Russell CAC 11 User Manual

MultiCon
Computer Room Air Cooled Condenser
Publication No. 401.5 September, 2009
5 Thru 164 Nominal tons
3050 Enterprise St., P.O. Box 1030, Brea, CA 92822-1030 • Tel: (714) 529-1935 • Fax: (714) 529-7203
Visit us on the Web: www.russellcoil.com
General
Russell’s
CAC/CBC air cooled condenser design allows less fluctuation in discharge head pressures when ambient temperatures vary. Combining a variable speed, header end fan(s), with fans controlled by standard cycling techniques provides a stable, energy efficient refrigeration system.
Features
MOTORS / CONTROLS
Header end Vari - speed motors are specifically designed for P66 application. Johnson P66 fan motor speed control:
Pressure sensing 230/1/60 or 460/1/60 power Single or Dual system input 24V control voltage Double wide condensers have 2 independent P66
controllers. Fan cycle control, temperature or pressure sensing, on remaining fans (if applicable). Units can be wired for an external control power source (24,115 or 208/230V) or control voltage can be provided by an 0.15 KVA inter nal control voltage transformer (24V only) unless otherwise specified. Fan guards are epoxy coated and fabricated from heavy gauge steel rod.
CAC models use only 3/4 HP single phase fan motors with 24” fan blades, and be wired for single or three phase input power.
CBC models use 3/4 HP single phase Vari - Speed fan
motor(s) and 24” fan blades on the header end fan sec tions, and 1-1/2 HP three phase constant speed motors with 30” fan blades on all other fan sections. These models are only available for three phase input power applications. Units are available for 230/1/60, 230/3/60, 460/1/60, or 460/3/60 applications (see page 6 for definition) [
Consult Factory
for 50 Hertz operation]. Motor assemblies are supported in all-welded, heavy gauge wire support structures. The wire structures are zinc - chromate coated for corrosion protection.
COILS
Coil fins are manufactured from die formed corrugated Aluminum. The tubes are seamless ½” OD Copper, arranged in a staggered pattern and mechanically expanded into the fins and tube sheets for optimum heat transfer efficiency. Tube sheets are clean punched from 0.080” Aluminum to resist wear at the tube.
Headers are produced from heavy wall Copper tubing, and are brazed to the coil using a high temperature brazing process. All coils are leak tested in a illuminated test tank at a pressure of 400 psig. Heavy gauge galvanized steel casing and support members.
OPTIONS
Flooded condenser control - available using three-
way modulating valves controlled by discharge pres­sure. Valves are shipped mounted. Motor fusing - available on all models. Motors can be fused individually or in pairs on double width units. Sub-cooling - available as an integral part of the condenser.
Disconnect switch - thru the door disconnect.
Fins - available in four options; Aluminum, Copper,
polyester coated Aluminum, and baked phenolic coated Aluminum. Multiple system circuiting - up to 4 separate systems are available per unit. Horizontal air discharge - available upon request for all models. Contact Russell for details.
2
Selections
For the proper selection of an air cooled condenser it is necessary to know the total heat rejection of the condenser. The Total Heat of Rejection (THR) is equivalent to the sum of the Net Refrigerating Effect (NRE) plus the heat of compression added by the compressor. The amount of heat added to the refrigerant will depend on the style of compressor, open or suction cooled, and the operating conditions of the system.
Whenever the THR values are available from the compressor manufacturer they should be used in selecting a condenser.
For those cases in which the THR data is unavailable it can be quickly estimated using the following equation and the appropriate factor from Tables 1 or 2.
Eq. (1) THR = Compressor Capacity x Heat Rejection Factor In those cases where the refrigeration system is of a multiple or
cascade style, the following equations should be used to estimate the total heat of rejection.
Open Compressor
Eq. (2) THR = Compressor Capacity + (2545 x BHP)
Suction Cooled Compressor
Eq. (3) THR = Compressor Capacity + (3413 x KW)
Altitude at which a condenser is to operate will also affect its capacity. In order to correctly select a condenser at a specific altitude, use the following equation and the appropriate correction factor from Table 3.
Eq. (4) THR Corrected =THR Design x Altitude Correction Factor
Selection Example
Given:
Altitude 5000 ft. Ambient Temperature 90°F Evaporator Temperature 20°F Maximum Condensing Temperature 110°F Refrigerant R-22 Compressor Capacity (NRE) 225,000 BTUH Compressor Type Suction Cooled
Assume compressor THR is not available
Calculate:
1. Total Heat Rejection
2. Design temperature difference
3. Russell condenser size
4. Actual system TD
5. Actual condensing temperature
Solution:
1. Calculate the system THR from Table 2, a suction cooled compressor, at 110°F condensing temperature and 20°F evap­orator temperature, will have a heat rejection factor of 1.33.
THR = Compressor Capacity x Heat Rejection Factor THR = 299,250 BTUH
THR Corrected “Altitude” = THR x Altitude Corr. Factor THR Corrected “Altitude” = 336,656 BTUH
2. Design TD = Condensing Temp. - Ambient Temp. Design TD = 20°F
3. Select condenser size: From page 4 locate single width CAC section of the page. Then using the TD of 20°F calculated in Step 2, go to the appropriate column and select a condenser whose THR equals or exceeds that of which we calculated in Step 1; 336,656 BTUH. A model CAC -37 with a THR of 366,000 BTUH will meet the required conditions.
4. Eq.(5) Actual TD = Design TD x Design THR
Actual Condenser Capacity at Design TD
Actual TD = 18.4°F
5. Eq.(6) Actual Condensing Temp. = Actual TD + Ambient Temp.
Actual Condensing Temp. = 108.4°F
HEAT REJECTION FACTORS TABLE 1 - OPEN COMPRESSOR
EVAP
. CONDENSING TEMPERA TURE
TEMP. 90° 100° 105° 110° 115° 120° 125° 130°
-40° 1.45 1.48 1.52 1.56 1.58 1.61
-35° 1.42 1.45 1.47 1.51 1.54 1.57
-30° 1.39 1.41 1.44 1.47 1.50 1.53
-25° 1.37 1.39 1.41 1.44 1.46 1.49 1.52
-20° 1.34 1.37 1.39 1.41 1.43 1.45 1.48 1.51
-15° 1.31 1.34 1.37 1.38 1.40 1.42 1.45 1.47
-10° 1.28 1.31 1.33 1.37 1.38 1.40 1.42 1.45 0° 1.24 1.28 1.29 1.32 1.33 1.35 1.38 1.41
10° 1.21 1.24 1.26 1.28 1.30 1.31 1.34 1.36 20° 1.18 1.21 1.23 1.24 1.26 1.28 1.30 1.32 30° 1.15 1.18 1.20 1.21 1.23 1.24 1.26 1.28 40° 1.13 1.15 1.17 1.18 1.19 1.20 1.22 1.24 50° 1.11 1.13 1.14 1.15 1.16 1.17 1.18 1.20
TABLE 2 - SUCTION COOLED COMPRESSOR
EVAP. CONDENSING TEMPERA TURE TEMP. 90° 100° 105° 110° 115° 120° 125° 130°
-40° 1.67 1.71 1.75 1.79 1.84 1.90
-35° 1.63 1.67 1.70 1.73 1.78 1.83
-30° 1.58 1.62 1.65 1.68 1.72 1.77
-25° 1.54 1.58 1.60 1.64 1.67 1.71 1.76
-20° 1.49 1.53 1.56 1.58 1.63 1.66 1.70 1.75
-15° 1.46 1.50 1.52 1.54 1.58 1.62 1.65 1.69
-10° 1.42 1.46 1.48 1.50 1.53 1.57 1.62 1.64 0° 1.36 1.40 1.42 1.44 1.47 1.50 1.54 1.56
10° 1.31 1.34 1.36 1.38 1.40 1.43 1.47 1.49 20° 1.26 1.29 1.31 1.33 1.35 1.37 1.40 1.43 30° 1.22 1.25 1.26 1.28 1.30 1.32 1.35 1.37 40° 1.18 1.21 1.22 1.24 1.25 1.27 1.30 1.32 50° 1.14 1.17 1.18 1.20 1.21 1.23 1.25 1.27
TABLE 3 - Altitude Correction Factor (ft.)
Altitude Sea Level 1000 2000 3000 4000 5000 6000 7000 8000 9000 10000
Factor 1.0 1.029 1.052 1.076 1.101 1.125 1.151 1.177 1.204 1.231 1.260
3
Loading...
+ 5 hidden pages