Salus PCSol 300 Installation And Operation Manual

Page 1
62.X
.2
REVISION
SOFTWARE
www.econet24.com
PUMP
PUMP
CIRCULATION
CIRCULATION PROGRAM
SIMPLE IN USE
INTELLIGENT
ALARM
CLOCK
CLOCK SUSTAIN
TEMPORARY
POWER
HEAD OUTPUT
ANTI-FREEZING
GRAPHIC
DISPLAY
POOL
TANK
PROTECTION
HEATER SUPPORT
PROGRAM
HEATER
PUMP ROTATION CONTROL
NIGHT
COOLING
HEAT DISCHARGE
VACUUM
COLLECTOR
10 DAYS
TWO COMPASS
DIRECTIONS
Controller
PCSol 300
FOR SOLAR COLLECTORS
INSTALLATION AND OPERATION MANUAL
2014-05-07
Page 2
Page 3
3
CONTENTS
1. SAFE INSTALLATION AND USE 4
2. GENERAL 5
3. DIRECTIVE WEEE 2002/96/EC 5
4. DOCUMENT KEEPING 5 OPERATING MANUAL 7
5. OPERATION 8
6. CONTROLLER MENU 8
7. SETTINGS MENU 10
7. SETTINGS MENU 10
8. TIME PROGRAMS 10
8.1. TDHWMIN ................................................. 10
8.2. CIRCULATION ........................................... 11
9. MENU ALARMS 11
10. OPTIONS MENU 13
10.1. RESTORING FACTORY SETTINGS ........ 13
10.2. READING DEFAULT SETTINGS ............. 13
10.3. CLEARING HEAT OUTPUT DATA ........... 13
11. OPERATION MANU 13
11.1. OPERATION\SETTINGS MENU ............. 13
11.2. OPERATION\LOUDNESS MENU ............ 14
11.3. OPERATION\CLOCK MENU .................. 14
12. HEAT OUTPUT 15
13. SOLAR APPLICATIONS 16
13.1. NIGHT COOLING ................................ 16
13.2. SOLAR THERMAL SCHEME A................ 16
13.3. SOLAR THERMAL SCHEME B................ 17
13.4. SOLAR THERMAL SCHEME C ............... 17
13.5. SOLAR THERMAL SCHEME D ............... 18
13.6. SOLAR THERMAL SCHEME E ................ 19
13.7. SOLAR THERMAL SCHEME F ................ 19
13.8. SOLAR THERMAL SCHEME G ............... 20
13.9. SOLAR THERMAL SCHEME H ............... 21
13.10. SOLAR THERMAL SCHEME I ................ 21
13.11. SOLAR THERMAL SCHEME J ................ 22
13.12. SOLAR THERMAL SCHEME K ............... 23
13.13. SOLAR THERMAL SCHEME L ................ 23
14. SHUT DOWN 24
15. ACCESS TO THE UNIT OVER THE INTERNET 25
15.1. BASIC DATA READING ........................ 25
15.2. DIAGRAM OF ACTIVE SOLAR CIRCUIT SYSTEM 25
15.3. USER PARAMETERS ............................ 26
15.4. SERVICE PARAMETERS ....................... 26
15.5. HEAT YIELD GRAPH ............................ 27
15.6. NETWORK SETTINGS.......................... 27
INSTALLATION MANUAL 29
16. TECHNICAL DATA 30
16.1. ELEMENTS OF THE SET ....................... 30
17. INSTALLATION OF PCSOL 300 30
17.1. INSTALLATION OF THE CONTROLLER .. 30
17.2. EXTERNAL CIRCUITS CONNECTION. .... 32
17.2.1. Use of connectors ............................... 32
17.2.2. Power supply connection ..................... 33
17.2.3. Temperature sensor connection ........... 33
17.2.4. Temperature sensor installation ........... 34
17.2.5. Output H connection ........................... 34
17.2.1. ecoNET internet module connection ..... 36
18. APPLICATION SCHEMES 37
18.1. SOLAR APPLICATION SCHEME A .......... 37
18.2. SOLAR APPLICATION SCHEME B .......... 38
18.3. SOLAR APPLICATION SCHEME C .......... 39
18.4. SOLAR APPLICATION SCHEME D ......... 40
18.5. SOLAR APPLICATION SCHEME E .......... 41
18.6. SOLAR APPLICATION SCHEME F .......... 42
18.7. SOLAR APPLICATION SCHEME G ......... 43
18.8. SOLAR APPLICATION SCHEME H ......... 44
18.9. SOLAR APPLICATION SCHEME I .......... 45
18.10. SOLAR APPLICATION SCHEME J .......... 46
18.11. SOLAR APPLICATION SCHEME K .......... 47
18.12. APLIKACJA SCHEMAT SOLARNY L ........ 48
19. CASING CLOSING 49
20. CONTROLLER OPTIONS 49
20.1. SYSTEM OPTIONS\SETTINGS .............. 50
20.2. I\O OPTIONS\CONFIGURATION ........... 51
20.2.1. Wire length compensation ................... 51
20.3. OPTIONS\FUNCTIONS ........................ 51
20.3.1. Vacuum collector function ................... 52
20.4. MANUAL MODE .................................. 52
20.5. SCHEME WIZARD ............................... 52
21. FUSE REPLACEMENT 53
Page 4
4
1. SAFE INSTALLATION AND USE
The controller is designed only for household
and similar use.
Before installation, service or maintenance and prior to making any connections, always disconnect power supply and make sure that the terminals and electric wires are not energized.
When the controller is switched off using keyboard or encoder, the controller terminals are still under dangerous voltage.
Controller may be used only for its intended purpose.
It is required to use auxiliary protection automatics to protect hot water system, CH system (if any) in case of the controller or software malfunction
Programmable settings must be selected suitably to your system type, taking into account all of its operating conditions. Wrongful settings may cause the collector or reservoir malfunction (e.g. collector overheating, etc.).
Programmed settings may be modified only by a person who read and understood this manual.
Use only in heating systems that are set up in accordance with valid regulations.
Electric system to which the controller is connected must be protected with a cut­out device suitable for expected loads.
Never use the controller when its casing is damaged.
In any case do not alter the controller components.
The controller has electronic disconnection for connected devices (operation 2.B according to PN-EN 60730-1). It means that at 230V voltage supply the pump outlets have dangerous voltage, even if the pumps are not controlled.
Do not allow children access to the controller.
Before you open casing, first disconnect power supply from the unit.
The controller must be installed in accordance with the requirements of EN 60335-1 standard, by qualified and authorized technician.
Do not install the unit when it is connected to voltage.
Short circuit in pump output will damage your unit.
Do not operate the unit when it is malfunctioning or was repaired by unauthorized persons.
Do not mount the unit on flammable materials.
Page 5
5
2. GENERAL
Controller PCSol 300 is an advanced electronic unit designed for distribution of heat from solar collectors. The controller is used to control solar circuit systems accordingly to indications from temperature sensors to recover highest possible energy from the collector.
Fig. 2.1 Basic functional diagram
3. DIRECTIVE WEEE 2002/96/EC
The product you have purchased was designed and made using the highest quality components that may be recycled and reused.
If the product is marked with the above crossed bin symbol, it means that it meets requirements of the European Directive 2002/96/EC.
It is recommended to know your local
electric and electronic products disposal system.
It is recommended to process in accordance with local regulations and not to dispose used products to household garbage containers. Proper disposal of outdated products will help to avoid potential adverse effects on the environment and human health.
4. DOCUMENT KEEPING
Please, keep carefully this installation and operating manual and any other relevant documents, so that they may be used at any time. In case when you move or sell the unit, please give the attached documents to its new user.
PCSol300
Page 6
Page 7
OPERATING MANUAL
PCSol 300
Page 8
8
3sek.
5. OPERATION
The controller has TOUCH&PLAY system that facilitates its operation. Encoder is operated by its rotating and pressing.
To start the controller, keep pressed encoder knob for 3 seconds. Welcome screen will be displayed:
Fig. 5.1 Welcome screen *
* starting screen may differ depending on controller version.
After the welcome screen the controller displays the main screen.
Fig. 5.2 Main screen
Controller outlets operation is each time indicated by their blinking on displayed diagram.
6. CONTROLLER MENU
Any time during controller operation, when you keep the encoder pressed for 3 seconds. it will cause exit to the main screen.
All controller settings are made through menu system. MENU is recalled by pressing encoder on
main screen to select icon.
Fig. 6.1 Recalling controller’s menu
When MENU is open, the unit will display a screen with icons that represent the controller functions:
Fig. 6.2 Controller menu
In middle on the screen you can see active item icon selected as in Fig. 6.2. Now, you may turn encoder knob to move through menu items. In main MENU there will be:
Fig. 6.3 Main menu items
Where: Icon TDHWmin (second one) is shown only, if active scheme is B and J. Circulation icon (third one), if active scheme is B, C, D, E, G, H, J,K, L.
Page 9
9
Values of settings are edited in scrollable submenu. Example for submenu preset is shown below. To edit setting value select required setting and press the knob; the value will start blinking. Now, rotate the knob to change the setting value. The changed value will be confirmed, when you press the knob again, and you may select other setting.
After edition in submenu you may select the following by pressing on selection: OK Confirms changes and exits to menu; it
allows reverse reaction to encoder turning;
CANCEL Rejects changes in entire submenu and exits to menu.
Fig. 6.4 Scrollable submenu
Fig. 6.5 Controller’s menu structure
only A, B, C, E, F, H, I, J, L
only B, C, D, E, G, H, J, K, L
only B
Page 10
10
7. SETTINGS MENU
Access
This menu is used to make basic settings of the controller. Change of parameters is only accepted when you use OK in left lower corner of the screen. Use CANCEL to reject any made changes. List of parameters in this menu depends on selected solar scheme. Parameters are described in details in section 13 about particular solar applications.
Depending on scheme and version of unit, the following parameters are available in Settings menu:
Parameter
Scheme
A B C D E F G H I J K
L
TsDHW
X X X X X X X
X
X
X
X
dTAB
X
X
dTCO
X
Eco mode
X
Night cooling
X
X X
X X
X
X
X
X
Night cooling ON
X
X X
X X
X
X
X
X
Night cooling OFF
X
X X
X X
X
X
X
X
TsPOOL
X
X
Priority
X
Alarm TCOLcr
X X X X X X X X X X X
X
8. TIME PROGRAMS
For correct operation of time programs it is required to set the clock.
8.1. TDHWmin
Access
Item available only in B scheme
Time program TDHWmin is minimal temperature of DHT reservoir (T3 sensor), below which the controller controls H output (heater or other additional heat source).
When you switch off the temperature value in value edition box, the time program will be set off and the controller will use stable value for TDHWmin parameter (single temperature value all the time), during edition it may be seen that the temperature has the same value all along the diagram.
Fig. 8.1 Edition of TDHWmin value
To set the TDHWmin to change in time, it is required to set schedule. It is done by setting sch. value in value edition box..
Fig. 8.2 Activating time program for TDHWmin
When sch. value is confirmed, new item MO-FR will be displayed; edit this value to select
one of the three time ranges: MO-FR – time program for days Monday to
Friday,
SAT. – time program for Saturday, SUN. – time program for Sunday.
After you confirmed desired time range, use the knob to move the position marker to the place (hour range), for which you want to edit value.
Fig. 8.3 Setting marker position
Here, press the knob to hide the position marker and to light the edition marker. When the edition marker is lit, turn the knob to change temperature value for current position marker.
Page 11
11
Fig. 8.4 Setting edition marker
When you set temperature and pressed the knob, both edition marker and position marker will be displayed on the screen, and you may turn the knob to copy the value to adjacent positions. Press again the knob to move to the position marker.
Fig. 8.5 Setting value movement
Select OK and press the knob, while in position marker mode, to confirm changes made in schedules. Activate CANCEL to exit without saving changes in schedules.
8.2. Circulation
Access
Item available only in schemes B, C, D, E, G, H, J, K, L
Changes in circulation time programs are introduced the same like it was demonstrated for TDHWmin schedule settings.
Fig. 8.6 Menu structure
Possible settings in value edit box are YES, NO AND sch. Value YES will enable constant circulation. Value NO will disable circulation. Value sch. will activate time program for circulation.
9. MENU ALARMS
Access
The controller may alarm on any irregularities in operation.
The controller has an intelligent alarm function. It means that the controller recognizes type of alarm condition and takes respective remedy actions accordingly to the conditions. For instance, if the sensor of reservoir extra heating with a heater fails, the controller prevents extra heating for the reservoir. Despite of alarm, the solar circuit will continue correct operation and the controller will not let the reservoir to be overheated.
Type of action taken by the smart alarm depends on the alarm type and on the solar application.
When in the main screen in the screen bottom ALARM! sign starts blinking (Fig. 5.2), it means alarm situation. Now, entering through menu to Alarms we have access to contents and code number of alarm reported by the controller (Fig. below).
Edition marker
Current marker hour range
Current marker value
Page 12
12
Fig. 9.1 Alarm screen
If the shown item number is higher than 1, it means multiple alarms, to be seen by turning the knob.
Lower left corner indicates the alarm code. Alarm codes are summarized in the table below, to facilitate their identifications and remedies:
List of alarms
No.
Alarm
1
DHW reservoir overheating
Maximal DHW reservoir temperature has been reached (exceeded temperature specified as TDHWmax). Pump that loads heat to reservoir is stopped. This alarm has higher priority than collector alarms (if collector temperature alarms occur at the same time, solar pump will not be started whatsoever). It is required to cool reservoir, e.g. by discharging hot water.
2
Solar panel overheating P1 stop
Collector pump will be stopped by the time, when collector temperature drops below TCOLmax. It is possible to start pump in manual service mode. Check work fluid flow (possible air in system or collector pump is not controlled). This alarm may be due to exceeded reservoir temperature alarm (Code 1).
3
Solar panel critical temperature
It means that collector critical temperature has been reached (parameter TCOLcr) and despite reaching temperatures (TsDHW, TsPOOL) collector pump will be started, until collector temperature drops below TCOLcr. Wait for
collector cool down. If menu option “Alarm TCOLcr” is set as NO, controller will not report
this alarm, but it will take described actions.
4
T1 sensor malfunction
Alarm informs on incorrect operation or damage to T1 sensor. Check connections for continuity (connect) or short circuit (eliminate) in sensor circuit. Alarm will stop collector pump, algorithm stops DHW reservoir loading.
5
T2 sensor malfunction
Alarm informs on incorrect operation or damage to T2 sensor. Check connections for continuity (connect) or short circuit (eliminate) in sensor circuit. Alarm will stop collector pump, algorithm stops DHW reservoir loading.
6
T3 sensor malfunction
Alarm informs on incorrect operation or damage to T3 sensor. Check connections for continuity (connect) or short circuit (eliminate) in sensor circuit. This alarm depends on solar thermal scheme. At B scheme (with heater) extra heating of reservoir will be stopped (output H is off) and alarm is not reported. In schemes A, C sensor has informative function and controller will not report any alarms from these sensors.
7
T4 sensor malfunction
Alarm informs on incorrect operation or damage to T4 sensor. Check connections for continuity (connect) or short circuit (eliminate) in sensor circuit. This alarm depends on Solar thermal scheme. Alarm is reported only at schemes D, G or K, where operational algorithm requires this sensor. At other schemes (B, C, E, F, H, I*) T4 sensor is used to calculate heat output and its malfunction is not reported, while heat output is not calculated.
*T4 sensor operation in I scheme depends on dTP2 parameter, as described in section 20.1
8
DHW A reservoir overheating
An alarm informing that the TDHWmax defined maximum temperature of DHW A (A buffer in K scheme) has been reached. A pump loading heat into this container/buffer will be halted. Container/buffer should be cooled down, e.g. by letting warm water our and/or disconnecting alternative heat source from the container.
9
DHW B reservoir overheating
Alarm on reaching maximal temperature defined in TDHWmax parameter in DHW B reservoir. Pump that loads heat to this reservoir will be stopped. Cool down this reservoir, e.g. by hot water discharge.
10
Solar panel A critical temperature
In system with two collectors (only Solar thermal scheme H) alarm on exceeding critical temperature (parameter TCOLcr) in A collector. Controller, despite that preset temperature TsDHW is reached, will start collector pump P1 in order to lower temperature below critical. Wait for collector cool down. If menu option Alarm TCOLcr” is set as NO, controller will not report this alarm, but it will take described actions.
Page 13
13
11
Solar panel B critical temperature
In system with two collectors (only Solar thermal scheme H) alarm on exceeding critical temperature (parameter TCOLcr) in B collector. Controller, despite that preset temperature TsDHW is reached, will start collector pump P2 in order to lower temperature below critical. Wait for collector cool down. If menu option Alarm TCOLcr” is set as NO, controller will not report this alarm, but it will take described actions.
12
Solar panel A overheating. P1 stop
A circuit collector pump (at scheme H) will be
stopped, until collector temperature drops below TCOLmax. It is possible to start pump in manual service mode.
13
Solar panel B overheating. P2 stop
B circuit collector pump (at scheme H) will be
stopped, until collector temperature drops below TCOLmax. It is possible to start pump in manual service mode.
14
Antifreeze STOP
During antifreeze performance collector pump is started to increase temperature of too cold solar work fluid. Energy from reservoir or pool will be used for this purpose. However, if reservoir or pool temperature is near 2°C, controller will stop antifreeze function to prevent heat source damage and will initiate alarm. Antifreeze function is wider described in section Options\Functions 20.3.
10. OPTIONS MENU
Access
You must log-in to enter the options. Login screen is presented in Fig. 10.1
Fig. 10.1 User login screen
Access to this menu is protected with password. This menu settings are used by installer/servicer. Detailed description of the options parameters is included in installation part of the manual.
Password 0000 will display submenu parameters only for reading.
10.1. Restoring factory settings
This menu allows restoring factory parameters and settings. In login screen enter password 0002 and confirm to restore only default user settings. Service parameters will not be changed. After restoration of factory settings, parameters available in Options menu will not be changed.
Before restoration the controller will show a request to confirm this action.
After restoring factory settings you must set the clock, as it has been reset to date: 00:00, 01-01-2010.
10.2. Reading default settings
The controller has default settings table (that will be restored). Default settings may be read by entering password 0005 in login screen. The table is only for reading type and it may not be edited.
10.3. Clearing heat output data
Password 0003 will clear any heat output
chart in the controller.
Password 0004 will clear heat output
counter.
After entering passwords 0003 and 0004
the controller will display request for
confirmation. Select “NO” to exit without
changes.
List of codes
0000
Table of option submenu settings only for reading
0002
Restores default settings of User group (not protected with password)
0003
Clears heat output chart
0004
Clears heat output counter
0005
Default settings table
Access to Options submenu
Restores default settings in groups User and Service in controller (all parameters)
11. OPERATION MANU
This menu is dedicated to the user. Here, you may change basic settings of the controller only operation.
11.1. Operation\Settings Menu
Access
This menu allows the user to access:
Page 14
14
Nameplate – It has three pages. Navigate
between pages by turning the knob left/right. First page (1/3) allows you to read information on the unit hardware and software version;
Fig. 11.1 2 Page (1/3) of Nameplate
Page (2/3) includes manufacturer’s contact details.
Fig. 11.3 Strona (2/3) Tabliczki znamionowej.
Page (3/3) includes information on microcontroller and software compilation;
Language – allows changing language of
descriptions. You may select the following:
PL-Polish, EN-English, IT-Italian, ES-Spanish, DA-Danish, RO-Romanian, EL-Greek, FR-French, CS-Czech, RU-Russian, DE-German;
Encoder direction – reverts reaction for
encoder turning;
Time Out – inactivity time, in seconds, after
which the unit automatically exits menu and the screen and knob illumination go off;
Menu speed adjusts fastness of menu
animations;
Ambient light – sets illumination pulsating after
the display turned off (when Time Out has elapsed). This function is useful to find the controller in dark rooms. Encoder knob light pulsation will be also performed after the controller is switched off.
11.2. Operation\Loudness Menu
This many includes sound settings. Turn encoder to move between sound settings and controller’s message sounds on and off.
Fig. 11.4 Sound settings screen.
When sounds are switched off, the knob
turning will not be confirmed by acoustic signals.
Switching alarm sounds on will cause that alarm events are reported together with sound signal. If this option is unchecked, any alarm messages will be silent: only display blinking. Alarms will not be confirmed by sound signal.
11.3. Operation\Clock Menu
Access
For correct operation of time programs the unit uses real-time clock, which must be set before the controller start working.
Not set or wrongly set clock will cause incorrect operation of time programs and night cooling function
Day of week as seen in main window will be calculated automatically.
Fig. 11.5 Clock setting screen
PCSol 300
About
OK
Page 15
15
Date and time setting must be confirmed with “OK”. When you select “CANCEL”, any changes will be rejected.
The controller has function of sustaining clock for 10 days. After this time, if power supply is not restored, the clock will reset.
12. HEAT OUTPUT
Access
The controller counts energy recovered from the collector. Heat output visualization differs depending on the controller version.
Heat output function is not available in solar thermal schemes D, G and K.
Calculation of heat output and momentary power requires additional temperature sensor CT6 connected to measurement input T4. If the sensor is not connected, heat output will not be counted.
In solar applications that for their operation require four temperature sensors, heat output counting is not possible. These applications are D and G. When the schemes are on, the controller menu will not display heat output icon and the function may not be entered.
The controller logs data on recovered energy from last 14 days in the form of bar chart.
Fig. 12.1 Heat output screen
Energy total counter is displayed at the bottom of the screen. It counts energy recovered from the solar panel from the beginning of the
unit’s lifetime. The counter data are stored in
non-volatile memory that is not affected by power losses.
First bar in the chart stands for energy recovered on current day and it is updated every full hour.
At midnight, the controller will move data one position to the right and start counting for new current day.
It is possible to turn the heat output chart on in the main screen (in place where active Solar thermal scheme is displayed). In the main screen, the controller displays data for 7 days.
Fig. 12.2 Heat output in main screen
Data are updated every full hour and the entire chart is moved at midnight. To see data for previous days, you must enter the heat output menu.
Fig. 12.3 Heat output in main screen
Page 16
16
13. SOLAR APPLICATIONS
13.1. Night cooling
Due to the fact that in solar thermal schemes C, F, I there is no risk of reservoir overheating and that other protection means are provided for them against overheating, the function of night cooling is not available in these schemes.
For correct operation of night cooling it is required that the clock is set.
Night cooling function is used to cool DHW reservoir by emitting excess heat through cold collector. It is done by starting the collector pump.
During night cooling, any alternative sources of energy will be switched off.
There are three settings for night cooling function: Night cooling, Night cooling ON, Night cooling OFF and they are in Adjustment menu. Night cooling- YES: switches on, NO: switches
off the night cooling mode. When the mode
is on, the controller, in hours 000÷500, if T2
sensor temperature is higher than specified
in Night cooling ON setting; will decide to
start night cooling. The controller will start
the collector pump in order to discharge to
reservoir and will be cooling the reservoir to
reach temperature specified in Night
cooling OFF setting. In this mode, the
controller additionally monitors the collector
temperature; cooling will be stopped for
some time, if T1+dToff>T2. Regardless
prior conditions, the controller will exit from
the cooling mode at 500 and return to normal
operation. Activation of night cooling mode is
indicated in the screen as blinking moon icon
near the collector picture. Night cooling ON - DHW reservoir temperature
(measured by T2), when reached, if night
cooling function is enabled (prior item)
000÷500 and the temperature at T2 sensor is
higher than Night cooling ON temperature,
the controller will decide on night cooling
activation. The controller will start the
collector pump to discharge the reservoir and
it will continue to cool the reservoir to the
temperature set for Night cooling OFF. Night cooling OFF - DHW reservoir
temperature (T2 sensor), to which the
controller will be cooling the reservoir during
night cooling function. When the temperature
drops to the one specified for Night cooling
OFF, the controller will stop night cooling.
Additionally, depending on selected scheme, the controller will control additional outputs, so as to discharge heat more efficiently.
In scheme B during night cooling, circulation on output P2 will be activated (regardless any time programs etc.); heater operation will stopped (output H is turned off, regardless any time programs etc.). In schemes D, E, G, J, K during night cooling, circulation on output H will be activated (regardless any time programs etc.).
13.2. Solar thermal scheme A
Loading of DHW reservoir with solar
collector.
This basic solar application.
Fig. 13.1 Solar thermal scheme A
The collector pump will be started with 100% capacity, when difference between T1 and T2 exceeds value of dTonDHW setting and it will be working for the time specified in tP setting. If upon this time the difference between T1 and T2 is still above dTonDHW, the pump speed will remain at 100%. If the temperature difference between T1 and T2 drops below dTonDHW, the controller will start reducing the pump speed, until the moment when T1 and T2 difference reaches value specified in dToffDHW setting. When T1 and T2 difference is between the values dTonDHW ÷ dToffDHW, the controller will calculate and set the pump speed proportionally. When dToffDHW is reached, the pump will work at minimal speed (parameter Pmin), below it will be stopped.
System will work by the time when T2 sensor preset temperature TsDHW is reached, than the collector pump P1 is stopped.
If the collector temperature T1 reaches critical value (TCOLcr parameter), the controller will allow the collector pump to be switched on to lower the collector temperature below HP1 hysteresis parameter.
If the reservoir temperature on T2 sensor reaches the value of TDHWmax, than the
controller, despite critical collector’s temperature
(TCOLcr), will stop the collector pump, disabling the collector cooling. It is to protect the reservoir from overheating.
Page 17
17
List of settings in Adjustment menu
TsDHW- Reservoir temperature preset. Night cooling- YES enables / NO disables night
cooling in hours 000÷500.
Night cooling ON DHW reservoir temperature
(T2 sensor), if exceeded at 0
00,
if night cooling function is enabled, the controller will decide on night cooling activation.
Night cooling OFF DHW reservoir
temperature (T2 sensor), to which the controller will cool the reservoir (if night
cooling is enabled and in hours 000÷5
00
Night cooling ON temperature is exceeded).
Alarm TCOLcr – Switching on (YES) or off (NO)
the alarm on exceeding TCOLcr temperature. This function does not affect
the controller’s operation. If the setting is set
as NO, the controller will not report any alarm after TCOLcr temperature has been exceeded on the collector’s sensor.
13.3. Solar thermal scheme B
Loading of DHW reservoir with a function of extra heating by the use of a heater.
Fig. 13.2 Solar thermal scheme B
The collector pump will be started with 100% capacity, if the difference between T1 and T2 exceeds value of dTonDHW setting and it will work for the time as specified in tP. If after this time the difference between T1 and T2 is still above dTonDHW, the pump speed will remain at 100%. If the said difference T1 and T2 drops below dTonDHW, the controller will start reducing the pump speed, until the difference between T1 and T2 reaches the value specified as
dToffDHW. When the difference between T1 and T2 is between the values dTonDHW ÷ dToffDHW, the controller will calculate and set
pump speed proportionally. If dToffDHW is reached, the pump will work at minimal speed (parameter Pmin), below it will be stopped.
The controller will heat up CWU reservoir using a heater or other heat source (H output) up to the temperature of TDHWmin. Functioning
of H output depends also on eco function set up, as described in „Adjustment” menu.
TDHWmin temperature is set through
main menu item TDHWmin.
List of settings in Adjustment menu:
TsDHW- Reservoir temperature preset.
Eco mode- economic mode on or off (power
saving) YES Extra heating of DHW reservoir with a heater or other source of heat (H output) to the temperature of TDHWmin, when the collector is not working (P1 pump stops due to poor sunlight). When the collector pumpis started, the controller will turn the heater off (H output). NO Extra heating of DHW reservoir with a heater or other source of heat (H output) up to the temperature of TDHWmin, regardless if the collector supplies energy or not.
Night cooling- YES enables / NO disables night
cooling mode in hours 000÷500.
Night cooling ON DHW reservoir temperature
(T2 sensor), which if exceeded at 0
00
(if night cooling function is enabled), the controller will decide on night cooling activation.
Night cooling OFF DHW reservoir
temperature (T2 sensor), to which the controller will be cooling down the reservoir (if night cooling function is enabled and in hours 000÷5
00
the temperature of Night
cooling ON has been exceeded).
Alarm TCOLcr – Switches on (YES) or off (NO)
the alarm on exceeding TCOLcr temperature. This function will not affect the controller operation. If the parameter is set as NO, the controller will not alarm when the temperature of TCOLcr is exceeded at the
collector’s sensor.
13.4. Solar thermal scheme C
Loading of DHW reservoir with excess heat discharge function.
Fig. 13.3 Solar thermal scheme C
The collector pump will be started with 100% capacity, if the difference between T1 and T2 exceeds value of dTonDHW setting and it will be working for the time specified in tP parameter. If after this time the difference between T1 and T2 is still above
Due to heat discharge function, this scheme has no night cooling function.
Page 18
18
dTonDHW, the pump speed will remain at 100%. If the said difference between temperatures T1 and T2 drops below dTonDHW, the controller will start reducing the pump speed, until the difference between T1 and T2 reaches the value specified as dToffDHW. If the difference between T1 and T2 is between the values dTonDHW ÷ dToffDHW, the controller will calculate and set the pump speed proportionally. When dToffDHW is reached, the pump will work at minimal speed (Pmin parameter), below it will be stopped.
The system will operate by the time when T2 sensor temperature reaches the preset TsDHW, and then it will be stopped.
If T1 collector temperature reaches critical value (TCOLcr), than the collector will allow the collector pump to be switched on, to reduce the critical temperature blow hysteresis HP1.
If the reservoir reaches maximal temperature TDHWmax, the P2 input (controls discharge valve) will be operated, until the reservoir temperature (T2 sensor) drops to the value T2<TDHWmax-HP2.
List of settings in Adjustment menu:
TsDHW- Reservoir temperature preset. Alarm TCOLcr – Switching on (YES) or off (NO)
the alarm on exceeding TCOLcr
temperature. This function will not affect the
controller operation. If the parameter is set
as NO the controller will not alarm after
TCOLcr temperature has been exceeded at
the collector’s sensor.
13.5. Solar thermal scheme D
Loading of DHW reservoir A with a function for heat transfer to DHW reservoir B.
Fig. 13.4 Solar thermal scheme D
The collector pump will be started with 100% capacity, if the difference between T1 and T2 exceeds the value of dTonDHW setting, and it will be working for the time specified in parameter tP. If after this time the difference between T1 and T2 is still above dTonDHW, the pump speed will remain at 100%. If the said difference between T1 and T2 drops below dTonDHW, the controller will start
reducing the pump speed, until the difference between T1 and T2 reaches the value specified as dToffDHW. If the difference between T1 and
T2 is between the values dTonDHW ÷ dToffDHW, the controller will calculate and set
the pump speed proportionally. When dToffDHW is reached, the pump will work at minimal speed (Pmin parameter), below it will be stopped.
If the difference between A and B reservoir temperature reaches the value of dTAB (T3 and T4 difference), P2 will be started to transfer heat to the reservoir B. The pump will be stopped, if the difference between temperatures T3 and T4 drops below the difference dTAB-HP2).
If the collector temperature T1 reaches the value of TCOLcr, the collector pump will be started (despite of reaching TsDHW temperature). This is aimed to reduce the
collector’s temperature. It will be stopped, when
T1 temperature drops below T1<TCOLcr-HP1, or if the reservoir temperature at T2 sensor
reaches the value of TDHWmax.
List of settings in Adjustment menu
TsDHW- Reservoir temperature preset A and B. dTAB- temperature difference between
reservoirs A and B (T3 and T4 sensors), that when reached causes the controller to start P2 pump, which transfers heat to the reservoir B. P2 will be stopped, if the difference of dTAB (T3 and T4 temperatures) drops by the value of auxiliary hysteresis HP2.
Night cooling- YES enables / NO disables night
cooling mode in hours 000÷500.
Night cooling ON DHW reservoir temperature
(T2 sensor) that when exceeded at 000, if night cooling function is enabled, the controller will decide on night cooling activation.
Night cooling OFF DHW reservoir
temperature (T2 sensor), to which the controller will be cooling down the reservoir (if night cooling function is enabled and if between 000÷5
00
Night cooling ON
temperature was exceeded).
Alarm TCOLcr – Switching on (YES) or off (NO)
the alarm on exceeding TCOLcr temperature. This function will not affect the controller operation. If the parameter is set as NO, the controller will not alarm if TCOLcr temperature has been exceeded at the
collector’s sensor.
Page 19
19
13.6. Solar thermal scheme E
Loading of two DHW reservoirs A and B
with priority function for reservoir A.
Fig. 13.5 Solar thermal scheme E
Both reservoirs are loaded up to the temperature set as TsDHW, measured at T2 sensor for reservoir A or T3 sensor for reservoir B. The controller checks which reservoir has not reached the temperature preset and decides on loading to this reservoir.
If neither of the reservoirs has reached the temperature preset, the controller first loads the reservoir A (reservoir A priority).
The collector pump P1 for the reservoir A or P2 for the reservoir B will be started at 100% capacity for the reservoir (depending on which one has not reached temperature preset), if the difference between T1 and T2 (for reservoir A) or T1 and T3 (for reservoir B) exceeds the value of dTonDHW setting. The pump will be working for the time specified in tP setting. If after this time the difference between T1 and T2 or T3 is still above dTonDHW, the pump speed will remain at 100%. If the said difference between temperatures drops below dTonDHW, the controller will start reducing the pump speed, until the value of dToffDHW is reached.
If the difference between T1 and T2 or T3 is between the values dTonDHW ÷ dToffDHW, the controller will calculate and set the pump speed proportionally. When dToffDHW is reached, the pump will work at minimal speed (Pmin), below it will be stopped.
System will switch again to reservoir A loading, when the temperature drops below the value of HP1 hysteresis.
Operating algorithm of the collector pump P1 with the reservoir A is identical as for the pump P2 at loading the reservoir B.
When both reservoirs reach the temperature preset TsDHW, the collector pumps will be stopped. The will be started at the moment, when in one of the reservoirs the temperature drops in relation to the temperature preset of hysteresis: respectively HP1 for P1 pump and HP2 for P2 pump. Eventually, when the temperature at the collector sensor T1 will reach
critical value (TCOLcr). Then, the controller will allow switching on the collector pump for the reservoir A or B (with the priority for the reservoir A), by the time, when the reservoirs temperatures reach TDHWmax. This will cause the collector pumps to stop.
List of settings in Adjustment menu:
TsDHW- Reservoir temperature preset A or B. Night cooling- YES switches on / NO switches
off night cooling mode in hours 000÷500.
Night cooling ON DHW reservoir temperature
(T2 sensor), when exceed at 000, if night cooling function is enabled, the controller will decide on night cooling activation.
Night cooling OFF DHW reservoir
temperature (T2 sensor) to which the controller will be cooling down the reservoir (if night cooling function is enabled and if in hours 000÷5
00
Night cooling ON
temperature has been exceeded).
Alarm TCOLcr – Switching on (YES) or off (NO)
the alarm on exceeding TCOLcr temperature. This function will not affect the controller operation. If the parameter is set as NO, the controller will not alarm after exceeding TCOLcr temperature at the collector sensor.
13.7. Solar thermal scheme F
Loading of DHW reservoir and pool with priorities function.
Fig. 13.6 Solar thermal scheme F
Depending on Priority setting (Pool/DHW), the system will first load the circuit to temperature preset of TsDHW or TsPOOL.
If the reservoir circuit has priority and it has not reached its temperature preset, then the collector pump will be started with 100% capacity, if the difference between T1 and T2 exceeds value of dTonDHW, and it will be working for the time specified in parameter tP. If after this time the difference between T1 and T2 is still above dTonDHW, the pump speed will remain at 100%. If the said difference between T1 and T2 drops below dTonDHW, the controller will start reducing the pump speed, until the difference between T1 and T2 reaches the value specified as dToffDHW. If the difference
Page 20
20
between T1 and T2 is between the values dTonDHW ÷ dToffDHW the controller will calculate and set pump speed proportionally.
When dToffDHW is reached, the pump will work at minimal speed (Pmin), below it will be stopped.
After reaching preset temperature in priority circuit, the controller will switch the circuit.
The pool circuit will work analogically, except that the temperatures are calculated from T1 and
T3 and the system uses auxiliary deltas dTonPOOL ÷ dToffPOOL. Pool exchanger P2
pump is always switched on/off with delay as specified in tDLY setting in relation to P1 pump.
When the second circuit is heated up to preset temperature, the collector pump is stopped. It will be restarted, when on any circuit the temperature drops by hysteresis value (HP1), in accordance with priority setting.
If the collector temperature reaches TCOLcr value, the collector pump will be started and the circuit will be switched to priority one in order to reduce the collector temperature. It will be stopped, when T1 temperature drops below
T1<TCOLcr-HP1.
If Priority is set for DHW, the collector unloading will be continued only to the time when TDHWmax is reached, and then the system switches to the pool. In the pool circuit there is no upper limit for discharging collector’s critical temperature.
Switching between DHW/POOL is controlled through H output. The circuit operation starts only when the switching time elapsed (tVALVE).
Due to pool system, the scheme has no night cooling function.
List of settings in Adjustment menu TsDHW- Reservoir temperature preset TsPOOL- Pool temperature preset Priority- Priority setting: reservoir (DHW) or
pool (POOL) loading.
Alarm TCOLcr – Switching on (YES) or off (NO)
the alarm on exceeding TCOLcr temperature. This function will not affect the controller operation. If the parameter is set as NO the controller will not alarm when TCOLcr temperature is exceeded at the collector sensor.
13.8. Solar thermal scheme G
Loading of DHW reservoir with solar collector and boiler.
Fig. 13.7 Solar thermal scheme G
The collector pump will be started with 100% capacity, if the difference between T1 and T2 exceeds value of dTonDHW setting and it will be working for the time specified in parameter tP. If after this time the difference between T1 and T2 is still above dTonDHW, the pump speed will remain at 100%. If the said difference between T1 and T2 drops below dTonDHW, the controller will start reducing the pump speed, until the difference between T1 and T2 reaches the value specified as dToffDHW. If the difference between T1 and T2 is between the values dTonDHW ÷ dToffDHW, the controller will calculate and set the pump speed proportionally.
When dToffDHW is reached, the pump will work at minimal speed (Pmin), below it will be stopped.
If TsDHW temperature is reached for sensor: T2- reservoir loading from collector will be stopped; T3 reservoir loading from boiler will be stropped.
The reservoir loading will be restarted, when one of the temperatures T2 or T3 drops below hysteresis HP1 for T2 or HP2 for T3.
If the collector temperature T1 reaches the value of TCOLcr, then the collector pump will be started (despite of reaching TsDHW temperature). It is aimed to reduce the
collector’s temperature. It will be stopped, when
T1 drops below T1<TCOLcr-HP1, or if the reservoir temperature at T2 sensor reaches the value of TDHWmax.
List of settings in Adjustment menu
TsDHW- Reservoir temperature preset dTCO – Minimal temperature difference between
T4 and T3 that starts loading of DHW
reservoir from boiler circuit CH (starting P2 pump).
Night cooling- Yes enables/ NO disables night
cooling mode in hours 000÷500.
Night cooling ON – DHW reservoir temperature
(T2 sensor), when exceeded at 0
00
if night
Page 21
21
cooling function is enabled, the controller will decide on night cooling activation.
Night cooling OFF DHW reservoir
temperature (T2 sensor), to which the controller will be cooling down the reservoir (if night cooling function is enabled and if in hours 000÷5
00
Night cooling ON
temperature is exceeded).
Alarm TCOLcr – Switching on (YES) or off (NO) the alarm on exceeding TCOLcr temperature. This function will not affect the controller operation. If the parameter is set as NO, the controller will not alarm when TCOLcr temperature is exceeded at the collector sensor.
13.9. Solar thermal scheme H
Loading of DHW reservoir with two collector sets oriented toward two directions.
Fig. 13.8 Solar thermal scheme H
The collector pump P1 of collector A will be started at 100% capacity, if the difference between T1 and T2 exceeds the value of dTonDHW and it will be working for the time specified in parameter tP. If after this time the difference between T1 and T2 is still above dTonDHW, the pump speed will remain at 100%. If the said difference between T1 and T2 drops below dTonDHW, the controller will start reducing the pump speed, until the difference between T1 and T2 reaches the value specified as dToffDHW. If the difference between T1 and
T2 is between the values dTonDHW ÷ dToffDHW, the controller will calculate and set
the pump speed proportionally. When dToffDHW is reached, the pump will work at minimal speed (Pmin), below it will be stopped.
The collector pump P2 of collector B will be started at 100% capacity, if the difference between T3 and T2 exceeds the value of dTonDHW and it will be working for the time specified in parameter tP. If after this time the difference T3 and T2 is still above dTonDHW, the pump speed will remain at 100%. If the said difference between T3 and T2 drops below dTonDHW, the controller will start reducing the pump speed, until the difference between T3 and T2 reaches the value specified as dToffDHW. If the difference between T3 and T2 is between the values dTonDHW ÷ dToffDHW, the controller will calculate and set the pump speed proportionally. When dToffDHW is reached, the
pump will work at minimal speed (Pmin), below it will be stopped.
The system will work, until T2 sensor reaches TsDHW preset, then collector pumps P1 and P2 are stopped.
If T1 or T3 collector temperature reaches critical value (TCOLcr), then the controller will allow switching on pump P1 or P2 (depending which collector has critical temperature) in order to reduce the collector temperature below hysteresis HP1 for P1 and HP2 for P2. If the reservoir temperature at T2 sensor reaches the value of TDHWmax, the controller, despite of critical collector temperature (TCOLcr), will stop the collector pumps, disabling the collector cooling. It is to protect the reservoir from overheating. List of parameters in Adjustment menu
TsDHW- Reservoir temperature preset Night cooling- YES enables/ NO disables night
cooling mode in hours 000÷500.
Night cooling ON – DHW reservoir temperature
(T2 sensor), when exceeded at 0
00
if night cooling function is enabled, the controller will decide on night cooling activation.
Night cooling OFF DHW reservoir
temperature (T2 sensor), to which the controller will be cooling down the reservoir (if night cooling function is enabled and if in hours 000÷5
00
Night cooling ON
temperature is exceeded).
Alarm TCOLcr – Switching on (YES) or off (NO)
the alarm on exceeding TCOLcr temperature. This function will not affect the controller operation. If the parameter is set as NO the controller will not alarm after
TCOLcr is exceeded for the collector sensors T1 and T3.
13.10. Solar thermal scheme I
Loading of pool system.
Fig. 13.9 Solar thermal scheme I
The collector pump will be started with 100% capacity, if the difference between T1 and T2 exceeds the value of dTonPOOL and it will be working for the time specified in parameter tP. If after this time the difference between T1 and T2 is still above dTonPOOL, the pump speed will remain at 100%. If the said difference between
Page 22
22
T1 and T2 drops below dTonPOOL, the controller will start reducing the pump speed, until the difference between T1 and T2 reaches the value specified as dToffPOOL. If the difference between T1 and T2 is between the values dTonPOOL ÷ dToffPOOL, the controller will calculate and set pump speed proportionally. When dToffPOOL is reached, the pump will work at minimal speed (Pmin), below it will be stopped.
The system operates, until T2 sensors reaches preset temperature TsPOOL, and then the collector pump P1 is stopped.
If T1 temperature in collector reaches critical value (TCOLcr), then the controller will allow the collector pump to be started, in order to reduce the collector’s temperature below hysteresis HP1.
P2 pump operation depends on dTP2 setting. If the setting is other than OFF, pump P2 will be started, if the difference T1-T4<dTP2 between collector and exchanger is lower than dTP2 setting value.
At the setting value OFF, the pump P2 will be started after the time tDLY from the start of P1 pump.
Pool exchanger P2 pump will be always stopped after tDLY time, counting from the moment when the collector pump P1 is stopped.
List of parameters in Adjustment menu
TsPOOL- Pool temperature preset. Alarm TCOLcr – Switching on (YES) or off (NO) the alarm on exceeding TCOLcr temperature.
The controller’s operation is the same at both
settings. If the parameter is set as NO, the controller will not alarm after exceeding TCOLcr at the collector sensor.
13.11. Solar thermal scheme J
Loading of DHW reservoir from solar collector and from back-up source.
Fig. 13.10 Solar thermal scheme J
The collector pump will be started with 100% capacity, if the difference between T1 and T2 exceeds the value of dTonDHW and it will be working for the time specified in parameter tP. If after this time the difference between T1 and T2
is still above dTonDHW the pump speed will remain at 100%. If the said difference between T1 and T2 drops below dTonDHW, the controller will start reducing the pump speed, until the difference between T1 and T2 reaches the value specified as dToffDHW. If the difference between T1 and T2 is between the values dTonDHW ÷ dToffDHW, the controller will calculate and set pump speed proportionally.
When dToffDHW is reached, the pump will work at minimal speed (Pmin), below it will be stopped.
If TsDHW temperature is reached for sensor: T2- reservoir loading from collector will be stopped by the time when measured temperature at T2 is lower than TsDHW –HP1.
If T1 temperature in the collector reaches the value of TCOLcr, the collector pump will be started (despite of reaching TsDHW). It is aimed
to reduce the collector’s temperature. It will be
stopped, when T1 drops below TCOLcr-HP1. If TDHWmax is reached at T2 sensor, loading of
heat to the reservoir is disabled (even if TCOLcr has been reached). It is to protect the reservoir from overheating.
The controller will heat DHW reservoir from back-up source (P2 outlet) up to TDHWmin temperature at T3 sensor. When the temperature is reached, the controller will disable P2 output. It will re-enabled when T3 sensor temperature is lower than TDHWmin-HP2 Setting TDHWmin may be changed through main menu item TDHWmin as described in section.
List of parameters in Adjustment menu
TsDHW- Reservoir temperature preset Night cooling- YES enables/ NO disables night
cooling mode in hours 000÷500.
Night cooling ON – DHW reservoir temperature
(T2 sensor) when exceeded at 000, if night cooling function is enabled, the controller will decide on night cooling activation.
Night cooling OFF DHW reservoir
temperature (T2 sensor), to which the controller will be cooling down the reservoir (if night cooling function is enabled and if in hours 000÷5
00
Night cooling ON
temperature is exceeded). Alarm TCOLcr – Switching on (YES) or off (NO) the alarm on exceeding TCOLcr. This function will not affect the controller operation. If the parameter is set as NO, the controller will not alarm after exceeding TCOLcr for the collector sensor T1.
Page 23
23
13.12. Solar thermal scheme K
Loading A container-in-container type buffer with low-temperature CH system assist.
Fig. 13.11 Solar thermal scheme K
Collector pump will be activated with 100% power, when T1-T2 difference exceeds dTwlDHW value and will operate for tP parameter time. If after this time T1 and T2 is still higher than dTwlDHW, then the pump will still operate at the highest output. If the aforementioned difference falls below dTwlDHW value, the regulator will start to gradually decrease pump output, until the difference reaches dTwyDHW value. When T1 and T2 difference is between dTwlDHW ÷ dTwyDHW values, the regulator will measure and adjust the output in a proportional manner. When dTwyDHW value is reached, the pump operates at its minimum output (Pmin parameter). Any value below will cause it to stop.
If temperature difference dTAB (T3 and
T4 difference) between A buffer (T3 sensor) and CO system return (T4 sensor) is not reached, P2 output (a valve controlling return from
system) will redirect return water to buffer’s
center. If T3 temperature increases above T4+dTAB, three-way system valve will be
switched in buffer’s bottom direction, and K boiler will be powered by water from boiler’s
center. “Presets” menu parameters list
TzDHW – Preset container’s temperature A and
B.
dTAB- temperature difference between A buffer
and system return (on T3 and T4 sensors), after which the regulator switches three-way valve. P2 is enabled, when dTAB difference (between T3 and T4 temperatures) falls by auxiliary hysteresis AH2.
Night cooling YES enables / NO disables
night cooling mode between 000÷500 hours.
Cooling temp ON. DHW container
temperature (on T2 sensor), if exceeded, and night cooling is enabled, the regulator will begin the cool down at 0 AM.
Cooling temp. OFF DHW container
temperature (on T2 sensor) to which the
regulator will be cooling down the container (if night cooling function is enabled and Cooling temp. ON temperature is exceeded between 000÷500).
TCOLkr alarm – Enabling (YES) or disabling
(NO) of the alarm of exceeding TCOLkr temperature. This function does not influence
regulator’s operation. If the parameter is set
to NO, the regulator will not set off an alarm after exceeding TCOLkr collector’s temperature.
13.13. Solar thermal scheme L
DHW tank is loaded by two solar collector sets oriented towards two points of compass using one pump group and collector circuit separating valve.
Fig. 13.12 Solar thermal scheme L
Regulator selects the solar collector of higher temperature to operate. Solar collector serving pump is activated with 100% capacity once the difference of T1 or T3 (subject to the solar collector selected) and T2 has exceeded the value of dTonDHW. The pump will work over the time set in tP. P2 valve is set at the position appropriate to switch the system into selected solar collector. If, upon elapsing of this time, the difference of T1 or T3 and T2 is still in excess of dTonDHW value, the pump rpm value will remain set at 100% all the time. Once the difference between T1 or T3 and T2 has dropped below dTonDHW value, regulator starts reducing pump rotary speed until the difference of T1 or
T3 and T2 has reached the value set in dToffDHW. In case the difference of T1 or T3 and T2 falls within the range from dTonDHW to dToffDHW, the regulator computes and sets the
rpm value proportionally.
Once the difference of T1 or T3 and T2 has reached the value set in dToffDHW, the pump runs with minimum rpm value (Pmin parameter) and in case it has dropped below this value, the pump stops.
If, in case of operation with one solar collector, temperature of the second collector has grown above the temperature of the first one (or v.v.) and the value of dTonDHW has been reached, the regulator switches over the solar collector circuit.
Page 24
24
3sek.
Once the pump has stopped, P2 valve is set at “0” (power supply is cut off). The system operates until the temperature of water in DHW tank has reached the value set in TzCWU (read-out of T2 sensor), then it stops.
Once T1 or T3 temperature of solar collector has reached the critical value of TCOLkr, the regulator (despite the set temperature of TzCWU has been reached) allows to start P1 collector serving pump and to set P2 valve at the solar collector of higher temperature in order to reduce the temperature of the collectors below the value of HP1 hysteresis.
Once the temperature of DHW tank has reached the value of TCWUmax (read-out of T2 sensor), the regulator, in-spite of reached critical temperature of the collectors (TCOLkr), stops collector serving pumps to prevent collector cooling down. It protects DHW tank from overheating.
List of parameters available in „Settings” menu
TzCWU - set temperature of DHW tank. Night cooling – YES / NO - switches on/off
night cooling mode active from 0000÷ 0500.
Night cooling ON – temperature of DHW tank
(read-out of T2 sensor), upon excess of which, the regulator will activate night cooling mode at 0
00
(provided that night
cooling function is enabled).
Night cooling OFF – temperature of DHW tank
(read-out of T2 sensor) to which the regulator will cool down DHW tank (provided that night cooling function is enabled and temperature of Tschł WŁ has been exceeded within the period of time from 0000 to 05
00
).
Alarm TCOLkr – switches on (YES) or off (NO)
the "Temperature of TCOLkr exceeded" alarm. This function does not affect the regulator operation. Setting this parameter at "NO” causes the regulator will not produce the alarm of exceeded TCOLkr temperature for T1 and T3 solar collector sensors.
14. SHUT DOWN
Access
This option displays screen windows, where you can confirm that you want to shut down the unit. After confirmation the controller is switched off.
Fig. 14.1 Shut down screen
The controller may be also switched off in main screen by pressing the encoder for 3 seconds. Confirmation screen will be displayed like in Fig. 14.1 After confirmation the controller is switched off.
Page 25
25
15. ACCESS TO THE UNIT OVER THE
INTERNET
By using an additional module - ecoNET300, the unit enables remote access to its data over a Wi-fi or LAN network. The interface is operated
by an ordinary search engine installed in any stationary and mobile communication devices.
15.1. Basic data reading
Fig. 15.1 WWW interface –tiles
15.2. Diagram of active solar circuit system
Fig. 15.2 WWW interface- diagram
Pumps are stopped after switching off the controller.
Page 26
26
15.3. User parameters
Fig. 15.3 WWW interface – user parameters
15.4. Service parameters
Fig. 15.4 WWW interface - service parameters
Page 27
27
15.5. Heat yield graph
Fig. 15.5 WWW interface - heat yield graph
15.6. Network settings
Fig. 15.6 WWW interface - network settings screen
Page 28
Page 29
INSTALLATION MANUAL
PCSol 300
Page 30
30
16. TECHNICAL DATA
Measurement inputs (low-voltage)
Collector temperature input (T1)
Temperature input (T2)
Temperature input (T3)
Temperature input (T4)
Other inputs/outputs: (low-voltage)
Communication port RS485 High-voltage outputs:
Output (H) 5-6V/0,1A (DC)
Output P1: 230V/ max 0,5A (AC)
Output P2: 230V/ max 0,5A (AC)
Power supply:
Controller: 230V(AC), 50Hz. I=1.02A*
Load ability P1,P2:
not more than 0.5A(AC)/output
Operating conditions
0° ≤ Ta ≤ 40°C, humidity 10-90%, without condensation
Protection degree
IP 20
Weight
~280g
* Power intake only by controller is 0.02A, 1,5W
Table of temperature measurement accuracy:
Internal structure
Pt1000 class B (CT6 and CT6w)
Temperature ranges
-40÷0°C
Temperatur e ranges
-40÷0°C
Accuracy*
±2°C
Accuracy*
±2°C
Displayed range
T1 (T3**)
Displayed range
T2, T3, T4
* at ambient temperature of 23°C ** in scheme H
16.1. Elements of the set
*To use solar thermal scheme B, C, E, F it is required to
purchase one additional CT6 sensor. * To use solar thermal scheme D, G, K it is required to purchase two additional CT6 sensors * To use solar thermal scheme H, L it is required to purchase one additional CT6W sensor. *To use heat output function it is required one additional CT6 sensor (Note: does not apply to schemes D, G, K in which heat output is not counted).
17. INSTALLATION OF PCSol 300
The controller is designed for operation in the environment where only dry conductive contaminations may be present (2 degree of contamination according to PN-EN 60730-1).
In addition, the controller may not be used in water condensation conditions and it may not be exposed to water.
The unit software does not ensure required protection level that must be assured by external protections of the solar system.
17.1. Installation of the controller
The controller is designed for vertical wall­mounted installation. External circuit wires are supposed be lead on surface. Mounting hole locations are presented as in the casing. Hole spacing dimensions are presented also in Fig.
17.2
Wires that enter the controller must be secured at entry locations.
Before opening the unit casing, disconnect power supply. The unit installation must be done at disconnected voltage.
The unit has any fuse replaceable by the installer or use. If the fuse was burnt during installation or operation, it means damage of the unit. Send the unit to authorized service for repair.
Controller must be installed by qualified and authorized technichian in accordance with EN 60335-1 standard.
For how to open the unit casing see the picture below.
- Controller PCSol 300
- Temperature sensor T1 (CT6w)
- Temperature sensor T2÷T4 (CT6)*
- Operating and installation manual
1 pc. 1 pc. 1 pc. 1 pc.
Page 31
31
Fig. 17.1 Casing opening
Fig. 17.2 Controller on-wall mounting
The controller must be installed in a way that:
it is securely mounted on flat base, using all mounting points (3 in controller casing itself and 4 intermediate plate);
degree of protection is ensured suitably to environmental conditions;
dust and water access is prevented;
permissible operating temperature is not exceeded for the controller (40°C);
air exchange inside casing is allowed;
access to dangerous parts is disabled;
electrical installation, to which the controller is connected, must be equipped with the device that allows disconnection of both supply poles, in accordance regulations that applies to such systems.
Page 32
32
17.2. External circuits connection.
Fig. 17.3 Controller inside view with terminals
17.2.1. Use of connectors
The controller is provided with spring loaded terminals suitable for reception of wire with an end sleeve. The table below includes permissible size ranges for wires connected to the controller terminals:
Circuit type
Wire cross-section
Power supply circuits
0.75÷1mm2*
Low-voltage circuits
0,25÷0,75mm2
* For installations with bare wire cables the maximal size is
1.5mm
2
For good connection between the terminal and cable, insulation and sleeve free length should be in the range of 8÷10mm.
To place wire in terminal press the terminal push with a flat screwdriver, insert the wire end (with a sleeve on) and then release the push.
Fig. 17.4 Using clamped terminals
Supply L
Supply N
Pump P1 [L]
Pump P1 [N]
Pump P2 [L]
Pump P2 [N]
Output H [+]
Output H [-]
Sensor T1 [+]
Sensor T1 [-]
Sensor T2 [+]
Sensor T2 [-]
Sensor T3 [+]
Sensor T3 [-]
Sensor T4 [+]
Sensor T4 [-]
Page 33
33
17.2.2. Power supply connection
The controller is designed for supply voltage 230V~, 50Hz. Supply is connected to terminals L, N. Electric connection diagram is presented in Fig. 17.5. and Fig. 17.6.
230V supply wires must be lead so as their contact with sensor and other low-voltage cabling is prevented, additionally, all cables may not contact surfaces with temperatures that exceed the cables operating temperature limits.
The controller has no PE protective connector, because the controller itself does not require grounding. PE terminals of the pump shall be connected with PE of supply network, according to periphery instructions and regulation concerning electric systems. Proper electric installation method is responsibility of the electrician. It is recommended to connect PE circuits through external screw connector, as presented in diagrams.
Fig. 17.5 Power supply connection
Fig. 17.6 Connection of pumps
Pump P2 is connected analogically as pump P1.
Fig. 17.7 Electro-valve connection
The connection shown in fig. 17.7 requires electro-valve coil adjusted to ~230 voltage.
17.2.3. Temperature sensor connection
Sensors are provided with two wires:
CT6w 1m long, silica wire; CT6 2m long.
If you need longer cables, use 0.5÷1.5mm2 cable
not longer than 30 meters, and connection points must secured against short circuit and humidity. Take a note that when extending the line with additional wire the sensor circuit resistance increases and it may cause errors in measurement. Such errors may be adjusted by the wire length compensation function described in menu I/O Configuration. Compensation method is described in section 20.2.1.
CT6w sensor is provided with special high-temperature silica cables, it must not be replaced with CT6 sensor, because of possible insulation damage when the collector temperature is high.
Supply L
Supply N
Supply N
Supply L
Pump P1 [L]
Pump P1 [N]
Pump P2 [L]
Pump P2 [N]
Scheme L
Supply
Supply
Supply L
Supply N
Pump P1 [L]
Pump P1 [N]
Pump P2 [L]
Pump P2 [N]
Page 34
34
Table of sensor resistance against temperature:
temperature
resistance
-25 ºC
-20 ºC
-10 ºC
0 ºC 10 ºC 20 ºC 25 ºC 30 ºC 40 ºC 50 ºC 60 ºC 70 ºC 80 ºC 90 ºC
100 ºC 110 ºC 120 ºC 130 ºC 140 ºC 150 ºC 160 ºC 170 ºC
901,9 Ω 921,6 Ω
960,9 Ω 1000,0 Ω 1039,0 Ω 1077,9 Ω 1097,3 Ω 1116,7 Ω 1155,4 Ω 1194,0 Ω 1232,4 Ω 1270,7 Ω 1309,0 Ω 1347,1 Ω 1385,0 Ω 1422,9 Ω 1460,7 Ω 1498,3 Ω 1535,8 Ω 1573,2 Ω 1610,5 Ω 1647,7 Ω
Fig. 17.8 Connection of temperature sensors*
*Sensor’s function may differ from the drawing
depending on selected scheme
17.2.4. Temperature sensor installation
Temperature sensors are equipped with brass coat with diameter of 6mm and 50mm long. They should be installed possibly close to the temperature measurement point. The sensors must be installed so that the brass coat is thermally insulated from the environment.
The collector temperature sensor must be located in the collector tube possibly deep, as this is conditional for correct measurement.
If you need mount your sensor on pipe surface (e.g. CH temp. measurement), then the sensor coat must be attached using a brace,
and the jointing point to insulate e.g. with foam or other insulating material, so that there is sufficient temperature convection to the sensor.
Fig. 17.9 Sensor installation on pipe surface
17.2.5. Output H connection
Output H is adapted to connect relay supplied
with voltage of 5…6V
(with coil resistance not lower than 60Ω) and power up to 0.5W.
Heater
For a heater connection, use relay connected as shown in Fig. 17.10. Wire that connects the controller and transmitter must not have resistance bigger than 1Ω (see Table of wire lengths and resistances in the section on wire length compensation 20.2.1).
The reservoir heater must be connected through a relay with maximal contact current not lower than the heater’s nominal current. Recommended relay type is Finder
44.62.7.006.0000 that has load ability of 2x10A. It is suitable for heater control
(resistance loads) with power up to 2.5k VA. The relay together with a base is available as accessories. If you choose to use other relay, check its technical parameters and if it meets safety standards.
Current received by a receiver may not be higher than nominal current of the relay load. Otherwise, it may be damaged and in extreme case it may cause damage to solar or heating system.
Sensor T1 [+]
Sensor T1 [-]
Sensor T2 [+]
Sensor T2 [-]
Sensor T3 [+]
Sensor T3 [-]
Sensor T4 [+]
Sensor T4 [-]
Insulating material
Pipe
Brace
Page 35
35
Fig. 17.10 Connection of relay to H output.
Three-way switching valve
The output may be used for a three-way switching valve that is controlled:
1. Unipolarly with return spring: such
valve connect to H output of the controller through a relay, like in Fig. 17.10
2. Bipolarly, right-left rotations (3-wire control): Neutral conductor is connected
directly to the valve, while wires that control direction of rotations are connected via a relay and its contacts to relevant terminals. Status relations on H outlet and respective direction of the valve switching are presented in application schemes. Change of rotation direction switching will cause incorrect operation of the unit.
Fig. 17.11 Connection of three-way, bipolarly controlled
valve to H output
If the valve has grounding terminal, connect it directly to the valve.
Connection of other valve types than specified above may lead to undesired operation and is not recommended.
Supply
Receiver
Output H [+]
Output H [-]
Supply 230~
Output H [+]
Output H [-]
Page 36
36
17.2.1. ecoNET internet module connection
ecoNET300 module can be connected to the Internet in two ways:
over Wi-fi to the local access point, directly through Ethernet cable for LAN network.
The most convenient way of connection is recommended. Both ways offer the same operation
functions of the controller.
Fig. 17.12 Internet connection structure
PCSol300
Page 37
37
18. APPLICATION SCHEMES
18.1. Solar Application scheme A
Loading of DHW reservoir from collector.
Fig. 18.1 Schemat aplikacyjny A
Installation notes
1. For the controller to count heat output, install additional CT6 sensor on the outlet of lower pipe coil
from DHW reservoir and connect to T4 input (or T3 for Basic). The sensor must be installed possibly near the connector pipe.
2. T3 sensor shows temperature in upper part of the reservoir, its connection is not required. In
Basic version it is used only for heat output counting.
Page 38
38
18.2. Solar Application scheme B
Loading of DHW reservoir from solar panel with additional function of extra heating with a heater,
when the solar panel stops supplying energy and with control of DHW circuit with circulation pump.
In this layout, it is required to connect T3 sensor and it must be installed in the reservoir over a heater. If T3 is disconnected from the controller or damaged, it will disable reservoir extra heating function. How to connect H output to a heater via a relay is presented in details in section 17.2.5.
Fig. 18.2 Application scheme B
Installation notes
1. For the controller to count heat output, install additional CT6 sensor on the outlet of lower pipe coil
from DHW reservoir and connect to T4 input. The sensor must be installed possibly near the connector pipe.
2. T3 sensor is used for controlling additional heat source (H output). Disconnection of the sensor will
disable H output and the algorithm of the reservoir loading from collector will work normally.
Page 39
39
18.3. Solar Application scheme C
Loading of DHW reservoir from a solar panel with additional function of heat discharge to drain system, when the reservoir maximal temperature (TDHWmax) is exceeded.
In this layout, T3 sensor is optional and its connection is not required.
Electro-valve must be connected to P2 pump outlet.
Fig. 18.3 Application scheme C
Installation notes
1. For the controller to count heat output, install additional CT6 sensor on the outlet of lower pipe coil
from DHW reservoir and connect to T4 input. The sensor must be installed possibly near the connector pipe.
2. T3 sensor shows temperature in upper part of the reservoir, its connection is not required.
3. Circulation pump is connected to H output through a relay with contact current not lower than the
current of the circulation pump. It is recommended to use relays with two switching tracks, see details in section 17.2.5 Output H output.
4. Discharge valve coil connected to P2 output must by adjusted to ~230 voltage, see fig. Fig. 18.3,
otherwise the valve should be controlled indirectly by an additional transmitter.
Setting notes
1. Heat discharge valve works until T2 drops below TDHWmax-HP2. Do not set HP2 value too high
as this result in large heat discharges.
Page 40
40
18.4. Solar Application scheme D
Loading of DHW reservoir from a solar panel and transfer of accumulated heat to the reservoir B.
Fig. 18.4 Application scheme D
Installation notes
1. This scheme requires two additional CT6 sensors.
2. Circulation pump is connected to H output through a relay with contact current not lower than the
current of the circulation pump. It is recommended to use relays with two switching tracks, see details in section 17.2.5 Output H.
Setting notes
1. Do not set HP2 value higher or equal to dTAB, because this will prevent loading stop when dTAB
value is reached.
2. With respect to night cooling mode used for the reservoir A and circulation activation for better
discharge of the container, it is recommended that circulation circuit is installed in the reservoir A.
Page 41
41
18.5. Solar Application scheme E
Loading of two DHW reservoirs (A and B) with loading priority for reservoir A.
Fig. 18.5 Application scheme E
Installation notes
1. For the controller to count heat output, it is required to install additional CT6 sensor outside
circuits of pumps P1 and P2 and connect it to T4 input. The sensor should be installed possibly close to the P1 and P2 pump outlet.
2. Circulation pump is connected to H output through a relay with contact current not lower than the
current of the circulation pump. It is recommended to use relays with two switching tracks, see details in section 17.2.5 Output H.
3. In the diagram the circulation pump is located on B tank, but its operation is not related with the
algorithm and it may be installed on A tank as well.
4. With respect to night cooling mode used for the reservoir A and circulation activation for better
discharge of the container, it is recommended that circulation circuit is installed in the reservoir A.
Page 42
42
18.6. Solar Application scheme F
Heating of DHW reservoir and pool with Priority function.
Fig. 18.6 Application scheme F
Installation notes
1. For the controller to count heat output, install additional CT6 sensor outside circuits of three-way
valve H and connect it to T4 input. The sensor should be installed possibly close to the H outlet.
2. The valve should be connected so that the controlled relay connected to output H (H=ON) set will
set the valve in pool loading position. Reverted connection will damage the system.
Setting notes
1. If the used three-way valve has switching time longer than 120sec, set maximal value for tVALVE.
2. If the used three-way valve has near zero switching time, set minimal value for tVALVE
3. When the circuits are being switched (tVALVE time) the collector pump is not working and the
circuit receives no heat. Pay attention to collector heat up time and if required set shorter tVALVE time.
4. During anti-freeze function, the exchanger pump will work longer than the collector pump by
double tDLY time. So select this parameter value that after P2 is stopped, the temperature of glycol in exchanger is not lower than 0°C, as it may damage the exchanger. If there is a risk that such situation may happen, switch off antifreeze function for the pool system.
Antifreeze function in pool circuit (with priority) may be used only at high awareness. Wrong settings or unfavorable conditions may damage the exchanger. Always consider all factors like, e.g., solar work fluid with below-zero temperature in the exchanger.
Page 43
43
18.7. Solar Application scheme G
Loading of DHW reservoir with solar collector and boiler.
Fig. 18.7 Application scheme G
Installation notes
1. Circulation pump is connected to H output through a relay with contact current not lower than the
current of the circulation pump. It is recommended to use relays with two switching tracks, see details in section 17.2.5 Output H.
Page 44
44
18.8. Solar Application scheme H
Loading of DHW reservoir from two sets of solar collectors oriented in two directions.
Fig. 18.8 Application scheme H
Installation notes
1. For correct operation the system must be equipped with return valves mounted on the solar panel
outlets. In other case, starting circuit of A collector will affect operation of B collector sensor, causing poor performance.
2. For the controller to count heat output, install additional CT6 sensor on DHW reservoir lower pipe
coil and connect it to T4 input. The sensor must be installed possibly near the connector pipe.
3. Circulation pump is connected to H output through a relay with contact current not lower than the
current of the circulation pump. It is recommended to use relays with two switching tracks, see details in section 17.2.5 Output H.
Setting notes
1. With the use of additional sensor T4, the controller allows effective controlling of P2 pump that will
be started, when the temperature of return from exchanger reaches dTP2 value.
Page 45
45
18.9. Solar Application scheme I
Loading of pool system from solar collector.
Fig. 18.9 Application scheme I
Installation notes
1. For the controller to count heat output, it is required to install additional CT6 sensor directly on the
return from the pool exchange, and connect it to T4 measurement input.
Setting notes
1. With the use of additional T4 sensor, the controller allows effective controlling of P2 pump that will
be started, when the temperature of return from exchanger reaches dTP2 value.
2. At long pipe lengths (between collector and exchanger), setting of dTP2 value lower than it results
from losses incurred in the collector-exchanger section will prevent starting of P2 pump, even at high temperatures in the collector. This setting must be selected specifically to each installation.
3. During anti-freeze function, the exchanger pump will work longer than the collector pump by
double tDLY time. So select this parameter value that after P2 is stopped, the temperature of glycol in exchanger is not lower than 0°C, as it may damage the exchanger. If there is a risk that such situation may happen, switch off antifreeze function for the pool system.
Antifreeze function in pool circuit (with priority) may be used only at high awareness. Wrong settings or unfavorable conditions may damage the exchanger. Always consider all factors like, e.g., solar work fluid with below-zero temperature in the exchanger.
Page 46
46
18.10. Solar Application scheme J
Collector operation with additional back-up source.
Fig. 18.10 Application scheme J
Installation notes:
1. For the controller to count heat output, it is required to install additional CT6 sensor directly on the
return from the DHW reservoir lower pipe coil and connect it to T4 measurement input.
2. Circulation pump is connected to H output through a relay with contact current not lower than the
current of the circulation pump. It is recommended to use relays with two switching tracks, see details in section 17.2.5 Output H.
Page 47
47
18.11. Solar Application scheme K
Charging A Buffet with a solar panel. „Container-in-container” type buffer. The regulator supports CH system.
Fig. 18.11 Application scheme K
*Pumps marked in the scheme as P are not controlled by BLUESol 02 regulator. Installation instructions
1. Two additional CT6 sensors are required for the application schema.
2. Connect the circulation pump to H output via a transmitter with connector voltage not lower than
circulation pump voltage. It is recommended to use transmitters with two switching circuits. Details can be found in chapter 17.2.5 Connecting H output.
Setting notes
1. Do not set HP2 value higher or equal to dTAB, because this will prevent loading stop when dTAB
value is reached.
Page 48
48
18.12. Aplikacja schemat solarny L
DHW tank is loaded by two solar collector sets oriented towards two points of compass using one pump group and collector circuit switching valve.
Fig. 18.12 Application scheme L
Installation notes
1. 3-way/1-way control valve was considered in this diagram. Valve is switched back by means of a
spring. Other valves may be controlled using relays as shown in Fig. 17.11
2. The valve should be so installed that high state of P2 output sets the flow in direction of A-solar
collector.
3. The valve may be connected to solar collector supply. . Valve way is as shown in
item 2.
4. To enable calculation of heat yield by the regulator: install additional CT6-type sensor at the outlet
of lower pipe coil from DHW tank and connect it to T4 input. The sensor should be mounted as close as possible to the outlet of pipe coil from DHW tank.
5. Connect circulating pump to H-output through relay of contact current not less than the current of
the pump. It is recommended to use relays with two switching channels – for details see section
17.2.5 Output H.
6. Setting recommendations
7. During interim periods, when sunlight falls on both solar collectors and the collector currently not
in use becomes overheated, reduce the set tOP time.
Mains 230V~
Supply L
Supply N
Pump P1 [L]
Pump P1 [N]
Pump P2 [L]
Pump P2 [N]
Output H [+]
Output H [-]
Sensor T1 [-]
Sensor T1 [+]
Sensor T2 [+]
Sensor T2 [-]
Sensor T3 [+]
Sensor T3 [-]
Sensor T4 [+]
Sensor T4 [-]
Page 49
49
19. CASING CLOSING
To close the unit casing hook the casing cover with recesses against the base insets (shown in Fig. 19.1)
Fig. 19.1 Casing closing first step
Then, press the cover in place indicated by red arrow (Fig. 19.2), until you clearly hear the latch click.
Fig. 19.2 Casing closing second step
20. CONTROLLER OPTIONS
Access
Access to the controller options is protected with password and to make any changes you must log-in with a service password.
Fig. 20.1 User login screen
To login place cursor in selected digit by its rotating, then press the button. When the digit is blinking, rotate the encoder to change its value. Confirm the digit by pressing again. Edition will move the cursor to next position. Confirm login by using “OK" or abandon login by using CANCEL” option. If the password is wrong, the unit will display a message Fig. 20.2.
Fig. 20.2 Information on incorrect password
Repeat login procedure.
Settings should be modified only by trained persons with adequate technical skills. Wrong parameters may cause irregular performance or damage to the equipment.
Page 50
50
20.1. System Options\Settings
The following settings are available
depending on scheme and version:
Setting
PCSol 300
A B C D E F G H I J K
L
dTonDHW
X X X X X X X X X X
X
dToffDHW
X X X X X X X X X X
X
dTonPOOL
X X
dToffPOOL
X X
TCOLmin
X X X X X X X X X X X
X
TCOLcr
X X X X X X X X X X X
X
TCOLmax
X X X X X X X X X X X
X
TDHWmax
X X X X X X X X X X
X
Pmin
X X X X X X X X X X X
X
tP
X X X X X X X X X X X
X
HP1
X X X X X X X X X X X
X
HP2
X X X X X X X X X X X
tVALVE
X
tDLY
X X
X
TCOmin
X
dTP2
X
Settings description
dTonDHW - temperature difference between T1
(T3 in scheme H) and T2 (T3 in scheme E) that will the collector pump P1 or P2 at 100% capacity.
dToffDHW - temperature difference between T1
(T3 in scheme H) and T2 (T3 in scheme E), at which the pump will work with minimal capacity Pmin. Below this value, the collector pump is stopped. It will be restated when dTonDHW value is reached.
dTonPOOL – in schemes with pool system,
temperature difference between T1 and T3 (for scheme F) and T1 and T2 (for scheme
I), which starts P1 pump at 100% capacity.
dToffPOOL - temperature difference between T1
and T3 (for scheme F) and T1 and T2 (for scheme I), at which the pump will work with minimal capacity Pmin. Below this value, the collector pump is stopped. It will be restated when dTonPOOL value is reached.
TCOLmin - minimal collector temperature, which
must be reached to allow reservoir loading. If the collector temperature has not reached this setting value, despite that loading conditions are met (resulting e.g. from reaching dTon) the controller would not start the collector pump.
The collector pump will be started only below
dToffDHW or dToffPOOL (depending on scheme).
TCOLcr collector critical temperature.
Temperature which regardless of reaching reservoir preset (TsDHW) or pool preset (TsPOOL) will start the collector pump at 100% capacity in order to discharge heat from the collector. It will be stopped when the collector temperature drops below TCOLcr-HPx (where x means the number of collector pump: 1 or 2). If AlarmTCOLcr setting has YES value, the unit displays alarm on exceeding critical collector temperature. This alarm allows starting collector pump, only when the system with DHW reservoir is not in condition of exceeded reservoir maximal temperature
TDHWmax alarm.
TCOLmax – reaching this collector temperature
will stop the collector pump. The controller reports alarm. The collector pump may be started only when the collector temperature drops below the temperature difference TCOLmax-HPx.
The controller dynamically limits minimal value of TCOLmax setting and maximal value of TCOLcr setting, so that set values give interval between TCOLcr and TCOLmax not lesser than 30°C. This protects from impulse increase of the collector temperature when the collector pump is started, after TCOLcr is reached. To set higher TCOLcr than allowed by the controller, increase TCOLmax value, so that the interval condition of 30°C is maintained.
- DHW reservoir maximal temperature that stops
collector pump and disables further loading of the reservoir. Alarm on exceeding DHW reservoir maximum temperature is displayed. This alarm has higher priority than alarm on TCOLcr and despite the alarm on collector critical temperature; the controller will disable starting the collector pump for the reservoir. Alarm will be stopped and the pump start released, when the reservoir temperature drops below TDHWmax-HPx.
Pmin – minimal capacity of the collector pump
reached if the difference between collector and reservoir temperatures drops to dToffDHW or dToffPOOL value (depending on scheme).
Page 51
51
tP Minimal time of the collector pump work. If
the difference between collector and reservoir temperatures drops to dTon, the collector pump will be started for the time of
tP. HP1- auxiliary hysteresis for P1 output. HP2 - auxiliary hysteresis for P2 output.
Too high values of HP1, HP2 settings may lead to large temperature oscillations in the system, so it is recommended to leave them at the level of 1°C.
tVALVE – minimal operation time of the
controller’s valve that switches the circuits
(used in solar application F). tDLY – time of delay for switching on/off the
pump downstream heat exchanger. TCOmin – minimal temperature in CH circuit
(measured by T4 sensor) in scheme G,
which allows loading of DHW reservoir from
the boiler system. Below this temperature
(even if there are conditions for reservoir
loading, i.e. TsDHW is lower than preset or
dTCO is reached), the controller will disable
the reservoir loading. This prevents CH
circuit operation below the boiler’s dew point. dTP2 – temperature difference between T1
collector and T4 exchanger, if reached the
controller will start exchanger pump in
scheme I. Operation with tDLY is also
possible, then dTP2 setting must set as
OFF. At such setting, the controller will run
P2 operational algorithm with delay of tDLY
in relation to P1 pump operation. Alarm from
T4 sensor will not be reported.
20.2. I\O Options\Configuration
Depending on the length of sensor extension cable, sensors will show temperature without taking into account resistance of connection lines. To compensate cable effects, it is required to perform sensor compensation procedure.
20.2.1. Wire length compensation
It consists in measurement of wires connected to a sensor (measurement track), reading value from the compensation table for connecting wire resistance, and programming this value in the controller. The controller will automatically move sensor’s characteristics to compensate the effect of additional resistance.
When you enter menu, the controller displays current values of temperature corrections. If the controller displays 0.0, it means that no correction has been introduced for given track.
To clear any compensation data for the track, enter 0.0 value.
The procedure may be conducted using ohmmeter to measure resistance of both cable conductors and selecting from the table respective value for measured resistance. If received result indicates correction above 2°C, it may means that the cable have resistance bigger than permissible or that they are too long.
Table of cable lengths and resistance.
size length
0,5mm2
0,75mm2
1mm2
5m
0,35Ω
0,1°C
0,23Ω
0,1°C
0,18Ω
0,1°C
10m
0,69Ω
0,2°C
0,46Ω
0,2°C
0,35Ω
0,1°C
15m
1,04Ω
0,3°C
0,69Ω
0,2°C
0,52Ω
0,2°C
20m
1,38Ω
0,4°C
0,92Ω
0,3°C
0,69Ω
0,2°C
25m
1,73Ω
0,5°C
1,15Ω
0,3°C
0,87Ω
0,3°C
30m
2,07Ω
0,6°C
1,38Ω
0,4°C
1,04 Ω
0,3°C
20.3. Options\Functions
Depending on scheme and version, the following settings are available in the Functions menu:
Setting
Scheme
A B C D E F G H I J K
L
Antifreeze
X X X X X X X X X X X
X
Work fluid
X X X X X X X X X X X
X
Flow P1
X X X X X X X X X X X
X
Flow P2
X
Vac. collector
X X X X X X X X X X X
X
Detect. level
X X X X X X X X X X X
X
Operation time
X X X X X X X X X X X
X
Antifreeze – setting ON enables the antifreeze
function. The collector pump will be started, if the solar work fluid temperature drops to the freezing value set for the work fluid. For correct operation of this function, it is required to select suitable solar work fluid. Collector pump will be stopped, if the work
fluid temperature rises by 2°C. When the
function is off, the controller will not monitor antifreeze and it may lead to damage of the solar system in winter period, so it is recommended that it remains on. In scheme E, antifreeze function operates in the circuit of reservoir A, in scheme F the function operates in priority circuit. If in the system with DHW reservoir the reservoir
temperature drops down to 2°C, the
Page 52
52
controller will alarm that it is not possible to continue antifreeze function.
Work fluid – type of fluid used in the system.
Correct setting is required for good performance of antifreeze function and heat output counting.
No.
Name
Freezing temperature
1
Ergolid EKO -15°C
-15°C
2
Ergolid EKO -20°C
-20°C
3
Ergolid EKO -25°C
-25°C
4
Ergolid EKO -35°C
-35°C
5
Ergolid A -15°C
-15°C
6
Ergolid A -20°C
-20°C
7
Ergolid A -25°C
-25°C
8
Ergolid A -35°C
-35°C
9
Tyfocor LS
-20°C
10
ECO MPG-SOL 20
-20°C
11
ECO MPG-SOL 28
-28°C
12
ECO MPG-SOL 32
-32°C
13
Henock 35P35
-35°C
Flow P1 – flow calibration function required for
correct heat output function. Rotometer or water meter must be installed in the sole work fluid circuit. When edition is open (value is blinking), the collector pump P1 will be controlled for maximum capacity. Now, read flow value directly from a rotometer or measure (using water meter) how many liters of work fluid will flow for one minute and program the value to the controller. Correct flow value is needed to correctly count heat output by the controller.
Flow P2 P2 pump calibration function for solar
scheme H. To calibrate solar work fluid circulation speed, it is required to have rotometer or water meter installed. When edition is open (value is blinking), the collector pump P2 will be controlled for maximum capacity. Correct flow value is needed to correctly count heat output by the controller. Flow calibration P2 is available only in Solar thermal scheme H.
For correct heat output counting in scheme H, calibration for both pumps is required.
Vac. collector – vacuum collector function
on/off. The function principle of operation is described in section 20.3.1.
Detect. level – setting that defines how much
the collector temperature must rise (at started vacuum collector function) in one minute, to activate the collector pump.
Operation time time to stop the collector
pump, after the temperature set in Dect. level is reached.
20.3.1. Vacuum collector function
Settings needed for the vacuum collector function are described previous section.
The vacuum collector function (when enabled) checks the collector temperature and starts the collector pump, if after one minute the collector temperature will increase by level set in Detection level; the collector pump will be started for the time set for Operation time. After this short impulse, unless normal conditions for starting collector pump occur, the controller
will continue checking the collector’s
temperature.
The vacuum collector function is disabled, if
the collector temperature is below 0°C and there
are alarm active that block the collector pump operation.
20.4. Manual mode
Manual mode allows manual controlling for
outputs: P1, P2, H.
Outputs are controlled directly after the
setting value edition is confirmed.
From this menu the controller will not return
to main screen automatically.
After you leave manual mode, the controller returns to output controlling in accordance with operating algorithm.
In the manual mode all automatic actions are stopped. Leaving the controller in this mode for longer time may damage the system
20.5. Scheme wizard
Scheme wizard is to select type of installation. It is done by turning the knob to browse through schemes. Number and type of schemes depend on the controller version.
After selection, the controller will request
to confirm the scheme.
Page 53
53
21. FUSE REPLACEMENT
Cut off power supply to the controller before fuse replacement.
A 1.25A time-delay subminiature fuse with minimum interrupting current of 100A should be used, as per IEC 60127 standard. An example of a fuse meeting the requirements is Schurter MXT-250 time-delay fuse. To replace, open controller's enclosure and replace burnt fuse with a new one (Fig. 21.1).
Fig. 21.1 Fuse replacement
Record of changes
3.X.1 z dn 9-06-2014 First edition
The manufacturer reserves the right to make changes in design and software without prior notice.
Page 54
Page 55
Page 56
SALUS Controls
ul. Bielska 4a, 43-200
Pszczyna , Poland
Loading...