SAF OPAL LT User Manual

Opal LT
Series
RVS-AX Analogue Soft Starter
8-170A, 220V-600V
Manufactured By SOLCON
Supplied By
R
R
V
V
S--
S
A
A
X
X
AAnnaalloogguuee SSoofftt SSttaarrtteerr 88--117700AA,, 222200--660000V
Innssttrruuccttiioonn
I

Ver. 3.2.04

V
Maannuuaall
M
1
Table of Contents

Page Subject

3 Starter Selection 4 Installation Notes 5 Wiring 6 Starter Settings 7 Motor Protection 8 Start-up Procedure 9 Technical Specification 10 Dimensions
Safety
Read this manual carefully before operating the equipment and follow its instructions.
Installation, operation and maintenance should be in strict accordance with this
manual, national codes and good practice. Installation or operation not performed in strict accordance with these instructions will void manufacturer's warranty.
Disconnect all power inputs before servicing the soft-starter and/or the motor.
After installation, check and verify that no parts (bolts, washers, etc) have fallen into
the starter.
Attention
1. This product was designed and tested for compliance with IEC947-4-2 for class A equipment.
2. Use of the product in domestic environments may cause radio interference, in which case the user may
be required to employ additional mitigation methods.
3. Utilization category is AC-53a or AC53b. Form1.
4. For further information, see Technical Specification.
Warnings
Internal components and P.C.B's are at Mains potential when the RVS-AX is
connected to mains. This voltage is extremely dangerous and may cause death or severe injury if contacted.
When RVS-AX is connected to Mains, even if start signal has not been issued, full
voltage may appear on motor's terminals. Therefore, for isolation purposes it is required to connect an isolating device (C/B, switch, line contactor, etc) upstream to the RVS-AX.
Starter must be properly grounded to ensure correct operation and safety.
Check that Power Factor capacitors are not connected to the output side of the soft
starter
The company reserves the right to make any improvements or modifications to its products without prior notice.
2
Starter Selection
The RVS-AX electronic soft starter incorporates six thyristors to start a three-phase squirrel cage induction motor. By supplying a slowly increasing voltage, it provides soft start and smooth stepless acceleration, while drawing the minimum current necessary to start the motor.
A Soft Stop feature can be enabled when the Ramp­Down potentiometer is adjusted. When used, upon stop signal (open contact terminals 1 and 2), motor's voltage is slowly reduced to zero.

Soft-Start Characteristics

I%U%
100
50
10
400
100
CurrentVoltage

Soft-Stop Characteristics

100
U%
The Soft-Stop characteristic may be used for controlled
50
deceleration of pumps and high friction loads.
10
Voltage

RVS-AX ratings and Frame sizes

Max. Motor FLA (Amp)
Starter Type FLC (Amp.)
8 RVS-AX 8 17 RVS-AX 17 31 RVS-AX 31 44 RVS-AX 44 58 RVS-AX 58 72 RVS-AX 72 85 RVS-AX 85
105 RVS-AX 105 145 RVS-AX 145 170 RVS-AX 170
Dimensions (mm) & Weights (Kg)
Size Width Height Depth Weights (Kg)
A1 120 232 105 A2 129 275 185 A3 129 380 185 A4 172 380 195
M%
100
Torque
Frame Size
(Aluminum)
A1
A2
A3
A4
2.6 5
8.4
11.8
The starter should be selected in accordance with the following criteria:
1. Motor Current & Starting Conditions
Select the starter according to motor's Full Load Ampere (FLA) - as indicated on its nameplate (even if the motor will not be fully loaded). The RVS-AX is designed to operate under the following maximum conditions:
Ambient
Temp.
40° C
I start Acc. Time
300% In 30 Sec 350% In 20 Sec 400% In 5 Sec
Max. Starts per Hour: four (4) starts per hour at
maximum ratings and up to 10 starts per hour at light load applications (consult factory).
: For very frequent starts (inching applications)
Note
the inching current should be considered as the Full Load Current (FLC) – consult factory.
2. Mains Voltage
Each starter is factory set for one of the following levels according to the Ordering Information.
Voltage Tolerance
380 - 415 V +10 -15 %
440 V +10 -15 %
460 - 500 V * +10 -15 %
575 - 600 V +10 -15 %
Frequency: 50 / 60 Hz.
* Starter’s rated 460-500VAC can be field modified
for system voltage of 220-240V, by placing the internal Jumper J3 as shown below.
220 to 240V 460 to 500V
WVU
123
J3
123123
3
Installation Notes
Prior to Installation
Check that Motor's Full Load Ampere (FLA) is lower than or equal to starters Full Load Current (FLC) and that Mains voltage is as indicated on the front panel.
Mounting
The starter must be mounted vertically. Allow
sufficient space above and below the starter for suitable airflow.
It is recommended to mount the starter directly on
the rear metal plate of the switchgear for better heat dissipation.
Do not mount the starter near heat sources.
Protect the starter from dust and corrosive
atmospheres.
Temperature Range and Heat Dissipation
The starter is rated to operate over a temperature range of –10
ºC (14ºF) to +40ºC (104ºF).
Relative non-condensed humidity inside the enclosure should not exceed 93%. The heat dissipation during continuous operation is Approx. 0.4 x In (in watts).
Example: When motor's current is 100 Amp, heat
dissipation will be approx. 40 watts. Internal enclosure heating can be reduced using additional ventilation.

Additional Ventilation

RVS-AX
General purpose enclosure with filter on the air inlet and Fan on air outlet.
RVS-AX
Fan, creating air circulation
Voltage Spike Protection
Voltage spikes can cause malfunction of the starter and damage the SCRs. When expected, use suitable protection such as Metal Oxide Varistors (consult factory for further details).
Short Circuit Protection
The RVS-AX should be protected against a short circuit by Thyristor Protection fuses. The recommended I
2
t values are:
RVS-AX type I²t (A²S) Ferraz Fuses RVS-AX 8 400 6,6 URS 35 RVS-AX 17 2,000 6,6 URS 45 RVS-AX 31 3,000 6,6 URS 63 RVS-AX 44 6,000 6,6 URB 100 RVS-AX 58 12,000 6,6 URB 150 RVS-AX 72 18,000 6,6 URB 160 RVS-AX 85 40,000 6,6 URD 200 RVS-AX 105 60,000 6,6 URD 250 RVS-AX 145 100,000 6,6 URD 355 RVS-AX 170 140,000 6,6 URD 400
Caution
Power factor correction capacitors must not be installed on starter's Load side. When required, Install capacitors on the Line side.
Warning
When Mains voltage is connected to the starter, even if start signal has not been initiated, full voltage may appear on the starter’s load terminals. Therefore, for isolation purposes it is required to connect an isolating device (C/B, switch, line contactor, etc) upstream to the RVS­AX (on the Line Side).
Built-in Bypass
The RVS-AX incorporates internal bypass relays allowing current flow through the thyristors only
C/T
C/T
during starting process. At the end of the starting process, the built-in relays
X 3
bypass the thyristors and carry the current to the Motor. Upon stop signal, or in
RVS-AX
M
case of fault, all three bypass relays will open and stop the motor. When Ramp-Down potentiometer is set to allow soft­Stop process, upon stop command, the bypass relays will open immediately and the current will flow through the thyristors. The voltage will then be reduced slowly and smoothly to zero.
4
Wiring
Block and Connection Diagram
Reduced Voltage Starter
Reset
Start Stop N
1234
NOTE:
The RVS-AX incorporates an internal control voltage transformer connected to phases L1&L3, in case of phase loss of L1 or L3 the starter will stop the motor. In case of phase loss for L2 the phase loss fault will trip the starter only if Terminal 3 – Neutral, is used).
Connection Diagram
L1 L2 L3
Neutral
Q1
I>I> I>
1
2
L
L
/
/
1
3
T1/U
M
On
Ramp-Up/Down
Run Overload Phase Loss
Over Tem p.
3 L
/ 5
x 3
T2/V
W1V1U1
1L 2L 3L
RVS -AX
T2/V T3/W
T1/U
RVS-AX
T3/W
Moto r FLC
50% 100%
Initial Voltage
10% 50%
Current Limit
100% 40 0%
Ramp-Up
230 Sec.
Ramp-Down
30 Sec.0.2
End of
Acceleration Fault
56 78
S1
Start / Stop
1 2
R1A
End Of Acceleration
Neutral
Not Used
3
4
Ground
R2A
R1C
765
Fault
R2C
8
Stop / Start ......................................... Terminals 1 - 2
By voltage free contact (Dry contact) Close: Start command. Open: Stop command.
Warning
Do not apply voltage to terminals 1 - 2.
Neutral......................................................Terminal 3
Neutral wire (when used) is required only for operation of the Phase Loss Protection (Phase Loss can not be detected when Neutral is not connected to Terminal 3). See detailed description in “Phase Loss” explanation.
Open terminal – not connected ................Terminal 4
End of Acceleration (E.O.A) .......... Terminals 5 - 6
Voltage free, N.O., 8A / 250VAC, 2000VA max. The contact closes after the time adjusted on the "Ramp-Up" potentiometer. The contact returns to its original position on stop signal, on fault condition, upon voltage outage and at the beginning of Soft Stop.
Use of E.O.A. Contact
This contact can be used for:
Activating a valve after a compressor has reached
full speed
Loading a conveyor after the motor has reached
full speed.
Fault contact .................................... Terminals 7 - 8
Voltage free, N.O., 8A / 250VAC, 2000VA max. The contact closes upon operation of any fault. The contact returns to its original position (after the fault has been removed) upon reset, or upon disconnection the Mains voltage.
Warning
Do not use the Fault contact to trip an upstream contactor. When the Fault contact trips the upstream contactor, Mains voltage will be disconnected, thus resetting the starter and the motor will restart instantaneously upon voltage restoration (see Fault Resetting).
Warning
Start/Stop with a maintained contact! When the line contactor is operated by a maintained
contact, in case of Mains failure, the motor will be automatically restarted upon voltage restoration. When resetting after a fault with the Reset button, the motor will restart upon fault reset. It is therefore recommended not to connect the fault relay to the line contactor.
5
Starter Settings
Front Panel Layout
°
°
°
°°
50% 100%
°
°
°
°°
10% 50%
°
°°
°°
100% 400%
°
°
°
°°
230 Sec.
°
°
°
°°
0.2 30 Sec.
FLC - Full Load Current (Motor FLC)
The adjustment allows easy setting of the RVS-AX current level, automatically adjusting current based functions (Overload, Current Limit, etc). Set FLC potentiometer according to the following equation:
FLC ×=
FLC
Where: Motor FLA is the motor's Full Load Current rating as shown on its nameplate. FLC is the starter Full Load Current as shown on its label. Example: When starting a 27A motor using RVS-AX 31:
27
FLC% =×=
31
Therefore set the FLC% to a reading of 87% (see Ex.)
Initial Voltage
Determines the initial voltage to the motor (torque is directly proportional to the square of the voltage). Range: 10-50% of nominal voltage. This adjustment also determines the inrush current and mechanical shock. Too high of a setting may cause high initial mechanical shock and high inrush current (even if Current Limit is set low, as the Initial Voltage setting over-rides the Current Limit setting). Too low of a setting may result in prolonged time until motor starts revolving. The motor should start revolving immediately
FLC %
Initial Voltage
Current Limi t
Ramp-Up
Ramp-Down
FLAMotor
100
87% 100
50% 100%
after Start signal.
°
°
°
°°
U%
100%
50%
10%
230Sec.
87 % FLC %
Current Limit
Determines motor's highest current during starting. Range is 100-400% of FLC (as set on starter's FLC adjustment).
I% 600% 400%
Too high of a setting will allow higher currents to be drawn from
100%
Mains, resulting in faster acceleration. Too low of a setting may prevent the motor from completing the acceleration process and reaching full speed. Generally, this setting should be set to the highest acceptable value in order to prevent stalling.
Caution
Starting Current should not exceed the allowable conditions as shown in page 3.
Ramp-up Time
Determines motor's voltage ramp­up time from initial to full
100%
U%
voltage. Range: 2-30 sec. It is recommended to set Ramp­Up Time to the minimum acceptable value (approx. 5 Sec).
230Sec.
Notes:
1. Setting Current Limit low will extend Ramp-Up
Time.
2.
When motor reaches full speed before voltage
reaches nominal, Ramp-Up Time adjustment is overridden, causing voltage to quickly ramp up to nominal.
Ramp-Down time (Soft-stop)
Used to control deceleration of high friction loads. When Ramp-
100%
U%
Down potentiometer is set, upon stop signal the starter output voltage is gradually ramped down. Range: 0.2-30 sec. When "Ramp-
0.2
30 sec
down Time" is set to minimum, the motor will stop immediately.
6
Motor Protection
Electronic Overload
The built-in inverse time electronic overload becomes operational after end of acceleration process. Trip current is factory set to 115% of Motor Full Load Current (from the setting on Motor FLC potentiometer), E.g. In order to increase the O/L trip point; increase FLC setting above the calculated level. Trip time varies from 60 sec. at 150% of n c
urrent.
ominal current to 2 sec. at 600% of nominal
Phase Loss
The protection becomes operational when the starter is energized; it protects the motor from single phasing. It will trip the starter wh
r more than 1 sec.
fo
When phase loss occurs during starting or when motor is not loaded, it may happen that motor will st without acc
urate indication of the Phase Loss LED.
Note: Phase loss protection operates
erminal 3 is connected to Neutral.
T
Fault Logic, Alarm an
Upon operation of any protection, the starter locks in a fault mode, disabling thyristors firing. The proper fault indication LED lights and the Fault contact closes. To reset the starter, after the fault has been removed, press Reset button on starter's front panel or discon
oltage.
v
nect Mains
1000
100
Seconds
10
1
024
I(Load)/In
531
en one or two phases are missing
only when
d Reset Circuits
On
Ramp Up / Down
Run
Overload
Phase Loss
Over Temp.
Reset
6
op
Heatsink Over temperature Protection
A thermal sensor mounted on the heatsink trips the starter when its heatsink temperature rises above 85ºC.
Warning
The Over-temperature Protection is designed to operate under normal conditions and will operate incase abnormal conditions occur:
Incorrect starter selection
Too frequent starting at max. conditions
Repeated starting under fault conditions
Extended low overload
Insufficient ventilation
Other abnormal conditions
Note- In case of frequent starting the internal thyristors may overheat before the heatsink reaches its over-temperature protection of 85 causing component malfunction.
ºC, thus
Caution
When starter is operated by a maintained contact, resetting the fault will start the motor immediately.
Warning
Do not use the Fault contact to trip an upstream contactor. When the Fault Contact closes on fault and trips the upstream contactor, Mains voltage will be disconnected, thus resetting the RVS-AX and the motor will restart instantaneously (see Fault Resetting).
7
Startup Procedure
1. Set FLC (Motor Full Load Current) -
according to
2.
Calculation:
3.
Set other potentiometers according to system
requirements (see next column for examples)
4.
Connect Mains voltage to starter Line
terminals.
5.
Start the motor, if it begins revolving shortly
after start signal proceed to Para. 5. If not, increase Initial Voltage setting until motor starts to turn shortly after start signal. When initial inrush current and mechanical shock are too high, decrease Initial Voltage setting and proceed to Para 6.
6.
Motor begins to turn. If speed smoothly
accelerates to nominal proceed to Para 6. If current during acceleration is too high, slightly decrease Current Limit setting. If motor speed does not increase to nominal, increase Current Limit setting.
7.
Disconnect the start command (open
Terminals 1 and 2) and wait until the motor stops.
8.
Slightly increase Initial Voltage and Current
Limit adjustments to allow for load variations.
9.
Start the motor again and verify that
acceleration process to full speed is as required.
10.
If acceleration time is too short, increase
Ramp-Up time setting.
When Soft stop is required, set Ramp-Down Potentiometer to the required time (minimum deceleration time is recommended). Check that soft stopping process is as required.
If Ramp Down potentiometer is not in the minimum setting. Emergency stop may be performed by disconnecting the mains voltage.
Motor FLA
FLC ×=
Note:
100
LCStarter F
Examples of Starting Curves
Light Loads - Pumps, Etc. Current limit - set to 300% Initial Voltage - set to 30% Ramp-up time - set to 5 sec.
U%
100%
50% 30%
10%
5
600% 400%
300%
100%
t
I%
t
Upon start, the voltage quickly increases to the Initial Voltage value (30% Un) and then gradually ramps-up to nominal. The current will simultaneously increase to peak current value, which can be the Current Limit setting or less, before smoothly decreasing to the operating current. The motor will accelerate to full speed quickly and smoothly.
High inertia loads – Crushers, Centrifuges, Mixers Etc. Current Limit - set to 350% Initial Voltage - set to 50% Ramp-Up time - set to 5 sec.
100%
50%
10%
U%
20
t
600%
350%
100%
I%
20
t
Upon Start the voltage and current increase until current reaches Current Limit value. The voltage remains at this value until motor reaches nominal speed, where current starts to decrease, voltage continues to ramp-up to nominal. At this time, the motor should have smoothly accelerated to full speed.
8
Technical Specification
Environment
Supply voltage Three phase, line to line,
380 – 415 Vac +10% -15% 460 – 500 Vac +10% -15% * 575 – 600 Vac +10% -15%
Frequency 50 / 60 Hz Load
Three-Phase, Three-Wire, Squirrel Cage Induction Motor
Degree of protection IP 20 Altitude 1000 m above sea level Consult factory for derating
Adjustments
FLC (Full Load Current) 50% - 100% Starting Torque (Initial Voltage) 10-50 % of full voltage Current limit 100 % - 400% of nominal current Ramp Up Time (soft start) 2 - 30 sec. Ramp Down Time (Soft Stop) 0.2 - 30 sec.
Protection
Electronic Overload Inverse time (I2t), factory preset at 115% of FLC, active only during Run. Phase Loss Trips when one phase is missing (When Neutral is connected) Heatsink Over temperature Trips when the heatsink temperature exceeds 85ºC. Reset buttons To reset the starter, after the fault has been removed.
Indications
Indication lights (LEDs)
Overload – Red Inverse time electronic overload becomes
Phase loss – Red Lights when one or two phases are missing for
Over temperature – Red Lights on and trips the starter when the heatsink
ON - Green Lights when three phases are connected to the
Ramp Up / Ramp Down – Yellow Lights upon start signal or during soft stopping. RUN – Green Lights upon end of starting. When the internal
Temperatures
Operating -10° to 40°C Storage -20° to 70°C Relative humidity 93 % - non condensed
EMC
Immunity to radio electric interference EN 1000-4-3 level 3 Conforming to EN 60947-4-2 Electrostatic discharge EN 1000-4-2 level 3 Conforming to EN 60947-4-2 Immunity to electrical transients EN 1000-4-4 level 4 Conforming to EN 60947-4-2 Shock waves of voltage / current EN 1000-4-5 level 3 Conforming to EN 60947-4-2 Radiated and conducted emissions EN 1000-4-6 level 3 Radio frequency emissions According to EN 55011 class A Conforming to EN 60947-4-2
Mechanical
Shock resistance 8 gn Conforming to EN 60947-4-2 Vibration resistance 2 gn Conforming to EN 60947-4-2
Output relay
End of Acceleration Contact N.O. Rated operating current 5 A, 250 V - Size A1
8 A, 250 V – Size A2
* 460 – 500 Vac is applicable for 220 – 240 Vac by changing the position of the internal jumper – J3. As shown in page 3.
RVS-AX.
bypass relays close.
operational after the End Of Acceleration process (see page 7).
more than 1 sec.
temperature rises above 85ºC.
9
Dimensions
\\SOLSRV1\Data\Catalogs and Marketing materials\Instruction Manuals\RVS-AX Instruction Manual 4-5-03.doc
18 Neville Street, Unit C
New Hamburg, ON N3A 4G7
Tel: 519-662-6489
Fax: 1-866-280-5247
www.safdrives.com www.opalstarters.com email: answers@opalstarters.com
(Replies given within 24 hours)
Loading...