Russell AA14-42B User Manual

Page 1
All-Temp2BAll-Temp
201 Thomas French Dr ive Scottsboro AL 35769 • Tel: (256) 259-7400 • Fax: (256) 259-7468
Low Profile Unit Cooler
Air Defrost - 3,900 to 39,000 BTUH
Electric Defrost - 3,600 to 28,000 BTUH
Hot Gas Defrost - 3,600 to 28,000 BTUH
Small to Medium Walk - Ins
Coolers & Freezer Applications
Visit us on the Web: http://coldzone.htpgusa.com
Available with
EC Motors
High Efficiency / High Reliability
NSF
®
Page 2
Sizes
There are 35 sizes available with 3,700 to 39,000 BTUH at a 10° TD ranging from 740 to 4,980 cfm. One through six fan models are available.
Housing
Rust-free, heavy gauge, textured Aluminum casing is light weight yet durable. Each fan section is baffled to prevent short cycling of the air. The unit is designed to mount flush to the ceiling and meets all NSF requirements. Slotted hangers are provided for easy installation. Drain fittings are installed in the horizontal position to gain more usable head­room in low ceiling applications. The end panels now are hinged to open up out for easy access to both the piping and electrical ends. Optional expansion valves can be conveniently installed inside the cabinet.
Coil
Seamless Copper tubes are staggered and mechanically expanded into corrugated Aluminum fins and heavy gauge tube sheets to achieve maximum heat transfer and strength. Die formed fin collars provide even fin spacing. Fin spac­ings available are 4, 6, and 8 fins per inch. Sweat connections are standard on all models and optional field installed flare connection kits are available at no extra charge.
Motors
Shaded Pole motors are 1/20 HP, permanently lubricated, ball bearing, with thermal overload protection. Available in 115V, 208/230V and 460V, single phase. Optional high efficiency PSC and EC motors are available in 115V and 230V.
Fans
Heavy duty 12” Aluminum fans are balanced to provide vibration-free operation. Our new low throw black plastic fan guards have an improved air pattern. The optional epoxy resin high throw fan guard moves air up to 50 feet.
Air Defrost
All models with the prefix “AA” are designed for use in cool­ers of 35°F and warmer. Complete air defrost systems for off-cycle or timed air defrost are available from ColdZone.
Electrical
Available in 115V, 208/230V, and 460V (see pages 4 & 5). All components are factory wired to convenient screw-type terminal strips. A large compartment is supplied internal to the unit for all electrical components and is easily accessible by removing the end panel. All models are UL & cUL listed.
Electric Defrost
Available on all models with the prefix “AE”. Designed for use where electric heat is used to defrost. Placement of the heaters internal to the coil allows for an extremely rapid and efficient defrost. This arrangement enables the heat to be conducted through the fins from the center out for an even defrost pattern. All heaters are wired to a terminal strip to allow a quick field change-over from single phase to three phase, 230V to 460V and vice versa. A lower heater is installed close to the drain pan for fast, reliable drainage. A defrost termination thermostat (DT) terminates the defrost cycle when the temperature is satisfied. A heater safety thermostat is installed to prevent heaters from overheating above 75° in case of DT failure. All heaters are flexible and can be easily replaced within 12 inches of the end of the units. A fan delay thermostat is supplied to allow the warm coil to cool after a defrost cycle prior to the fans turning on. Complete electric defrost refrigeration systems are also available from ColdZone.
Hot Gas Defrost
Two types available - Re-Evap models with the prefix “AH” and reverse cycle with the prefix “AG”. All models include a fixed DTFD factory wired and a hot gas drain pan circuit to defrost the drain pan. On all Hot Gas models, the drain fit­ting is located on the left-hand rear of the unit when facing the fan guards. Re-evap models include a Heat Exchanger/Re-Evaporator shipped together with the unit for field installation. Complete Re-Evap Refrigeration Systems are available from ColdZone. Contact factor y for piping information.
Features
The All-Temp²B is the original low profile unit cooler that has established an industry standard as being the all purpose design for walk-in coolers, freezers and other applications. They feature an air draw-through design offering air, electric and hot gas defrost models.
• High efficiency PSC or ECM fan motors
• Coated Aluminum fins or Copper Fins
• Baked white enamel housing
• Epoxy resin high throw guards for up to 50 ft.
• Reheat kits (not UL listed)
• Factory mounted expansion valves
Optional Features
r
2 7
Page 3
Nomenclature
AA18-41B-A- E
All-Temp²B
Type of Defrost
A = Air Defrost E = Electric Defrost H = Hot Gas Re-evap G = Hot Gas Rev. Cycle
BTUH in hundreds
Fins per inch
Number of fans
ColdZone’s EC motors
bring the benefits inherent to unit bearing motor design
to the refrigeration Unit Cooler market.
Voltage Code A = 115V B = 208/1/60 C = 230/1/60 D = 208-230/1/60 E = 208-230/3/60 F = 460/1/60
• Large oil resevoir
• Totally enclosed construction
• Journal bearing machined into the cast iron endbell
• Spiral grooved shaft pump guarantees positive oil circulation
• Threaded shaft uses hubless fan blade.
Subtract 6% from total savings for medium temperature air defrost units that run 24 hours per day. SP = 1/20 HP Shaded pole motor (Standard motors) PSC = 1/20 HP PSC motor (Optional motors available at additional cost) EC = 50 Watt Electronically Commutated motor (Optional motors available at additional cost)
Energy Savings per Motor
by Changing to More Efficient Unit Cooler Motors (based on Energy Cost of $0.10 per kWh)
Revision Code
Motor Type S = Shaded Pole E = ECM P = PSC
Cond. Unit
Energy
Savings
$/Yr
Motor
Change
Std Motor
Power
Watts/Mtr
Change to
Motor
Power
Watts/Mtr
Reduced
Power
Watts/Mtr
Run
Time
Hrs/ Day
Motor
Energy
Savings
kWh/Yr
Motor
Energy
Savings
$/Yr
Reduced Box Load MBTU/Yr
SP to PSC 120 85 35 22 281 28 959 18 47 0.6 PSC to EC 85 47 38 22 305 31 1041 20 51 2.0
SP to EC 120 47 73 22 586 59 2000 38 97 1.3
Yearly Saving
$ Per
MTR
Pay
back in
Yrs
$120
$100
$80
$60
$40
$20
Dollars Saved
$0
123456789101112
Yearly Savings per motor
Months of year
SP to PSC PSC to EC
Page 4
4 5
Air Defrost /
Specifications
Ordering Information Required
It is vital that the information listed below is given with each evaporator order. Orders without this information may be delayed. Evaporators with options such as solenoid and expansion valves will not be processed until all the required infor mation is given.
(1) Model Number (2) Type of Motor
(3) Voltage, frequency and phase of motors
and heaters (when applicable) (4) Refrigerant type (5) Evaporator temperature (6) Evaporator T .D.
(1) All fan motors are wired for single phase.
6
F P
I
4
F P
I
8
F P
I
,,,
,
,,,
,
,,,
,
,,,,,
,,,,,,,,,
,
,,,,,
,,,,,
,,,,,
,,,,,
,,,,,,,,,
,
,,,,,
,,,
,
,,,,,
,,,,,,,,,
,
,,,,,
,,,,,
,,,,,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
Model
Number
AA18-41B 4 AA18-53B 5 AA18-66B 6 AA28-76B 7
AA28-97B 9 AA28-106B 10 AA28-122B 12 AA28-134B 13 AA38-160B 16 AA38-195B 19 AA48-212B 21 AA48-264B 26 AA58-275B 27 AA68-318B 31 AA68-390B 39
AA16-39B 3
AA16-48B 4
AA16-58B 5
AA26-70B 7
AA26-87B 8 AA26-115B 11 AA36-145B 14 AA36-170B 17 AA46-192B 19 AA46-230B 23 AA56-245B 24 AA66-295B 29 AA66-345B 34
AA14-42B 4
AA24-84B 8 AA24-105B 10 AA34-130B 13 AA44-170B 17 AA54-215B 21 AA64-255B 25
BTUH
Capacity @ 25°F S.T.
10° TD 12° TD 115V 230V 460V 115V 230V 115V 230V
100 4,900 800 2.0 1.0 0.5 1.0 0.5 0.9 0.45 300 6,400 770 2.0 1.0 0.5 1.0 0.5 0.9 0.45 600 7,900 740 2.0 1.0 0.5 1.0 0.5 0.9 0.45 600 9,100 1,460 4.0 2.0 1.0 2.0 1.0 1.8 0.90 700 11,600 1,420 4.0 2.0 1.0 2.0 1.0 1.8 0.90
600 12,700 1,540 4.0 2.0 1.0 2.0 1.0 1.8 0.90 200 14,600 1,380 4.0 2.0 1.0 2.0 1.0 1.8 0.90 400 16,100 1,480 4.0 2.0 1.0 2.0 1.0 1.8 0.90 000 19,200 2,310 6.0 3.0 1.5 3.0 1.5 2.7 1.35 500 23,400 2,220 6.0 3.0 1.5 3.0 1.5 2.7 1.35 200 25,400 3,080 8.0 4.0 2.0 4.0 2.0 3.6 1.80 400 31,700 2,960 8.0 4.0 2.0 4.0 2.0 3.6 1.80 500 33,000 3,850 10.0 5.0 2.5 5.0 2.5 4.5 2.25 800 38,200 4,620 12.0 6.0 3.0 6.0 3.0 5.4 2.70
000 46,800 4,440 12.0 6.0 3.0 6.0 3.0 5.4 2.70 900 4,700 830 2.0 1.0 0.5 1.0 0.5 0.9 0.45 800 5,800 800 2.0 1.0 0.5 1.0 0.5 0.9 0.45 800 7,000 780 2.0 1.0 0.5 1.0 0.5 0.9 0.45 000 8,400 1,540 4.0 2.0 1.0 2.0 1.0 1.8 0.90 700 10,400 1,500 4.0 2.0 1.0 2.0 1.0 1.8 0.90
500 13,800 1,560 4.0 2.0 1.0 2.0 1.0 1.8 0.90
500 17,400 2,400 6.0 3.0 1.5 3.0 1.5 2.7 1.35
000 20,400 2,340 6.0 3.0 1.5 3.0 1.5 2.7 1.35
200 23,000 3,200 8.0 4.0 2.0 4.0 2.0 3.6 1.80
000 27,600 3,120 8.0 4.0 2.0 4.0 2.0 3.6 1.80
500 29,400 4,000 10.0 5.0 2.5 5.0 2.5 4.5 2.25
500 35,400 4,800 12.0 6.0 3.0 6.0 3.0 5.4 2.70
500 41,400 4,680 12.0 6.0 3.0 6.0 3.0 5.4 2.70 200 5,000 830 2.0 1.0 0.5 1.0 0.5 0.9 0.45 400 10,100 1,660 4.0 2.0 1.0 2.0 1.0 1.8 0.90
500 12,600 1,620 4.0 2.0 1.0 2.0 1.0 1.8 0.90
000 15,600 2,490 6.0 3.0 1.5 3.0 1.5 2.7 1.35
000 20,400 3,320 8.0 4.0 2.0 4.0 2.0 3.6 1.80
500 25,800 4,150 10.0 5.0 2.5 5.0 2.5 4.5 2.25
500 30,600 4,980 12.0 6.0 3.0 6.0 3.0 5.4 2.70
CFM
Standard Motor
Total Fan Motor AMPS - 1 Phase
Optional PSC Motor
Optional ECM Motor
Page 5
All-Temp2B
Electric Defrost /
Specifications
(1) All fan motors are wired for single phase. (2) For 208/230 volt models, heaters are wired as standard for single phase on 1 through 4 fan models. 5 and 6 fan models are
wired 3 phase. 460 Volt models are only available in single phase and are compatible with all 3 phase systems.
Hot Gas Defrost /
Specifications
(1) All fan motors are wired for single phase operation
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
,
6
F P
I
4
F P
I
Model
6
F
P
I
4
F
P
I
Number
AE16-36B AE16-41B AE16-46B AE26-60B AE26-75B AE26-92B AE36-120B AE36-140B AE46-164B AE46-185B AE56-210B AE66-245B AE66-280B AE14-37B AE24-72B AE24-85B AE34-105B AE44-140B AE54-180B AE64-215B
-30°F -20°F -10°F +20° 230V 460V 230V 230V 1 PH 3 PH 1 PH 3,400 3,600 3,700 3,900 830 1.0 0.54 0.5 0.45 4.4 3.8 2.2 1,000 3,900 4,100 4,300 4,800 800 1.0 0.54 0.5 0.45 4.4 3.8 2.2 1,000 4,400 4,600 4,800 5,800 780 1.0 0.54 0.5 0.45 4.4 3.8 2.2 1,000 5,700 6,000 6,200 7,000 1,540 2.0 1.1 1.0 0.90 7.0 6.0 3.5 1,600 7,100 7,500 7,800 8,700 1,500 2.0 1.1 1.0 0.90 7.0 6.0 3.5 1,600 8,700 9,200 9,600 11,500 1,560 2.0 1.1 1.0 0.90 8.7 7.5 4.4 2,000
11,400 12,000 12,500 14,500 2,400 3.0 1.6 1.5 1.35 13.0 11.3 6.4 3,000 13,300 14,000 14,600 17,000 2,340 3.0 1.6 1.5 1.35 13.0 11.3 6.4 3,000 15,000 16,400 17,100 19,200 3,200 4.0 2.2 2.0 1.80 17.4 15.1 8.7 4,000 17,600 18,500 19,200 23,000 3,120 4.0 2.2 2.0 1.80 17.4 15.1 8.7 4,000 20,000 21,000 21,800 24,500 4,000 5.0 2.7 2.5 2.25 21.7 18.8 10.9 5,000 23,300 24,500 25,500 29,500 4,800 6.0 3.2 3.0 2.70 25.0 21.7 12.5 5,750 26,600 28,000 29,100 34,500 4,680 6.0 3.2 3.0 2.70 25.0 21.7 12.5 5,750
3,500 3,700 3,800 4,200 830 1.0 0.54 0.5 0.45 4.4 3.8 2.2 1,000 6,800 7,200 7,500 8,400 1,660 2.0 1.1 1.0 0.90 8.7 7.5 4.4 2,000 8,100 8,500 8,800 10,500 1,620 2.0 1.1 1.0 0.90 8.7 7.5 4.4 2,000
10,000 10,500 10,900 13,000 2,490 3.0 1.6 1.5 1.35 13.0 11.3 6.4 3,000 13,300 14,000 14,600 17,000 3,320 4.0 2.2 2.0 1.80 17.4 15.1 8.7 4,000 17,100 18,000 18,700 21,500 4,150 5.0 2.7 2.5 2.25 21.7 18.8 10.9 5,000 20,400 21,500 22,400 25,500 4,980 6.0 3.2 3.0 2.70 25.0 21.7 12.5 5,750
BTUH Capacity @ 10° T.D.
Evaporator Temperature
CFM
Motor Amps
Shaded Pole
1
PSC ECM 460V
Heater Amps 230V
2
Watts
Re-Evap Rev. Cycle -30° -20° -10° +20° 115V 230V 460V 115V 230V 115V 230V AH16-36B AG16-36B 3
AH16-41B AG16-41B 3 AH16-46B AG16-46B 4 AH26-60B AG26-60B 5 AH26-75B AG26-75B 7 AH26-92B AG26-92B 8 AH36-120B AG36-120B 11 AH36-140B AG36-140B 13 AH46-164B AG46-164B 15 AH46-185B AG46-185B 17 AH56-210B AG56-210B 20 AH66-245B AG66-245B 23 AH66-280B AG66-280B 26 AH14-37B AG14-37B 3 AH24-72B AG24-72B 6 AH24-85B AG24-85B 8 AH34-105B AG34-105B 10 AH44-140B AG44-140B 13 AH54-180B AG54-180B 17 AH64-215B AG64-215B 20
Number ECM
BTUH Capacity @ 10° T.D.
Evaporator Temperature PSCStandard
400 3,600 3,700 3,900 830 1.9 1.0 0.54 1.0 0.50 0.9 0.45 1A 900 4,100 4,300 4,800 800 1.9 1.0 0.54 1.0 0.50 0.9 0.45 1A 400 4,600 4,800 5,800 780 1.9 1.0 0.54 1.0 0.50 0.9 0.45 1A 700 6,000 6,200 7,000 1,540 3.8 2.0 1.1 2.0 1.0 1.8 0.90 2A 100 7,500 7,800 8,700 1,500 3.8 2.0 1.1 2.0 1.0 1.8 0.90 2A 700 9,200 9,600 11,500 1,560 3.8 2.0 1.1 2.0 1.0 1.8 0.90 2A
400 12,000 12,500 14,500 2,400 5.7 3.0 1.6 3.0 1.50 2.7 1.35 3A 300 14,000 14,600 17,000 2,340 5.7 3.0 1.6 3.0 1.50 2.7 1.35 3A 000 16,400 17,100 19,200 3,200 7.6 4.0 2.2 4.0 2.0 3.6 1.80 3A 600 18,500 19,200 23,000 3,120 7.6 4.0 2.2 4.0 2.0 3.6 1.80 3A 000 21,000 21,800 24,500 4,000 9.5 5.0 2.7 5.0 2.50 4.5 2.25 3A 300 24,500 25,500 29,500 4,800 11.4 6.0 3.2 6.0 3.0 5.4 2.70 4A
600 28,000 29,100 34,500 4,680 11.4 6.0 3.2 6.0 3.0 5.4 2.70 4A 500 3,700 3,800 4,200 830 1.9 1.0 0.54 1.0 0.50 0.9 0.45 1A 800 7,200 7,500 8,400 1,660 3.8 2.0 1.1 2.0 1.0 1.8 0.90 2A 100 8,500 8,800 10,500 1,620 3.8 2.0 1.1 2.0 1.0 1.8 0.90 2A
000 10,500 10,900 13,000 2,490 3.8 3.0 1.6 3.0 1.50 2.7 1.35 2A
300 14,000 14,600 17,000 3,320 7.6 4.0 2.2 4.0 2.0 3.6 1.80 3A
100 18,000 18,700 21,500 4,150 9.5 5.0 2.7 5.0 2.5 4.5 2.25 3A
400 21,500 22,400 25,500 4,980 11.4 6.0 3.2 6.0 3.0 5.4 2.70 3A
CFM
Fan Motor Amps¹Model
Re-Evap
HEA
Unmtd.
Page 6
6 3
Physical Data
g
g
Installation Notes:
(1) Install 12” away from back wall. (2) Drain connection on AA and AE units are centered on drain pan;
and on the left end (facing air discharge) on AH and AG units. (3) For long air throw requirements, specify high throw fan guard. (4) Unit height at drain end of hot gas models is as follows: 1,2, and 3
fan models = 15-7/8”, 4,5, and 6 fan models = 16-1/4”.
Models
AA AE/AH/AG Liquid† Suction Suction Han
18-41B EXT 1/2 ODS 5/8 ODS 2 19 18-53B EXT 1/2 5/8 2 19 18-66B EXT 1/2 5/8 2 19 28-76B EXT 1/2 5/8 2 33 28-97B EXT 1/2 7/8 2 33 28-106B EXT 1/2 7/8 2 37 28-122B EXT 1/2 7/8 2 33 28-134B EXT 1/2 7/8 2 37 38-160B EXT 1/2 1-1/8 2 55 38-195B EXT 1/2 1-1/8 2 55 48-212B EXT 1/2 1-1/8 3 36½ 36½ 81½ 254 48-264B EXT 1/2 1-1/8 3 36½ 36½ 81½ 262 58-275B EXT 1/2 1-1/8 3 54½ 36½ 99½ 312 68-318B EXT 1/2 1-1/8 4 36½ 36 36½ 117½ 354 68-390B EXT 1/2 1-1/8 4 36½ 36 36½ 117½ 370 16-39B 16-36B EXT 1/2 ODS 5/8 ODS 5/8 ODS 5/8 ODS 2 19 16-48B 16-41B EXT 1/2 5/8 5/8 5/8 2 19 16-58B 16-46B EXT 1/2 5/8 5/8 5/8 2 19 26-70B 26-60B EXT 1/2 5/8 7/8 5/8 2 33 26-87B 26-75B EXT 1/2 7/8 7/8 5/8 2 33 26-115B 26-92B EXT 1/2 7/8 7/8 5/8 2 37 36-145B 36-120B EXT 1/2 7/8 7/8 5/8 2 55 36-170B 36-140B EXT 1/2 1-1/8 1-1/8 5/8 2 55 46-192B 46-164B EXT 1/2 1-1/8 1-1/8 5/8 3 36½ 36½ 81½ 255 46-230B 46-185B EXT 1/2 1-1/8 1-1/8 5/8 3 36½ 36½ 81½ 265 56-245B 56-210B EXT 1/2 1-1/8 1-1/8 5/8 3 54½ 36½ 99½ 306 66-295B 66-245B EXT 1/2 1-1/8 1-1/8 5/8 4 36½ 36 36½ 117½ 353 66-345B 66-280B EXT 1/2 1-1/8 1-1/8 5/8 4 36½ 36 36½ 117½ 368 14-42B 14-37B EXT 1/2 ODS 5/8 ODS 5/8 ODS 5/8 ODS 2 19 24-84B 24-72B EXT 1/2 7/8 7/8 5/8 2 37 24-105B 24-85B EXT 1/2 7/8 7/8 5/8 2 37 34-130B 34-105B EXT 1/2 7/8 7/8 5/8 2 55 44-170B 44-140B EXT 1/2 7/8 1-1/8 5/8 3 36½ 36½ 81½ 251 54-215B 54-180B EXT 1/2 1-1/8 1-1/8 5/8 3 54½ 36½ 99½ 299 64-255B 64-215B EXT 1/2 1-1/8 1-1/8 5/8 4 36½ 36 36½ 117½ 340
TXV
TYPE
Refri
erant Connections
All AA AE/AH/AG of Wt.
HG‡
No. Ship
ers A B C W (lbs.)
Dimensions
(Inches)
27½ 33 — 27½ 34 — 27½ 36 — 41½ 48 — 41½ 51 — 45½ 58 — 41½ 60 — 45½ 63 — 63½ 79 — 63½ 84
27½ 41 — 27½ 44 — 27½ 47 — 41½ 54 — 41½ 55 — 45½ 62 — 63½ 78 — 63½ 85
27½ 42 — 45½ 49 — 45½ 55 — 63½ 79
Page 7
r
Electric Defrost Kits
Electric defrost kits consist of components that are necessary to control the defrost cycle. The optional kits are available as a factory installed option when ordered with a condensing unit. Not all Ed-Kits are available for all condensing unit models. The contents of each kit is described below, along with the function of each component. * - 1/2 through 3 HP models require ED-210 or ED-213.
Electric Defrost Kits
Timer: Initiates the defrost cycle. Also used as a over-
ride protection for defrost termination.
Auxiliary Switch: Is mounted on the compressor con-
tactor and prevents the defrost contactor from oper­ating whenever the compressor is energized.
Block-Out Relay: Serves the same function as auxil-
iary switch. Used when defrost contactor is not required (lower wattage single phase only).
Defrost Contactor: Carries amperage load for heaters. Fan Contactor: Used with 460V motors or when 230V
motors are wired 3 phase.
Sequencing Relays: Provides interconnection of multi-
ple unit coolers on a single system so that each unit cooler is allowed to individually terminate defrost on temperature.
¹ For use with 2 evaporators , 1/2 through 3 HP R-series systems ONLY!
Model
Numbe AE16-36B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 AE16-41B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 AE16-46B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 AE26-60B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 AE26-75B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 AE26-92B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 AE36-120B ED-10 ED-12 ED-20* ED-22 ED-33 ED-32 AE36-140B ED-10 ED-12 ED-20* ED-22 ED-33 ED-32 AE46-164B ED-10 ED-12 ED-23* ED-22 ED-35 ED-32 AE46-185B ED-10 ED-12 ED-23* ED-22 ED-35 ED-32 AE56-210B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34 AE66-245B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34 AE66-280B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34 AE14-37B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 AE24-72B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 AE24-85B ED-10 ED-12 ED-20* ED-22 ED-30 ED-32 AE34-105B ED-10 ED-12 ED-20* ED-22 ED-33 ED-32 AE44-140B ED-10 ED-12 ED-23* ED-22 ED-35 ED-32 AE54-180B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34 AE64-215B ED-11 ED-12 ED-23* ED-22 ED-35 ED-34
1 Unit Cooler Per System 2 Unit Coolers Per System 3 Unit Coolers Per System
230V 460V 230V 460V 230V 460V
KIT NO.
ED10-230/1 1 1-30A — ED11-230/3 1 1 1-30A
ED12-460/3 1 1 1-30A 1-25A — ¹ED210-230/1 1 1-30A — ¹ED213-230/1 1 1 1-50A — ¹ED213-230/3 1 1 1-50A
ED20-230/1 1 1-30A 2
ED22-460/3 1 1 2-15A 1-25A 2
ED23-230/1 1 1 2-25A 2
ED23-230/3 1 1 2-25A 2
ED30-230/1 1 1-30A 3
ED32-460/3 1 1 3-10A 1-25A 3
ED33-230/1 1 1 3-16A 3
ED34-460/3 1 1 3-16A 1-25A 3
ED35-230/1 1 1 3-33A 3
ED35-230/3 1 1 3-33A 3
TIMER
SWITCH
AUXILIARY
RELAY
BLOCK-OUT
DEFROST
FAN
CONTACTOR
CONTACTOR
RELAY
SEQUENCING
Page 8
2
B
201 Thomas French Dr ive Scottsboro AL 35769 • Tel: (256) 259-7400 • Fax: (256) 259-7468
Visit us on the Web: http://coldzone.htpgusa.com