Russell 10H22, DLD10M44 Installation Manual

Safety Information and Guidelines.....................................................…….....
Locating and Mounting Condensing Units ....................................………......
Locating and Mounting Evaporators........................................……......…......
Piping .............................................................................................……......
Leak Testing ................................................................................…...……....
Suction Line Design ...............................................................…….…...........
Equivalent Feet of Tube ........................................................…….........….....
Weight of Refrigerant in Copper Tube.................................…….....….…........
Recommended Line Sizes ..........................................................…….….....
Field Wiring.....................................................................................…….......
Field Wiring Diagrams ................................................................……..….....
Evacuation .................................................................................…….….......
Charging and Start-Up .................................................................…….….....
Charging Flooded Condenser Systems .................….......................………...
Pressure Control Settings ..............................................................………...
Indoor Condensing Unit Ventilation ................................................………....
Defrosting Evaporators ...................................................................…...…...
Product Loading and Air Circulation .............................................…….….....
Operating Pressures and Temperatures .......................................……...…...
System Start-Up Check List ...........................................................…...…....
System Service Check List ...........................................................………....
Trouble-Shooting Systems ............................................................…….......
System Maintenance .....................................................................…….......
Ordering Replacement Parts .......................................................………......
SYSTEMS
IOM 550.1
JULY, 2003
THE GUIDE FOR
INSTALLING, STARTING - UP,
OPERATING and MAINTAINING
RUSSELL REFRIGERATION SYSTEMS
TABLE OF CONTENTS
2 2
3 4 - 5 6 - 7
7
8
9
9
10 - 13
14
14 - 16
17 18 19 20 20
21 - 22
22 23 24 25
26 - 27
28 28
221 S. Berry St. • P.O. Box 1030 • Brea, CA 92822-1030 • Tel: (714) 529-1935 • FAX (714) 529-7203
SAFETY INFORMATION
!
LOCK
disconnects in the
OFF
position to prevent accidental turning on and injury.
!
Check all items against the bill of lading to make sure all crates and cartons have been received.
If there are any shortages or damage, report it immediately to the carrier and file a freight claim.
Damaged equipment is the delivering carrier's responsibility. Take care not to damage equipment
when uncrating. Check for concealed damage. Do not return damaged equipment to the factory
without prior approval. A Return Material Authorization (RMA) must be obtained in advance.
Check the unit specplate. Verify that the specplate voltage agrees with the available power supply.
Large condensing units, remote condensers, and evaporators should be left on their shipping skid
until at their final location. Do not use the shipping skid as a permanent base.
Good rigging and handling practice must be used to protect units from damage. Having proper
handling equipment at the jobsite is most important and should be planned in advance. Always use
spreader bars when lifting with cable, chain, or slings. Do not hoist a crate from it's upper members.
If rigging is required, support the crate from the skid. All crates are blocked up for forklift handling.
Do not forklift against sheetmetal panels or coils. Always lift against a structural part of the skid or
unit at the center of gravity. Secure units to a forklift to prevent slipping off.
Large condensing units have compressors mounted near one end that offsets the center of gravity.
Find the center of gravity near the compressor end to prevent tipping when lifting. Smaller, lighter
units may be carefully manhandled for short distances. Observe the units for additional lifting and
rigging decals.
READ THESE INSTRUCTIONS ALL THE WAY THROUGH BEFORE STARTING WORK
Make sure all power sources are disconnected before doing any service work.
Commercial refrigeration equipment should be installed, started-up, maintained, and serviced by trained and certified personnel having experience with this type of equipment.
All field wiring must conform to the requirements of the equipment, applicable local codes and the National Electrical Code. Always use correct size copper conductors.
Sheet metal and coil surface have sharp edges that are a potential injury hazard. Handle carefully, using gloves and other protective safety wear to prevent injury.
COMPLY WITH SAFETY AND CAUTION LABELS ON THE EQUIPMENT
THINK SAFETY! WORK SAFELY
RECEIVING YOUR EQUIPMENT
INSPECTION
« « « « Items returned without an RMA label will be refused. « «« «
RIGGING and HANDLING
2
3
LOCATING AND MOUNTING CONDENSING UNITS
Condensing units must be located where there is an unrestricted supply of clean, fresh air. Areas with corrosive vapors or materials should be avoided, as should areas with polluted air. Do not locate units where air discharge from one will enter into the air intake of others. Avoid locating units in restricted spaces where heat will build up and can enter the condenser. Condensing units with horizontal air flow should be positioned so that the direction of air flow through the condenser is the same as the prevailing wind. Make sure there is room around the unit for regular inspection and service. Mount all condensing units level.
Roof mounted condensing units must have adequate support for their operating weight plus a safety factor. They should be mounted above supporting walls, over hallways, storage areas, or auxillary areas that are not sensitive to noise or vibration. Mount them where sound levels are not an important factor.
Pad mounted condensing units should be mounted on smooth and level pads a minimum of 4 inches above ground level. They should be mounted away from windows, doors, and other areas sensitive to noise. The area surrounding a pad mounted unit preferably will be concrete, asphalt, or other smooth, hard, clean level surface. This will keep the condenser coil clean from grass, dirt, and weed clippings. A security fence also helps to keep leaves and other debris out of the coil. Protecting the condensing unit also protects the product stored in the cooler or freezer!
Condensing units, piping and disconnects should not be accessible to unauthorized persons. To protect the equipment from tampering and vandalism and protect people from accidental
injury, a security fence with locked access is highly recommended. Condensing units accessible to the general public often receive damage to the coil, piping, fans, or other components. Protect your equipment, your products in storage, and protect yourself from liability. Prevent accidents and loss.
Condensing units must be mounted to pads or structural rails with adequate size bolts to prevent the unit from shifting or changing postion. Mounting holes are provided for proper size fasteners. Iso-pads are recommended to absorb vibration and reduce noise. Seismic isolators may be required in some localities. Follow the isolator manufacturers recommendation when selecting and applying isolators. Mount units level.
Condensing units with spring mounted compressors are shipped with blocks or retainers under the compressor feet to keep it from shaking during shipment. On Copeland H and K model compressors, remove the blocks and loosen the mounting nut to have 1/16 inch between the nut and rubber spacer. On 3 HP and larger models, mounting nuts must be removed to insert the rubber spacer. Remove the blocks, insert the rubber spacer over the mounting stud, replace the nuts and tighten to 1/16 inch from the spacer. Do not tighten mounting nuts tight against the rubber spacer or foot. Units with iso-pad mounted compressors are shipped with the mounting nuts tight and they should be checked to be sure they have not loosened in shipment.
Observe minimum clearance recommendations below. Do not locate any unit to be bordered by tall walls or obstructions on three or more sides, even when the clearance are observed. The minimum space between units is 2x dimensions shown.
Table 1
CONDENSING MINIMUM
UNIT DIMENSION (Inches)
DESCRIPTI ON A B C
MiniCon 1/2 thru 2 HP 60 24 36
MiniCon 3 thru 6 HP 72 24 36
D Series 3 thru 22 HP 72 30 48
V Series 20 thru 80 HP 48 48 48
B
CONDENSING UNIT
DISCHARGE AIR INTAKE AIR
A C
B
Drawing 1
12"
15"
18"
24"
30"
36"
42"
48"
*
H
LOCATING WALK-IN EVAPORATORS
Table 2
EVAPORATOR
HEIGHT (Key Dim.)
H
Critical Minimum Dimension
Front wall
Door
MINIMUM DIMENSION FOR GOOD AIR CIRCULATION
AND EVAPORATOR PERFORMANCE
Unit to
Back Wall *
1 x H
Unit to
Side Wall
1 x H
Unit
to Unit
2 x H
12" 12" 24" 60" 15" 15" 30" 75" 18" 18" 36" 90" 24" 24" 48" 120" 30" 30" 60" 150" 36" 36" 72" 180" 42" 42" 84" 210" 48" 48" 96" 240"
H = Height of Evaporator ‡ Minimum walk-in height of 7'-0"
Obstruction
Free Area
Air
5 x H Min.
Product Storage Area
Unit to
Front Wall
5 x H
Air Product
Unit
to Floor
3 x H
60" ‡ 60" ‡ 60" ‡ 72"
90" 108" 126" 144"
Evap.
12"
3 x H
* Refer to Table 2 for dimension H Floor
SIDE VIEW
Drawings are not to scale No doors at side or back of evaporators. Back wall
H
H 2 x H H
Side Evaporator wall
Air Air
Evaporator
5 x H Side
Alternate wall Door location
* Refer to Table 2 for dimension H Door Front wall
TOP VIEW
4
Locate evaporators for the air pattern to cover all of the piping, and personnel. Heavy zinc plated or stainless
LOCATING AND MOUNTING WALK-IN EVAPORATORS
See Table 3
See Table 3
room. Do not restrict the inlet or outlet air stream. steel bolts should be used to mount evaporators. We Avoid placing evaporators above or close to doors. recommend a minimum 5/16" diameter for All-Temp, Direct the air stream toward the door when possible Flow-Temp and Ceiling-Temp units. A minimum 3/8" diameter or arrange to blow down an aisle. Allow sufficient should be used with Inter-Temp and Ultra-Temp units. clearance for air circulation and servicing the unit. Use flat washers next to hanger bars and tighten all fasteners The ceiling structure must have adequate strength to support all mechanical equipment, components,
Drawing 4 Drawing 5
Air
condensate draining. All drain lines must be trapped.
securely. Hang all unit coolers level to insure positive
Air
2 x H* 2 x H*
EVAP.
Air
EVAP.
Air
*Refer to Table 2 for dimension H
TOP VIEW - Large coolers or freezers where one wall will not accommodate all evaporators or desired air throw is excessive.
Drawing 6 Drawing 7
Air
A C
EVAP. B EVAP.
A A
C
EVAP.
Air Air
Air Air D
C
Air
TOP VIEW - Single Centermount Unit
TOP VIEW - Multiple Centermount Units
RECOMMENDED SPACING FOR CENTERMOUNT EVAPORATORS
Table 3
A B C
Min. Min. Max. Max. Min. Max.
Dimensions are in feet. One foot minimum between bottom of unit and top of product.
Max. Min.
1' 2' 16' 12' 8' 24'
8' 3'
D
5
PIPING
Condensing Unit and Evaporator coils are thoroughly cleaned and dehydrated at the factory. Care must be taken when field piping to prevent foreign materials and moisture from entering the system. Do not leave units or piping open to the atmosphere any longer than necessary. Use ACR grade Copper tube, keeping it dry, clean, and capped. If type “L” tube is used, it should be thoroughly cleaned internally. When brazing, always pass dry nitrogen through the tubing to prevent oxide and scale from forming. A suitable silver alloy solder should be used on suction and liquid lines. Use only Wrot Copper fittings. Long radius elbows should be used. Install all piping and components in accordance with local and national codes and in conformance with good refrigeration practice for proper operation of the systems.
The suction line and its components must be selected and installed with extreme care. The suction line must be sized for high enough refrigeration velocity to assure good oil return, and low enough pressure drop to prevent excessive system capacity loss. The optimum line size for a system will result in a reasonable velocity at minimum pressure drop. Total suction line pressure loss should not exceed 2°F equivalent loss.
Suction line risers must be carefully selected, have an oil trap at the bottom and at 15 foot intervals up the riser. The should be the same size as the vertical riser connected to its outlet. Riser should not be larger in diameter than horizontal runs.
Horizontal runs of suction line should slope 1 inch per 10 feet in the direction of flow. A 1/4 inch male flare Schrader fitting should be installed in the suction line at the evaporator outlet to obtain accurate evaporator pressure and superheat readings. Refer to pages 8 though 13 for line size recommendations and piping diagrams. Note the maximum size for suction line risers.
Liquid lines, both horizontal and vertical, are normally the same size. In vertical lines with upward flow there will be a pressure loss similar to that in water line riser, due to the lift involved. If ignored, this pres­sure loss can result in liquid line flash gas that will prevent good expansion valve and system performance. Sizing the liquid line too small will also
result in flash gas. Sizing a liquid line larger than
necessary will increase the system refrigerant charge. Flash gas can be avoided by adding subcooling to the system, however, subcooling should not be considered as an acceptable alternative to properly sized liquid lines.
One method to obtain liquid subcooling and return gas superheat is to join the liquid and suction line together and then insulate them. This economical method is often used on vertical lines. Another alternative is to use a manufactured liquid-suction heat exchanger. This type of heat exchanger is usually located inside the cooler or freezer, near the evaporator. D series and V series condensing units include an integral liquid subcooling circuit in the condenser coil. Any one of these methods will normally provide enough subcooling to offset the liquid line pressure loss due to friction and lift. Liquid lines with more than 30 feet of vertical lift need special attention!
A liquid line solenoid should be installed near the expansion valve inlet. If there are multiple evaporators, locate the solenoid near the branch line to the first evaporator.
Before installing the expansion valve on the distributor, check the distributor to be sure it has a nozzle installed or is a venturi type. For optimum
performance, the expansion valve outlet should be installed directly to the distributor. If reducing couplings or adapters are required keep them close coupled. Do not have elbows between the expansion valve and distributor. The expansion valve must be
selected to match the system capacity. Follow the
expansion valve manufacturers ratings when select­ing the valve and use the appropriate capacity multi­plier if liquid is subcooled below 70°F. If the amount of liquid subcooling may vary, a balanced port expan­sion valve should be used.
Evaporators with 1/2 inch flare nut (FN) inlet distributors can be converted to a sweat type inlet. All distributors have room to remove the flare with a mini-cutter. The inlet would be 1/2 inch OD and an expansion valve with 1/2” ODF outlet would fit. Alco type HFS or Sporlan type EG, SBF or S expansion valves are available with 1/2” ODF extended Copper outlet connections. To protect the valve(s), wrap them with a wet rag while brazing. Disassembly of the valve is not required.
6
Expansion valves are supplied with clamps for securing the bulb to the suction line. The bulb must be secured at the evaporator outlet, on the side of a horizontal run of suction line, at the 4 o’clock or 8 o’clock position, before any traps. The bulb must be in uniform contact with clean Copper tube and must not bridge any fitting or uneven surface. A thermal mastic or heat transfer compound may be used with the expansion valve bulb and suction line for quicker expansion valve response. DO not overtighten bulb clamps or deform the bulb in any way.
Drain lines should be the size of the evaporator drain pan connection or larger. They should not be reduced in size. Plastic drain lines are often used in coolers, however, Copper or metal lines are recommended if room temperature is below 35°F. All drain lines must be protected from freezing. All drain lines must be trapped
and run to an open drain. Drain lines should be sloped 4 inches per foot to insure positive drainage. Never connect a condensate drain directly to a sewer line. Never drain onto a floor or walkway, creating a safety hazard. Traps must be in warm ambient or be protected from freezing. It may be necessary to run heat tape the entire length of the drain line and trap to prevent freezing. Insulating the drain line is recommended with the heat tape energized continuously. Drain properly and safely!
All piping must be adequately supported to prevent vibration and breaking. Tube clamps should have a gasketed surface to prevent abrasion. Inspect all piping while the equipment is operating and add supports to prevent stress and vibration. When the liquid solenoid opens and closes, the liquid line will
tend to move forcefully. Without proper support the joints at the liquid solenoid, expansion valve, distributor, and distributor leads can fracture. Take care to secure the liquid line at the evaporator. Line supports are inexpensive compared to downtime and refrigerant loss. All piping must be protected where it passes through walls or ceilings. Precautions should be taken to see that the piping does not touch any structural members and is properly supported in order to prevent the transmission of vibration into the building. The piping chase must be thoroughly sealed to protect the tube and prevent ambient air from entering the refrigerated space. Seal around the drain line where it passes through the wall. Air leaks can cause equipment problems, damage the structure and product, increase load, increase operating cost, and can cause a safety hazard. Eliminate all air leaks. See Table 11 for recommended line support spacing.
In low temperature application, or where proper oil circulation cannot be maintained, an oil separator may be required. When operating at evaporator temperatures of -20°F and lower, oil separators should be considered in order to minimize the amount of oil in circulation.
In addition to the critical nature of oil return, there is no better invitation to system difficulties than an excessive refrigerant charge. A reasonable pressure
drop is far more preferable than oversized lines which
can contain refrigerant far in excess of the systems needs. On systems with a larger refrigerant charge,
or on systems where liquid floodback is likely to
occur, a suction line accumulator is strongly recommended.
LEAK TESTING
After all refrigerant connections are made, have been
visually inspected and secured, add proper system
refrigerant until the pressure is 25 to 35 PSI. Then pressurize with dry nitrogen up to 120 to 140 PSI. Always use a pressure reducing regulator. Wait 20 to 30 minutes for the refrigerant to reach all parts of the system. Using an electronic leak detector, check all connections and components, both factory and field installed
. The compressor, evaporator coil, and condenser coil must be checked. Valves and controls must be checked. Repair any leaks found and re-check until no leaks are located and the pressure holds steady. Leave the system
pressurized overnight to verify that the pressure remains unchanged.
Unlocated leaks can mean unprofitable call back, additional refrigerant cost, higher energy cost, and possible internal contamination and failure of the system. With highly hygroscopic polyol ester (POE) lubricants, leak detection is essential to prevent moisture from entering a system. The system installation must be leak free!
After leak testing has been completed, the system must be thoroughly evacuated before charging.
7
DOUBLE RISER WHEN REQUIRED
LOOP TO PREVENT LIQUID DRAINING INTO COMPRESSOR
SLOPE
EVAPORATORS ABOVE
COMPRESSOR
DOUBLE RISER
WHEN REQUIRED
EVAPORATORS BELOW
COMPRESSOR
EVAPORATOR ABOVE
COMPRESSOR
EVAPORATOR BELOW
COMPRESSOR
SMALLER
DOUBLE RISERDOUBLE TRAP
15' MAX
ADD TRAP
SLOPE
RISER
SLOPE
LARGER RISER
SLOPE
SLOPE
EVAPORATORS ABOVE
COMPRESSOR
SLOPE
SUCTION LINE DESIGN
8
Loading...
+ 19 hidden pages