2 Rheem Heating, Cooling and Water Heating
RBHP- Series
■ Quiet, efficient X-13 (ECM) motor technology providing nominal
airflow to 0.5 inch [12 kPa] of external static pressure.
■ Field selectable airflow to meet the requirements of particular
applications.
■ Low continuous fan speed.
■ The most compact unit design available.
■ Attractive pre-painted cabinet exterior.
■ Rugged double wall steel cabinet construction, designed for
added strength and versatility.
■ .5" foil faced insulation mechanically retained in blower
compartment.
■ Four leg rubber insulated wire motor mount.
■ Circuit breakers standard on models above 11 kW and optional
on models with 11 kW or less.
■ Models supplied with circuit breakers meet UL and cUL require-
ments as a service disconnect switch.
■ Provisions for field electrical connections from either side of air
handler cabinet.
■ Tab lock blower housing with integrated electric heaters, con-
trols, motor and blower. Slide out design for service and maintenance convenience.
■ Exclusive dependable Incoloy sheath type electric heating
elements located in the blower housing provide mixed warm air.
■ Field convertible for vertical upflow, vertical downflow, horizon-
tal left hand or right hand air supply.
■ Common combustible floor base accessory fits all model sizes
when required for downflow installations on combustible floors.
■ Durable framed cleanable air filter provided as standard in unit
filter rack.
■ MultiFlex
®
indoor coil design provides low air side pressure
drop, high performance and extremely compact size. All coils
come with PVC condensate elbow standard.
■ All indoor coils have copper tubing and aluminum fins.
■ Molded polymer corrosion resistant condensate drain pan is
provided on all indoor coils.
■ Both supply and return duct flanges provided as standard on air
handler cabinet.
■ Connection points for both high voltage and low voltage control
wiring inside air handler cabinet.
■ Concentric knockouts are provided for power connection to
cabinet. Installer may pull desired hole size up to 2 inches
[51 mm] for 1
1
/2
inch [38 mm] conduit.
■ Patented watt restrictor on heat pump models to control electric
heat during heating operation.
■ Internal checked TX valves are used on the RCHJ & RCHL
Heat Pump indoor coil for more quiet refrigerant metering.
■ Front refrigerant and drain connections.
Engineering Features
Watt-restrictor
BLOWER
SECTION
X-13 (ECM)
MOTOR
GENERAL TERMS OF
LIMITED WARRANTY
Rheem®will furnish a replacement for any part of this product
which fails in normal use and service within the applicable
periods stated, in accordance with the terms of the limited
warranty.
Conditional Parts (Registration Required) ..Ten (10) Years
For Complete Details of the Limited Warranty, Including
Applicable Terms and Conditions, See Your Local Installer or
Contact the Manufacturer for a Copy.
Supplemental heat, provided by electric heating elements may be necessary in some areas
when heating requirements for indoor comfort exceed the capacity of the heat pump system.
When supplemental heat is required, units with the Watt Restrictor will restrict the amount of
supplemental electric heat that can be energized dependent on the heat output of the heat
pump (temperature of the air leaving the indoor heat pump coil).
The Watt-restrictor utilizes sensing devices in the unit to sense the air temperature leaving
the indoor coil and disengage unnecessary heating elements when that temperature is at
least 85°F [29°C]. (In this mode your system is controlled by the first stage of the wall thermostat.) This occurs only when the second stage of the wall thermostat calls for heat.
Since the heat output of the heat pump is dependent upon the outdoor air temperature, this
control performs the same function as a field installed outdoor thermostat.
An additional benefit of the Watt Restrictor is that it can sense a degradation in heat pump
performance due to causes other than outdoor temperature and react accordingly to bring
on more supplemental electric heat.
[ ] Designates Metric Conversions