2 . Use proper parts: Use only exact re p l a c e-
ment parts. (Also, we recommend re p l a c i n g
parts rather than repairing them.)
3 . Use the proper tools: Use the proper tools
and test equipment, and know how to use
them. Using defective tools or test equipment may cause problems later- i n t e r m i t t e n t
contact, for example.
4 . Power Cord: Prior to re p a i r, check the
power cord and replace it if necessary.
5 . Avoid using an extension cord, and avoid
tapping into a power cord. This practice
may result in malfunction or fire .
6 . After completing repairs and re a s s e m b l y,
check the insulation resistance. Pro c e d u re :
Prior to applying power, measure the re s i stance between the power cord and the
g round terminal. The resistance must be
g reater than 30 megohms.
Fig. 1-1 Avoid Dangerous Contact
Fig. 1-2 No Tapping and No Extension Cords
7 . Make sure that the grounds are adequate.
8 . Make sure that the installation conditions
a re satisfactory. Relocate the unit if necess a r y.
9 . Keep children away from the unit while it is
being re p a i re d .
1 0 . Be sure to clean the unit and its surro u n d-
ing are a .
Fig. 1-3 No Kids Nearby!
Fig. 1-4 Clean the Unit
Samsung Electronics
1-1
M E M O
1-2
Samsung Electronics
2. Product Specifications
2-1 Table
Model
Item
Type-
CoolingBTU/h
DehumidityingI/h
Air volumeCoolingm3/min
Performance
NoiseCoolingdB
Energy efficiency ratio CoolingBTU/h.W
Power V/Hz
Power ConsumptionCoolingW
Operating CurrentCoolingA
Power factorCooling%
Power
Starting currentA
Power cordLengthm
Number of core wire
Fuse capacityA
Outer Width x Heightmm
dimensionx Depthinch
Weightkg
Refrigerant pipeLiquidOD(mm)x L(m)
GAS
Drain hoseID(mm)x L(m)
Size
Compressor Type
MotorType
Rated outputW
Blower Type
Motor Type
Rated outputW
Heat exchanger
Refrigerant control unit
Freezer oil capacity
Refrigerant to change(R-22)
Protection device
Cooling test Condition
Maximum operation Condition
A S 0 7 A 1 V E
Indoor unitOutdoor unit
Wall-mounting
7,500
1.2
6.0
3545
11.2
1/220 - 240~/50
670
2.8
99.7
17.0
2-
250V 10/16A
3.15-
815x298x182720x532x245
32.08x11.73x7.1728.35x20.94x9.65
9.627
ø6.35 x 5
ø9.52 x 5
ø17 x 2000
-Rotary
--
-675
Cross-fanPropeller
ResinSteel
3515
2Row 12Step1Row 20Step
CAPILLARY TUBE
280
670
-MST24AMN-12008
INDOOR UNIT : DB27°C WB19°C OUTDOOR UNIT : DB35°C WB24°C
INDOOR UNIT : DB32°C WB23°C OUTDOOR UNIT : DB43°C WB26°C
A S 0 9 A 1 V E
Indoor unitOutdoor unit
Wall-mounting
9,000
1.6
6.1
3545
10.2
1/220 - 240~/50
880
4.0
91.7
22.0
2-
250V 10/16A
3.15-
815x298x182720x532x245
32.08x11.73x7.1728.35x20.94x9.65
9.628
ø6.35 x 5
ø9.52 x 5
ø17 x 2000
-Rotary
--
-895
Cross-fanPropeller
ResinSteel
3515
2Row 12Step1Row 20Step
CAPILLARY TUBE
360
680
-MRA12037-12007
A S 1 2 A 1 V E
Indoor unitOutdoor unit
Wall-mounting
12,000
1.9
7.8
3849
10.2
1/220 - 240~/50
1180
5.0
98.3
30.0
2-
250V 10/16A
3.15-
815x298x182720x532x245
32.08x11.73x7.1728.35x20.94x9.65
9.631
ø6.35 x 5
ø12.7 x 5
ø17 x 2000
-Rotary
--
-1210
Cross-fanPropeller
ResinSteel
3520
2Row 12Step2Row 20Step
CAPILLARY TUBE
410
930
-MRA12030-12008
A S 0 9 A 1 V B
Indoor unitOutdoor unit
Wall-mounting
9,000
1.6
6.1
3647
10.2
1/220/60
880
4.0
99.9
24.0
2-
250V 10/16A
3.15-
815x298x182720x532x245
32.08x11.73x7.1728.35x20.94x9.65
9.627
ø6.35 x 5
ø9.52 x 5
ø17 x 2000
-Rotary
--
-879
Cross-fanPropeller
ResinSteel
3520
2Row 12Step1Row 20Step
CAPILLARY TUBE
360
660
-MRA12093-12007
Indoor unitOutdoor unit
3.15-
815x298x182720x532x245
32.08x11.73x7.1728.35x20.94x9.65
Cross-fanPropeller
ResinSteel
2Row 12Step2Row 20Step
A S 1 2 A 1 V B
Wall-mounting
12,000
1.9
7.8
3950
9.4
1/200/60
1280
5.8
99.9
31.0
2-
250V 10/16A
9.631
ø6.35 x 5
ø12.7 x 5
ø17 x 2000
-Rotary
--
-1300
3520
CAPILLARY TUBE
410
880
-MRA12002-9200
INDOOR UNIT : DB27°C WB19.5°C OUTDOOR UNIT : DB35°C WB24°C
INDOOR UNIT : DB32°C WB22.5°C OUTDOOR UNIT : DB43°C WB25.5°C
Samsung Electronics
2-1
2-2 Dimensions
2-2-1 Indoor Unit
Air out
2-2-1 Outdoor Unit
Air
in
(Front view)
(Rear view)
(Remote control)
Installation plate
2-2
(Front view)
(Rear view)
Samsung Electronics
2-3 Refrigerating Cycle Block Diagram
INDOOR UNIT
Heat
exchanger
(Evaporator)
OUTDOOR UNIT
Capillary tube
T
Liquid side
T
Gas side
2-way valve
3-way valve
Compressor
Heat
exchanger
(Condenser)
Cooling
Gas leak check point
Samsung Electronics
2-3
M E M O
2-4
Samsung Electronics
3. Operating Instructions and Installation
3-1 Operating Instructions
3-1-1 Name & Function of Key in remote controller
NO
NAMED OF KEY
1
2
3
MODE
4
5
6
7
8
TURBO
OFF
(UP)
(DOWN)
On/Off Button. Use this button to start and stop air conditioner.
Temp. up button. If the button is pressed once,
the setting temperature is increased by 1°C
Temp. up button. If the button is pressed once,
the setting temperature is decreased by 1°C
Each time you press this button,
MODE is changed in the following order.
Use this button to provide heavy duty cooling & Heating for 30 minutes.
Set up the reserve or cancel the timer on and timer off quickly
Use this button for sleep operation.
(The SLEEP mode can be selected at COOL and HEAT mode.)
Adjusts air flow vertically.
Each time you press this button.
Each time you press this button,
FAN SPEED is changed in the following order.
FUNCTION OF KEY
: Auto Mode
: Cool Mode
: Dry Mode
: Fan Only
9
C
O
10
V
E
R
11
12
13
14
15
Samsung Electronics
T
I
M
E
R
ON TIMER
OFF TIMER
SET
CANCEL
TIME
(UP)
(DOWN)
Set up the time that operation start.
Set up the time that operation stop.
Use this button to reserve the timer on.
Use this button to reserve or cancel the timer on and timer off.
If the button is pressed once, the time increase by one minute
during the time set mode, and ten minutes during the timer set mode.
If the button is pressed once, the time decrease by one minute
during the time set mode, and ten minutes during the timer set mode.
Without regard to ON/OFF condition in remote controller,
use this button to set current time.
Adjust the current time using button.
(Data can be transmitted after setting up the time)
3-1
Operating Instructions and Installation
3-1-1 Name & Function of Key in remote controller
1. A U TO MODE : In this mode, operation
C O O L mode is selected automatically by the
room temperature of initial operation.
Operation Type
Tr≥ 24.5°C+∆TCompressor ON
Cool Operation
Tr≤ 24°C+∆TCompressor OFF
∆T= -1°, -2°C, 0°C+1°C+2°C
∆T is controlled by setting temperature
up/down key of remote contro l l e r
* FAN SPEED : A U TO
2. C O O L MODE : The unit operates accord i n g
to the diff e rence between the setting and
room temperature. (18°C~30°C)
3. D RY MODE : Has 3 states, each determined
by room temperature .
The unit operates in DRY m o d e .
*Co m p ressor ON/OFF Time is contro l l e d
compulsorily(can not set up the fan speed,
always bre e z e ) .
* P rotective function : Low temperature
release. (Prevention against fre e z e )
Room Temp
4. TURBO MODE : This mode is available in
A U TO, COOL, DRY, FAN MODE.
When this button is pressed at first, the air
conditioner is operated “powerful” state for
30 minutes re g a rdless of the set temperat u re, room temperature .
When this button is pressed again, or when
the operating time is 30 minutes, turbo
operation mode is canceled and returned to
the previous mode.
*But, if you press the TURBO button in DRY
or FAN mode that is changed with A U TO
mode automatically.
5 . S L E E P MODE : Sleep mode is available
only in COOL m o d e .
The operation will stop after 6 hours.
*In COOL mode : The setting temperature
is automatically raised by 1°C each 1hour
When the temperature has been raised by
total of 2°C, that temperature is maint a i n e d .
6. FAN SPEED : Manual (3 step), Auto (4 step)
Fan speed automatically varies depending
on both the diff e rence between setting and
the room temperature .
3-2
Samsung Electronics
Operating Instructions and Installation
7 . C O M P U L S O RY O P E R ATION :
For operating the air conditioner without
the remote contro l l e r.
* A U TO : The operating is the same function that A U TO MODE in the remote cont ro l l e r.
8 .SWING : BLADE-H is rotated vertically by
the stepping motor.
*Memory louver : When ON/OFF button is
p ressed at stop state, the BLADE-H re t u r n s
to its original location which is operating
state before stop
*Swing Set : Press the button under the
remote control is displayed on LCD the ,
and the blades move up and down, about 43°.
If the one more time press thebutton, blatles location is stop.
9 .Quick OFF TIMER: OFF timer (quick timer)
allows reservation or cancel the timer on
and timer off quickly
When OFF timer button is pressed at operating state, LCD displays the polling state
s e q u e n t i a l l y.
The LCD also displays the time re m a i n i n g .
OFF TIMER : The air Conditioner is turned
OFF at a specified time using .
OFF TIMER
*ON TIMER : Only timer LED lights on.
*OFF TIMER : Both timer and operation
LED lights on.
*3 minutes delay timer.
11 . SELF Diagnosis
LED DISPLAY
o p e r-
T I M E R
a t i o n
FA N
Tu r b o
Check Point
I n t e r ruption of electric power and Power on.
Abnormal condition of the room sensor.
Abnormal condition of the indoor unit's heat exchanger sensor.
Indoor unit fan motor lock.
L E D
:
b l i n k i n g
: LED off
1 2 . BUZZER SOUND : Whenever the ON/OFF
button is pressed or whenever change
occurs to the condition which is set up or
select, the compulsory operation mode,
buzzer is sounded "beep"
1 0 . 24-Hour ON/OFF Real Setting Ti m e r. : The
air conditioner is turned ON at a specified
time using .
ON TIMER
Samsung Electronics
3-3
3-2 Installation
3-2-1 Selecting Area for Installation
Select an area for installation that is suitable
to the customer's needs.
3-2-1(a) Indoor Unit
1 . Make sure that you install the indoor unit in
an area providing good ventilation. It must
not be blocked by an obstacle affecting the
airflow near the air inlet and the air outlet.
2 . Make sure that you install the indoor unit in
an area allowing good air handling and
endurance of vibration of the indoor unit.
3. Make sure that you install the indoor unit in
an area where there is no source of heat or
vapor nearby.
4 . Make sure that you install the indoor unit in
an area from which hot or cool air is spre a d
evenly in a ro o m .
5 . Make sure that you install the indoor unit in
an area away from TVs, audio units, cordless phones, fluorescent lighting fixture s
and other electrical appliances (at least 1
m e t e r ) .
6 . Make sure that you install the indoor unit in
an area which provides easy pipe connection with the outdoor unit, and easy
drainage for condensed water.
(Fix the unit firmly if it is mounted in a
high place.)
3 . Make sure that you install the outdoor unit
in area providing good ventilation and
which is not dusty. It must not be blocked
by any obstacle affecting the airflow near
the air inlet and the air outlet.
4 . Make sure that you install the outdoor unit
in area free from animals or plants.
5 . Make sure that you install the outdoor unit
in area not blocking the traff i c .
6. Make sure that you install the outdoor unit
in area easy to drain condensed water fro m
the indoor unit.
7. Make sure that you install the outdoor unit
in area which provides easy connection
within the maximum allowable length of a
coolant pipe(10 meters).
Note
1. Add 10 grams of refrigerant (R-22) for
every 1 meter if the pipe length exceeds
the standard pipe length of 5 meters.
2. Maintain a height between the indoor and
outdoor units of less than 3 meters.
8 . Make sure that you install the outdoor unit
in an area which is large enough to accommodate the measurements
shown in figure on the next page.
7. Make sure that you install the indoor unit in
an area which is large enough to accomodate the measurements shown in figure on
the next page.
3-2-1(b) Outdoor Unit
1 . Make sure that you install the outdoor unit
in area not exposed to the rain or direct sun
l i g h t .
(Install a separate sunblind if exposed to
d i rect sun light.)
2 . Make sure that you install the outdoor unit
in area allowing good air moment, not
amplifying noise or vibration, especially to
avoid disturbing neighbours.
Caution :
It is harmful to the air conditioner if it is used in the following environments: greasy areas (including areas near machines),
salty areas such as coast areas, areas where sulfuric gas is present such as hot spring areas. Contact your dealer for advice.
3-4
3-2-1(c) Remote Control Unit
1 .Make sure that you install the remote con-
t rol unit in an area free from obstacles such
as curtains etc, which may block signals
f rom the remote control unit.
2. Make sure that you install the remote cont rol unit in an area not exposed to
d i rect sunlight, and where there is no sourc e
of heat.
3. Make sure that you install the remote cont rol unit in an area away from TVs, audio
units, cordless phones, fluorescent lighting
f i x t u res and other electrical appliances (at
least 1 meter).
Samsung Electronics
3-2-2 Installation diagram of indoor unit and outdoor unit
Operating Instructions and Installation
A Indoor unit gas leak test check point
Indoor unit
Piping
1
3
2
Tape vinyl
B Drain hose installation
Cut the piping hole
sloped slightly
5 6
250mm
or more
Piping may be laid to the rear, left,
right or down .
1. Determine the position of the pipe and drain hose hole
using the right figure and drill the hole with an inner
diameter of 65mm so that it slants slightly downwards.
2. If you are fixing the indoor unit to a… Then follow Steps…
Wall 3.
Window frame 4 to 6.
3. Fix the installation plate to the wall in a manner appropriate to the weight of the indoor unit.
If you are mounting the plate on a concrete wall with
anchor bolts, the anchor bolts must not project by more
than 20mm.
4. Determine the positions of the wooden uprights to be
attached to the window frame.
3-2-2(b) Purging the Unit
5. Attach the wooden uprights to the window frame in a
manner appropriate to the weight of the indoor unit.
6. Using tapped screws, attach the installation plate to the
wooden uprights, as illustrated in the last figure opposite.
On delivery, the indoor unit is loaded with an inert gas.
All this gas must therefore be purged before connecting the
assembly piping. To purge the inert gas, proceed as fol lows.
Unscrew the caps at the end of each pipe.
Result : All inert gas escapes from the indoor unit.
•To prevent dirt or foreign objects from getting into
the pipes during installation, do NOT remove the
caps completely until you are ready to connect the
piping.
3-6
Samsung Electronics
3-2-2(c) Connecting the Assembly Cable.
The outdoor unit is powered from the indoor unit via the assembly
cable. If the outdoor unit is more than five metres away from the
indoor unit, the cable must first be extended to a maximum of
ten metre s .
1 . Extend the assembly cable if necessary.
< AS09A1VB / AS12A1VB >
Indoor unit
Outdoor unit
< The others >
2 . Open the front grille by pulling on the tabs on the lower right and
left sides of the indoor unit.
3 . Remove the screw securing the connector cover.
4 . Pass the assembly cable through the rear of the indoor unit and
connect the assembly cable to terminals 1, 3, 5(1,2,3,5).
• Each wire is labelled with the corresponding terminal number.
5 . Pass the other end of the cable through the 65mm hole in the wall.
6 . Replace the connector cover, carefully tightening the scre w.
7 . Close the front grille.
8 . For further details on how to plug the other end of the assembly
cable into the outdoor unit, refer to page 12.
Operating Instructions and Installation
Indoor unit
Outdoor unit
Samsung Electronics
3-7
Operating Instructions and Installation
3-2-2(d) Installing and Connecting the Indoor Unit Drain Hose
C a re must be taken when installing the drain hose for the indoor unit to ensure that any condensa tion water is correctly drained outside.l When passing the drain hose through the 65mm hole drilled
in the wall, check that none of the following situations occur.
The hose must
NOT slope upw
ards.
The end of the drain
hose must NOT be
placed in water.
Do NOT bend the
hose in different
directions.
Keep a clearance of at
least 5cm between the
end of the hose and the
ground.
Do NOT place the end
of the drain hose in a
hollow.
To install the drain hose, proceed as follows.
1. If necessary, connect the 2-metre extension to the drain hose.
2 . If you are using the extension, insulate the inside part of the extension drain hose with a shield.
3. Pass the drain hose under the refrigerant piping, taking care to keep the drain hose tight.
4. Pass the drain hose through the hole in the wall, making sure that it is sloping downwards, as
shown in the illustrations above.
Shield
The hose will be fixed permanently into position once
the whole installation has been tested for gas leaks;
refer to page 16 for further details.
Drain hoseExtension drain hose
3-2-2(e) Outdoor unit installation
Wiring connection
1. Remove the cover-E parts.
2. Firmly connect the cable connector in the terminal block.
3. Fasten the M4 ring terminal to the hole marked
4. Firmly fix the ass'y cable with clamp wire holder.
5. Assemble the cover-E parts.
6. To prevent the entry of water, form a trap of the ass'y cable as illustrated in the installation diagram of indoor and outdoor unit.
3-8
Cover-E parts
Screw
<AS12A1VB/AS09A1VB ONLY><OTHERS MODEL>
Samsung Electronics
Cover-E parts
Screw
3-2-2(f) Flare Modification
• Tools used
Flare modification procedure
Operating Instructions and Installation
1 ) Cut the pipe using a pipe cutter.
Oblique RaughnessBurr
3 ) Insert a flare nut into the pipe and
modifty flare .
2 ) Remove burrs at the tip of the pipe cut.
Caution : Burrs not removed may result in
leakage of gas.
Pipe
Reamer
D
A
Outer diameterA(mm)
ø6.35mm1.3
ø9.52mm1.8
ø12.7mm2.0
* Unproper flaring
Samsung Electronics
InclinedSurface
damaged
CrackedUneven
thickness
3-9
Operating Instructions and Installation
3-2-2(g) Air-Purge Procedure
• Use the refrigerant of the outdoor unit to purge air inside indoor unit and pipe.
1. Remove the caps from the 2-way valve(B)
and the 3-way valve(A).
2 Turn the 2-way valve cock approx. 45°
counterclockwise to open it. Close it
about 10 seconds later.
Valve stem
3 Check refrigerant leakage of each joint parts
(A, B, C & D in right figure)
Valve stem
Stopper
not
Leaking
leaking
If leaking, tighten the flare nut one more time.
If continues to leak, although the pipe fixing
area has been tightened again,
repair the leaking area.
4. Open the 2-way valve again.
5. Open the service valve cap of the 3-way
valve and press the needle valve to
discharge gas for 3 seconds and leave it
for about 1 minute.
Repeat the above procedure for 3 times
to purge air.
6. Open the 2-way valve and 3-way valve
completely
Indoor Unit
Liquid pipe side
2-way valve3-way valve
Gas pipe side
7. Close the cap of each valve.
8. Check each valve for leakage.
3-10
Outdoor Unit
Samsung Electronics