Wiring
All wiring must be done in compliance with local and national codes. Use only Copper conductors.
Electric defrost units are supplied with a temperature sensing defrost termination switch which will
end the defrost at a preset coil temperature. A high limit control is provided to prevent overheating if
there is a component failure.A fan delay control is installed to allow the coil temperature to drop
below the freezing point of the water condensate on the fins before star ting the fans.
See the unit rating label for electrical requirements.The wiring diagram is located in the end panel of
the unit cooler. Page 3 shown some examples of typical Inter-Temp wiring diagrams.
Expansion valve
Expansion valves should be selected and installed in accordance with the valve manufacturers
recommendations. Units that require externally equalized expansion valves must have the equalizer
line connected.The expansion valve bulb must be clamped securely at the 4 o’clock or 8 o’clock
position on a horizontal run of the suction line. Proper location and full contact of the bulb is
extremely important to the performance of the system.
New expansion valves usually need to be adjusted. Superheat setting should be checked after the
system has run long enough to reach a balanced state. Low temperature systems will usually
operate more efficiently with a superheat setting ranging from 6 to 8 degrees at design room
temperature, medium temp rooms from 8 to 12 degrees.
To obtain evaporator superheat:
1. Measure the suction line temperature at the expansion valve bulb with an accurate electronic
thermometer.
2. Obtain a suction pressure reading at the schrader fitting at the evaporator suction connection.
3. Convert the pressure reading to temperature by using a temperature/pressure conversion chart.
4. Subtract the converted temperature from the measured temperature.The resulting difference
represents the evaporator superheat.
(For close coupled systems, it may be necessary to increase the evaporator superheat to insure the
minimum acceptable superheat at the compressor.)
The maximum recommended evaporator TD for medium temperature rooms is 15 degrees. 12 - 13
degrees is the maximum recommended TD for low temperature systems.
Evacuation
Proper installation recommended must include a deep evacuation of the system (See system IOM
550). A clean/dry system is essential when charging refrigerant.
General Maintenance
Disconnect all electrical power to the unit before inspecting or cleaning. Unit coolers should be
checked periodically and cleaned of all dirt or grease accumulation. Fan blades and guards may
require more frequent cleaning. Do not use ammonia or other cleaning agents that are corrosive to
Copper or Aluminum.The drain pan should be lowered and thoroughly cleaned to prevent any drain
restriction.The fan motors are life lubricated and do not require periodic oiling.
2