Ceiling-Temp
Extra Low Profile
Unit Cooler
Publication No. 119.6
August, 2012
NSF®
• Applications
The Ceiling-Temp unit cooler is designed for use in walk-in coolers and freezers with low headroom clearance. It’s extra low height allows more product to be stored on shelves. The dual air flow design pro vides even temperatures throughout the box.
• Sizes
• Housing
Rust free heavy gauge textured Aluminum is standard.Optionally available with white enamel coating.
• Electrical
Available in 115V, 208-230V and 460V/1. All components are factory wired to terminal strips and are UL and CUL listed.
There are twenty models available, ranging in capacity from 4,800 to 25,000 BTUH @ 10o TD.
• Coil
The coil is constructed from seamless Copper tubes which are staggered and mechanically expanded into heavy gauge, corrugated, Aluminum fins, assuring maximum heat transfer. Optionally available with Copper or phenolic coated fins (phenolic fins are for air defrost only).
• Motors /Fans
Fan motors and blades can be easily accessed by lowering the hinged drain pan. All motors are permanently lubricated with thermal overload protection. Optional high efficiency PSC motors or ECM motors are available in 115V or 208-230V/1 only.
• Defrost
All models are available in air and electric defrost designs. Air defrost units are suitable for use
in coolers down to 35oF. Electric defrost units are designed for use in rooms down to -10oF.
201 Thomas French Drive, Scottsboro AL. 35769 • Tel (714) 529 - 4461 • Fax (714) 529 - 8503
Specifications
AIR DEFROST Models
8 FPI
6 FPI
MODEL |
BTUH @ +25oF S.T. |
CFM |
SP* MOTOR AMPS |
PSC* MOTOR AMPS |
ECM* MOTOR AMPS |
|||||
NUMBER |
10oT.D. |
15oT.D. |
115/1 |
208-230/1 |
115/1 |
208-230/1 |
115/1 |
208-230/1 |
||
|
||||||||||
CTA38-75 |
7,500 |
11,250 |
1,455 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
|
CTA38-88 |
8,800 |
13,200 |
1,305 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
|
CTA38-98 |
9,800 |
14,700 |
1,200 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
|
CTA48-112 |
11,200 |
16,800 |
2,120 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
|
CTA48-130 |
13,000 |
19,500 |
1,920 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
|
CTA48-150 |
15,000 |
22,500 |
1,760 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
|
CTA58-162 |
16,200 |
24,300 |
2,320 |
5.5 |
2.8 |
2.5 |
1.5 |
2.90 |
1.45 |
|
CTA48-210 |
21,000 |
31,500 |
1,820 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
|
CTA58-230 |
23,000 |
34,500 |
2,650 |
5.5 |
2.8 |
2.5 |
1.5 |
2.90 |
1.45 |
|
CTA68-250 |
25,000 |
37,500 |
2,970 |
6.6 |
3.3 |
3.0 |
1.8 |
3.48 |
1.74 |
|
CTA36-64 |
6,400 |
9,600 |
1,560 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
|
CTA36-82 |
8,200 |
12,300 |
1,425 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
|
CTA36-93 |
9,300 |
13,950 |
1,305 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
|
CTA46-100 |
10,000 |
15,000 |
2,160 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
|
CTA46-123 |
12,300 |
18,450 |
2,040 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
|
CTA46-140 |
14,000 |
21,000 |
1,920 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
|
CTA56-157 |
15,700 |
23,500 |
2,360 |
5.5 |
2.8 |
2.5 |
1.5 |
2.90 |
1.45 |
|
CTA46-190 |
19,000 |
28,500 |
1,940 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
|
CTA56-208 |
20,800 |
31,200 |
2,850 |
5.5 |
2.8 |
2.5 |
1.5 |
2.90 |
1.45 |
|
CTA66-232 |
23,200 |
34,800 |
2,970 |
6.6 |
3.3 |
3.0 |
1.8 |
3.48 |
1.74 |
SP* = Shaded Pole motor(s) PSC* = Permenant Split Capacitor(s) EC* = Electronically Commutated Motor(s) Standard voltage for CTA models is 115/1/60
ELECTRIC DEFROST Models
|
MODEL |
BTUH @ 10oT.D. |
CFM |
SP* MOTOR |
PSC* MOTOR |
ECM* MOTOR |
DEFROST |
DEFROST AMPS |
|
|||||
|
NUMBER |
-20oS.T. |
+15oT.D. |
115/1 |
208-230/1 |
115/1 |
208-230/1 |
115/1 |
208-230/1 |
WATTS |
208-230/1 |
460/1 |
|
|
|
|
|
||||||||||||
|
CTE36-53 |
5,300 |
6,360 |
1440 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
2070 |
9.0 |
4.5 |
|
|
CTE36-62 |
6,200 |
7,440 |
1290 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
2070 |
9.0 |
4.5 |
|
FPI |
CTE36-69 |
6,900 |
8,200 |
1245 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
2070 |
9.0 |
4.5 |
|
CTE46-77 |
7,700 |
9,240 |
2075 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
2990 |
13.0 |
6.5 |
|
|
|
|
|||||||||||||
6 |
CTE46-90 |
9,000 |
10,800 |
1860 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
2990 |
13.0 |
6.5 |
|
|
CTE46-100 |
10,000 |
12,000 |
1740 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
2990 |
13.0 |
6.5 |
|
|
CTE56-125 |
12,500 |
15,000 |
2160 |
5.5 |
2.8 |
2.5 |
1.5 |
2.90 |
1.45 |
3910 |
17.0 |
8.5 |
|
|
CTE46-140 |
14,000 |
16,800 |
1820 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
3910 |
17.0 |
8.5 |
|
|
CTE56-160 |
16,000 |
19,200 |
2550 |
5.5 |
2.8 |
2.5 |
1.5 |
2.90 |
1.45 |
3910 |
17.0 |
8.5 |
|
|
CTE66-218 |
21,800 |
23,200 |
3000 |
6.6 |
3.3 |
3.0 |
1.8 |
3.48 |
1.74 |
3910 |
17.0 |
8.5 |
|
|
CTE34-48 |
4,800 |
5,760 |
1500 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
2070 |
9.0 |
4.5 |
|
|
CTE34-58 |
5,800 |
6,960 |
1395 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
2070 |
9.0 |
4.5 |
|
|
CTE34-65 |
6,500 |
7,800 |
1350 |
3.3 |
1.7 |
1.5 |
0.9 |
1.74 |
0.87 |
2070 |
9.0 |
4.5 |
|
FPI |
CTE44-72 |
7,200 |
8,640 |
2120 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
2990 |
13.0 |
6.5 |
|
CTE44-84 |
8,400 |
10,080 |
1980 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
2990 |
13.0 |
6.5 |
|
|
|
|
|||||||||||||
4 |
CTE44-95 |
9,500 |
11,400 |
1900 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
2990 |
13.0 |
6.5 |
|
CTE54-115 |
11,500 |
13,800 |
2280 |
5.5 |
2.8 |
2.5 |
1.5 |
2.90 |
1.45 |
3910 |
17.0 |
8.5 |
|
|
|
|
|||||||||||||
|
CTE44-128 |
12,800 |
15,360 |
1940 |
4.4 |
2.2 |
2.0 |
1.2 |
2.32 |
1.16 |
3910 |
17.0 |
8.5 |
|
|
CTE54-145 |
14,500 |
17,400 |
2650 |
5.5 |
2.8 |
2.5 |
1.5 |
2.90 |
1.45 |
3910 |
17.0 |
8.5 |
|
|
CTE64-173 |
17,300 |
20,760 |
3080 |
6.6 |
3.3 |
3.0 |
1.8 |
3.48 |
1.74 |
3910 |
17.0 |
8.5 |
|
SP* = Shaded Pole motor(s) PSC* = Permenant Split Capacitor(s) EC* = Electronically Commutated Motor(s) 230V/1 motors are suitable for 208V operation. Standard voltage for CTE models is 208-230/1/60