Safety precautions
Please follow the following safety information for safety of the installer and the user.
DVM S air conditioner uses R-410A refrigerant.
• When using R-410A, moisture or foreign substances may aect the performance and reliability of the
product. Safety precautions must be obeyed when installing the refrigerant pipe.
• The designed maximum pressure of the system is 4.1MPa and therefore select appropriate material and
thickness according to the regulations.
• R-410A is a quasi-azeotrope of two refrigerants and it has to be charged in liquid phase when lling the
refrigerant. (If you charge vapor refrigerant, it may change the blend of the refrigerant and cause product
malfunction.)
You must connect the indoor units for R-410A refrigerant. Refer to product catalog to nd out the models
names for connectable indoor units. (If you connect the indoor units that are not designed for R-410A, it
cannot operated normally.)
After completing the installation and trial operation, explain to the user how to use and maintain the product. Also,
hand over this installation manual so that it can be stored by the user.
Manufacturer is not responsible for the incidents occurred by improper installation. Installer is responsible for
any installation related claims from the user occurred by neglecting warnings and cautions stated in this manual.
(Installer will be responsible for any service charges that may occur)
Generally, system air conditioners should not be relocated after installation. But when it has to be relocated for
inevitable reasons, please contact Samsung’s qualied dealers for system air conditioners.
WARNING
CAUTION
• Hazards or unsafe practices that may result in severe personal injury or death.
• Hazards or unsafe practices that may result in minor personal injury (to installer/user) or
property damage.
SEVERE WARNING SIGNS
Consult qualied installer or dealer for installation.
When installation is done by unqualied person, problems such as water leakage, electric shock or re may occur.
Installation work must be done properly according to this installation manual.
When installation is not done properly, it may cause water leakage, electric shock or re.
When installing the unit in a small room, take measure to keep the refrigerant concentration from exceeding
allowable safety limits in case of refrigerant leakage. Consult the dealer for precautionary measure before the
installation.
When refrigerant leaks and exceed dangerous concentration level, it may cause suocation accidents.
If any gas or impurities, except R-410A refrigerant, come into the refrigerant pipe, serious problem may occur and
it may cause injury.
Use the supplied accessories, specied components and tools for the installation.
Do not use the pipe and the installation product used for the R-22 refrigerant.
Failure to use the specied components can cause product fall down, water leakage, electrical shock, and re. (The
pipe and are components used for R-22 refrigerant must not be used)
Install the outdoor unit on a hard and even place that can support its weight.
If the place cannot support its weight, the outdoor unit may fall down and it may cause injury.
3
DVM S HE_IM_DB68-05461A-08_EN.indd 32017-03-24 오후 1:38:14
Safety precautions
Check the following before installation and service work.
Before welding, remove dangerous and inammable things that may cause an explosion and re around the work.
Before welding, remove the refrigerant from inside the pipe or the product.
- If you perform welding while refrigerant is in the pipe, it may increase the pressure of the refrigerant and cause
the pipe to burst. If the pipe bursts or explodes, it may cause severe injury to the installer.
When welding, use the nitrogen gas to eliminate oxidation inside the pipe.
Do not modify the product on your own.
Potential risk of electric shock, re, product failure or injury.
Fix the outdoor unit securely on foundation to resist strong wind or earthquake.
If the outdoor unit is not properly xed, it turns over and accidents may occur.
Electric work must be done by qualied persons, complying the national wiring regulations and installed
according to the instruction stated in the installation manual with leased circuit.
Capacity shortage on the leased circuit and improper installation may cause electric shock or re.
Make sure to perform grounding work.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod or telephone grounding. Improper
grounding could cause electric shock.
Wiring must be connected with the designated wires and it must be xed securely so that it does not apply any
external force to the connection part of the terminals.
If connection for xation is not properly done, it may cause heat generation or re.
Neatly arrange the wires in the electrical parts to make sure that electrical cover is closed securely without any
gaps.
If the cover is not properly closed, heat may generate on the electrical terminal and cause electric shock or re.
Exclusive circuit breaker (MCCB, ELB) must be installed to the power supply.
When overcurrent or current leakage occurs with no circuit breaker installed, power will not be cut-o and it may
cause electric shock or re.
Do not use damaged parts. It may cause re or electric shock.
You must cut-o the power before you work on, or adjust any power supply part for product installation,
maintenance, repair or any other services.
There is risk of electric shock.
Even when the power is o, it is dangerous when you come in contact with inverter PCB, fan PCB since high
pressure DC voltage is charged to those parts.
When replacing/repairing the PCB, cut-o the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
If the refrigerant gas leaks during the installation, you should ventilate the room.
When the refrigerant gas gets in contact with ammable substance, it may generate toxic gas.
Gas leakage must be checked after installation is completed.
When the refrigerant gas gets in contact with ammable substance, it may generate toxic gas.
You can get a frostbite if you get in contact with the leaked refrigerant gas.
Supply power to the product during winter time since the product will operate in protection mode itself when the
temperature decrease below 0°C.
If you cut-o the power, compressor protection mode cannot be operated and may cause damage to the product.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction
concerning use of the appliance by a person responsible for their safety.Children should be supervised to ensure
that they do not play with the appliance.
4
DVM S HE_IM_DB68-05461A-08_EN.indd 42017-03-24 오후 1:38:14
ENGLISH
For use in Europe : This appliance can be used by children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given
supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without
supervision.
CAUTION SIGNS
Do not install the drain pipe directly to the bottom part of the outdoor unit and built a proper drainage so that
water drains out smoothly. If not, pipe may freeze or bursts during winter time and cause damage to the product
or water leakage.
When the draining work is not done properly, water leak may occur and cause property damage.
Install the power cable and communication cable of the indoor and outdoor unit at least 1.5m away from the
electric appliances and install it at least 2m away from the lightning conductor.
Noise may be generated from the electronic devices, depending on the status of the electric wave.
Install the outdoor unit within the angle stated in the table, according to the height of the building.
Do not leave the refrigerant container under the hot sunlight. (There is risk of explosion.)
You must use the appropriate pipes according to the standard since the pressure of the refrigerant is very high.
Make sure that the pipes does not get any weaker by welding it too much.
Make sure to install the product away from children’s’ reach. (Sharp parts of the heat exchanger is may cause
personal injury and when parts of the product gets damage, it may decrease product’s performance.)
Lighting rod
Protective angle:
25˚~55˚
Height of the building Protection control
20m or less 55˚
40m or less 35˚
60m or less 25˚
Install the indoor unit away from lighting apparatus that uses ballast stabilizer.
If you use the wireless remote control, it may not operate normally due to ballast stabilizer.
Do not install the product in following places.
Place where outdoor unit’s noise and warm air may disturb neighbors. (It may cause property loss.)
Do not leave any obstacles around the inlet and outlet of the product. (It may cause damage or accidents.)
The place where there is mineral oil or arsenic acid.
- Those parts may get damaged due to burned resin and cause water leakage or product may fall.
- The eciency of the heat exchanger may reduce or product may break.
The place where corrosive gas such as sulfurous acid gas generates from the vent pipe or air outlet.
- The copper pipe or connection pipe may corrode and refrigerant may leak.
The place where there is a machine that generates electromagnetic waves.
- The air conditioner may not operate normally due to problems in control system.
The place where there is a danger of combustible gas leakage or place where thinner or gasoline is handled.
- (There is risk of re or explosion.)
The place with carbon ber or ammable dust.
The place near seashore or hot spring where there is risk of outdoor unit corrosion.
5
DVM S HE_IM_DB68-05461A-08_EN.indd 52017-03-24 오후 1:38:14
Safety precautions
Changes in DVM S (inverter) compare to conventional models that has to noted when installing
For optimal distribution of the refrigerant, you must use Y-joint as branch joint for connecting outdoor units. (To
not use T-joint)
You cannot operate normally if you do not complete the trial operation through outdoor unit key mode. You must
use KEY MODE to run trial operation.
DVM S air conditioner uses R-410A refrigerant.
Check the compatibility of other products such as indoor unit, EEV kits etc. which will be connected to DVM S.
Make sure to note that outdoor unit combination is dierent from DVM PLUS III and IV.
The length of maximum piping, level dierence, the quantity of connectable indoor units, the installation at the
outdoor joints and the outdoor unit combinations are dierent from the conventional models.
If the pipe length is over 2 m between outdoor units, make traps to prevent oil stagnation. Oil stagnation may
occur when outdoor unit at the end of module stops while other outdoor units are still in operation.
6
DVM S HE_IM_DB68-05461A-08_EN.indd 62017-03-24 오후 1:38:14
• Safely store or dispose the packaging materials.
CAUTION
- Sharp metals such as nails or wooden material packaging that may break into pieces become a cause for
personal injury.
- Make sure to store or dispose the vinyl type packaging material to keep it out of reach of children.
Children may put them over their face, which is very dangerous since it may lead them to suocation.
7
DVM S HE_IM_DB68-05461A-08_EN.indd 72017-03-24 오후 1:38:15
Preparing for installation
Outdoor unit combination
Make sure to use an indoor unit that is compatible with DVM S.
Indoor units can be connected within the range indicated in following table.
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating
capacity of the indoor unit may decrease.
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity.
0.5 × Σ(Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ(Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is
set to 64 since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned
from 0~63. If the indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AMFNQDEH, AMJNVDKH) can be connected.
• Use the following table to determine the size and number of outdoor units needed to achieve thecapacity
requirements.
DVM S HE_IM_DB68-05461A-08_EN.indd 222017-03-24 오후 1:38:16
ENGLISH
Moving the outdoor unit
Select the moving path in advance.
Be sure that moving path can support weight of the outdoor unit.
Do not slant the product more than 30˚ when carrying it. (Do not lay the product down in sideways.)
Surface of the heat exchanger is sharp. Be careful not to get injured while moving the product.
• You must use certain part of the product when moving the product.
CAUTION
When moving with a crane
Fasten the wire rope as shown in the gure.
To protect damage or scratches, insert a piece of cloth between the
Wire rope
outdoor unit and the wire rope.
Holes for wire rope
to go through
When moving with a forklift
Carefully insert the forklift forks into the forklift holes at the bottom
of the outdoor unit.
Be careful with the forklift from damaging the product.
Forklift
Holes for forklift
forks to go
through
When moving the product without wooden pallet and the crane is not available for use
Connect a wire rope to the outdoor unit as you would move it with
a crane.
Hang the wire rope to the forklift fork to move the outdoor unit.
Forklift
Wire rope
Forklift holes
23
DVM S HE_IM_DB68-05461A-08_EN.indd 232017-03-24 오후 1:38:16
Selecting installation location
Decide the installation location, with the consideration of the following conditions, under user’s approval.
Place where hot discharge air or noise from the outdoor unit may not disturb the neighbor (Especially in residential
areas, keep the operation hours in mind.)
Place where structure can bear the weight and vibration of the outdoor unit.
Place with at surface where rainwater does not settle or leak.
Place where it is not exposed to strong wind.
Well ventilated place with sucient service place for repairs and maintenance. (Discharge duct can be purchased
separately)
Place where you can connect the refrigerant pipes between indoor and outdoor units within allowable distance.
Place where it allows easy waterproong and draining work for the condensation water generated from the
outdoor unit during heating operation.
Place where there is no risk of inammable gas leakage.
Place where there is no direct inuence of snow or rain.
Do not install the product in a place where it will be directly exposed to sea breeze.
- Consult an installation expert (or company) since you will need to take extra anti-corrosion measures if you need
to install the product in a place where it can be exposed to direct sea breeze. (You have to remove dusts and
salinity on the heat exchanger and apply designated rust inhibitor more than once a year.)
Outdoor
unit
Sea breeze
Sea
Outdoor
unit
Caution when installing the product in seashore
- When installing the product in seashore, make sure to install it behind a structure (such as building) that can
block the sea breeze or install protection wall around the outdoor unit.
- Make sure to install the product in a place where it allows smooth drainage.
Protection wall
Sea
Sea breeze
Outdoor
unit
Sea
Protection wall should be constructed with a solid material
that can block the sea breeze and the height and width of the
wall should be 1.5 times larger than the size of the outdoor
unit. (You must secure more than 700mm of space between
the protection wall and the outdoor unit for air circulation.)
Sea breeze
Outdoor unit
Outdoor
unit
24
DVM S HE_IM_DB68-05461A-08_EN.indd 242017-03-24 오후 1:38:17
ENGLISH
• System air conditioner may cause static noise when listening to AM stations. Therefore, select an
installation location for indoor unit where electrical wiring can be done while keeping certain distance
CAUTION
from a radio, computer and stereo equipment.
- Especially, keep the unit at least 3m away from the electrical equipment in an area with weak
electromagnetic waves and put the main power cable and communication cables in a separately
installed protection tube.
- Make sure that there is no equipment that generates electromagnetic waves. If not electromagnetic
waves may cause problem to the control systems which may lead to air conditioner malfunction.
(Example: Remote control sensor of the indoor unit may not receive the signal very well, due to ballast
stabilizer of the lighting equipment.)
• In regions with heavy snowfall, make sure to install the outdoor unit where there is no concerns of direct
snowfall on the outdoor unit. Also, build higher base support so that accumulated snow does not block
the air inlet or the heat exchanger.
• R-410A refrigerant is a safe, nontoxic and nonammable refrigerant. However, if the place holds any
concerns for exceeding dangerous level of refrigerant concentration in case of refrigerant leakage, extra
ventilation system is required.
• When you install the outdoor unit in high places such as roof, install fence or guardrail around it. When
there is no fence or guardrail, service person could fall.
• Do not install the product in places where corrosive gases such as sulfur oxides, ammonia, and sulfurous
gas are produced. (e.g. Toilet outlet, ventilation opening, sewage works, dyeing complex, cattle shed,
sulfuric hot spring, nuclear power plant, ship etc.) When installing the product in those places, contact an
installation specialty store as the copper pipe and brazing part will need additional corrosion proof or antirust additive to prevent corrosion.
• Make sure to keep any inammable materials (such as wooden materials, oil etc.) around the outdoor unit.
When there's re, those inammable material will easily catch the re and may pass it on to the product.
• Depending on the condition of power supply, unstable power or voltage any cause malfunction of the
parts or control system. (At the ship or places using power supply from electric generator...etc)
• Make sure to install MCU when using HR products.
• When you select the location to install MCU, the location is far away from indoor rooms because the
refrigerant running of MCU may create noise.
25
DVM S HE_IM_DB68-05461A-08_EN.indd 252017-03-24 오후 1:38:17
Space requirement for installation
Space requirement was decided based on following conditions; Cooling mode, outdoor temperature of 35°C.
Larger space is required if the outdoor temperature is higher than 35°C or if the place is heated easily by quantity
of solar radiation.
When you secure installation space, consider path for people and the direction of the wind.
Secure installation space as shown in the below illustration, considering ventilation and the service space.
If the installation space is narrow, installer or other worker may get injured during work and may also cause
problem to the product.
If you install multiple number of outdoor units in one space, make sure to secure enough ventilation space if there’s
any walls around the product that may disturb the air ow. If enough ventilation space is not secured, product may
malfunction.
You may install the outdoor units with 20mm of space between the product, but product’s performance may
decrease depending on the installation environment.
Single installation
(Unit : mm)
Over 300
Over 100 (S2)Over 500 (S1)
Front
Over 100Over 100
Over 100
side
<Case 1><Case 2>
Front side
Height of the wall is
unlimited
26
DVM S HE_IM_DB68-05461A-08_EN.indd 262017-03-24 오후 1:38:17
ENGLISH
Module installation
Over 200
Over 300
Front
side
Over 400Over 400
Front side
Over 100
Over 100
<Case 1><Case 2>
Over 100Over 100 O ver 100Over 100
Over 100
Front side
Over 100 O ver 100
Front side
Over 100
Over 100
Over 100
<Case 3>
(S2)
Over 300
(S1)
Over 500
Over 500Over 500Over 600
For <Case 1> or <Case 3>
• Height of the wall on the front side should not be higher than 1500mm.
• Height of the wall on the air inlet side should not be higher than 500mm.
• Height of the wall on the side is not limited.
• If the height of the wall exceeds by certain value (h1, h2), additional clearance [(h1)/2, (h2)/2 : Half of the
exceeded distance] should be added to the service space (S1, S2).
(Unit : mm)
Height of
the wall is
unlimited
Front side
1500h1
S1+h1/2S2+h2/2
Air inlet side
500h2
27
DVM S HE_IM_DB68-05461A-08_EN.indd 272017-03-24 오후 1:38:17
Accessories
Accessories
You must keep following accessories until the installation is nished.
Hand over the installation manual to the customer after nishing the installation.
Installation manual (1)Packing socket (1)
Models with packing socket : AM120/140XVGH, AM240/260XVAGH, AM180XVHGR.
Socket can be dierent depending on the model.
Optional accessories
Following optional accessories are needed for connecting pipes between the indoor and outdoor units.
ClassicationModel NameSpecication
MXJ-YA1509M15.0kW and below
MXJ-YA2512MOver 15.0kW~40.0kW and below
MXJ-YA2812MOver 40.0kW~45.0kW and below
Y-Joint
Y-Joint (Only H/R)
Distribution header
Y-Joint
- Outdoor unit
Y-Joint (Only H/R)
- Outdoor unit
If you use an indoor unit with no internal EEV(Electric Expansion Valve), you will need an EEV kit.
Only use the genuine accessories listed in above table and do not use imitated accessories.
MXJ-YA2815MOver 45.0kW~70.3kW and below
MXJ-YA3419M Over 70.3kW~98.4kW and below
MXJ-YA4119MOver 98.4kW~135.2kW and below
MXJ-YA4422MOver 135.2kW
MXJ-YA1500M22.4kW and below
MXJ-YA2500MOver 22.4kW~70.3kW and below
MXJ-YA3100MOver 70.3kW~135.2kW and below
MXJ-YA3800MOver 135.2kW
MXJ-HA2512M45.0kW and below (for 4 rooms)
MXJ-HA3115M70.3kW and below (for 8 rooms)
MXJ-HA3819MOver 70.3kW ~ 135.2kW and below (for 8 rooms)
MXJ-TA3419M135.2kW and below
MXJ-TA4122MOver 140.2kW
MXJ-TA3100M135.2kW and below
MXJ-TA3800M140.2kW and Over
28
DVM S HE_IM_DB68-05461A-08_EN.indd 282017-03-24 오후 1:38:17
ENGLISH
Base construction and installation of the outdoor unit
• Make sure to remove the wooden pallet before installing the outdoor unit. If you do not remove the
wooden pallet, there is risk of re during welding the pipes. If the outdoor unit is installed with wooden
WARNING
pallet on, and it was used for long period time, wooden palette may break and cause electrical hazard or
high pressure may damage the pipes.
Fix an outdoor unit rmly on the base ground with anchor bolts.
Manufacturer is not responsible for the damage occurred by not following the installation standards.
1. Make sure that the height of the base ground is 200mm or higher to protect the outdoor unit from rain water or
other external conditions. Also, install a draining pit around the base ground and connect the drain pipe to the
drainage.
2. Considering the vibration and weight of the outdoor unit, strength of the base ground must be strong to prevent
noise and the top surface of it should be at.
3. Base ground should be 1.5 times larger than the bottom of the outdoor unit.
4. Outdoor unit must be xed rmly so that it can withstand the wind speed of 30m/s. If you cannot x the outdoor
unit on the base ground, x it by side or use extra structure.
5. In heating operation, defrost water may form so you must really care about the drainage and waterproong the
oor. To prevent defrost water from stagnating or freezing, construct a drainage with over 1/50 slope. (Ice may
form on the oor in winter season.)
6. It is necessary to add wire mesh or steel bar during concrete construction for the base ground to prevent damages
or cracks.
7. When installing multiple outdoor units at the same place, construct a H beam or an anti-vibration frame on the
base ground to install the outdoor unit.
8. After installing a H beam or an anti-vibration frame, apply corrosion protection and other necessary coating.
9. When concrete construction for outdoor unit installation is completed, install an anti-vibration pad (t=20mm or
more) or an anti-vibration frame to prevent vibration of the outdoor unit from transferring to the base ground.
10. Place the outdoor unit on a H beam or an anti-vibration frame and x it with the bolt, nut and washer. (The bearing
force has to be over 3.5kN)
Base ground construction
Bottom surface of the base
ground must be horizontally
Draining pit
Over 200 mm
leveled
Over 200 mm
Over 200 mm
<When installing on the ground>
<When installing on the roof>
29
DVM S HE_IM_DB68-05461A-08_EN.indd 292017-03-24 오후 1:38:18
Base construction and installation of the outdoor unit