Rudd RHKL-HM2417JA Installation Manual

FORM NO. H11-523 REV. 8
Supersedes Form No. H11-523 Rev. 7
AIR HANDLERS
AIR HANDLERS
RHKL- SERIES
featuring Industry Standard R-410A Refrigerant
Features
®
ECM®Motor, which in most applications, enhances the SEER rating of the out­door unit. It also slowly ramps its speed up for quiet oper­ation and enhanced customer satisfaction.
Versatile 4-way convertible design for upflow, downflow,
horizontal left and horizontal right applications.
Nominal airflow up to 1.0" external static pressure.
Factory-installed high efficiency indoor coil.
Sturdy cabinet construction with 1.0 inch [25.4 mm] of
foil faced insulation for excellent sound and insulating characteristics.
Field-installed auxiliary electric heater kits provide exact
heat for indoor comfort. Kits include circuit breakers which meet U.L. and cUL requirements for service disconnect.
Dip switch settings for selectable, customized cooling air-
flow over a wide variety of applications.
On-demand dehumidification terminal that adjusts airflow
to help control humidity for unsurpassed comfort in cool­ing mode.
External filter required.
2 Rheem Heating, Cooling and Water Heating
RHKL- Series
Quiet, efficient ECM motor technology providing nominal airflow
up to 1.0 inch [25 kPa] of external static pressure.
Interface board with dip switches conveniently located in the
blower compartment allows for precise, field selectable airflow to meet the requirements of particular applications.
Selectable continuous fan “on” options.
The most compact unit design available.
Attractive pre-painted cabinet exterior.
Rugged steel cabinet construction, designed for added
strength and versatility.
1.0" foil faced insulation mechanically retained in blower
compartment.
Four leg rubber insulated motor mount.
Field-installed auxiliary heater kit includes circuit breakers that
meet UL and cUL requirements as a service disconnect switch.
Blower housing with integrated controls, motor and blower.
Slide out design for service and maintenance convenience.
Field convertible for vertical upflow, vertical downflow, horizon-
tal left hand or right hand air supply.
Combustible floor base accessory available when required for
downflow installations on combustible floors.
Indoor coil design provides low air side pressure drop, high
performance and extremely compact size. All coils come with PVC condensate elbow standard.
Coils are constructed of aluminum fins bonded to internally
grooved copper tubing.
Molded polymer corrosion resistant condensate drain pan is
provided on all indoor coils.
Supply duct flanges provided as standard on air handler
cabinet.
Provisions for field electrical connections available from either
side or top of the air handler cabinet.
Connection point for high voltage wiring is inside the air han-
dler cabinet. Low voltage connection is made on the outside of the air handler cabinet.
Concentric knockouts are provided for power connection to
cabinet. Installer may pull desired hole size up to 2 inches [51 mm] for 1
1
/2 inch [38 mm] conduit.
Internal checked TX valves are used on the Heat Pump indoor
coil for more quiet refrigerant metering.
Front refrigerant and drain connections.
[ ] Designates Metric Conversions
Engineering Features
GENERAL TERMS OF LIMITED WARRANTY
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable periods stated, in accordance with the terms of the limited warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.
Conditional Parts Warranty
(Registration Required)........................Ten (10) Years
All Parts ........................................................Five (5) Years
Rheem Heating, Cooling and Water Heating 3
RHKL—HM2417J A
Design Variation
A = 1st Design
Voltage
J = 208/240/1/60
Cabinet Size
17 = 17.5" [431.8 mm] (600-1200 CFM) 21 = 21" [533.4 mm] (1400-1600 CFM) 24 = 24.5" [609.6 mm] (1600-1800 CFM)
Capacity
24 = 18,000/24,000 BTUH
[5.27 to 7.03 kW]
36 = 30,000/36,000 BTUH
[8.79 to 10.55 kW]
38 = 30,000/36,000/42,000 BTUH
[8.79 to 12.31 kW]
48 = 42,000/48,000 BTUH
[12.31 to 14.06 kW]
60 = 60,000 BTUH
[17.58 kW]
HM = A/C or HP, Multi-Position
(Upflow & Horizontal Left is the factory configuration)
Refrigerant
L = R-410A
K = Premium
Classification
H = Air Handler
Rheem
MODEL NUMBER DATA
Coil Specifications/Airflow Pressure Drop
[ ] Designates Metric Conversions
AVAILABLE MODELS
R-410A MODELS
RHKL-HM2417JA RHKL-HM3617JA RHKL-HM3821JA RHKL-HM4821JA RHKL-HM4824JA RHKL-HM6024JA
4 Rheem Heating, Cooling and Water Heating
Unit Dimensions
Unit Dimensions & Weights
[ ] Designates Metric Conversions
( ) Designates Unit with Double Coil Cabinet
UPFLOW UNIT SHOWN: UNIT MAY BE INSTALLED UPFLOW, DOWNFLOW, HORIZONTAL RIGHT OR LEFT AIR SUPPLY.
Return Air Opening Dimensions
ELECTRICAL CONNECTIONS MAY EXIT TOP OR EITHER SIDE
7
HIGH VOLTAGE CONNECTION
3
/32 [27.8 mm], 131/32 [50 mm] DIA.
1 KNOCKOUTS. IF LARGER REQUIRED, PULL HOLE SIZE REQUIRED UP TO 2 [50.8 mm] DIA.
1
/2 [38.1 mm] CONDUIT
FOR 1
LOW VOLTAGE CONNECTION
5
/8 [15.9 mm] AND 7/8 [22.2 mm] KNOCKOUT
(OUTSIDE OF CABINET)
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
HORIZONTAL APPLICATION ONLY
PRIMARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
AUXILIARY DRAIN CONNECTION
3
/4 [19.1 mm] FEMALE PIPE THREAD (NPT)
UPFLOW/DOWNFLOW APPLICATION ONLY
LIQUID LINE CONNECTION COPPER (SWEAT)
VAPOR LINE CONNECTION COPPER (SWEAT)
DOWNFLOW APPLICATION AND HORIZONTAL RIGHT
INDOOR COIL AND COIL DOOR ROTATES 180°
HORIZONTAL ADAPTER KIT
VAPOR LINE
CONNECTION
AUXILIARY HORIZONTAL
DRAIN CONNECTION
/8 [22.2 mm],
SUPPLY AIR
105/16
[262 mm]
A
19
RETURN AIR
515/16
[151 mm]
NOTE: 24CLEARANCE REQUIRED IN FRONT OF UNIT FOR FILTER AND COIL MAINTENANCE.
W
1
/2 [495 mm]
OPENING
4
[105 mm]
11
/16
21
[551 mm]
1
/8
31/16
[76 mm]
H
1
Cabinet Size
3
/16[48 mm]
Model
17 16 191/2 21 191/2 191/2 24 23 191/2
1
1
/8[29 mm]
1
/16
1
[27 mm]
3
/8
1
[35 mm]
13
/16
2
[71 mm]
Opening Width
Return Air
(Inches)
51/4
[133 mm]
53/8
[136 mm]
Return Air Opening
Depth/Length
(Inches)
PRIMARY DRAIN
CONNECTION
AUXILIARY UPFLOW/DOWNFLOW
DRAIN CONNECTION
LIQUID LINE CONNECTION
VERTICAL DRAIN PAN
Model
RHKL
Model
Cabinet
2417 17 3617 17
Size
Unit
Width
“W” In. [mm]
171/2 [445] 171/2 [445]
Unit
Height
“H” In. [mm]
421/2 [1080] 421/2 [1080]
211/2 [533] 501/2 [1282]3821 21 191/2 [495] 1000 [472] 1200 [566] 150/166 [68/75] 4821 21 191/2 [495] 1400 [661] 1600 [755] 150/166 [68/75] 4824 24 231/2 [584] 1600 [755] 162/180 [73/81] 6024 24 231/2 [584] 1800 [850] 181/198 [82/90]
211/2 [533]
241/2 [622]
241/2 [622]
501/2 [1282] 551/2 [1410] 551/2 [1410]
Supply
Duct
“A” In. [mm]
161/2 [406] 161/2 [406]
CFM (Nom.) [L/s]
Lo Hi
600 [283] 800 [378] 82/96 [37/44]
1000 [472] 1200 [566] 92/106 [37/48]
Air Flow
Unit Weight/Shipping Weight (Lbs.) [kg]
Unit With
Coil (Max. KW)
Loading...