750.750.75
333.0 x 1 + 350.0 x 2342.0 x 1 + 350.0 x 2350.0 x 3
355.0 x 1 + 372.0 x 2364.0 x 1 + 372.0 x 2372.0 x 3
NOTE
• Specification may be subject to change without prior notice.
• Specification comply with EN14511.
1) Nominal capacities are based on (Equivalent refrigerant piping 7.5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Allowed combination ratio of the total rated indoor unit capacity over the rated outdoor unit capacity is
50~130%.
3) Sound pressure level is obtained in an anechoic room.
- Sound pressure level is a relative value, depending on the distance and acoustic environment.
- Sound pressure level may differ depending on operation condition.
- dBA = A-weighted sound pressure level
- Reference acoustic pressure 0 dB = 20uPa
4) These products contain R410A which is fluorinated greenhouse gas.
5) Sound power level is an absolute value that a sound source generates.
- dBA = A-weighted sound power level
- Reference power : 1pW
- Measured according to ISO 3741
6) Sound values of multi combination are theoretical values based on sound results of individual installed units.
7) These products contain R410A which is fluorinated greenhouse gas.
8) If outdoor unit is located in a higher position than indoor unit, level difference is 110m or under.
(If the level difference is higher than 50m, make a decision by PDM kit installation Guide software whether
the PDM kit should be installed or not.)
- PDM kit: Pressure Drop Modulation kit
When the outdoor unit is below the indoor unit & the level differences are 40m or more, contact your local
dealer for more information.
※ In case you want to know more information regarding capacity and correction, please refer to capacity table