Samson TROVIS SAFE 3730 Series, TROVIS SAFE 3730-6, 3730 Series, 3730-6 Operating Instructions Manual

Series 3730 TROVIS SAFE 3730-6 Electropneumatic
Positioner EXPERTplus Valve Diagnostics
Operating Instructions
EB 8389-1S EN
Firmware version 1.1x Edition May 2015
DANGER!
Hazardous situations which, if not avoided, will result in death or serious injury
WARNING!
Hazardous situations which, if not avoided, could result in death or seri­ous injury
2 EB 8389-1S EN
NOTICE
Property damage message or mal­function
Note:
Additional information
Tip:
Recommended action
Contents
1 Description ....................................................................................................7
1.1 General ........................................................................................................7
1.2 Start-up .........................................................................................................9
1.3 Diagnostic functions .....................................................................................10
1.3.1 Type of application.......................................................................................11
1.3.2 Assessment ..................................................................................................11
2 Monitoring ..................................................................................................13
2.1 Status messages ...........................................................................................13
2.1.1 Resetting status messages .............................................................................13
2.1.2 Condensed state ..........................................................................................17
2.2 Logging .......................................................................................................18
3 Data logger ................................................................................................21
3.1 Permanent data logging ...............................................................................21
3.2 Triggered data logging ................................................................................. 22
3.2.1 Triggered by condensed state ........................................................................22
3.2.2 Triggered by set point, valve position, set point deviation or signal pressure ......23
3.2.3 Triggered by binary input .............................................................................24
3.2.4 Triggered by internal solenoid valve/forced venting ........................................25
3.2.5 Triggered by set point or internal solenoid valve/forced venting .......................25
4 Valve signature ...........................................................................................27
4.1 Reference graphs .........................................................................................28
4.1.1 Analysis and monitoring ...............................................................................28
4.2 Valve signature, signal pressure(x) .................................................................29
4.2.1 Analysis and monitoring ...............................................................................30
4.3 Course of supply pressure .............................................................................31
4.3.1 Analysis and monitoring ...............................................................................32
4.4 Valve signature, friction(x) ............................................................................33
4.4.1 Analysis and monitoring ...............................................................................34
4.5 Resetting single status messages ....................................................................34
5 On/off valve ...............................................................................................37
5.1 Diagnostics for on/off valve ..........................................................................38
5.2 Analysis and monitoring ...............................................................................39
5.3 Resetting single status messages ....................................................................40
EB 8389-1S EN 3
Contents
6 Valve position x histogram ..........................................................................41
6.1 Analysis and monitoring ...............................................................................42
6.2 Resetting single status messages ....................................................................42
7 Set point deviation e histogram ....................................................................44
7.1 Analysis and monitoring ...............................................................................45
7.2 Resetting single status messages ....................................................................46
8 Cycle counter histogram ..............................................................................49
8.1 Analysis and monitoring ...............................................................................50
8.2 Resetting single status messages ....................................................................50
9 Leakage sensor ...........................................................................................53
9.1 Start-up of the leakage sensor .......................................................................54
9.1.1 Manufacturer reference ................................................................................54
9.1.2 Process reference .........................................................................................57
9.2 Short-term monitoring ..................................................................................62
9.2.3 Resetting single status messages ....................................................................63
9.3 Long-term monitoring ...................................................................................63
9.3.1 Resetting single status messages ....................................................................63
9.4 Sound level(x) ..............................................................................................64
9.4.2 Resetting single status messages ....................................................................64
10 Course of end position .................................................................................67
10.1 Analysis and monitoring ...............................................................................68
10.2 Resetting single status messages ....................................................................68
11 Valve dead band ......................................................................................... 69
11.1 Resetting single status messages ....................................................................70
12 Partial stroke test (PST) ................................................................................73
12.1 Start triggered by the set point ......................................................................78
12.2 Start triggered by the binary input.................................................................78
12.3 Analysis and monitoring ...............................................................................79
12.4 Resetting single status messages ....................................................................80
13 Full stroke test (FST) .....................................................................................83
13.1 Analysis and monitoring ...............................................................................87
4 EB 8389-1S EN
Contents
13.2 Resetting single status messages ....................................................................87
14 SIL operator test ..........................................................................................88
14.1 Analysis and monitoring ...............................................................................90
15 Binary input ................................................................................................ 91
®
16 Dynamic HART
variables ............................................................................93
17 Appendix ....................................................................................................95
17.1 Code list ......................................................................................................95
17.2 Error messages and recommended corrective action .....................................102
17.3 Diagnostic data points saved in a non-volatile memory ................................. 107
17.4 Resetting parameters ..................................................................................108
EB 8389-1S EN 5
Overview
Throttling service
On/off service
No conguration required for monitoring
Travel histogram
u Section 6
Set point deviation histogram e
u Section 7
Cycle counter histogram
u Section 8
Course of end position
u Section 10
Note:
− Tests highlighted in red border require an initialization with valve signature
Tests highlighted in gray can optimize the proper functioning of safety equipment according to IEC61508 and IEC61511, provided these tests are performed regularly.
Conguration required for diagnosis
Data logger
u Section 3
Valve signature
u Section 4
Packing
u Section 8
Leakage sensor
u Section 9
Valve dead band
u Section 11
Full stroke test (FST)
u Section 13
No conguration required for monitoring
Travel histogram
u Section 6
Set point deviation histogram e
u Section 7
Cycle counter histogram
u Section 8
Course of end position
u Section 10
Conguration required for diagnosis
Data logger
u Section 3
On/off diagnosis
u Section 5
Packing
u Section 8
Leakage sensor
u Section 9
Valve dead band
u Section 11
Partial stroke test (PST)
u Section 12
Full stroke test (FST)
u Section 13
6 EB 8389-1S EN
Description
1 Description
1.1 General
These instructions supplement the standard Mounting and Operating Instructions for the
TROVIS SAFE3730-6 Positioner (uEB8384-6S EN).
EXPERTplus is a diagnostic rmware inte-
grated into the positioner which allows the predictive, status-oriented maintenance of valves with pneumatic actuators.
EXPERTplus records the valve condition while the process is running (in automatic mode) and generates messages on the required maintenance work. In addition, numerous tests can be performed in manual mode to pinpoint emerging faults.
The diagnostic functions of EXPERTplus are completely integrated into the positioner. Di­agnostic data are compiled, saved and ana-
lyzed in the positioner itself. Classied status
messages on the state of the valve are gener­ated from the analysis.
All the parameter settings that are changed must also be downloaded onto the posi­tioner to allow them to become effective.
Local operation
Some parameters can be changed at the po­sitioner as well as over the operator interface. T
he positioner code of these parameters are written in parentheses. Refer to the Mounting and Operating Instructions of the TROVIS
SAFE3730-6 Positioner (EB8384-6SEN) for
a list of all parameters that can be changed at the positioner.
The operation described in the following sections illustrates operation using TROVIS­VIEW4. The default settings of the position­er and TROVIS-VIEW4 are written in square brackets [ ]. Settings highlighted in gray refer to operation using TROVIS­VIEW4.
Operation using TROVIS-VIEW 4/DD/DTM/
eDD
EXPERTplus allows the parameters to be viewed or changed using the TROVIS-
VIEW4 software or DD/DTM/eDD. TROVIS-VIEW4 · SAMSON operator inter-
face used to congure various SAMSON de-
vices
DTM · Device type manager to describe the device and communication properties
DD/eDD · Device description/enhanced device description
EB 8389-1S EN 7
DescriptionDescription
Initialization mode
â â â
MAX NOM MAN/MAN2
â
Initialization including valve
signature
ß à
Yes
START-UP
â â
Zero
Valve signature (D1)
Code 81 Code 81
ß Not successful
ß Successful
Automatic change to
AUTO operating mode
à
No
Throttling or on/off service
Later recording of
reference graphs
â
Operating mode = MAN
Valve signature (D1)
All reference values are overwritten!
ß Not successful
â
Operating mode = AUTO
ß
8 EB 8389-1S EN
Description
1.2 Start-up
The positioner must be initialized to use the full scope of the valve diagnostics. During ini­tialization the positioner adapts itself optimal­ly to the friction conditions and the signal pr
essure required by the control valve. The positioner can be initialized using one of the following initialization modes: maximum
range (MAX), nominal range (NOM), manual setting 1 (MAN) and manual setting 2 (MAN2).
Maximum range (MAX)
Initialization mode for simple start-up of valves with two clearly dened mechani­cal end positions, e.g. three-way valves
Nominal range (NOM)
Initialization mode for all globe valves
Manual setting 1 (MAN)
Initialization mode for globe valves re-
quiring OPEN position to be entered
manually
Manual setting 2 (MAN2)
Initialization mode for globe valves re-
quiring the end positions (OPEN and
CLOSED positions) to be entered manu­ally
The type of application, pressure limit and the start-up parameters required for the se­lected initialization must be entered to initial­ize the positioner.
Note:
Positioner start-up is described in detail in the associated Mounting and Oper­ating Instructions (
uEB8384-6S EN
).
The monitoring of friction, supply pressure, leakage, actuator springs, course of end po­sition and zero point shift requires additional reference tests of the valve signature to be performed. Refer to Section 4. The reference tests required for the diagnostic functions cannot be performed if the positioner has been initialized in the substitute calibration
(SUB) mode. By setting 'Initialization includ­ing valve signature' = Yes, the positioner re-
cords the reference data automatically after initialization.
Start-up
− Type of application (Code 49 - h0): Control valve, [On/off valve]
− Initialization mode (Code 6): [Maximum
range(MAX)], Nominal range (NOM), Manual setting 1 (MAN) or Manual setting 2 (MAN2)
− Initialization including valve signature (Code 48 - h0): [Yes]
− Pin position (Code 4): [Off], 17, 25, 35, 50, 70, 100, 200 mm, 90°
− Pressure limit (Code 16): 1.4 to [7.0] bar
During positioner initialization, the 'Kp level' and 'Tv level' are optimally set. If the posi-
tioner tends to overshoot impermissibly due to other disturbances, the proportional-ac­tion coefcient (Kp level) and derivative-ac­tion time (Tv level) can be adapted accord­ingly. Increment the derivative-action time until the desired behavior is reached. When the maximum value of 4 is reached for the derivative-action time, the proportional-ac-
tion coefcient can be reduced in steps.
EB 8389-1S EN 9
Description
NOTICE
Kp level changes affect the set point deviation.
After changing the proportional-action coef-
cient 'Kp level', we recommend to recali­brate the ne lter in the positioner. Use the 'Fine-tuning after Kp change' function for
this.
Start-up > Control parameters
Proportional-action coefcient Kp level (Code 17): 0 to 17, [7]
− Derivative-action time Tv level (Code 18): Off, 1 to 4, [2]
Fine-tuning after Kp change
1.3 Diagnostic functions
There are two different types of diagnostic functions:
1. Monitoring functions
Data are compiled, saved and analyzed by the positioner while the process is running without disrupting the process. The positioner follows the set point to po-
sition the valve. A classied status alarm
or fault alarm is generated if the posi­tioner detects an event.
2. Dynamic tests
Similar to the monitoring function, data are compiled, saved and analyzed by the positioner. However, in this case, the valve position is not determined by the set point, but by the settings of the test. The dynamic tests can only be started when the conditions in the plant allow it (e.g. plant shutdown or service work in the workshop). For reasons of safety, the dynamic tests, except for partial stroke testing, can only be performed in the
MAN operating mode.
A dynamic test is stopped and the posi­tioner changes to the fail-safe position when the electrical signal falls below a certain level or when the solenoid valve is triggered or the forced venting func­tion is activated.
10 EB 8389-1S EN
1.3.1 Type of application
Different diagnostic functions are available depending on the type of application select­ed in EXPERTplus. The types of application 'Control valve' and 'On/off valve' are available. Depending on the type of applica­tion selected, the positioner behaves differ­ently in the automatic mode (AUTO):
Control valve
The positioner uses the set point to posi­tion the valve. The valve position (current position) ap­pears in % on the display.
On/off valve
Discrete analysis of the set point The valve position (current position) in % and O/C (Open/Close) appear in alter­nating sequence on the display. See
uSection 5.
Description
1.3.2 Assessment
Table 1 shows the diagnostic functions and their statements on the condition of the valve depending on the type of application.
EB 8389-1S EN 11
Description
Description
Table 1: Diagnostic functions and test analysis
Control
Diagnostic functions
valve
Monitoring
Data logger Depending on trigger status
Valve signature
On/off valve Breakaway time
Valve position histogram
Set point deviation histogram
Cycle counter histogram
Leakage sensor − Seat leakage u 9 on page 53 Course of end
position
Dynamic tests
Valve dead band − Dead band u 11 on page 69 Partial stroke test
(PST)
Full stroke test (FST) − Overshooting
• Full scope of functions
U Function is performed, but not analyzed
– Function is not performed
On/off
valve Assessment See section
selected
U
− Change in friction
− Supply pressure
− Defective actuator springs
− Pneumatic leakage
− Transit time
− Valve end position
U
− Change in manipulated variable range
− Manipulated variable range
− Manipulated variable range limitation
− Seat leakage
− Positioner-valve linkage
− Average set point deviation
− Packing leakage
− Dynamic stress factor
− Course of end position
− Zero shift
− Overshooting
− Dead time
− T86
− Settling time
− Dead time
− T86
− Settling time
u 3 on page 21
u 4 on page 27
u 5 on page 37
u 6 on page 41
u 7 on page 44
u 8 on page 49
u 10 on page 67
u 12 on page 73
u
13 on page 83
12 EB 8389-1S EN
Monitoring
2 Monitoring
2.1 Status messages
The valve diagnostics integrated into the po-
sitioner generates classied status messages.
Messages generated from the analysis of the
diagnosis can be classied according to the
possible causes. See u Section 4 to 13.
The following classications are possible:
No message
If an event is classied as “No message”,
this event does not have any affect on the condensed state.
Function check
Test or calibration procedures are per­formed in the positioner. The positioner is temporarily unable to perform its control task as long as the procedure is taking place.
− Maintenance request/maintenance re- quired
The positioner still performs its control task (with restrictions). A maintenance demand or above average wear has been determined. The wear tolerance will soon be exhausted or is reducing at a faster rate than expected. Maintenance is necessary in the medium term.
Out of specication
The positioner is running outside the
specied operating conditions.
Failure
The positioner cannot perform its control task due to a functional fault in the posi­tioner itself or in one of its peripherals or
an initialization has not yet been suc­cessfully completed.
You can view these messages in TROVIS-
VIEW4 in the Diagnostics folder (> Monitor- ing) and its subfolders. The 'Positioner sta­tus', 'Valve status', 'Actuator status' and 'Valve position status' messages provide a
condensed state of the status messages of each subfolder.
2.1.1 Resetting status messages
When a status message is generated, you
should rst locate the source of the fault and
take action to remedy it. For recommended action concerning the sta-
tus messages see u Section 17.2. Status messages can be reset individually or
using the reset function. Table 2 on page 15 contains an overview on how the di­agnosis can be reset. Resetting is performed in the Diagnostics folder (> Service/mainte­nance > Reset).
If you want to keep measured data and the analysis after resetting the positioner, it is possible to upload them onto a computer.
Resetting single status messages
− Status messages represented by a code
in the positioner can be conrmed at the
positioner itself. Select the error code
and conrm it by pushing the rotary
pushbutton. See the standard instructions of the positioner u EB 8384-6S EN.
− On resetting histograms and diagrams, the data for short-term monitoring are also reset.
EB 8389-1S EN 13
Monitoring
− Resetting measured data does not cause the diagnostic parameters and reference value to be reset as well.
− The positioner does not need to be re-ini- tialized after resetting.
Reset measured diagnostic data
Code 36 - Diag
− Parameters are reset as described in u Section 17.4.
− Resets diagnostics assessment.
− Reference values remain unchanged.
Status classication and data logs re- main saved.
− The positioner does not need to be re-ini- tialized after resetting.
− If the diagnostic data are to be reset at regular intervals, enter the time in "De­sired time until ‘Reset measured diagnos­tic data" (Code 48 - h3). The setting "00:00:00" causes the resetting at regu­lar intervals to be deactivated.
Reset start-up parameters
Code 36 - Std
− Parameters are reset as described in
u Section 17.4.
− Resets diagnostics assessment.
− Reference values are deleted.
Status classication remains unchanged.
− Data logs are reset.
− The positioner must be re-initialized after resetting.
Reset to default settings
Code 36 - DS
− Parameters are reset as described in
u Section 17.4.
− Resets diagnostics assessment.
− Reference values are deleted.
Status classication and data logs are deleted.
− The positioner must be re-initialized after resetting.
Note:
Before mounting the positioner on a new control valve, perform a reset by selecting the command 'Reset to de-
fault settings' (Code 36 - DS) and re-
initialize the positioner.
14 EB 8389-1S EN
Monitoring
Monitoring
Table 2: Resetting the diagnosis
Resetting
single status
messages
Reference graphs
Data logger Conguration and measured values NO YES YES YES
Valve signature Signal pressure(x) Measured values YES YES YES YES
On/off valve Conguration YES NO YES YES
Valve position x histogram Measured values YES YES YES YES
Set point deviation e histogram Measured values YES YES YES YES
Cycle counter histogram Measured values YES YES YES YES
Leakage sensor Short-term monitoring 'Sensitivity sound level'
Course of lower end position Measured values YES YES YES YES
Valve dead band Conguration and
Partial stroke test (PST) Conguration and
Valve signature NO NO YES YES
Leakage sensor Manufacturer reference YES NO YES YES
Process reference YES NO YES YES
Course of supply pressure Conguration NO NO YES YES
Measured values YES YES YES YES
Friction(x) Measured values YES YES YES YES
Measured values YES YES YES YES
Short-term monitoring 'Sampling time' and
measured values
Short-term monitoring 'Sampling time' and
measured values
Short-term monitoring Measured values YES YES YES YES
and measured values
Long-term monitoring Measured values YES YES YES YES
Sound level(x) Measured values YES YES YES YES
Reference value YES NO YES YES
measured values
measured values
* Except for 'Sampling time' parameter
YES YES YES YES
YES YES YES YES
YES YES YES YES
YES YES YES YES
YES NO* YES YES
Code 36
Diag Std DS
EB 8389-1S EN 15
Monitoring
Resetting
single status
messages
Full stroke test (FST) Conguration and
measured values
* Except for 'Sampling time' and 'Max. test duration' parameters
Alarm settings NO See uSec.17.4
Status classication according to NAMUR107 NO NO NO YES
All logged messages, see u Section 2.2 YES NO YES YES
Operating hours counter NO NO NO NO
Device in operation NO NO YES YES
Device switched on since initialization NO NO YES YES
Device in operation since initialization NO NO YES YES
YES NO* YES YES
Code 36
Diag Std DS
16 EB 8389-1S EN
Monitoring
2.1.2 Condensed state
To provide a better overview on the condi­tion of the positioner, all status messages are summarized in a condensed state which is
made up from a summary of all classied
messages in the positioner. The status mes­sage with the highest priority determines which condensed state is set.
The condensed state appears in TROVIS-
VIEW4 on the right-hand side of the info
bar and in the Measured process values folder. See u Table 3 for a description of the icons and their meaning.
Additionally, the condensed state can be used to trigger the data logger. See uSec­tion 3.2.1.
Note:
The condensed state is marked by until the positioner data have been up­loaded.
The condensed state can be read in the posi­tioner display in Code 48 - d6. See u Table
3.
Condensed state at the fault alarm output
The condensed state also be read out at the fault alarm output if one of the following conditions occurs:
1. Condensed state 'Failure' is activated.
2. Condensed state 'Function check' is acti­vated and the fault alarm output is acti­vated.
3. Condensed state 'Maintenance required'
or 'Out of specication' is activated and
the fault alarm output is activated.
Table 3: Condensed state reading
Status message TROVIS-VIEW 4/DTM Positioner Priority
Failure
Function check
Out of specication
Maintenance request/ maintenance required
No message, OK
EB 8389-1S EN 17
red
orange
yellow
blue
green
Text e.g. TESTING, TUNE or
TEST
blinking
Monitoring
Device settings > Alarm settings
Fault alarm at condensed state 'Function
2.
check' (Code 32): Yes
3. − Error message in case of 'Maintenance re- quired' and 'Out of specication' con-
densed states (Code 33): Yes
2.2 Logging
The last 30 generated messages are saved in the positioner with a time-stamp (logged by the operating hours counter) and with details on how long the message exists.
You can view these messages in TROVIS­VIEW4 in the Diagnostics folder (> Monitor- ing > Logging).
Logging starts automatically 15 minutes after initialization. It does not need to be activated by the user.
Messages are logged when:
Their status classication is not 'No mes-
sage'.
− Their recording in the logging is activat- ed.
The 'Internal solenoid valve/forced vent- ing/supply pressure' message is only ad­ditionally logged when the time entered
in 'Min. interval for new logging of inter­nal solenoid valve' has elapsed between the generation of two 'Internal solenoid valve/forced venting/supply pressure'
messages.
Note:
Logging can only be deactivated when
the associated status classication is set to 'No message'.
Device settings > Alarm settings > Status classication > Logging
Supply pressure: [Yes], No
Change in friction: [Yes], No
Seat leakage: [Yes], No
Packing leakage: [Yes], No
Pneumatic leakage: [Yes], No
Defective actuator springs: [Yes], No
− Manipulated variable range limitation: [Yes],
No
Course of end position: [Yes], No
Positioner-valve linkage: [Yes], No
Manipulated variable range: [Yes], No
− Change in manipulated variable range: [Yes],
No
Partial stroke test (PST) [Yes], No
Full stroke test (FST): [Yes], No
On/off valve: [Yes], No
Code 50-58, 61, 63, 76, 81: [Yes], No
Binary input: [Yes], No
Data logger: [Yes], No
− Internal solenoid valve/forced venting/supply
pressure: [Yes], No
− Min. interval for new logging of internal solenoid valve: 0 to 5000 s, [300 s]
18 EB 8389-1S EN
The following messages are not logged if they are generated due to a hardware error:
− Packing leakage
− Pneumatic leakage
− Manipulated variable range limitation
− Course of end position
− Positioner-valve linkage
− Manipulated variable range
− Change in manipulated variable range
In this case, only the original hardware error is logged:
− x > range (Code 50)
− Internal solenoid valve/forced venting/ supply pressure (Code 54)
Transit time not reached (Code55)
− Inconsistent data memory (Code 59)
− Internal device error (Code 60)
− x signal (Code 62)
− i/p converter (Code 64)
− Hardware (Code 65)
Monitoring
EB 8389-1S EN 19
Monitoring
Data logger
â â
Permanent Triggered
â â
Sampling time
â
Start
START-UP
â
100 measured val-
(w, x, e, p
Function
1)
â â â â â
Con-
densed
state
â â â
Trigger condition
ues
) â
out
Triggered by
, x, e
w or p
out
Trigger value
Trigger band
Trigger condition
Trigger lead time
Sampling time
Start
Solenoid
BE
valve/ forced
venting
w or solenoid
valve/forced
venting
Trigger value
Trigger band
Trigger condition
â
1)
â
Trigger event
â
Logged by operating hours
counter
â â
PROCESS
Measured values (w, x, e, pout) before trigger
event
(Number = Trigger lead/Sampling time)
Measured values (w, x, e, pout) after trigger event
+
(Number = 100 – Trigger lead/Sampling time)
â
Total 100 measured values (w, x, e, pout)
1)
The data logger is started by the software, e.g. TROVIS-VIEW 4
20 EB 8389-1S EN
Data logger
3 Data logger
The data logger records the measured vari­ables (valve position x, set point w, set point deviation e and signal pressure p corded data are plotted against time in a graph.
Note:
The data logger is interrupted and must be reactivated when one of the following events occurs:
Failure of power supply of the posi­tioner
Failure of power supply of the exter­nal solenoid valve
). The re-
out
3.1 Permanent data logging
The measured variables are logged at the
rate dened in 'Sampling time' and saved in
a circular buffer, which holds 100 data points per measured variable at one time.
Note:
You can read the measured data
logged over the past 24 hours from
the 'Data logger' graph when the Di­agnostics folder (> Data logger) is left
open over this period.
Fig. 1: Diagnostics > Data logger
EB 8389-1S EN 21
Data logger
Dening parameters
1. Select 'Permanent' (Function).
2. Enter sampling time.
3. Start data logger.
The 'Test information' status indicates 'Test active'.
Diagnostics > Data logger
1.
− Function: [Permanent]
2. − Sampling time: 0.2 to 3600.0 s, [1.0 s]
3. − Start data logger
Note:
Right-click 'Cancel data logger' and select 'Execute' to stop the data logger ('Test information' = 'Test not active').
3.2 Triggered data logging
Measured values are saved in a circular buf-
fer after the event dened in 'Triggered by'
has occurred (see u Section 3.2.1 to 3.2.5). The event that has triggered data logging is recorded. Data logging is terminated after 100 measured values per measured variable have been saved in the circular buffer. The
'Sampling time' determines the time between recordings. A 'Trigger lead time' greater
than 0 also leads to the measuring values before the triggering event for the time se­lected being included in the 100 measured
values per measured variable. The 'Trigger lead time' may include the value 100 x 'Sampling time' at the maximum.
Dening parameters
1. Select 'Triggered' (Function).
2. Select the triggering event.
3. Enter sampling time.
4. Start data logger.
The 'Test information' status indicates 'Test active'.
When the data logging is nished, the Progress bar indicates 'Memory full, data recording completed'.
Note:
Right-click 'Cancel data logger' and select 'Execute' to stop the data logger ('Test information' = 'Test not active').
3.2.1 Triggered by condensed state
The measured values are included in the trig­gered event when the condensed state de­ned in 'Triggered by condensed state' aris­es.
Note:
If 'Function check' is selected as the condensed state ('Triggered by con­densed state'), data are logged when a dynamic test starts. Data from each test start are logged.
Diagnostics > Data logger
1.
− Function: Triggered.
2. − Sampling time: 0.2 to 3600.0 s, [1.0 s]
3. − Triggered by: Condensed state
22 EB 8389-1S EN
Data logger
rigger band
gg
w, x, y, e
ger band
w, x, y, e
rigger band
rigger band
w, x, y, e
− Trigger lead time:
0.0 s to 100 x 'Sampling time', [20.0 s]
Triggered by condensed state: No message, Function check [Maintenance required], Maintenance demanded, Out of specica­tion, Failure
4. − Start data logger
3.2.2 Triggered by set point, valve position, set point deviation or signal pres­sure
The measured values are included in the trig­gered data logging when the conditions for the selected measured variable (set point w, valve position x, set point deviation e or sig­nal pressure p
'Trigger band' and 'Trigger condition' are
met.
'Trigger condition' = Decreasing signal/ lower band value undercut
) dened in 'Trigger value',
out
'Trigger condition' = Increasing signal/ upper band value exceeded
Upper band limit = Trigger value Trigger value
Trigger band
+ ½ Trig
The conditions for starting a trigger event are met when the value falls below the limit
('Trigger value' – ½ 'Trigger band').
'Trigger condition' = Band exit
Upper band limit = Trigger value + ½ T
Trigger value
Lower band limit = Trigger value - ½ T
Trigger band
Trigger value Lower band limit = Trigger value – ½ T
er band
Tri
The conditions for starting a trigger event are met when the value falls below the limit
('Trigger value' – ½ 'Trigger band') or ex­ceeds the limit ('Trigger value' + ½ 'Trigger band').
The conditions for starting a trigger event are met when the value falls below the limit
This function is only active when 'Trigger band' ≠ 0.
('Trigger value' – ½ 'Trigger band').
EB 8389-1S EN 23
Data logger
ger band
w, x, y, e
'Trigger condition' = Band entry
Upper band limit = Trigger value Trigger value Lower band limit = Trigger value - ½ Trigger band Trigger band
+ ½ Trig
The conditions for starting a trigger event are met when the value exceeds the limit
('Trigger value' – ½ 'Trigger band') or falls below the limit ('Trigger value' + ½ 'Trigger band').
This function is only active when 'Trigger band' ≠ 0.
Diagnostics > Data logger
1.
− Function: Triggered
2. − Triggered by: Valve position, set point devi- ation, signal pressure or set point
− Trigger value:
0.0 to 100.0 %, [99.0 %] (set point, valve position, set point deviation)
0.0 to 7000.0 mbar, [99.0 mbar] (signal pressure)
− Trigger band:
0.0 to 100.0 %, [99.0 %] (set point, valve position, set point deviation)
0.0 to 10000.0 1/s, [99.0 1/s] (drive sig­nal)
− Trigger lead time:
0.0 s to 100 x 'Sampling time', [20.0 s]
− Trigger condition: [Decreasing signal/lower band value undercut], Increasing signal/up-
per band value exceeded, Band exit, Band
entry
3. − Sampling time: 0.2 to 3600.0 s, [1.0 s]
4. − Start data logger
3.2.3 Triggered by binary in­put
This setting is only active when a binary in­put is installed in the positioner. If this is not
the case, the Progress bar indicates 'Cannot start data logger – trigger cannot be set'.
The measured values are included in the trig­gered data logging when the state of the bi­nary input changes.
Diagnostics > Data logger
1.
− Function: Triggered
2. − Triggered by: Binary input
− Trigger lead time:
0.0 s to 100 x 'Sampling time', [20.0 s]
3. − Sampling time: 0.2 to 3600.0 s, [1.0 s]
4. − Start data logger
24 EB 8389-1S EN
Data logger
3.2.4 Triggered by internal so­lenoid valve/forced venting
This setting is only active when an internal solenoid valve/forced venting is installed in the positioner. See 'Internal solenoid valve/
forced venting' reading. If this is not the case, the Progress bar indicates 'Cannot start data logger – trigger cannot be set'.
The measured values are included in the trig­gered data logging when the solenoid valve is triggered or the forced venting is activat­ed.
Diagnostics > Data logger
1.
− Function: Triggered
2. − Triggered by: Internal solenoid valve/
forced venting
− Trigger lead time:
0.0 s to 100 x 'Sampling time', [20.0 s]
3. − Sampling time: 0.2 to 3600.0 s, [1.0 s]
4. − Start data logger
tions dened in 'Triggered by internal sole­noid valve/forced venting“ or 'Triggered by set point' are met.
Diagnostics > Data logger
1.
− Function: Triggered
− Triggered by: Set point or internal solenoid
valve/forced venting
Trigger value: 0.0 to 100.0 %, [99.0%]
− Trigger band: 0.0 to 100.0 %, [99.0 %]
− Trigger lead time:
0.0 s to 100 x 'Sampling time', [1.0 s]
− Trigger condition: [Decreasing signal/lower band value undercut], Increasing signal/up-
per band value exceeded, Band exit, Band
entry
3. − Sampling time: 0.2 to 3600.0 s, [20.0 s]
4. − Start data logger
3.2.5 Triggered by set point or internal solenoid valve/ forced venting
This setting is only active when an internal solenoid valve/forced venting is installed in
the positioner. See 'Internal solenoid valve/ forced venting' reading. If this is not the case, the Progress bar indicates 'Cannot start data logger – trigger cannot be set'.
The measured values are included in the trig­gered data logging when one of the condi-
EB 8389-1S EN 25
Data logger
Valve signature
Requirements:
– Actuator: Single-acting
– Type of application: Control valve
Only applies to rst start-up after reset with Code 36 –
DS or Std.
â
Initialization including valve signature
â à
Start initialization
â
Valve signature recording
â
START-UP
Valve signature, signal pressure(x) Course of supply pressure Valve signature, friction(x)
â â
Alarm settings Recording threshold
Alar
â
m settings
ATC ATO and ATC
Zero limit,
lag time
Lower limit Upper limit
Status classication (NE 107) Status classication (NE 107) Status classication (NE 107)
Zero
x0 > (ZP
+ Zero limit)
Init
x0 < (– Zero limit)
Spring pre-load
-
ing
Reduced spring pre-loading
essure Change in friction
Supply pr
Not
available
Too low
Perm.
Too high
limit exceeded
â â â â â â
Analysis (NE 107)/logged by
operating hours counter
PROCESS
Zero
Defective actuator
springs
Analysis (NE 107)/logged by
operating hours counter
Analysis (NE 107)/logged by
operating hours counter
Supply pressure status Change in friction
Min. supply pressure
Max. supply pressure
Dwell time (supply pressure
< 1.0bar)
l time (supply pressure
Dwel
> 7.0bar)
Valve signature
canceled
Not successful
â
Lower in total range Lower/higher in mid-
position Lower/higher near
max. OPEN position
Lower/higher near CLOSED position
â
R
eset 'Pressure sensor monitoring values'
26 EB 8389-1S EN
Valve signature
4 Valve signature
The valve signature plots the signal pressure p
as a function of valve position x.
out
All diagnostic functions dependent on the signal pressure are based on the valve sig­nature, e.g. to detect pneumatic leakage or to reveal an excessively high or low supply pressure.
Note:
Additionally, the pneumatics are mon­itored using the 'Leakage limit' param eter, which is adjustable between 0 and 100% in the Device settings fold- er (> Alarm settings). The positioner generates the 'Pneumatic leakage' message whenever the leakage ex
ceeds this limit value. 'No message' is
assigned by default.
Requirements
1. A single-acting actuator is mounted on the valve.
2. The valve operates as a control valve.
Device settings > Actuator
1.
− Principle of operation (Code 48 - d11):
Single-acting
Start-up
2.
− Type of application (Code 49 - h0):
Control valve
-
To perform monitoring while the process is
running, the reference graph must rst be
plotted.
-
Fig. 2: Start-up > Reference graphs > Valve signature
EB 8389-1S EN 27
Valve signature
4.1 Reference graphs
During the plotting of the reference graph (Fig. 2), the valve is moved very slowly from the end position at which no pressure is ap­plied to the actuator to the position at which the maximum air signal is applied to the ac­tuator. The valve is then moved back again to its end position. During which, the posi­tioner switches to open-loop control (control without feedback).
The sensitivity of reference graph plotting de-
nes at which speed the valve is moved. The
time span how long the reference graph is to be plotted depends on the sensitivity select-
ed. Select 'High' for valves with small bench
ranges and/or high friction. After the reference graph has been plotted,
the recorded data points for signal pressure p
and valve position x are converted into
out
xed points.
Note:
The valve positions cannot be predict­ed in open-loop control (control with­out feedback). The reference graph may differ for the same valve after each logging.
Dening parameters
The reference graph is automatically plotted
after initialization when 'Initialization includ­ing valve signature' = Yes.
Start-up
− Initialization including valve signature (Code 48 - h0): [Yes]
The reference graph can also be plotted sep­arately outside initialization.
1. Switch to manual mode.
2. Select 'Sensitivity' from the drop-down list.
3. Start test.
The 'Test information' status indicates 'Test active'. 'D1' and 'TEST' are indicat-
ed in alternating sequence on the posi­tioner display.
'Function check'
is activated as the
condensed state.
Start-up
1.
− Enter operating mode (Code 0): Manual
2.Start-up > Reference graphs > Valve
signature
− Sensitivity: Low, [Medium], High
3. − Start test
4.1.1 Analysis and monitoring
The positioner records the data for lling and
venting the actuator. It then determines the characteristic values listed below:
'Mean hysteresis': Average hysteresis
(average signal pressure change Δp
relation to the spring range)
'Min. hysteresis': Lowest possible hystere- sis (minimum signal pressure change
Δp
in relation to the spring range)
out
'Max. hysteresis': Highest possible hys- teresis (maximum signal pressure change
Δp
in relation to the spring range)
out
in
out
28 EB 8389-1S EN
Valve signature
'Detected lower spring range value': Sig- nal pressure p
lled with the minimum amount of air
'Detected upper spring range value': Sig- nal pressure p
lled with the maximum amount of air
The 'Valve signature canceled' message is
generated if the test is canceled.
Start-up > Initialization result
− Valve signature canceled (Code 81): , , ,
The 'Test status' reading indicates the reason
why the test was canceled:
No supply pressure: The supply pressure
was under 500mbar during the test.
− Valve moved too quickly. Recommended action: Increase sensitivity
− Position at p air): (1) Even though the pressure was in-
creased in steps from 0bar to the maxi­mum amount of air for lling the actua-
tor, the valve was not able to reach the maximum position in closed-loop opera­tion. (2) The minimum valve position without tight-closing is below 96%. Recommended action: Increase supply pressure.
− Position at p (1) Even though the pressure was re­duced in steps from the maximum amount of air for lling the actuator, the valve was not able to reach the minimum
when the actuator is
out
when the actuator is
out
not reached (lling with
max
not reached (venting):
min
position in closed-loop operation. The valve might be jammed. (2) The minimum valve position without
tight-closing is above 4%.
− Time-out
− Double-acting actuator
− Internal error
− Current too low
− Internal solenoid valve/forced venting triggered
SUB initialization
4.2 Valve signature, signal pressure(x)
The positioner records the data for lling and
venting the actuator during closed-loop op­eration. The recorded data can be directly compared with the reference graph. Addi­tionally, the minimum, maximum and current supply pressure are shown in the graph.
Data are recorded in the background re­gardless of the operating mode selected if a reference graph has already been plotted. Data logging does not need to be activated.
Note:
The positioner determines the mini­mum and maximum supply pressure while plotting the reference graph. The current supply pressure may fall below the minimum supply pressure and ex­ceed the maximum supply pressure.
Dening parameters
1. Record reference graph. u Section 4.2.
EB 8389-1S EN 29
Valve signature
2. Set the limit for zero monitoring in con­trol valves with closed position ATC (air to close).
3. Select classication for status messages. See u Section 4.2.1.
Device settings > Alarm settings
2.
− Zero limit (Code 48 - d5):
0.0 to 100.0 %, [5.0 %]
− Lag time: 1 to 9999 s, [30 s]
3.Device settings > Alarm settings > Status
classication > Positioner
− Zero (Code 58):
Device settings > Alarm settings > Status classication > Actuator
Defective actuator springs
− Reduced spring pre-loading:
, [ ], ,
[ ], , ,
4.2.1 Analysis and monitoring
If the monitoring line has a smaller gradient than the reference line, this pinpoints to a re­duced compression of the actuator springs.
Diagnostics > Monitoring > Actuator
− Defective actuator springs:
Valves with ATC (air to close) closed posi­tion
In valves with ATC closed position, the posi­tioner generates a zero error when the valve position in the tight-closing position is larger than the sum of the initialization zero points
and 'Zero limit' or smaller than the negative 'Zero limit' after the adjusted 'Lag time' has
elapsed.
Diagnostics > Monitoring > Positioner
− Zero (Code 58):
, , ,
, , ,
Fig. 3: Diagnostics > Monitoring/tests > Valve signature > Valve signature, signal pressure(x)
30 EB 8389-1S EN
Loading...
+ 90 hidden pages