I hereby declare that the liquid ring pumps are in conformity with the following harmonized standards:
DS/EN ISO 12100:2011 Safety of machinery - General principles for design - Risk assessment and risk
DS/EN 1012-2 + A1:2009 Compressors and Pumps - Safety requirements - Part 2: Vacuum pumps
The standards above only apply to the extent that it is relevant for the purpose of the pump.
The product must not be used before the complete system, which it must be incorporated in, has been conformity
assessed and found to comply with all relevant health and safety requirements of 2006/42/EC and other relevant
directives. The product must be included in the overall risk assessment.
Important technical and safety instructions are shown by symbols. If the instructions are not performed
correctly, it can lead to personnel injuries or incorrect function of the pump.
To be used with all safety instructions that must be followed. A failure to follow the
instructions may result in injuries and/or incorrect machine operation
1.3 Field of application
Inlet of foreign objects can damage the pump
The pump is designed exclusively to pump gases, including atmospheric air
WARNING!
Avoid cavitation of the pump! For further information, see instruction manual for the
Samson Pumps vacuum limiter
It must be ensured that the inlet gas cannot react with the service liquid and create aggressive bonds that
break down the pump's components.
For other operating data, see specifications.
• The pump must only be used with media that is not aggressive to the pump's materials. See section 7
for components and materials.
1.4 Disposal
Samson’s liquid ring pump is manufactured so that most of the device can be reused/recycled.
Samson Pumps offer users of the company’s pumps the option of returning used pumps to be restored or
scrapped.
Alternatively, the pump must be taken apart and sorted into its separate components, by the customer
(see section 7 for the pump’s material).
These components must be disposed of in accordance with national regulations.
Truck Master 2500
5
2 TECHNICAL DATA
498
48 k6Ø
270
20Ø
2.1 Dimensions
300
400
1074
647
100
579
549312
M16x2
Ø107
Ø180
DOC1627354_1D
6
2.2 Specifications
A failure to meet these specifications may result in damage to the pump
DescriptionMinimumMaximum
Ambient temperature, operationBelow 0°C - see chapter 5.3-20°C55°C
Ambient temperature, storage-20°C55°C
Humidity -100%
Intake temperature, suction side -60°C
Intake temperature, service liquid-60°C
Service liquid pipe connection, dimension¾”-
Service liquid pipe connection, length-6 m
Noise level- 80 dB(A)
Water volume-34 L
Maximum radial load on drive shaft-3480 N
1200 rpm33 kW-
Heat input for cooler calculation
Revolutions1200 rpm1500 rpm
Pressure150 mbar abs.1 bar(g)
Lubricating grease
Weight321 kg
1300 rpm36 kW-
1400 rpm41 kW-
1500 rpm48 kW-
Type of greaseSKF LGWA2
Automatic lubricationSKF LAGD 125/WA2
Truck Master 2500
7
2.3 Power consumption and output
2.3.1 Vacuum
Vacuum[%]80706050403020
1200 [rpm]
1300 [rpm]
1400 [rpm]
1500 [rpm]
Flow
Flow
Wet
Dry
[m³/h]
1261184617771803185218461860
941144215451596169917091738
Consumption [kW]45
Torque[Nm]358
Flow
Flow
Wet
Dry
[m³/h]
1522194119141963197219801965
1136151716651737180918331837
Consumption [kW]48
Torque[Nm]353
Flow
Flow
Wet
Dry
[m³/h]
1655212620552159213722052075
1235166117871910196020421939
Consumption [kW]56
Torque[Nm]382
Flow
Flow
Wet
Dry
[m³/h]
1962238923612423244524652322
1464186620532144224322822170
Consumption [kW]64
Torque[Nm]407
2.3.2 Pressure
Pressure[bar(g)]00.250.50.751
Flow[m³/h]1300122611791070993
1200 [rpm]
1300 [rpm]
1400 [rpm]
1500 [rpm]
The data Flow
• Air temperature 20°C
• Service liquid temperature 15°C
• Test performed with dry air and 1,013 mbar absolute pressure
• Tolerance ±10%
Consumption [kW]3943495459
Torque[Nm]310342390430470
Flow[m³/h]14251328126111711097
Consumption [kW]4149556167
Torque[Nm]301360404448492
Flow[m³/h] 16051569143313411271
Consumption [kW]5455616874
Torque[Nm]368375416464505
Flow[m³/h] 18241636163315311390
Consumption [kW]6264707682
Torque[Nm]395407446484522
is based on the following parameters:
Dry
8
2.3.3 Correction factor - Temperature
When the temperature of the service liquid
exceeds 15°C, the pump’s capacity will be affected
with respect to the specified values.
To determine the output at a higher temperature,
the correction factor can be used.
Capacity at service liquid temperature
higher than 15°C :
= Q
x K
Q
t>15
15
1
DOC1628005_1A
2.3.4 Correction factor - Wet and dry gas
Normal atmospheric air contains water vapor. In this case water will condense inside the pump and will
create a higher flow.
Below you can find a correction factor table for the performance based on condensing gas with an inlet
temperature of 50°C 100% saturated and service liquid temperature of 15°C.
Suction pressure % Vacuum80706050403020
Correction factor wet gas
K
1,341,281,151,131,091,081,07
Wet
The performance of the pump can thereby be calculated as:
V
= V
Dry
x K
Wet
Wet
Truck Master 2500
9
2.4 Handling and transport
The pump must not be used if it is damaged or the identification plate is missing
The pump must be transported in such way that
it is not exposed to vibrations and impacts that
can overload the bearings.
The pump must be inspected for damages upon
delivery. If the pump is damaged, it must not be
used and the damage must be reported to the
manufacturer.
Ensure that the pump’s identification plate
is intact and that the marking of the pump
corresponds to its use.
The pump must only be handled using approved
lifting eyes, in accordance with nationally
applicable regulations and only in a vertical
motion.
DOC1627355_1
The pump can be transported in the following
ways:
DOC11093A
10
2.5 Pump storage and draining procedure
A failure to comply with the requirements for storing the pump may result in internal
damage to the device
If the temperature is below freezing point of the service liquid, it could damage the pump
Under these conditions, the pump must be drained completely
All plugs and protective covers must be fitted during storage
The pump’s service liquid is drained on delivery, and the pump can be immediately stored in accordance
with the technical specifications.
After operation, the pump can be stored for 30 days without further action.
If the pump remains out of operation for a longer period of time after use, its service liquid must be
drained, and the liquid supply to the pump must be shut off.
When emptying the pump, it is important that all chambers inside the pump are emptied.
The pump can be fitted with valves in the draining connections. See below.
Truck Master 2500
DOC1627356_1
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.