Russell HTA14-42B User Manual

Page 1
All-Temp²B
221 S. Berry St., P.O. Box 1030, Brea, CA 92822-1030 • Tel: (714) 529-1935 • Fax: (714) 529-7203
Low Profile Unit Cooler
Publication No. 100.14 January, 2008
MEA
Electric Defrost - 3,600 to 28,000 BTUH
Hot Gas Defrost - 3,600 to 28,000 BTUH
Small to Medium Walk - Ins
Coolers & Freezer Applications
Visit us on the Web: www.russellcoil.com
Now available with optional
ECM Motors
High Efficiency / High Reliability
Page 2
All-Temp²B
Sizes
There are 35 sizes available with 3,700 to 39,000 BTUH at a 10° TD ranging from 740 to 4,980 cfm. One through six fan models are available.
Housing
Rust-free, heavy gauge, textured Aluminum casing is light weight yet durable. Each fan section is baffled to prevent short cycling of the air. The unit is designed to mount flush to the ceiling and meets all NSF requirements. Slotted hangers are provided for easy installation. Drain fittings are installed in the horizontal position to gain more usable head­room in low ceiling applications. The end panels now are hinged to open up out for easy access to both the piping and electrical ends. Optional expansion valves can be conveniently installed inside the cabinet.
Coil
Seamless Copper tubes are staggered and mechanically expanded into corrugated Aluminum fins and heavy gauge tube sheets to achieve maximum heat transfer and strength. Die formed fin collars provide even fin spacing. Fin spac­ings available are 4, 6, and 8 fins per inch. Sweat connections are standard on all models and optional field installed flare connection kits are available at no extra charge.
Motors
Standard motors are 1/20 HP, permanently lubricated, ball bearing, with thermal overload protection. Available in 115V, 208/230V and 460V, single phase. Optional high efficiency PSC and ECM motors are available in 115V and 230V.
Fans
Heavy duty 12” Aluminum fans are balanced to provide vibration-free operation. Our new low throw black plastic fan guards have an improved air pattern. The optional epoxy resin high throw fan guard moves air up to 50 feet.
Air Defrost
All models with the prefix “HTA” are designed for use in cool­ers of 35°F and warmer. Complete air defrost systems for off-cycle or timed air defrost are available.
Electrical
Available in 115V, 208/230V, and 460V (see pages 4 & 5). All components are factory wired to convenient screw-type terminal strips. A large compartment is supplied internal to the unit for all electrical components and is easily accessible by removing the end panel. All models are UL & cUL listed.
Electric Defrost
Available on all models with the prefix “HTE”. Designed for use where electric heat is used to defrost. Placement of the heaters internal to the coil allows for an extremely rapid and efficient defrost. This arrangement enables the heat to be conducted through the fins from the center out for an even defrost pattern. All heaters are wired to a terminal strip to allow a quick field change-over from single phase to three phase, 230V to 460V and vice versa. A lower heater is installed close to the drain pan for fast, reliable drainage. A defrost termination thermostat (DT) terminates the defrost cycle when the temperature is satisfied. A heater safety thermostat is installed to prevent heaters from overheating above 75° in case of DT failure. All heaters are flexible and can be easily replaced within 12 inches of the end of the units. A fan delay thermostat is supplied to allow the warm coil to cool after a defrost cycle prior to the fans turning on. Complete electric defrost refrigeration systems are available.
Features
The All-Temp²B is the original low profile unit cooler that has established an industry standard as being the all purpose design for walk-in coolers, freezers and other applications. They feature an air draw-through design offering air, electric and hot gas defrost models.
• High efficiency PSC or ECM fan motors
• Coated Aluminum fins or Copper Fins
• Baked white enamel housing
• Epoxy resin high throw guards for up to 50 ft.
• Reheat kits (not UL listed)
• Factory mounted expansion valves
Optional Features
2
Page 3
All-Temp²B
Nomenclature
HT A 1 8 - 41 B - A
All-Temp²B
Type of Defrost
A = Air Defrost E = Electric Defrost
Revision Code
BTUH in hundreds
Fins per inch
Number of fans
HTPG’s optional ECM motors
bring the benefits inherent to unit bearing motor design
to the refrigeration Unit Cooler market.
3
Voltage Code A = 115V B = 208/1/60 C = 230/1/60 D = 208-230/1/60 E = 208-230/3/60 F = 460/1/60
• Large oil resevoir
• Totally enclosed construction
• Journal bearing machined into the cast iron endbell
• Spiral grooved shaft pump guarantees positive oil circulation
• Threaded shaft uses hubless fan blade.
Subtract 6% from total savings for medium temperature air defrost units that run 24 hours per day. SP = 1/20 HP Shaded pole motor (Standard motors) PSC = 1/20 HP PSC motor (Optional motors available at additional cost) ECM = 50 Watt Electronically Commutated motor (Optional motors available at additional cost)
Energy Savings per Motor
by Changing to More Efficient Unit Cooler Motors (baseded on Energy Cost of $0.10 per kWh)
1234567891011
3.88 7.76 11.64 15.52 19.39 23.27 27.15 31.03 34.91 38.79 42.67
4.21 8.42 12.63 16.85 21.06 25.27 29.48 33.69 37.90 42.11 46.32
8.09 16.18 24.27 32.36 40.45 48.54 56.63 64.72 72.81 80.90 88.99
12111098765432
Yearly Savings per motor
$0
$20
$40
$60
$80
$100
$120
123456789101112
Months of year
Dollars Saved
SP to PSC PSC to EC SP to EC
Motor
Change
Std Motor
Power
Watts/Mtr
Change to
Motor
Power
Watts/Mtr
Reduced
Power
Watts/Mtr
Run
Time
Hrs/ Day
Motor
Energy
Savings
kWh/Yr
Motor
Energy
Savings
$/Yr
Reduced
Box Load
MBTU/Yr
Cond. Unit
Energy
Savings
$/Yr
Yearly
Saving $
Per
MTR
Pay
back in
Yrs
SP to PSC 120 85 35 22 281 28 959 18 47 0.6
PSC to EC 85 47 38 22 305 31 1041 20 51 2
SP to EC 120 47 73 22 586 59 2000 38 97 1.3
Page 4
All-Temp²B
Air Defrost / Specifications
Ordering Information Required
It is vital that the information listed below is given with each evaporator order. Orders without this information may be delayed. Evaporators with options such as solenoid and expansion valves will not be processed until all the required information is given.
(1) Model Number (2) Type of Motor
(3) Voltage, frequency and phase of motors
and heaters (when applicable) (4) Refrigerant type (5) Evaporator temperature (6) Evaporator T.D.
4
(1) All fan motors are wired for single phase. Standard motors are shaded pole. High efficiency PSC motors (Permanent Split Capacitor) and ECM (Electronically Commutated) motors are optional.
Model
Number
BTUH
CFM
Total Fan Motor AMPS - 1 Phase
Capacity @ 25°F S.T. Standard Motor Optional PSC Motor Optional ECM Motor
10° TD 12° TD 115V 230V 460V 115V 230V 115V 230V
HTA18-41B 4,100 4,900 800 2.0 1.0 0.5 1.0 0.5 0.9 0.45 HTA18-53B 5,300 6,400 770 2.0 1.0 0.5 1.0 0.5 0.9 0.45 HTA18-66B 6,600 7,900 740 2.0 1.0 0.5 1.0 0.5 0.9 0.45 HTA28-76B 7,600 9,100 1,460 4.0 2.0 1.0 2.0 1.0 1.8 0.90
HTA28-97B 9,700 11,600 1,420 4.0 2.0 1.0 2.0 1.0 1.8 0.90 HTA28-106B 10,600 12,700 1,540 4.0 2.0 1.0 2.0 1.0 1.8 0.90 HTA28-122B 12,200 14,600 1,380 4.0 2.0 1.0 2.0 1.0 1.8 0.90 HTA28-134B 13,400 16,100 1,480 4.0 2.0 1.0 2.0 1.0 1.8 0.90 HTA38-160B 16,000 19,200 2,310 6.0 3.0 1.5 3.0 1.5 2.7 1.35 HTA38-195B 19,500 23,400 2,220 6.0 3.0 1.5 3.0 1.5 2.7 1.35 HTA48-212B 21,200 25,400 3,080 8.0 4.0 2.0 4.0 2.0 3.6 1.80 HTA48-264B 26,400 31,700 2,960 8.0 4.0 2.0 4.0 2.0 3.6 1.80 HTA58-275B 27,500 33,000 3,850 10.0 5.0 2.5 5.0 2.5 4.5 2.25 HTA68-318B 31,800 38,200 4,620 12.0 6.0 3.0 6.0 3.0 5.4 2.70 HTA68-390B 39,000 46,800 4,440 12.0 6.0 3.0 6.0 3.0 5.4 2.70
HTA16-39B 3,900 4,700 830 2.0 1.0 0.5 1.0 0.5 0.9 0.45
HTA16-48B 4,800 5,800 800 2.0 1.0 0.5 1.0 0.5 0.9 0.45
HTA16-58B 5,800 7,000 780 2.0 1.0 0.5 1.0 0.5 0.9 0.45
HTA26-70B 7,000 8,400 1,540 4.0 2.0 1.0 2.0 1.0 1.8 0.90
HTA26-87B 8,700 10,400 1,500 4.0 2.0 1.0 2.0 1.0 1.8 0.90 HTA26-115B 11,500 13,800 1,560 4.0 2.0 1.0 2.0 1.0 1.8 0.90 HTA36-145B 14,500 17,400 2,400 6.0 3.0 1.5 3.0 1.5 2.7 1.35 HTA36-170B 17,000 20,400 2,340 6.0 3.0 1.5 3.0 1.5 2.7 1.35 HTA46-192B 19,200 23,000 3,200 8.0 4.0 2.0 4.0 2.0 3.6 1.80 HTA46-230B 23,000 27,600 3,120 8.0 4.0 2.0 4.0 2.0 3.6 1.80 HTA56-245B 24,500 29,400 4,000 10.0 5.0 2.5 5.0 2.5 4.5 2.25 HTA66-295B 29,500 35,400 4,800 12.0 6.0 3.0 6.0 3.0 5.4 2.70 HTA66-345B 34,500 41,400 4,680 12.0 6.0 3.0 6.0 3.0 5.4 2.70
HTA14-42B 4,200 5,000 830 2.0 1.0 0.5 1.0 0.5 0.9 0.45
HTA24-84B 8,400 10,100 1,660 4.0 2.0 1.0 2.0 1.0 1.8 0.90 HTA24-105B 10,500 12,600 1,620 4.0 2.0 1.0 2.0 1.0 1.8 0.90 HTA34-130B 13,000 15,600 2,490 6.0 3.0 1.5 3.0 1.5 2.7 1.35 HTA44-170B 17,000 20,400 3,320 8.0 4.0 2.0 4.0 2.0 3.6 1.80 HTA54-215B 21,500 25,800 4,150 10.0 5.0 2.5 5.0 2.5 4.5 2.25 HTA64-255B 25,500 30,600 4,980 12.0 6.0 3.0 6.0 3.0 5.4 2.70
6
F P
I
4
F P
I
8
F P
I
Page 5
All-Temp²BAll-Temp²B
Electric Defrost / Specifications
(1) All fan motors are wired for single phase. Standard motors are shaded pole. High efficiency PSC (Permanent Split Capacitor) & ECM (Electronically commutated) motors are optional. (2) For 208/230 volt models, heaters are wired as standard for single phase on 1 through 4 fan models. 5 and 6 fan models are
wired 3 phase. 460 Volt models are only available in single phase and are compatible with all 3 phase systems.
5
Model
Number
BTUH Capacity @ 10° T.D.
CFM
Motor Amps¹ Heater Amps²
Watts
Evaporator Temperature Standard PSC ECM 208/230V 460V
-30° -20° -10° +20° 230V 460V 230V 230V 1 PH 3 PH 1 PH HTE16-36B 3,400 3,600 3,700 3,900 830 1 0.5 0.5 0.45 4.4 2.6 2.2 1,000 HTE16-41B 3,900 4,100 4,300 4,800 800 1 0.5 0.5 0.45 4.4 2.6 2.2 1,000 HTE16-46B 4,400 4,600 4,800 5,800 780 1 0.5 0.5 0.45 4.4 2.6 2.2 1,000 HTE26-60B 5,700 6,000 6,200 7,000 1,540 2 1 1 0.90 7 6 3.5 1,600 HTE26-75B 7,100 7,500 7,800 8,700 1,500 2 1 1 0.90 7 6 3.5 1,600 HTE26-92B 8,700 9,200 9,600 11,500 1,560 2 1 1 0.90 8.7 7.5 4.4 2,000
HTE36-120B 11,400 12,000 12,500 14,500 2,400 3 1.5 1.5 1.35 13 11.3 6.4 3,000 HTE36-140B 13,300 14,000 14,600 17,000 2,340 3 1.5 1.5 1.35 13 11.3 6.4 3,000 HTE46-164B 15,000 16,400 17,100 19,200 3,200 4 2 2 1.80 17.4 15.1 8.7 4,000 HTE46-185B 17,600 18,500 19,200 23,000 3,120 4 2 2 1.80 17.4 15.1 8.7 4,000 HTE56-210B 20,000 21,000 21,800 24,500 4,000 5 2.5 2.5 2.25 18.8 10.9 5,000 HTE66-245B 23,300 24,500 25,500 29,500 4,800 6 3 3 2.70 22.6 13 6,000 HTE66-280B 26,600 28,000 29,100 34,500 4,680 6 3 3 2.70 22.6 13 6,000
HTE14-37B 3,500 3,700 3,800 4,200 830 1 0.5 0.5 0.45 4.4 2.6 2.2 1,000 HTE24-72B 6,800 7,200 7,500 8,400 1,660 2 1 1 0.90 8.7 7.5 4.4 2,000 HTE24-85B 8,100 8,500 8,800 10,500 1,620 2 1 1 0.90 8.7 7.5 4.4 2,000
HTE34-105B 10,000 10,500 10,900 13,000 2,490 3 1.5 1.5 1.35 13 11.3 6.4 3,000 HTE44-140B 13,300 14,000 14,600 17,000 3,320 4 2 2 1.80 17.4 15.1 8.7 4,000 HTE54-180B 17,100 18,000 18,700 21,500 4,150 5 2.5 2.5 2.25 18.8 10.9 5,000 HTE64-215B 20,400 21,500 22,400 25,500 4,980 6 3 3 2.70 22.6 13 6,000
6
F P
I
4
F P
I
Page 6
All-Temp²B
Physical Data
DRAIN - HTA, HTE UNITS
DRAIN - HOT GAS
ELECTRICAL KNOCKOUTS (4) BACK AND (3) TOP
SUCTION CONN
LIQ AND HG CONN KNOCKOUTS
(3) BACK AND (3) TOP
5 1/4
CBA3 1/4
W
15 1/4
13 1/4
11 1/2
1 1/42 1/2
12 5/8 1/2
15
2 3/4
1/2 x 1" MTG SLOTS
3/4 MPT DRAIN
3 1/8
Installation Notes:
(1) Install 12” away from back wall. (2) Drain connection on HTA and HTE units are centered on drain pan,
and on the left end (facing air discharge) on hot gas defrost units. (3) For long air throw requirements, specify high throw fan guard. (4) Unit height at drain end of hot gas models is as follows: 1,2, and 3
fan models = 15-7/8”, 4,5, and 6 fan models = 16-1/4”.
6
Models
TXV
TYPE
Refrigerant Connections
No. of
Hangers
Dimensions (Inches)
Ship
Wt.
(lbs.)
All Liquid†
HTA
Suction
HTE
Suction
HG‡
HTA HTE A B C W
18-41B EXT 1/2 ODS 5/8 ODS — 2 19 27½ 33 18-53B EXT 1/2 5/8 2 19 27½ 34 18-66B EXT 1/2 5/8 2 19 27½ 36 28-76B EXT 1/2 5/8 2 33 41½ 48 28-97B EXT 1/2 7/8 2 33 41½ 51 28-106B EXT 1/2 7/8 2 37 45½ 58 28-122B EXT 1/2 7/8 2 33 41½ 60 28-134B EXT 1/2 7/8 2 37 45½ 63 38-160B EXT 1/2 1-1/8 2 55 63½ 79 38-195B EXT 1/2 1-1/8 2 55 63½ 84 48-212B EXT 1/2 1-1/8 3 36½ 36½ 81½ 254 48-264B EXT 1/2 1-1/8 3 36½ 36½ 81½ 262 58-275B EXT 1/2 1-1/8 3 54½ 36½ 99½ 312 68-318B EXT 1/2 1-1/8 4 36½ 36 36½ 117½ 354 68-390B EXT 1/2 1-1/8 4 36½ 36 36½ 117½ 370 16-39B 16-36B EXT 1/2 ODS 5/8 ODS 5/8 ODS 5/8 ODS 2 19 27½ 41 16-48B 16-41B EXT 1/2 5/8 5/8 5/8 2 19 27½ 44 16-58B 16-46B EXT 1/2 5/8 5/8 5/8 2 19 27½ 47 26-70B 26-60B EXT 1/2 5/8 7/8 5/8 2 33 41½ 54 26-87B 26-75B EXT 1/2 7/8 7/8 5/8 2 33 41½ 55 26-115B 26-92B EXT 1/2 7/8 7/8 5/8 2 37 45½ 62 36-145B 36-120B EXT 1/2 7/8 7/8 5/8 2 55 63½ 78 36-170B 36-140B EXT 1/2 1-1/8 1-1/8 5/8 2 55 63½ 85 46-192B 46-164B EXT 1/2 1-1/8 1-1/8 5/8 3 36½ 36½ 81½ 255 46-230B 46-185B EXT 1/2 1-1/8 1-1/8 5/8 3 36½ 36½ 81½ 265 56-245B 56-210B EXT 1/2 1-1/8 1-1/8 5/8 3 54½ 36½ 99½ 306 66-295B 66-245B EXT 1/2 1-1/8 1-1/8 5/8 4 36½ 36 36½ 117½ 353 66-345B 66-280B EXT 1/2 1-1/8 1-1/8 5/8 4 36½ 36 36½ 117½ 368 14-42B 14-37B EXT 1/2 ODS 5/8 ODS 5/8 ODS 5/8 ODS 2 19 27½ 42 24-84B 24-72B EXT 1/2 7/8 7/8 5/8 2 37 45½ 49 24-105B 24-85B EXT 1/2 7/8 7/8 5/8 2 37 45½ 55 34-130B 34-105B EXT 1/2 7/8 7/8 5/8 2 55 63½ 79 44-170B 44-140B EXT 1/2 7/8 1-1/8 5/8 3 36½ 36½ 81½ 251 54-215B 54-180B EXT 1/2 1-1/8 1-1/8 5/8 3 54½ 36½ 99½ 299 64-255B 64-215B EXT 1/2 1-1/8 1-1/8 5/8 4 36½ 36 36½ 117½ 340
Page 7
All-Temp²B
Electric Defrost Kits
Electric defrost kits consist of components that are necessary to control the defrost cycle. The optional kits are available as a factory installed option when ordered with a condensing unit. Not all Ed-Kits are available for all condensing unit models. The contents of each kit is described below, along with the function of each component. * - 1/2 through 3 HP models require ED-210 or ED-213.
Electric Defrost Kits
Timer: Initiates the defrost cycle. Also used as a over-
ride protection for defrost termination.
Auxiliary Switch: Is mounted on the compressor con-
tactor and prevents the defrost contactor from oper­ating whenever the compressor is energized.
Block-Out Relay: Serves the same function as auxil-
iary switch. Used when defrost contactor is not required (lower wattage single phase only).
Defrost Contactor: Carries amperage load for
heaters.
Fan Contactor: Used with 460V motors or when 230V
motors are wired 3 phase.
Sequencing Relays: Provides interconnection of multi-
ple unit coolers on a single system so that each unit cooler is allowed to individually terminate defrost on temperature.
¹ For use with 2 evaporators , 1/2 through 3 HP R-series systems ONLY!
7
Model
Number
1 Unit Cooler Per System 2 Unit Coolers Per System 3 Unit Coolers Per System
230V 460V 230V 460V 230V 460V
HTE16-36B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 HTE16-41B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 HTE16-46B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 HTE26-60B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 HTE26-75B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 HTE26-92B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 HTE36-120B ED-10 ED-12 ED-20* ED-22 ED-33 ED-32 HTE36-140B ED-10 ED-12 ED-20* ED-22 ED-33 ED-32 HTE46-164B ED-10 ED-12 ED-23* ED-22 ED-35 ED-32 HTE46-185B ED-10 ED-12 ED-23* ED-22 ED-35 ED-32 HTE56-210B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34 HTE66-245B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34 HTE66-280B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34 HTE14-37B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 HTE24-72B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 HTE24-85B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 HTE34-105B ED-10 ED-12 ED-20* ED-22 ED-33 ED-32 HTE44-140B ED-10 ED-12 ED-23* ED-22 ED-35 ED-32 HTE54-180B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34 HTE64-215B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34
KIT NO.
TIMER
AUXILIARY
SWITCH
BLOCK-OUT
RELAY
DEFROST
CONTACTOR
FAN
CONTACTOR
SEQUENCING
RELAY
ED10-230/1 1 1-30A — ED11-230/3 1 1 1-30A
ED12-460/3 1 1 1-30A 1-25A — ¹ED210-230/1 1 1-30A — ¹ED213-230/1 1 1 1-50A — ¹ED213-230/3 1 1 1-50A
ED20-230/1 1 1-30A 2
ED22-460/3 1 1 2-15A 1-25A 2
ED23-230/1 1 1 2-25A 2
ED23-230/3 1 1 2-25A 2
ED30-230/1 1 1-30A 3
ED32-460/3 1 1 3-10A 1-25A 3
ED33-230/1 1 1 3-16A 3
ED34-460/3 1 1 3-16A 1-25A 3
ED35-230/1 1 1 3-33A 3
ED35-230/3 1 1 3-33A 3
Page 8
All-Temp²B
221 S. Berry St., P.O. Box 1030, Brea, CA 92822-1030 • Tel: (714) 529-1935 • Fax: (714) 529-7203
Visit us on the Web: www.russellcoil.com
All-Temp²B
Low Profile Unit coolers
MiniCon
Cond. units 1/2 - 6 HP
D-Series
Condensing Units 3-22 HP
Inter-Temp
Medium Profile Unit Coolers
V-Series
Condensing Units 20-30 HP
Ultra-Temp
High Capacity Warehouse Unit Coolers
1/2 Through 80 HP
1/2 Through 80 HP
COMPLETE REFRIGERATION PACKAGES
COMPLETE REFRIGERATION PACKAGES
• AIR DEFROST
• AIR DEFROST
• ELECTRIC DEFROST
• ELECTRIC DEFROST
• HOT GAS DEFROST
• HOT GAS DEFROST
• SIERRA
• SIERRA
• HIGH SIERRA
• HIGH SIERRA
CONTACT YOUR HTPG REPRESENATIVE FOR DETAILS
Loading...