Russell CTE34-48, CFA48-210 Installation Manual

INSTALLATION AND MAINTENANCE MANUAL
Ceiling-Temp, Dual-Flo and Height Saver Unit Coolers
Bulletin No. IOM 119.1
January, 2002
Inspection
When the equipment is received, t he number of crates and cartons should be checked against the bill of lading for possible shortages. Any damage should be noted immediately and a report given to the freight carrier and the factory. It is the customer’s responsibility to file all freight claims with the carrier.
Installation
Installation and maintenance must be preformed by qualified personnel who are familiar with the local codes and regulations and who are experienced with this type of equipment. Unit name plates should be checked to make sure voltages are in agreement with the power available. Caution: Avoid contact with sharp edges and coil surface as they are potential hazards.
Location
Determine the best location for the unit cooler in the room to be refrigerated. Placement of the unit should be centered in the room and away from an open door to keep warm, outside air from being drawn into the unit.This dual discharge unit, draws air up through the fan blades and discharges out the coils length. Proper clearances should be maintained for proper air flow and service access to the unit as follows: 18” minimum between each coil and wall: 12” on each end of the unit. Before unit is raised into position all packaging should be removed making sure the unit is not set on the drain fitting or refrigerant connections. The unit should be supported on 5/16” minimum rod hangers at all mounting slots. To meet NSF requirements, the unit must be positioned flush with the ceiling and all gaps properly caulked.
Drain Line
The drain line should be pitched at a minimum of 4” per foot to allow proper drainage and should exit the room as soon as possible. The drain line should be insulated and sealed where it passes thru the wall and trapped outside the refrigerated area and protected from freezing. In rooms with temperatures below 34° F, the drain line should be heated and insulated.
Refrigerant Connections
Refrigerant connections should be installed in accordance with all applicable codes and using good refrigeration practices. A suction line trap must be installed prior to any risers in the suction line. Horizontal suction lines should be sloped to provide proper oil return to the compressor. Suction lines should be properly insulated to prevent sweating and higher return gas temperatures.
Expansion V alve
Expansion valves are to be installed in accordance with the valve manufacturer’s recommendations. The external equalizer line must be connected. Proper location of the sensing bulb is extremely important to the performance of the coil.Good thermal contact to the suction line is essen­tial. On solder type valves, a wet cloth wrapped around the valve during installation will help protect it from over­heating and damage during the installation process. Superheat settings should be checked after the system has balanced out at the desired room temperature. On systems sized for a 10° to 12° F TD, the valve should be adjusted to maintain 4° to 6° F superheat. Higher evap­orator TD will allow a higher superheat setting. On multi­ple evaporator systems, the piping should be arranged such that the flow from any valve cannot affect the bulb of an other.
Wiring
Wiring should be done in accordance with all national and local codes. Electric defrost units are supplied with a temperature sensing defrost termination switch which will terminate the defrost at a preset temperature. A fan delay switch is also provided to allow the coil to cool down prior to the fans restarting after the defrost cycle. The time clock should be adjusted to have a maximum 30 minute override to prevent overheating and steaming of the coils. Typically one to two defrosts per day are recommended however, the number of defrosts are ulti­mately dictated by the usage of the box and the actual amount of frost buildup on the coils.
Evacuation
Proper evacuation is essential prior to charging of the system. This avoids many problems that may arise due to lack of detail in this step. After charging, the system should be checked through all cycles to ensure proper operation.
General Maintenance
General maintenance involves an occasional cleaning of dirt accumulation on the fans, fan guards and coils. The motors are life lubricated and do not require any regular maintenance.
Loading...
+ 2 hidden pages