3
CONDENSING UNIT INSTALLATION (continued.)
Condensing units with spring mounted compressors are shipped with retainers under the
compressor feet to prevent damage during shipment. For Copeland H and K body
compressors, remove the retainers and loosen the mounting nut to allow 1/16” clearance
between the nut and rubber spacer. For 3HP and larger units, the mounting nuts must be
removed to insert the rubber spacer. Insert the rubber spacer over the mounting studs,
replace the nut and tighten to within 1/16” of the spacer. DO NOT
TIGHTEN THE NUTS
AGAINST THE SPACER OR FOOT.
Units with iso-pad mounted compressors are shipped with the mounting nuts tight. These
should be checked to make certain that they have not loosened during shipment.
LOCATING AND MOUNTING UNIT COOLERS
Determine the best location for the unit in the walk-in cooler or freezer. Consider the air pattern required to cover the entire space. For High Sierra Systems with two unit coolers, locate
the unit coolers so that the piping runs from the suction and liquid line tees are equal in size
and length.
Do not restrict the inlet or outlet air stream. Place the unit cooler as far as possible from
any door openings. Direct the discharge air stream towards the door whenever possible.
This will help to prevent warm, moist air from being drawn into the coil (Drawings 2, 3 and
Table 2). Adequate clearances should be maintained around the unit cooler to allow for
proper airflow through the unit and for regular maintenance and service to be preformed.
For all Hot Gas defrost unit coolers, ensure that the drain pan is in contact with the Hot Gas
drain pan loop after installation. If the drain pan is removed for any reason, verify
that it has
physical contact with the defrost loop when replaced.
The drain line should be pitched a minimum of 4" per foot to allow proper drainage and
should exit the room as quickly as possible. Do not reduce the drain line size. Do not locate
line bends, elbows or drain traps within the refrigerated space. All drain lines must be
trapped outside of the enclosure where the temperature is never below 35 degrees. Drain
lines should run to an open drain and should never be attached directly to a sewage or waste
line. Drain lines must be protected from possible freezing. Freezer units must have copper
drain lines that are heated and insulated.
Remove all packaging materials before lifting the unit into position. Be certain that the unit is
not sitting on the drain fitting or refrigerant connections. All-Temp units should be hung using
5/16" minimum diameter, stainless steel support rods or fasteners at all hanging slots. Use
minimum 3/8" hanger rods for Inter-Temp and Ultra-Temp models.
Tighten all fasteners securely. All units must be positioned level, flush with the ceiling and all
gaps must be properly caulked. Allow minimum clearances on all sides of the unit cooler(s) as
indicated in Table 2 (next page).