Expansion valves are supplied with clamps for
securing the bulb to the suction line. The bulb must
be secured at the evaporator outlet, on the side of a
horizontal run of suction line, at the 4 o’clock or 8
o’clock position, before any traps. The bulb must be
in uniform contact with clean Copper tube and must
not bridge any fitting or uneven surface. A thermal
mastic or heat transfer compound may be used with
the expansion valve bulb and suction line for quicker
expansion valve response. DO not overtighten bulb
clamps or deform the bulb in any way.
Drain lines should be the size of the evaporator drain
pan connection or larger. They should not be
reduced in size. Plastic drain lines are often used in
coolers, however, Copper or metal lines are
recommended if room temperature is below 35°F. All
drain lines must be protected from freezing. All drain
lines must be trapped
and run to an open drain.
Drain lines should be sloped 4 inches per foot to
insure positive drainage. Never connect a
condensate drain directly to a sewer line. Never
drain onto a floor or walkway, creating a safety
hazard. Traps must be in warm ambient or be
protected from freezing. It may be necessary to run
heat tape the entire length of the drain line and trap
to prevent freezing. Insulating the drain line is
recommended with the heat tape energized
continuously. Drain properly and safely!
All piping must be adequately supported to prevent
vibration and breaking. Tube clamps should have a
gasketed surface to prevent abrasion. Inspect all
piping while the equipment is operating and add
supports to prevent stress and vibration. When the
liquid solenoid opens and closes, the liquid line will
tend to move forcefully. Without proper support the
joints at the liquid solenoid, expansion valve,
distributor, and distributor leads can fracture. Take
care to secure the liquid line at the evaporator. Line
supports are inexpensive compared to downtime and
refrigerant loss. All piping must be protected where
it passes through walls or ceilings. Precautions
should be taken to see that the piping does not touch
any structural members and is properly supported in
order to prevent the transmission of vibration into the
building. The piping chase must be thoroughly
sealed to protect the tube and prevent ambient air
from entering the refrigerated space. Seal around
the drain line where it passes through the wall. Air
leaks can cause equipment problems, damage the
structure and product, increase load, increase
operating cost, and can cause a safety hazard.
Eliminate all air leaks. See Table 11 for
recommended line support spacing.
In low temperature application, or where proper oil
circulation cannot be maintained, an oil separator
may be required. When operating at evaporator
temperatures of -20°F and lower, oil separators
should be considered in order to minimize the
amount of oil in circulation.
In addition to the critical nature of oil return, there is
no better invitation to system difficulties than an
excessive refrigerant charge. A reasonable pressure
drop is far more preferable than oversized lines which
can contain refrigerant far in excess of the systems
needs. On systems with a larger refrigerant charge,
or on systems where liquid floodback is likely to
occur, a suction line accumulator is strongly
recommended.
LEAK TESTING
After all refrigerant connections are made, have been
visually inspected and secured, add proper system
refrigerant until the pressure is 25 to 35 PSI. Then
pressurize with dry nitrogen up to 120 to 140 PSI.
Always use a pressure reducing regulator. Wait 20 to
30 minutes for the refrigerant to reach all parts of the
system. Using an electronic leak detector, check all
connections and components, both factory and field
installed
. The compressor, evaporator coil, and
condenser coil must be checked. Valves and
controls must be checked. Repair any leaks found
and re-check until no leaks are located and the
pressure holds steady. Leave the system
pressurized overnight to verify that the pressure
remains unchanged.
Unlocated leaks can mean unprofitable call back,
additional refrigerant cost, higher energy cost, and
possible internal contamination and failure of the
system. With highly hygroscopic polyol ester (POE)
lubricants, leak detection is essential to prevent
moisture from entering a system. The system
installation must be leak free!
After leak testing has been completed, the system
must be thoroughly evacuated before charging.
7