HTPGroup, a division of Carrier
Commercial Refrigeration Inc.
Evaporator
Cross-reference
Selection Tables
For Russell Evaporators
To Copeland, Maneurop,
And Tecumseh
Condensing Units
Bulletin No. 106.2
February 2007
221 S. Berry St., P.O. BOX 1030, Brea, CA, 92622-1030 Tel(714) 529-1935 FAX(714) 529-720
This cross-reference guide is designed to assist you in the quick selection
of a Russell evaporator to a Copeland, Maneurop, or Tecumseh air cooled
condensing unit. The Russell evaporators in this guide are chosen to balance
out with the condensing unit capacity at a 9° to 11° temperature difference.
Suction temperatures have been selected for three typical industry
applications; +25°F,-10°F, and -20°F.
To use this guide:
1) Go to the page that corresponds to the condensing unit
manufacturer of your choice.
2) Select a condensing unit that meets the required capacity at
any one of the three suction temperatures specified above.
3) Choose the style of evaporator that best fits your application.
Do not use this guide if you require a larger or smaller T.D.
as a change in T.D. will affect relative humidity requirements.
4) For specific information on the evaporator (physical data, electrical
data, options, etc…) see the appropriate Russell bulletin:
All - Temp2B Bulletin 100
Inter - Temp Bulletin 102
Ultra - Temp Bulletin 101
Flow - Temp Bulletin 110
Ceiling - Temp Bulletin 119
"SL" Slim - Temp Bulletin 112 &109
"ASL" Slim - Temp Bulletin 113
Mini Twin - Temp Bulletin 117
Twin - Temp Bulletin 111
T - Temp Bulletin 116
Wall - Temp Bulletin 114
Wedge - Temp Bulletin 115
For special application or operating conditions
contact the Russell Application Department.
RUSSELL / MANEUROP
SUGGESTED GUIDE FOR MATCHING RUSSELL UNIT COOLERS
WITH MANEUROP CONDENSING UNITS
High Temperature / +25 Deg. Suction, 90 Deg. Ambien
Maneurop Russell Unit Coolers
Model All-Temp²B Inter-Temp Ceiling-Temp Flow-Temp Ultra-Temp
Numbe
MT018 R-22 13,250 38-134B 28-151 48-150 36-135 --MT022 R-22 18,950 38-195B 28-210 48-210 46-220 1-182
MT028 R-22 25,860 48-264B 38-260 68-250 46-265 1-232
MT032 R-22 28,300 48-264B 38-260 68-250 46-265 2-300
MT036 R-22 33,020 68-318B 38-320 (2) 58-162 (2) 36-160 2-365
MT050 R-22 41,720 (2) 48-212B 28-450 (2) 48-210 (2) 46-220 2-433
MT064 R-22 54,370 (2) 48-264B 38-540 (2) 58-230 (3) 46-160 2-490
MT072 R-22 59,900 (2) 48-264B 38-540 (3) 48-210 (3) 46-220 3-648
MT100 R-22 84,160 (3) 58-275B (2) 28-410 --- (3) 46-265 4-866
MT125 R-22 108,500 (3) 68-390B (2) 38-540 --- --- 4-1100
MT144 R-22 123,700 (3) 68-390B (2) 36-620 --- --- (2) 3-648
MT160 R-22 136,020 (3) 68-390B (2) 38-690 --- --- (2) 3-648
BTUHRefrig.
AA ITA CTA FL UAH
Low Temperature / -20 Deg. Suction, 90 Deg. Ambien
Maneurop Russell Unit Coolers
Model Slim-Temp All-Temp²B Inter-Temp Ceiling-Temp Ultra-Temp
Numbe
LTZ022 R-404A 6,630 35-70 26-75B --- 36-69 --LTZ028 R-404A 9,650 45-94 26-92B 24-105 46-90 --LTZ044 R-404A 16,460 65-150 46-164B 26-150 56-160 1-152
LTZ050 R-404A 20,660 (2) 45-94 56-210B 36-270 66-218 2-240
LTZ088 R-404A 29,900 (2) 65-150 66-280B 26-320 (2) 46-140 2-304
LTZ100 R-404A 40,330 (3) 55-117 (2) 56-210B 36-385 (2) 66-218 3-445
Refrig. BTUH
ASLE AE ITE CTE UEL
Low Temperature / -10 Deg. Suction, 90 Deg. Ambien
Maneurop Russell Unit Coolers
Model Slim-Temp All-Temp²B Inter-Temp Ceiling-Temp Ultra-Temp
Numbe
MTZ018 R-404A 4,660 25-46 16-46B --- 36-53 --MTZ022 R-404A 6,800 35-70 26-60B --- 36-69 --MTZ028 R-404A 9,480 45-94 26-92B --- 46-90 --MTZ032 R-404A 10,130 45-94 26-92B --- 46-100 --MTZ036 R-404A 11,840 55-117 36-120B 24-105 46-100 1-125
MTZ050 R-404A 18,600 (2) 45-94 46-185B 36-185 56-160 1-193
MTZ064 R-404A 23,790 (2) 55-117 66-245B 35-230 66-218 2-240
MTZ072 R-404A 27,210 (3) 45-94 66-280B 26-270 (2) 46-140 2-240
MTZ100 R-404A 32,810 (3) 55-117 (2) 46-164B 26-320 (2) 56-160 2-304
MTZ125 R-404A 44,220 --- (2) 56-210B 36-460 (2) 66-218 3-445
MTZ144 R-404A 52,480 --- (2) 66-245B 36-520 (3) 46-173 3-540
MTZ160 R-404A 57,760 --- (2) 66-280B 36-520 (3) 66-218 3-540
Refrig. BTUH
ASLE AE ITE CTE UEL
Page 3