Medium Profile Unit Cooler
Publication No. 102.5 September, 2008
Air Defrost – 12,600 to 69,000 BTUH
Electric Defrost – 10,500 to 52,000 BTUH
Hot Gas Defrost – 10,500 to 52,000 BTUH
3050 Enterprise St. • P.O. Box 1030 • Brea, CA 92822-1030 • Tel: (714) 529-1935 • Fax: (714) 529-
Cooler & Freezer Applications
7203
Features
• APPLICATIONS — Inter-Temp unit coolers are ideally suited for a wide range of coolers and freezers. ITA models are designed for use in coolers above 35°F. ITE, ITG, and ITH units are suited for 35°F coolers, when mechanical defrosts are required, as well as for freezers with temperatures ranging down to -30°F.
• Sizes — There are 37 models offered, with capacities from 10,500 BTUH up to 69,000 BTUH @ 10°TD. Air flow ranges from 3,320 CFM to 9,130 CFM.
• HOUSING — Each unit is constructed with a rust-free, heavy gauge, textured, aluminum housing which is light weight yet extremely durable. Air and electric defrost models have hinged drain pans to allow for con­venient servicing and maintenance (Hot Gas drain pans are not hinged). Slotted hangers are provided on all units for fast installation.
• COIL — Seamless copper tubes are staggered and mechanically expanded into heavy gauge corrugated aluminum fins to assure maximum heat transfer. Die formed fin collars are provided for accurate fin spacing. Heavy gauge hangers are fastened directly to the tube sheet of the coil to provide high structural strength.
• REFRIGERANTS — Inter-Temp unit coolers are designed for most refrigerants including, R-22, R-404A, R-134a, R-502 and R-507. Please specify system refrigerant requirements when ordering. A separate compartment is provided for all refrigerant connections which allows ample room for internal mounting of expansion valves. Inter-Temps can also be used with chilled water or glycol solutions, contact factory for selection.
• Fans — Powerful heavy duty aluminum fans are individually balanced to provide vibration free operation.
• Wire fan guards — Standard heavy gauge wire fan guards are epoxy coated for corrosion resistance. Optional air straighteners are available for increased air throw when required.
• Mot o rs — PSC-Permanent Split Capacitor or EC-Electronically Commutated, ball bearing type, life lubricated and thermally protected. Inter-Temp unit coolers use either 1/8 HP, 1050 rpm or 1/3 HP, 1075 rpm motors.
Air Throw – Air throw is greatly affected by installa­tion variables. Optimum air throw is obtained by high ceiling with no interference from beams, or return air restrictions. Inter-Temp unit coolers will throw air up to 50 feet under ideal conditions, 60 to 70 feet with air straighteners.
• ELECTRICAL — Available in 115V/1, 208/230/1, 208/230/3, 460/1 or 460/3. Inter-Temps can also be operated on 220/1/50, 220/3/50, 380/1/50 and
80/3/50 power. All components are factory wired to
3 convenient screw type terminal blocks. A large compartment is supplied for all electrical components and is easily accessible by removing the end panel.
• AIR DEFROST — Available on ITA series only, for use in coolers at +35°F and above. Complete air defrost systems are available from Russell.
• ELECTRIC DEFROST — These units are available as ITE models. The placement of heaters within the refrigeration coil allows for a more efficient and rapid defrost cycle than other designs. This arrangement enables the energy from the heaters to be conducted from the center of the core out, providing an even defrost pattern. All heaters are factory installed and wired to screw type terminal blocks, allowing for quick field hook up or change over from 1 to 3 phase with the installation of jumper wires. Separate, fixed defrost termination, fan delay and heater saftey controls are factory mounted for optimum performance of each control func tion. Drain pans are heated for fast, reliable drainage. Timer and contactors are available as options. Complete electric defrost systems are avail­able from Russell. Contact the factory for details.
• HOT GAS RE-EVAP DEFROST — Available on all but the ITA models. These units include separate fixed defrost termination and fan delay controls which are factory mounted for optimum performance of each control func tion. A hot gas drain pan circuit is provided, thus eliminating the need for electric heat and additional wiring. A heat exchanger/re-evapora­tor is supplied with every unit. Refer to the current Russell Technical Bulletin HG for piping. Complete Hot Gas Re-Evap systems are available from Russell, contact the factory for details.
• HOT GAS REVERSE CYCLE DEFROST —
Available on all but the ITA models. These units include separate fixed defrost termination and fan delay controls which are factory mounted for opti­mum performance of each control function. A hot gas drain pan circuit is provided, thus eliminating the need for electric heat and additional wiring. Refer to the current Russell Technical Bulletin HG for piping. This unit is also used for Alternating Evaporator System.
2 7
Energy Savings per Motor
Motor
HP and
R
PM
Standard
PSC Motor
Input Power
W
atts/Mtr
Optional EC
Motor Input
Power
W
atts/Mtr
Reduced
Power
Consumption
W
atts/Mtr
Run Time
H
rs/Day
Motor
Energy
Savings
k
Wh/Yr
Motor
Energy
Savings
$
/Yr
Reduced
Box Load
M
BTU/Yr
Cond. Unit
Energy
Savings
k
Wh/Yr
Cond.
Unit
Energy
Savings
$
/Yr
Yearly
Savings
$
/Motor
Pay-
back
Y
rs
1/8 1075 141 70 71 22 570 57 1,945 374 37 94 1.5 1/3 1075 357 225 132 22 1060 106 3,617 695 70 176 0.9
Subtract 6% from total savings for medium temperature 24 run hours per day.
by Changing to More Efficient Unit Cooler Motors (based on Energy Cost of $0.10 per kWh)
Nomenclature
IT •26-150 -D- P
Inter-Temp Models
A = Air Defrost
E = Electric Defrost
H = Hot Gas Re-evap
G = Hot Gas Rev. Cycle
Number of fans
Fins per inch
Motor Type P = PSC E = EC
Voltage Code A = 115V B = 208/1/60 C = 230/1/60
BTUH in hundreds
D = 208-230/1/60 E = 208-230/3/60 F = 460/1/60 G = 460/3/60