Russell ITA24-126 Installation Manual

INTER-TEMP INSTALLATION MAINTENANCE MANUAL
IOM 102.1 NOVEMBER, 2003
MODELS: ITA, ITE, ITG, ITH
AIR, ELECTRIC AND HOT GAS DEFROST
Inspection
Installation
Installation and maintenance are to be performed by qualified personnel who are familiar with local codes and regulations. Installers should have previous experience with this type of equipment. CAUTION: Avoid contact with sharp edges and coil surface.They are potential hazards.
Determine the best location for the unit in the walk-in cooler or freezer. (See system IOM 550) Place the unit as far as possible from any door openings.This will help to prevent warm, moist air from being drawn into the unit, reducing the potential for icing problems. Inter-Temp units are draw­through types, which discharge air directly from the fan into the room.Adequate clearance should be maintained to allow for proper air flow through the unit and to allow for regular maintenance and service. Allow a minimum of 24” of clearance on all sides of the unit.
Remove all packing materials before the unit is raised into position. Be certain that the unit is not sitting on the drain fitting or refrigerant connections.The unit should be supported on 3/8” minimum thickness stainless steel support rods or fasteners at the hanging slots.The unit must be positioned flush with the ceiling and all gaps properly caulked.
The drain line should be pitched a minimum of 4” per foot to allow proper drainage and should exit the room as quickly as possible.Do not locate bends, elbows or drain traps within the refrigerated space. Do not reduce the drain line size. All drain lines must be trapped outside of the enclosure where the temperature is never below 35 degrees. Drain lines should run to an open drain and should never be connected directly to a sewage or waste line.Drain lines may be heated and insulated to prevent freezing.
Wiring
All wiring must be done in compliance with local and national codes. Use only Copper conductors. Electric defrost units are supplied with a temperature sensing defrost termination switch which will end the defrost at a preset coil temperature. A high limit control is provided to prevent overheating if there is a component failure.A fan delay control is installed to allow the coil temperature to drop below the freezing point of the water condensate on the fins before star ting the fans.
See the unit rating label for electrical requirements.The wiring diagram is located in the end panel of the unit cooler. Page 3 shown some examples of typical Inter-Temp wiring diagrams.
Expansion valve
Expansion valves should be selected and installed in accordance with the valve manufacturers recommendations. Units that require externally equalized expansion valves must have the equalizer line connected.The expansion valve bulb must be clamped securely at the 4 o’clock or 8 o’clock position on a horizontal run of the suction line. Proper location and full contact of the bulb is extremely important to the performance of the system.
New expansion valves usually need to be adjusted. Superheat setting should be checked after the system has run long enough to reach a balanced state. Low temperature systems will usually operate more efficiently with a superheat setting ranging from 6 to 8 degrees at design room temperature, medium temp rooms from 8 to 12 degrees.
To obtain evaporator superheat:
1. Measure the suction line temperature at the expansion valve bulb with an accurate electronic thermometer.
2. Obtain a suction pressure reading at the schrader fitting at the evaporator suction connection.
3. Convert the pressure reading to temperature by using a temperature/pressure conversion chart.
4. Subtract the converted temperature from the measured temperature.The resulting difference represents the evaporator superheat.
(For close coupled systems, it may be necessary to increase the evaporator superheat to insure the minimum acceptable superheat at the compressor.)
The maximum recommended evaporator TD for medium temperature rooms is 15 degrees. 12 - 13 degrees is the maximum recommended TD for low temperature systems.
Evacuation
Proper installation recommended must include a deep evacuation of the system (See system IOM
550). A clean/dry system is essential when charging refrigerant.
General Maintenance
Disconnect all electrical power to the unit before inspecting or cleaning. Unit coolers should be
checked periodically and cleaned of all dirt or grease accumulation. Fan blades and guards may require more frequent cleaning. Do not use ammonia or other cleaning agents that are corrosive to Copper or Aluminum.The drain pan should be lowered and thoroughly cleaned to prevent any drain restriction.The fan motors are life lubricated and do not require periodic oiling.
2
Loading...
+ 2 hidden pages