RHLA/RHLL feature GE’s new X-13 (ECM) motor which
provides enhanced SEER performance with most Rheem
outdoor units.
■
11/2 ton [5.3 kW] through 5 ton [17.6 kW] models are
between 42
1
/2 to 551/2 inches [1080 to 1410 mm] tall and 22
inches [559 mm] deep.
■
Versatile 4-way convertible design for upflow, downflow,
horizontal left and horizontal right applications.
■
Factory-installed high efficiency indoor coil.
■
All models meet or exceed 330 to 400 CFM [156 to 189 L/s]
per ton at .3 inches [.7 kPa] of external static pressure.
■
Enhanced airflow up to .7" external static pressure.
■
Sturdy construction with 1.0 inch [.24 kPa] of reinforced foil
faced jacket insulation for excellent thermal and sound
insulation.
■
Field-installed auxiliary electric heater kits provide exact
heat for indoor comfort. Kits include circuit breakers which
meet UL and cUL requirements for service disconnect.
Page 2
2Rheem Heating, Cooling and Water Heating
Engineering Features
GENERAL TERMS OF LIMITED WARRANTY
Rheem will furnish a replacement for any part of this product
which fails in normal use and service within the applicable
periods stated, in accordance with the terms of the limited
warranty.
Conditional Parts (Registration Required) .........Ten (10) Years
For Complete Details of the Limited Warranty, Including
Applicable Terms and Conditions, See Your Local Installer or
Contact the Manufacturer for a Copy.
RHLL/RHSL- Series
■
The most compact unit design available, all standard heat air
handler models only 42
1
/2 to 551/2 inches [1079 to 1409 mm] high.
■
Attractive pre-painted cabinet exterior.
■
Rugged wall steel cabinet construction, designed for added
strength and versatility.
■
1.0" foil faced insulation mechanically retained in blower
compartment for excellent thermal and sound performance.
■
Four leg blower motor mount.
■
Blower housing with controls, motor and blower. Slide out
design for service and maintenance convenience.
■
Traditional open wire element design for heat applications.
■
Field convertible for vertical downflow, horizontal left hand or
right hand air supply.
■
3 combustible floor base accessories fit all model sizes when
required for downflow installations on combustible floors.
■
Indoor coil design provides low air side pressure drop, high
performance and extremely compact size.
[ ] Designates Metric Conversions
■
Expansion valve on indoor coil provides for operation with air
conditioning or heat pump using the same coil.
■
Coils are constructed of aluminum fins bonded to internally
grooved copper tubing.
■
Molded polymer corrosion resistant condensate drain pan is
provided on all indoor coils.
■
Supply duct flanges provided as standard on air handler cabinet.
■
Provisions for field electrical, connections available from either
side or top of the air handler cabinet.
■
Connection point for high voltage wiring is inside the air handler
cabinet. Low voltage connection is made on the outside of the
air handler cabinet.
■
Concentric knockouts are provided for power connection to
cabinet. Installer may pull desired hole size up to 2 inches
[51 mm] for 1
• Supply circuit protective devices may be fuses or
“HACR” type circuit breakers.
• Largest motor load is included in single circuit
and multiple circuit.
• If non-standard fuse size is specified, use the next
larger fuse size.
• J Voltage (230V) single-phase air handler is
designed to be used with single or three phase
230 volt power. In the case of connecting 3-phase
power to the air handler terminal block, bring
only two leads to the terminal block. Cap, insulate and fully secure the third lead.
• The air handlers are shipped from the factory with
the proper indoor coil installed, and cannot be
ordered without a coil.
• The air handlers do not have an internal filter
rack. An external filter rack or other means of
filtration is required.
Page 4
4Rheem Heating, Cooling and Water Heating
Return Air Opening Dimensions
Unit Dimensions
[ ] Designates Metric Conversions
( ) Designates Unit with Double Coil Cabinet
Unit Dimensions & Weights
ELECTRICAL CONNECTIONS
MAY EXIT TOP OR EITHER SIDE
HIGH VOLTAGE CONNECTION
3
/32 [27.8 mm], 131/32 [50 mm] DIA. KNOCKOUTS.
1
LOW VOLTAGE CONNECTION
5
/8 [15.9 mm] AND 7/8 [22.2 mm] KNOCKOUT
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
HORIZONTAL APPLICATION ONLY
PRIMARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
UPFLOW/DOWNFLOW APPLICATION ONLY
LIQUID LINE CONNECTION
COPPER (SWEAT)
VAPOR LINE CONNECTION
COPPER (SWEAT)
7
/8 [22.2 mm],
SUPPLY AIR
5
10
/16
[262 mm]
A
191/2 [495 mm]
RETURN AIR
OPENING
UPFLOW UNIT SHOWN:
UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW,
HORIZONTAL RIGHT OR LEFT AIR SUPPLY.
NOTE: 24 CLEARANCE REQUIRED IN FRONT OF
UNIT FOR FILTER AND COIL MAINTENANCE.
Airflow performance data is based on cooling performance
with a coil and no filter in place. Select performance table for
appropriate unit size, voltage and number of electric heaters to
be used. Make sure external static applied to unit allows operation within the minimum and maximum limits shown in table
below for both cooling and electric heat operation. For optimum
blower performance, operate the unit in the .3 [8 mm] to .7
inches [18 mm] W.C. external static range. Units with coils
should be applied with a minimum of .1 inch [3 mm] W.C.
external static range.
Airflow Operating Limits
[ ] Designates Metric Conversions
Model Cabinet Size1717/21
Cooling BTUH x 1,000
Cooling Tons Nominal
Heat Pump or Air Conditioning
Maximum Heat/Cool CFM [L/s]
(37.5 CFM [18 L/s]/1,000 BTUH)
(450 CFM [212 L/s]/Ton Nominal)
Heat Pump or Air Conditioning
Nominal Heat/Cool CFM [L/s]
(33.3 CFM [16 L/s]/1,000 BTUH)
(400 CFM [189 L/s]/Ton Nominal)
Heat Pump or Air Conditioning
Minimum Heat/Cool CFM [L/s]
(30.0 CFM [14 L/s]/1,200 BTUH)
(360 CFM [170 L/s]/Ton Nominal)
Maximum kW Electric Heating
& Minimum Electric Heat CFM [L/s]13487 [230]13617 [291]18814 [384]181054 [497]
Maximum Electric Heat Rise °F [°C]80 [26.7]63 [17.2]66 [18.9]51 [10.6]49 [9.4]50 [10]50 [10]
-018
1.5
675
[319]
600
[283]
540
[255]
-024
2
900
[425]
800
[378]
720
[340]
-030
2.5
1125
[531]
1000
[472]
900
[425]
-036
3
1350
[637]
1200
[566]
1080
[510]
-038
3.5
1350
[637]
1200
[566]
1080
[510]
18
1042 [492]
21
-042
3.5
1575
[743]
1400
[661]
1260
[595]
20
1171 [553]251502 [709]251502 [709]
-048
4
1800
[850]
1600
[755]
1440
[680]
-048
4
1800
[850]
1600
[755]
1440
[680]
24
-060
5
1930
[911]
1800
[850]
1620
[765]
30
1666 [786]
54 [12.2]52 [11.1]
Page 7
Rheem Heating, Cooling and Water Heating7
240V Airflow Performance Data—RHSL (PSC Motor)
Notes: • All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• If the application external static is less than 0.5" WC, adjust the motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap. Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the yellow motor wire.
• Replace the cap on the purple motor wire.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.
Approximate Airflow = Airflow without heater - (Airflow without heater - Airflow with maximum heater) x (N kW/maximum heater kW)
Notes:• All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• All 115V PSC motors are shipped on high speed.
• If the application external static is less than 0.5" WC, adjust the
motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and
plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap.
Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the
yellow motor wire.
• Replace the cap on the purple motor wire.
• All 480V PSC motors are shipped on high speed.
• If the application external static is less than 0.5" WC, adjust the
motor speed to the low static speed as described below for 3-ton
through 4-ton air handlers.
• Unplug the black motor wire off the relay and remove the cap from
the red motor wire.
• Plug the red motor wire to the relay and connect the black motor
wire with the yellow motor wire.
• For 5-ton air handler, unplug the black motor wire off the relay and
plug in the red motor wire, then cap the black motor wire. There is
no yellow motor wire on 5-ton air handler.
WARNING: Do not connect red motor wire with yellow motor wire in any
circumstance on 480V PSC motors. Connecting red motor wire with yellow
motor wire will result in permanent motor damage.
• The above airflow table lists the airflow information for air handlers
without heater and air handler with maximum heater allowed for each
model.
• The following formula can be used to calculate the approximate airflow, if a
smaller (N kW) than the maximum heater kit is installed. Approximate
Airflow = Airflow without heater - (Airflow without heater - Airflow with
maximum heater) x (N kW/maximum heater kW)
[ ] Designates Metric Conversions
Rheem Heating, Cooling and Water Heating9
Model
No.
RHSL
-1817
No Heater
-1817
with 13 kW
Heater
-2417
No Heater
-2417
with 13 kW
Heater
-3017
No Heater
-3017
with 18 kW
Heater
-3617/-3621
No Heater
Motor
Speed
from
Factory
High
High
High
High
High
High
High
Manufacturer
Recommended
Air-Flow Range
(Min/Max) CFM
Notes:• All 208/240V PSC motors have voltage taps for 208 and 240 volts.
• All 208/240V PSC motors are shipped on high speed and 240 volts.
• All 115V PSC motors are shipped on high speed.
• If the application external static is less than 0.5" WC, adjust the
motor speed to the low static speed as described below:
• Unplug the black motor wire off the relay on the control board and
plug in the red motor wire.
• Replace the cap on the black motor wire.
• Voltage change (208/240V motors):
• Move the orange lead to transformer 208V tap from 240V tap.
Replace the wire cap on 240V tap.
• Unplug the purple motor wire off the transformer and plug in the
yellow motor wire.
• Replace the cap on the purple motor wire.
• All 480V PSC motors are shipped on high speed.
• If the application external static is less than 0.5" WC, adjust the
motor speed to the low static speed as described below for 3-ton
through 4-ton air handlers.
• Unplug the black motor wire off the relay and remove the cap from
the red motor wire.
• Plug the red motor wire to the relay and connect the black motor
wire with the yellow motor wire.
• For 5-ton air handler, unplug the black motor wire off the relay and
plug in the red motor wire, then cap the black motor wire. There is
no yellow motor wire on 5-ton air handler.
WARNING: Do not connect red motor wire with yellow motor wire in any
circumstance on 480V PSC motors. Connecting red motor wire with yellow
motor wire will result in permanent motor damage.
• The above airflow table lists the airflow information for air handlers
without heater and air handler with maximum heater allowed for each
model.
• The following formula can be used to calculate the approximate airflow, if a
smaller (N kW) than the maximum heater kit is installed. Approximate
Airflow = Airflow without heater - (Airflow without heater - Airflow with
maximum heater) x (N kW/maximum heater kW)
Notes: X-13 (ECM) motor speed changes.
All X-13 (ECM) motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage.
Speed tab 4 (low static) and Speed tab 5 (high static) are for higher tonnage.
X-13 (ECM) air handlers are always shipped from factory at Speed tab 5, except for -4824, which is set at Speed tab 3. For instance, RHLL-HM2417JA is
always shipped at high static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the X-13 (ECM) motor.
The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static Speed tab 3 (lower tonnage)
and 5 (higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate Speed tab as required by the application needs.
• The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.Approximate Airflow = Airflow without heater – (Airflow without heater – Airflow with maximum heater) x (N kW/maximum heater kW)
Notes: X-13 (ECM) motor speed changes.
All X-13 (ECM) motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage.
Speed tab 4 (low static) and Speed tab 5 (high static) are for higher tonnage.
X-13 (ECM) air handlers are always shipped from factory at Speed tab 5, except for -4824, which is set at Speed tab 3. For instance, RHLL-HM2417JA is
always shipped at high static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the X-13 (ECM) motor.
The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static Speed tab 3 (lower tonnage)
and 5 (higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate Speed tab as required by the application needs.
• The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.Approximate Airflow = Airflow without heater – (Airflow without heater – Airflow with maximum heater) x (N kW/maximum heater kW)
Notes: X-13 (ECM) motor speed changes.
All X-13 (ECM) motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage.
Speed tab 4 (low static) and Speed tab 5 (high static) are for higher tonnage.
X-13 (ECM) air handlers are always shipped from factory at Speed tab 5, except for -4824, which is set at Speed tab 3. For instance, RHLL-HM2417JA is
always shipped at high static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the X-13 (ECM) motor.
The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static Speed tab 3 (lower tonnage)
and 5 (higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate Speed tab as required by the application needs.
• The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.Approximate Airflow = Airflow without heater – (Airflow without heater – Airflow with maximum heater) x (N kW/maximum heater kW)
Notes: X-13 (ECM) motor speed changes.
All X-13 (ECM) motors have 5 speed tabs. Speed tab 1 is for continuous fan. Speed tab 2 (low static) and Speed tab 3 (high static) are for lower tonnage.
Speed tab 4 (low static) and Speed tab 5 (high static) are for higher tonnage.
X-13 (ECM) air handlers are always shipped from factory at Speed tab 5, except for -4824, which is set at Speed tab 3. For instance, RHLL-HM2417JA is
always shipped at high static 2-ton airflow (Speed tab 5). To change to 1.5-ton airflow, move the blue wire to Speed tab 2 or 3 on the X-13 (ECM) motor.
The low static Speed tab 2 (lower tonnage) and 4 (higher tonnage) are used for external static below 0.5" WC. The high static Speed tab 3 (lower tonnage)
and 5 (higher tonnage) are used for external static exceeding 0.5" WC. Move the blue wire to the appropriate Speed tab as required by the application needs.
• The airflow for continuous fan (Speed tab 1) is always set at 50% of the Speed tab 4.
• The above airflow table lists the airflow information for air handlers without heater and air handler with maximum heater allowed for each model.
• The following formula can be used to calculate the approximate airflow, if a smaller (N kW) than the maximum heater kit is installed.Approximate Airflow = Airflow without heater – (Airflow without heater – Airflow with maximum heater) x (N kW/maximum heater kW)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all
auxiliary heating requirements.
➀ This does not include “D Voltage”. D Voltage = 480 Volts.
• Supply circuit protective devices may be fused or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as
multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be
used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details.
• Largest motor load is included in single circuit or circuit 1 of multiple circuit.
• Heater loads are balanced on 3 PH. models with 3 or 6 heaters only.
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• No electrical heating elements are permitted to be used with “A” voltage (115V) air handler.
• J voltage (208/240V) single phase air handler is designed to be used with single or three phase
208/240V volt electric heaters. In the case of connecting 3 phase power to air handler terminal
block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure
the third lead.
• Do not use 480V electrical heaters on 208/240V air handlers.
• Do not use 208/240V electrical heaters on 480V air handlers.
RHSL Electrical Data – with Electric Heat (con’t.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all
auxiliary heating requirements.
➀ This does not include “D Voltage”. D Voltage = 480 Volts.
* Values only. No single point kit available.
• Supply circuit protective devices may be fused or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as
multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be
used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details.
• Largest motor load is included in single circuit or circuit 1 of multiple circuit.
• Heater loads are balanced on 3 PH. models with 3 or 6 heaters only.
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• No electrical heating elements are permitted to be used with “A” voltage (115V) air handler.
• J voltage (208/240V) single phase air handler is designed to be used with single or three phase
208/240V electric heaters. In the case of connecting 3 phase power to air handler terminal block
without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the
third lead.
• Do not use 480V electrical heaters on 208/240V air handlers.
• Do not use 208/240V electrical heaters on 480V air handlers.
RHSL Electrical Data – with Electric Heat (con’t.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all
auxiliary heating requirements.
➀ This does not include “D Voltage”. D Voltage = 480 Volts.
• Supply circuit protective devices may be fused or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as
multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be
used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details.
• Largest motor load is included in single circuit or circuit 1 of multiple circuit.
• Heater loads are balanced on 3 PH. models with 3 or 6 heaters only.
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• No electrical heating elements are permitted to be used with “A” voltage (115V) air handler.
• J voltage (208/240V) single phase air handler is designed to be used with single or three phase
208/240V volt electric heaters. In the case of connecting 3 phase power to air handler terminal
block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure
the third lead.
• Do not use 480V electrical heaters on 208/240V air handlers.
• Do not use 208/240V electrical heaters on 480V air handlers.
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all
auxiliary heating requirements.
* Values only. No single point kit available.
• Supply circuit protective devices may be fused or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as
multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be
used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details.
• Largest motor load is included in single circuit or circuit 1 of multiple circuit.
• Heater loads are balanced on 3 PH. models with 3 or 6 heaters only.
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• No electrical heating elements are permitted to be used with “A” voltage (115V) air handler.
• J voltage (208/240V) single phase air handler is designed to be used with single or three phase
208/240V volt electric heaters. In the case of connecting 3 phase power to air handler terminal
block without the heater, bring only two leads to terminal block. Cap, insulate and fully secure
the third lead.
• Do not use 480V electrical heaters on 208/240V air handlers.
• Do not use 208/240V electrical heaters on 480V air handlers.
RHLL Electrical Data – with Electric Heat (con’t.)
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all
auxiliary heating requirements.
* Values only. No single point kit available.
• Supply circuit protective devices may be fused or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as
multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be
used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details.
• Largest motor load is included in single circuit or circuit 1 of multiple circuit.
• Heater loads are balanced on 3 PH. models with 3 or 6 heaters only.
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• No electrical heating elements are permitted to be used with “A” voltage (115V) air handler.
• J voltage (208/240V) single phase air handler is designed to be used with single or three phase
208/240V electric heaters. In the case of connecting 3 phase power to air handler terminal block
without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the
third lead.
• Do not use 480V electrical heaters on 208/240V air handlers.
• Do not use 208/240V electrical heaters on 480V air handlers.
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all
auxiliary heating requirements.
* Values only. No single point kit available.
• Supply circuit protective devices may be fused or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• If the kit is listed under both single and multiple circuits, the kit is shipped from factory as
multiple circuits. For single phase application, Jumper bar kit RXBJ-A21 and RXBJ-A31 can be
used to convert multiple circuits to a single supply circuit. Refer to Accessory Section for details.
• Largest motor load is included in single circuit or circuit 1 of multiple circuit.
• Heater loads are balanced on 3 PH. models with 3 or 6 heaters only.
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• No electrical heating elements are permitted to be used with “A” voltage (115V) air handler.
• J voltage (208/240V) single phase air handler is designed to be used with single or three phase
208/240V electric heaters. In the case of connecting 3 phase power to air handler terminal block
without the heater, bring only two leads to terminal block. Cap, insulate and fully secure the
third lead.
• Do not use 480V electrical heaters on 208/240V air handlers.
• Do not use 208/240V electrical heaters on 480V air handlers.
• Field wiring must comply with the National Electrical Code
(C.E.C. in Canada) and any applicable local ordinance.
• Supply wiring must be 75°C minimum copper conductors only.
• See electrical data for product Ampacity rating and Circuit
Protector requirement.
Grounding
• This product must be sufficiently grounded in accordance with
National Electrical Code (C.E.C. in Canada) and any applicable
local ordinance.
• A grounding lug is provided.
RXHF-
Accessories-Kits—Parts
• Auxiliary Horizontal Overflow Pan Accessory RXBM-
• External Filter Base RXHF-
*Accommodates 1" or 2" filter
[ ] Designates Metric Conversions
• Combustible Floor Base RXHB-
• Jumper Bar Kit 3 Ckt. to 1 Ckt. RXBJ-A31 is used to convert
single phase multiple three circuit units to a single supply
circuit. Kit includes cover and screw for line side terminals.
• Jumper Bar Kit 2 Ckt. to 1 Ckt. RXBJ-A21 is used to convert
single phase multiple two circuit units to a single supply circuit.
Kit includes cover and screw for line side terminals.
• Note: No jumper bar kit is available to convert three phase
multiple two circuit units to a single supply circuit.
• Auxiliary Electric Heater Kits RXBH-
Heater Kits include circuit breakers which meet UL and cUL
requirements for service disconnect. See the Electric Heat
Electrical Data in this specification sheet for specific Heater Kit
Model numbers.
• Horizontal Adapter Kit RXHH-
This horizontal adapter kit is used to convert Upflow/Downflow
only models to horizontal flow. See the following table to order
proper horizontal adapter kit.
• External Filter Rack RXHF-B17, B21, B24
*Accommodates 1" filter
Model Cabinet SizePart Number*
RXHF-B17
RXHF-B21
Filter Size In. [mm]
RXHF-B24
24
25 x 20 [635 x 508]
17
16 x 20 [406 x 508]
21
20 x 20 [508 x 508]
A
16.90
20.40
25.00
B
20.77
20.77
21.04
Model Cabinet SizeFilter Size In. [mm]
1716 x 20 [406 x 508]
2120 x 20 [508 x 508]
Part Number*
RXHF-17
RXHF-21
RXHF-242425 x 20 [635 x 508]22.70
19.20
15.70
A
25.5
21.0
17.5
B
Nominal Cooling
Capacity-Tons
Auxiliary Horizontal Overflow Pan
Accessory Model Number
11/2 - 3
RXBM-AC48
31/2 - 5RXBM-AC61
Coil Model
Horizontal Adapter Kit
Model Number (10-Pack Qty.)
RXHH-A01 x 10
RXHH-A02 x 10
Horizontal Adapter Kit
Model Number (Single Qty.)
RXHH-A03 x 103617/3621RXHH-A03
2414RXHH-A01
2417RXHH-A02
3821/4821/4824RXHH-A04RXHH-A04 x 10
8024RXHH-A05RXHH-A05 x 10
RXHF-B
B
A
B
A
11/2
[38 mm]
Model Cabinet Size
17
21
24
Combustible Floor
Base Model Number
RXHB-17
RXHB-21
RXHB-24
Page 23
Rheem Heating, Cooling and Water Heating23
NOTES
Page 24
Before proceeding with installation, refer
to installation instructions packaged
with each model, as well as complying
with all Federal, State, Provincial, and
Local codes, regulations, and practices.
Rheem Heating,
Cooling and
Water Heating
P.O. Box 17010, Fort Smith, AR 72917
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A.4-10 DCFORM NO. H11-524 REV. 8
Supersedes Form No. H11-524 Rev. 7
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.