Russell FDL1001B User Manual

Publication No. RU-FSD-1012A
FS/FD Series
AIR-COOLED FLUID
COOLER
Standard Features:
• Vertical air discharge confi guration
• Galvanized steel frame and casing
• Aluminum Fins / Copper tubes
• 6 pole 1140 RPM motors
• Heavy gauge Aluminum Fan blades with steel hub
• Fully baffl ed fan modules
• Weather tight control panel
• Epoxy Coated Fan guards
Consider The Possibilities
• Cools most any non-corrosive fl uid
• Closed-circuit cooling avoids contamination
• Cold weather economizer for interior cooling loads
• HVAC and computer room air conditioning
• Industrial cooling applications
- Cutting fl uids
- Machinery cooling jackets
- Electrical gear
Optional Features:
• Horizontal air discharge confi guration
• Aluminum Casing (galvanized frame and legs)
• Coated or Copper fi ns
• Flip top hinged fan panels
• Removable side access panels
• Control panel mounting location
• Motor fusing
• Circuit breakers
• Fan control toggle switches
• Fused disconnect switch
2
FS/FD SERIES
Table of Contents
Nomenclature Features and Options Performance Range Tables — 1140 RPM Models Performance Range Tables — 825 RPM Models Fan and Motor Data Sound Pressure Options Electrical Control Options Typical Wiring Diagrams — Single Phase Typical Wiring Diagrams — Three Phase Detail Photographs and Features Weights and Volumes Connection Sizes Fan Motor Amps Dimensional Drawings Standard Specifications
......................................................................................... 2
............................................................................. 3
................................................................................ 6
........................................................................ 6
...................................................................... 7
.............................................7
...............................................8
...........................................................9
............................................................................10
...................................................................................10
....................................................................................10
.................................................................... 10-11
.........................................................Back Cover
................................. 4
................................... 5
Standard and Optional Features
3
FS/FD SERIES
UNIT MODEL
DESCRIPTION Notes FS FS-204A— 603A
General Construction and Configuration Vertical Air Discharge Configuration
Horizontal Air Discharge Configuration Opt Opt Galvanized Steel Frame and Casing Std Std Embossed Aluminum Casing (Galvanized Steel Frame and Legs) Opt Opt Heavy Gauge Galvanized Steel Legs (Vert. Air Disch): 18" Leg Length 15" (Std) Std
30" or Custom Leg Length A N/A Opt
Fluid Cooler Coil
16 Gauge Galvanized Steel Casing and Aluminum Tube Sheets Std Std
Aluminum Fins Mechanically Expanded into Copper Tubes Std Std Special Fin Materials: Up to .010" Thick Aluminum Opt Opt
Copper Fin Stock Opt Opt Polyester-Coated Fin Stock Opt Opt
ElectroFin™ and Phenolic-Coated Coils Opt Opt
Fan Section
6-Pole (1140 RPM), 1 -Phase (PSC) or 3-Phase Fan Motors: Open Type E Std Std
Totaly Enclosed B Opt Opt
Fan Motor Mounting Std Std
FS-101A thru 203A — Steel Rail Rigid Mounting Std N/A
All Others — Welded heavy-gauge rod mounting frames N/A Std Fan Blades - Heavy Gauge Aluminum Blades, Painted Steel Hubs Std Std
Fully Baffled Fan Modules Std Std
'Flip Top' Hinged Fan Panels - Easy Access for Coil Cleaning and Fan/Motor Service N/A Opt
Control Panel
Weather-Tight Galvanized Steel Enclosure with All Motor Leads Pulled C Std Std
Mounting Location: Header End Std Std Temperature Fan Cycling - Individual- or Paired-Fan Contactors (Must specify) Opt Opt Custom Fan Cycling Wiring and Logic Opt Opt Motor Fusing - Individually or in Pairs Opt Opt Circuit Breakers BOpt Opt Fan Control Circuit Toggle Switches Opt Opt Control Transformer BOpt Opt Fused Disconnect Switch (Mounted) B Opt Opt
Shipping
Vertical Discharge Models FS-101A thru 203A D Std — Vertical Discharge Models All Others — Legs are collapsed for shipping Std
and must be re-extended during installation Horizontal Discharge Models
Legs Disassembled - Unit is Cartoned or Crated See Note D See Note A
101 A— 203 A FD -40 1B— 120 3B
Std Std
Notes
A. Contact factory for information B. Not UL Listed C. Units which are fi ve and six fans long are furnished with motor leads wired to 3-Phase Terminal Blocks. D. Legs disassembled; units shipped in carton or crate. Models FS-101A thru 203A can be either horizontal or vertical
depending on method of leg assembly.
E. 1-Phase PSC Motors available on models FS-101A thru 207A only.
4
FS/FD SERIES
Table 1: Range of Performance † - 1140 RPM—6-Pole Fans
Single Fan-Width Units
Model No.
Minimum Maximum
MBH ∆T GPM MBH ∆T GPM
FSS
101A 26.8 6.0 10 30.4 3.2 20
102A 42.0 9.2 10 48.0 5.2 20
103A 63.6 14.0 10 84.0 6.4 30
104A 80.0 17.6 10 106.8 4.8 50
201A 100.0 22.4 10 172.4 5.6 70
202A 122.4 27.2 10 213.6 4.8 100
203A 169.2 18.8 20 233.2 3.6 140
204A 182.4 20.4 20 272.8 6.0 100
205A 196.4 22.0 20 306.8 6.8 100
206A 224.4 25.2 20 368.0 5.2 160
207A 238.8 26.8 20 407.2 5.6 160
Single Fan-Width Units Double Fan-Width Units
Model No.
Minimum Maximum
MBH ∆T GPM MBH ∆T GPM
FSS
208A 261.2 29.2 20 507.6 7.2 160
209A 337.6 25.2 30 545.6 7.6 160
210A 357.2 26.4 30 590.4 6.0 220
211A 395.6 29.2 30 668.9 5.3 280
301A 419.6 31.2 30 826.0 7.2 260
302A 513.6 28.8 40 887.2 5.6 340
303A 535.6 30.0 40 962.8 5.2 400
401A 556.0 30.8 40 1044.4 10.4 220
402A 588.0 32.8 40 1142.4 8.4 300
403A 607.6 34.0 40 1258.4 7.2 380
404A 620.8 34.8 40 1306.4 7.6 380
501A 636.8 35.6 40 1382.8 10.8 280
502A 652.8 36.4 40 1538.0 9.6 360
503A 795.2 35.6 50 1598.4 10.0 360
601A 893.2
1030.4
602A 32.8 70 1780.4 12.4 320
1181.2
603A 29.2 90 1852.0 12.8 320
33.2 60 1598.0 13.6 260
Model No.
FDS
401 B 470.0 34.8 30 1048.8 10.4 220
402B 590.0 32.8 40 1145.2 8.4 300
403B 623.9 34.8 40 1289.2 5.2 550
404B 637.2 35.6 40 1336.0 5.4 550
601 B 735.2 32.8 50 1643.2 7.2 500
602B 782.0 34.8 50 1730.4 6.8 550
603B 924.4 34.4 60 1847.2 9.2 450
801 B 1010.4 32.0 70 2097.6 10.4 450
802B 1066.4 34.0 70 2256.6 9.2 550
803B 1122.4 35.6 70 2413.6 9.6 550
804B 1142.4 36.4 70 2508.0 10.0 550
1001B 1273.2 35.6 80 2756.8 11.2 550
1002B 1436.0 35.6 90 2950.4 12.0 550
1003B 1590.4 35.6 100 3068.8 12.4 550
1201B 1786.4 33.2 120 3168.8 14.0 500
1202B 1845.2 34.4 120 3460.5 14.0 550
1203B 2113.3 33.7 140 3601.6 14.6 550
Minimum Maximum
† 100° F. Entering air temperature; 140° F. Entering fl uid temperature; 40% Ethylene Glycol Performance ranges are given to suggest approximate capacity of units. Contact factory for computer-rated units before fi nal selection. Please Specify: Capacity or leaving fl uid temperature Fluid type & concentration Entering fl uid temperature Flow rate in GPM Entering air temperature
MBH ∆T GPM MBH ∆T GPM
Loading...