Samsung AM***KN4DEH Installation Manual

Air conditioner
Installation manual
AM✴✴✴KN4DEH
• Thank you for purchasing this Samsung air conditioner.
• Before operating this unit, please read this manual carefully and retain it for future reference.
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 1 2016-02-03 오전 11:14:43
2
English
Contents
Safety Information 3
Installation Procedure 5
Step 1 Checking and preparing accessories Step 2 Choosing the installation location Step 3 Optional: Insulating the body of the indoor unit Step 4 Installing the indoor unit Step 5 Purging inert gas from the indoor unit Step 6 Cutting and flaring the pipes Step 7 Connecting the assembly pipes to the refrigerant pipes Step 8 Performing the gas leak test Step 9 Insulating the refrigerant pipes Step 10 Installing the drain hose and drain pipe Step 11 Performing the drainage test Step 12 Connecting the power and communication cables Step 13 Setting the indoor unit addresses and the installation options
Appendix 40
Troubleshooting
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 2 2016-02-03 오전 11:14:43
3
English
Safety Information
WARNING
• Hazards or unsafe practices that may result in severe
personal injury or death.
CAUTION
• Hazards or unsafe practices that may result in minor
personal injury or property damage.
• Carefully follow the precautions listed below because
they are essential to guarantee the safety of the equipment.
WARNING
• Always disconnect the air conditioner from the power
supply before servicing it or accessing its internal components.
• Verify that installation and testing operations are
performed by qualified personnel.
• Verify that the air conditioner is not installed in an
easily accessible area.
General information
WARNING
• Carefully read the content of this manual before
installing the air conditioner and store the manual in a safe place in order to be able to use it as reference after installation.
• For maximum safety, installers should always
carefully read the following warnings.
• Store the operation and installation manual in a safe
location and remember to hand it over to the new owner if the air conditioner is sold or transferred.
• This manual explains how to install an indoor unit
with a split system with two SAMSUNG units. The use of other types of units with different control systems may damage the units and invalidate the warranty. The manufacturer shall not be responsible for damages arising from the use of non compliant units.
• This product has been determined to be in compliance with the Low Voltage Directive (2006/95/EC), and the Electromagnetic Compatibility Directive (2004/108/ EC) and the Machinery Directive (2006/42/EC) of the European Union.
• The manufacturer shall not be responsible for damage originating from unauthorized changes or the improper connection of electric and requirements set forth in the “Operating limits” table, included in the manual, shall immediately invalidate the warranty.
• The air conditioner should be used only for the applications for which it has been designed: the indoor unit is not suitable to be installed in areas used for laundry.
• Do not use the units if damaged. If problems occur, switch the unit off and disconnect it from the power supply.
• In order to prevent electric shocks, fires or injuries, always stop the unit, disable the protection switch and contact SAMSUNG’s technical support if the unit produces smoke, if the power cable is hot or damaged or if the unit is very noisy.
• Always remember to inspect the unit, electric connections, refrigerant tubes and protections regularly. These operations should be performed by qualified personnel only.
• The unit contains moving parts, which should always be kept out of the reach of children.
• Do not attempt to repair, move, alter or reinstall the unit. If performed by unauthorized personnel, these operations may cause electric shocks or fires.
• Do not place containers with liquids or other objects on the unit.
• All the materials used for the manufacture and packaging of the air conditioner are recyclable.
• The packing material and exhaust batteries of the remote controller(optional) must be disposed of in accordance with current laws.
• The air conditioner contains a refrigerant that has to be disposed of as special waste. At the end of its life cycle, the air conditioner must be disposed of in authorized centres or returned to the retailer so that it can be disposed of correctly and safely.
Safety Information
Safety Information
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 3 2016-02-03 오전 11:14:43
4
Safety Information
English
Safety Information
Installing the unit
WARNING
IMPORTANT: When installing the unit, always remember to connect first the refrigerant tubes, then the electrical lines.
• Always disassemble the electric lines before the refrigerant tubes.
• Upon receipt, inspect the product to verify that it has not been damaged during transport. If the product appears damaged, DO NOT INSTALL it and immediately report the damage to the carrier or retailer (if the installer or the authorized technician has collected the material from the retailer.)
• After completing the installation, always carry out a functional test and provide the instructions on how to operate the air conditioner to the user.
• Do not use the air conditioner in environments with hazardous substances or close to equipment that release free flames to avoid the occurrence of fires, explosions or injuries.
• Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from both sides and allow repairs or maintenance operations to be carried out. The unit’s components should be accessible and easy to disassemble without endangering people and objects. For this reason, when provisions of the installation manual are not complied with, the cost required to access and repair the units (in SAFETY CONDITIONS, as set out in prevailing regulations) with harnesses, ladders, scaffolding or any other elevation system will NOT be considered part of the warranty and will be charged to the end customer.
Power supply line, fuse or circuit breaker
WARNING
• Always make sure that the power supply is compliant with current safety standards. Always install the air conditioner in compliance with current local safety standards.
• Always verify that a suitable grounding connection is available.
• Verify that the voltage and frequency of the power supply comply with the specifications and that the installed power is sufficient to ensure the operation of any other domestic appliance connected to the same electric lines.
• Always verify that the cut-off and protection switches are suitably dimensioned.
• Verify that the air conditioner is connected to the power supply in accordance with the instructions provided in the wiring diagram included in the manual.
• Always verify that electric connections (cable entry, section of leads, protections…) are compliant with the electric specifications and with the instructions provided in the wiring scheme. Always verify that all connections comply with the standards applicable to the installation of air conditioners.
• Devices disconnected from the power supply should be completely disconnected in the condition of overvoltage category.
CAUTION
Make sure that you earth the cables.
• Do not connect the earth wire to the gas pipe, water pipe, lighting rod or telephone wire. If earthing is not complete, electric shock or fire may occur.
Install the circuit breaker.
• If the circuit breaker is not installed, electric shock or fire may occur.
Make sure that the condensed water dripping from the drain hose runs out properly and safely.
Install the power cable and communication cable of the indoor and outdoor unit at least 1m away from the electric appliance.
Install the indoor unit away from lighting apparatus using the ballast.
• If you use the wireless remote control, reception error may occur due to the ballast of the lighting apparatus.
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 4 2016-02-03 오전 11:14:43
5
Installation Procedure
English
Installation Procedure
Installation Procedure
Do not install the air conditioner in following places.
• Place where there is mineral oil or arsenic acid. Resin parts flame and the accessories may drop or water may leak. The capacity of the heat exchanger may reduce or the air conditioner may be out of order.
• The place where corrosive gas such as sulphuric acid gas generates from the vent pipe or air outlet.
• The copper pipe or connection pipe may corrode and refrigerant may leak.
• The place where there is a machine that generates electromagnetic waves. The air conditioner may not operate normally due to control system.
• The place where there is a danger of existing combustible gas, carbon fibre or flammable dust.
• The place where thinner or gasoline is handled. Gas may leak and it may cause fire.
Step 1 Checking and preparing accessories
The following accessories are supplied with the indoor unit. The type and quantity may differ, depending on the specifications.
Insulation pipe (3 ea) Cable-tie (6 ea)
Drain hose (1 ea) Installation manual (1 ea)
Clamp (1 ea) User manual (1 ea)
Installation template (1 ea)
Step 2 Choosing the installation location
Installation location requirements
• There must be no obstacles near the air inlet and outlet.
• Install the indoor unit on a ceiling that can support its weight.
• Maintain sufficient clearance around the indoor unit.
• Before installing the indoor unit, be sure to check
whether the chosen location is well-drained.
• The indoor unit must be installed such that it is beyond public access and is not touchable by users.
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 5 2016-02-03 오전 11:14:44
6
Installation Procedure
Installation Procedure
English
Indoor unit dimensions
Category Ceiling type Open type
Front
1000
358
Ceiling opening dimension
960 (950 - 960)
Ceiling opening dimension
960 (950 - 960)
116
1050
883
Large
385
166
66
357
404
128
181
190
317
100
153
162
289
138
94
Small
385
166
66
357
404
128
181
190
233
100
153
162
205
138
94
Common
646
646
H1 Large: 180, Small: 150 H2 Large: 152, Small: 122
H2
942
787
80
ø100
H1
Ceiling type Open type
Model
AM045KN4DEH* AM056KN4DEH*
AM071KN4DEH* AM090KN4DEH*
AM112KN4DEH* AM128KN4DEH* AM140KN4DEH*
Chassis Small Large
Net dimension
(W × D × H)
mm 947 x 947 x 281 947 x 947 x 281 947 x 947 x 365
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 6 2016-02-03 오전 11:14:45
7
Installation Procedure
English
Net weight kg 21.0 21.0 24.0
Liquid pipe connection ø6.35 ø9.52 ø9.52
Gas pipe connection ø12.7 ø15.88 ø15.88
Drain hose connection mm Outer diameter : ø32, Inner diameter : ø26.5
Spacing requirements
A : 1500 mm or more
A
A
A
A
'H2' mm
Indoor unit
Obstruction
20 mm
1500 mm or more
10 mm
2500 mm or more
(Unit: mm)
Model
AM045KN4DEH* AM056KN4DEH*
AM071KN4DEH* AM090KN4DEH*
AM112KN4DEH* AM128KN4DEH* AM140KN4DEH*
H2 261 261 345
CAUTION
• The indoor unit must be installed according to the specified distances in order to permit accessibility from each side, to guarantee correct operation, maintenance, and repair of the unit. The components of the indoor unit must be reachable and removable under safe conditions for people and the unit.
• Do not hold the discharge while carrying the indoor unit to avoid the possibility of breakage.
• You must hold the hanger plate on the corner and carry the indoor unit.
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 7 2016-02-03 오전 11:14:45
8
Installation Procedure
Installation Procedure
English
Step 3 Optional: Insulating the body of the indoor unit
If you install a cassette type indoor unit on the ceiling when temperature is over 27°C and humidity is over 80%, you must apply an extra 10 mm thick polyethylene insulation or a similar type of insulation to the body of the indoor unit.
Cut away the part where pipes are pulled out for the insulating work.
A
Insulate the end of the pipe and some curved area by using separate insulator.
NOTE
• A: Reference for the outer circumference of the unit (When insulating the body of the indoor unit, use A as the reference for its outer circumference.)
Indoor unit type and models Dimensions
All way cassette
type <S>
(947 x 947 x 281)
AM045KN4DEH* AM056KN4DEH* AM071KN4DEH* AM090KN4DEH*
2610 x 130
All way cassette
type <L>
(947 x 947 x 365)
AM112KN4DEH* AM128KN4DEH* AM140KN4DEH*
2610 x 215
Step 4 Installing the indoor unit
When deciding on the location of the air conditioner the following restrictions must be taken into account.
1 Determine the positions of the pipe and the drain
hose hole as shown in the pattern sheet, and drill the hole with an inner diameter of 14 mm.
NOTE
• Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity. For this reason, before drilling the holes, be sure to maintain the correct dimensions between the markings.
2 Insert bolt anchors, use existing ceiling supports or
construct a suitable support as shown in figure.
Concrete
Hole in anchor Hole in plug
Suspension bolt (M10) - eld supply
Insert
3 Install the suspension bolts, depending on the ceiling
type.
Ceiling support
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 8 2016-02-03 오전 11:14:46
9
Installation Procedure
English
CAUTION
• Make sure that the ceiling is strong enough to support the weight of the indoor unit. Before hanging the unit, test the strength of each attached suspension bolt.
• If the length of the suspension bolt is more than 1.5 m, you are required to prevent vibration.
4 Screw eight nuts and washers to the suspension bolts,
making space for hanging the indoor unit.
CAUTION
• You must install all of the suspension rods.
• It is important to leave sufficient space in the false
ceiling to allow access for maintenance or repairs to the drainage pipe connection, the refrigerant pipe connection, or to remove the unit if necessary.
5 Hang the indoor unit to the suspension bolts between
two nuts. Screw the nuts to suspend the unit. Cut a pad stopper and place it on the bracket at this time
1
2
2
6 Adjust the unit to the appropriate position, taking into
account the installation area for the front panel.
• Place the pattern sheet on the indoor unit.
• Adjust the space between the ceiling and the
indoor unit by using a dimension gauge.
• Fix the indoor unit securely after adjusting the
level of the unit by using a leveller.
• Remove the pattern sheet and install the front
panel.
11.5 mm
Indoor unit
Ceiling
Gauge of dimensions
Step 5 Purging inert gas from the indoor unit
The indoor unit comes with nitrogen gas (inert gas) charged at the factory. Therefore, all inert gas must be purged before connecting the assembly piping.
Unscrew the pinch pipe at the end of each refrigerant pipe.
Liquid side
Gas side
Insulator
NOTE
• To prevent dirt or foreign objects from getting into the pipes during installation, do not remove the pinch pipe completely until you are ready to connect the piping.
Step 6 Cutting and flaring the pipes
1 Make sure that you have the required tools available:
pipe cutter, reamer, flaring tool, and pipe holder.
2 If you wish to shorten the pipes, cut them with a pipe
cutter, ensuring that the cut edge remains at a 90° angle to the side of the pipe. Refer to the illustrations below for examples of edges cut correctly and incorrectly.
Pipe cutter
Pipe
Oblique
Rough
Burr
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 9 2016-02-03 오전 11:14:46
10
Installation Procedure
Installation Procedure
English
3 To prevent any gas from leaking out, remove all burrs
at the cut edge of the pipe, using a reamer.
4 Slide a flare nut on to the pipe and modify the flare.
Pipe
Flare
D
A
Flare
R 0.4 to 0.8 mm
D
L
90° ±2°
45° ±2°
Outer Diameter (D) Depth (A) Flare dimension (L)
Ø6.35 mm 1.3 mm 8.7 to 9.1 mm
Ø9.52 mm 1.8 mm 12.8 to 13.2 mm
Ø12.70 mm 2.0 mm 16.2 to 16.6 mm
Ø15.88 mm 2.2 mm 19.3 to 19.7 mm
Ø19.05 mm 2.2 mm 23.6 to 24.0 mm
5 Check that the flaring is correct, referring to the
illustrations below for examples of incorrect flaring.
Correct
Inclined
Damaged
Surface
Cracked
Uneven
Thickness
Step 7 Connecting the assembly pipes to the refrigerant pipes
There are two refrigerant pipes of different diameters :
• A smaller one for the liquid refrigerant.
• A larger one for the gas refrigerant. The inside of
copper pipe must be clean and has no dust.
1 Remove the pinch pipe on the pipes and connect the
assembly pipes to each pipe, tightening the nuts, first manually and then with a torque wrench, a spanner applying the following torque.
Torque wrench
Flare nut
Spanner
Union
1
2
3
3
Outer Diameter (mm) Torque (N•m)
Ø6.35 14 to 18
Ø9.52 34 to 42
Ø12.70 49 to 61
Ø15.88 68 to 82
Ø19.05 100 to 120
(1 N•m=10kgf•cm)
NOTE
• If the pipes must be shortened, see Step 6 Cutting and flaring the pipes on page 9.
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 10 2016-02-03 오전 11:14:47
11
Installation Procedure
English
2 Be sure to use an insulator thick enough to cover the
refrigerant tube to protect the condensate water on the outside of the pipe falling onto the floor and to improve the efficiency of the unit.
3 Cut off any excess foam insulation. 4 Make sure that there are no cracks or waves on the
bent area.
5 It would be necessary to double the insulation
thickness (10 mm or more) to prevent condensation even on the insulator when if the installed area is warm and humid.
6 Do not use joints or extensions for the pipes
connecting the indoor and outdoor units. The only permitted connections are those for which the units are designed.
CAUTION
• Connect the indoor and outdoor units using pipes with flared connections (not supplied). For the lines, use insulated, unwelded, degreased and deoxidized copper pipe (Cu DHP type to ISO 1337 or UNI EN 12735-1), suitable for operating pressures of at least
4.2 MPa and for a burst pressure of at least 20.7 Mpa. Copper pipe for hydro-sanitary applications is completely unsuitable.
• For sizing and limits (height difference, line length, max. bends, refrigerant charge, etc.) see the outdoor unit installation manual.
• All refrigerant connection must be accessible, in order to permit either unit maintenance or removing it completely.
• If the pipes require brazing, make sure that oxygen free nitrogen (OFN) is flowing through the system.
• Nitrogen blowing pressure range is 0.02 to 0.05 MPa.
Step 8 Performing the gas leak test
To identify potential gas leaks on the indoor unit, inspect the connection area of each refrigerant pipe using a leak detector for R-410A.
Before recreating the vacuum and recirculating the refrigerant gas, pressurize the whole system with nitrogen (using a cylinder with a pressure reducer) at a pressure above 4 MPa in order to immediately detect leaks on the refrigerant fittings.
Made vacuum for 15 minutes and pressurising system with nitrogen.
Liquid side
Gas side
Insulator
Step 9 Insulating the refrigerant pipes
Once you have checked that there are no leaks in the system, you can insulate the piping and hose.
1 To avoid condensation problems, place Acrylonitrile
Butadien Rubber separately around each refrigerant pipe.
No gap
NBR
NOTE
• Always make the seam of pipes face upwards.
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 11 2016-02-03 오전 11:14:47
12
Installation Procedure
Installation Procedure
English
CAUTION
• The insulation has to be produced in full compliance with European regulation EEC / EU 2037 / 2000 requiring the use of sheaths insulation without using CFC and HCFC gases for health and the environment.
2 Wind insulating tape around the pipes and drain hose
avoiding compressing the insulation too much.
3 Finish wrapping insulating tape around the rest of the
pipes leading to the outdoor unit.
4 The pipes and electrical cables connecting the indoor
unit with the outdoor unit must be fixed to the wall with suitable ducts.
Indoor unit
Insulation cover pipe
Insulation pipe
Be sure to overlap the insulation.
CAUTION
• Install the insulation not to get wider and use the adhesives on the connection part of it to prevent moisture from entering.
• Wind the refrigerant pipe with insulation tape if it is exposed to outside sunlight.
• Install the refrigerant pipe respecting that the insulation does not get thinner on the bent part or hanger of pipe.
• Add the additional insulation if the insulation plate gets thinner.
Refrigerant pipe insulation
Hanger
Additional
insulation
a
a x 3
• Must fit tightly against body without any gap.
• All refrigerant connection must be accessible, in order
to permit either unit maintenance or removal.
5 Select the insulation of the refrigerant pipe.
• Insulate the gas side and liquid side pipe, noting
the insulation thickness that must differ according to the pipe size.
• Standard: Less than an indoor temperature of
30°C, with humidity at 85%. If installing in a high humidity environment, use one grade thicker insulator by referring to the table below. If installing in an unfavourable environment, use thicker one.
• The heat-resistance temperature of the insulator
must be more than 120°C.
Pipe Pipe size
Insulation Type (Heating/Cooling)
Remarks
Standard
[30°C, 85%]
High humidity
[30°C, over 85%]
EPDM, NBR
Liquid
pipe
Ø6.35 to Ø9.52 9t
Internal temperature is
higher than 120°C
Ø12.7 to Ø50.80 13t
Gas pipe
Ø6.35 13t 19t
Ø9.52 to Ø25.40
19t
25t
Ø28.58 to Ø44.45 32t
Ø50.80 25t 38t
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 12 2016-02-03 오전 11:14:47
13
Installation Procedure
English
• When installing insulation in the places and conditions below, use the same insulation that is used for high humidity conditions.
<Geological condition>
High humidity locations such as shorelines, hot springs, lake or riversides, and ridges (when part of the building is covered by earth and sand)
<Operation purpose condition>
Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
Ceilings frequently exposed to moisture and cooling are not covered. For example, pipes installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently.
Places (where the pipes are installed) that are highly humid due to a lack of ventilation.
Step 10 Installing the drain hose and drain pipe
1 Push the supplied drain hose as far as possible over
the drain socket.
2 Tighten the metal clamp as shown in the picture.
3 Wrap the supplied large sealing pad over the metal
clamp and drain hose to insulate and fix it with clamps.
4 Insulate the complete drain piping inside the building
(field supply). If the drain hose cannot be sufficiently set on a slope, fit the hose with drain raising piping (field supply).
5 Push the drain hose up to insulation when connecting
the drain hose to drain socket.
Metal clamp
Drain socket
Drain hose
Large seailng pad
Drain pipe
Be sure to bond the drain hose and the main pipe.
Drain hose
PVC Tube Joint + VP25 (OD: 32 mm, ID: 25 mm)
Drain pipe
CAUTION
Check that the indoor unit is level with the ceiling by using the leveller.
• Install air ventilation to drain condensation smoothly.
Air ventilation
Ceiling
• If it is necessary to increase the height of the drain pipe, install the drain pipe straight within 300 mm from the drain hose port. If it is raised higher than 550 mm, there may be water leaks.
Band joint
300 mm or less
20 mm or more
Drain hose
Ceiling
300 to 550 mm
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 13 2016-02-03 오전 11:14:48
14
Installation Procedure
Installation Procedure
English
• Do not give the hose an upward gradient beyond the connection port. This will cause water to flow backwards when the unit is stopped, resulting in water leaks.
Under gradient
Ceiling
• Do not apply force to the piping on the unit side when connecting the drain hose. The hose should not be allowed to hang loose from its connection to the unit. Fasten the hose to a wall, frame or other support as close to the unit as possible.
Support pieces
1 to 1.5 m
1/100 or more
Ceiling
• Install horizontally.
Indoor unit
Be horizontal
Flexible hose
• Max. allowable aixs gap
Indoor unit
Max. 20 mm
• Max. allowable bending angle
Indoor unit
Max. 30˚
NOTE
• If a concentrated drain pipe is installed, refer to the figure below.
Centralized horizontal drain pipe (more than 1/100 slope)
Main drain pipe
Full thread bolt hanger
1000 to 1500 mm
300 to 550 mm
200 mm or more
Individual
air vent
Main air vent (must be installed)
• If 3 or more units are installed, install the main air vent at the front of the farthest indoor unit from the main drain pipe.
• To prevent water from flowing back to indoor units, install an individual air vent at the top of each indoor unit.
– The air vents should be T or 7 shaped to prevent
dust or foreign substances from entering.
– You may not need to install air vent if the
horizontal drain pipe is in proper slope.
DVM360_AC_Indoor_IM_EU_Eng_EN.indb 14 2016-02-03 오전 11:14:49