Page 1
FORM NO. A11-189 REV. 5
Supersedes Form No. A11-189 Rev. 4
CONDENSING UNITS
RASL- JEZ
Two-Stage
Efficiencies up to 18.50 SEER
Nominal Size 2 to 3 Tons [7.03 kW] to [10.6 kW]
Two Models
Cooling Capacity
24,000 to 37,600 BTU/HR
[7.03 kW] to [11.02 kW]
The Rheem Prestige Series™ High Efficiency Two-Stage RASLJEZ Condensing Unit was designed with performance in mind.
These units offer comfort, energy conservation and dependability
for single, multi-family and light commercial applications.
The Rheem Prestige Series™ Two-Stage RASL- JEZ Condensing
Units are the result of an ongoing development program for
improved efficiencies. With system SEER’s ranging to 18.50,
these units continue a tradition of high efficiency.
■ The Comfort Control System™ provides on-board diagnostics
and fault history for condensing units with single-phase compressors by detecting system and electrical problems without
adding sensors. It can also communicate “fault codes” to
enabled “L terminal” thermostats. The integrated diagnostics
with Active Protection™ prevents compressor operation when
potentially harmful conditions are detected.
■
7-Segment LED Display is exclusive only to Rheem products.
The information-display quickly and accurately shows technicians the source of malfunctions.
■
Features a ten-year conditional unit replacement warranty when
properly installed with a new Rheem Air Handler or Rheem
Indoor Coil with a Rheem Gas Furnace. See product warranty
card for additional information.
■ Reliable Two-Stage Scroll™ Compressor for precise tempera-
ture control providing ultimate comfort.
■ Comfort Alert™ Diagnostics comes installed in each Rheem
Prestige Series™ model.
■ All controls are accessible by removing one service panel.
Removable top grille provides access to the condenser fan
motor and condenser coil.
■ Attractive, louvered wrap-around jacket protects the coil from
yard hazards and weather extremes. Top grille is steel reinforced for extra strength. Cabinet is powder painted for allweather protection.
■ Air is discharged upward away from bushes and shrubs. The
discharge pattern of the top grille provides minimum air restriction, resulting in quiet fan operation.
■ Exclusive Combination Grille/Motor Mount secures the motor to
the underside of the discharge grille. The grille protects the
motor windings and bearings from rain and snow.
■ For quiet operation and improved efficiency, the 3 ton model
feature the Genteq™ ECM two-speed motor with a 3-blade outdoor fan.
■ All models meet or exceed a 1000-hour salt spray test per ASTM
B117 Standard Practice for Operating Salt Spray Testing
Apparatus.
■ On-demand dehumidification terminal, when matched with a
Prestige Series Air Handler or premium ECM Gas Furnace products, adjusts airflow to help control humidity for unsurpassed
comfort in the cooling mode.
Equipped with
the Award Winning
Comfort Control System
™
• Increased Reliability
• On-Board Diagnostics
• Fault Recall
• Active Protection
™
18.0
Page 2
2 Rheem Heating, Cooling and Water Heating
■
The Rheem exclusive 7-Segment LED Display easily shows
system operating status codes and
diagnostic codes.
■
A Sealed Switch replaces the standard
contactor and
features optical
control and
latching mechanism. The sealed
switch prevents
infiltration of
insects and dust. A minimal switching arc,
by the optical control, offers greater reliability. The latching mechanism consumes
less power while reducing chatter.
■
The Status Indication and System Diagnostics feature thermostat communication capability, built-in diagnostics, high
& low voltage monitoring and high & low pressure switch
monitoring. The thermostat communication capability alerts the
homeowner to any necessary service
requirements. Faster, more accurate
service is provided by the built-in
diagnostics, by providing the HVAC
professional with dependable information. With the high and low voltage
monitoring feature, the control
provides alerts for out-of-range conditions. In addition, high and low pressure-switch monitoring prevents the system from operating outside of its normal parameters.
■
The fault recall feature will allow for the last six fault-codes
to be displayed, and will retain these codes even if power
failure occurs.
■
Built-in short-cycle protection allows the compressor to
restart easily without oil removal.
■
A 30-second minimum run-time for every compressor call
allows the oil to return to the compressor.
■
Active Protection monitors the system to prevent nuisance
lockouts and prevents compressor operation when potentially harmful conditions are detected.
■
The compressor and fan are
controlled independently,
which reduces the starting load
and light dimming.
■
A manual push-button is
offered to operate the compressor and fan for 5 seconds to
allow for an operation check.
■
In order to save time and
money, replacement automotive fuses can be utilized instead of replacing the entire
control board.
STANDARD FEATURES
RASL- JEZ Condensing Units
1. Scroll compressor is hermetically sealed and incorporates
internal high temperature motor overload protection, and
durable insulation on the motor windings. It is externally
mounted on rubber grommets to reduce vibration and noise.
2. Compressors have an internal pressure relief assembly to
protect against excessive pressure differential.
3. All refrigerant connections are on the exterior of the unit,
located close to the ground for neat appearing installations.
4. Cabinet is constructed of powder painted galvanized
steel. The full wrap-around louvered grille protects the coil
from damage.
5. Sound Blanket-enhanced compressor sound blanket is
standard.
6. Copper tube—aluminum fin coils are used on all models.
7. The control box is located in the top corner of the cabinet
providing for easy access through a service panel.
8. Service valves are standard on all models.
9. Field connections for power and control wiring are kept
separate.
10. Every unit is factory charged and run-tested.
11. Separate compressor compartment for easy service access.
12. Drawn, painted base pan for extra corrosion resistance and
sound reduction.
13. The RASL- JEZ has a 10-year limited parts warranty, plus a
10-year conditional unit replacement warranty. Refer to the
General Terms of Limited Warranty for more details.
14. Hard Start Kits—Standard on all JEZ models.
15. Control Box Cover.
16. The RASL- JEZ is shipped with a liquid line filter drier, and
also features factory-installed low and high pressure
controls.
FEATURES & BENEFITS OF THE COMFORT CONTROL SYSTEM
™
2-STAGE SCROLL ULTRA
TECH
™
COMPRESSOR
The 2-Stage Scroll UltraTech™ compressor is the key to
efficiency for this Rheem model. It’s the latest in high-efficiency
compressor technology. The
advanced scroll compressor
offers low noise and vibration
characteristics and features
tolerance to liquid refrigerant and
system contamination. The Scroll
UltraTech™ also has low start
torque, eliminating start problems
in the field. And its unique design
enables the RASL- JEZ
condensing unit to perform
efficiently, quietly and reliably.
All controls and compressor
are accessible for servicing by
removal of the service panel.
Page 3
Rheem Heating, Cooling and Water Heating 3
Accessories
■
Low Ambient Control —Cycles outdoor fan to maintain
adequate condensing pressures assuring liquid refrigerant
flow to the coil. Allows indoor cooling with outdoor
temperatures down to 0°F [–17.8°C]. (Model No. RXADA08). It is recommended that this control be installed in units
to be operated at outdoor ambient temperatures under 70°F
[21°C].
■
Thermostats
■
Compressor Crankcase Heater (Model No. 44-1740244CCH) Add to minimize refrigeration migration and to help
eliminate any startup noise or bearing “wash out”.
R A S L 036
COOLING
CAPACITY
024 = 24,000 BTU/HR [7.03 kW]
036 = 36,000 BTU/HR [10.55 kW]
J E Z
RHEEM REMOTE
CONDENSING
UNIT
18-SEER DESIGN
SERIES
L = FIRST DESIGN
SERIES
ELECTRICAL
DESIGNATION
J = 208/230V-1-60
VARIATIONS
E = EQUIPPED
WITH THE
COMFORT
CONTROL
SYSTEM
™
COOLING
CONNECTION
FITTING
Z = SWEAT
W/SCROLL
—
Model Number Identification
[ ] Designates Metric Conversions
Page 4
4 Rheem Heating, Cooling and Water Heating
Performance Data @ AHRI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
Rev.
2/24/2010
024JEZ
RCSN-H*2421 ➀
RCFM-H*2417+RXMD-C06 Coil Only
RCFM-H*2417A*
Model Numbers
ID Coil
RCFM-H*2417
ID Air Mover
RHPN-HM2421
RGFD-06?MCK?
RGFD-07?MCK?
RGFE-06?MCK?
RGFE-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGGE-06?MCK?
RGGE-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGJF-06?MCK?
RGJF-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGRM-04?MAE?
RGRM-06?MAE?
RGRM-07?MAE?
RGTM-06?MAE?
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
Stage
1
2 17,700 [5.2] 6,900 [2.0]
1 - dehumid
2 - dehumid 16,750 [4.9] 7,650 [2.2] 650 [307] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,500 [5.1] 6,900 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,500 [5.1] 6,900 [2.0] 800 [378] 74
1 13,500 [4.0] 5,100 [1.5]
2 17,350 [5.1] 7,050 [2.1] 800 [378] 74
1 13,500 [4.0] 5,100 [1.5]
2 17,700 [5.2] 7,100 [2.1] 825 [389] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,500 [4.0] 5,100 [1.5]
2 17,700 [5.2] 7,100 [2.1] 825 [389] 74
1 13,500 [4.0] 5,100 [1.5]
2 17,350 [5.1] 7,050 [2.1] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,500 [4.0] 5,100 [1.5]
2 17,700 [5.2] 7,100 [2.1] 825 [389] 74
1 13,500 [4.0] 5,100 [1.5]
2 17,350 [5.1] 7,050 [2.1] 800 [378] 74
1
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,350 [3.9] 5,150 [1.5]
2 17,650 [5.2] 6,950 [2.0] 775 [366]
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1 13,550 [4.0] 5,050 [1.5]
2 17,850 [5.2] 6,950 [2.0] 850 [401] 74
1 14,000 [4.1] 5,300 [1.6]
2 17,700 [5.2] 7,100 [2.1] 825 [389] 74
1 13,050 [3.8] 5,050 [1.5]
2 17,200 [5.0] 6,800 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,500 [5.1] 6,900 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,500 [5.1] 6,900 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
Net
Sensible
BTU/H [kW]
13,700 [4.0] 5,100 [1.5] 600 [283]
12,600 [3.7] 5,700 [1.7] 500 [236] 71
13,500 [4.0] 5,200 [1.5]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
24,400 [7.1] 16.00 12.65
24,400 [7.1] 16.00 12.75
24,400 [7.1] 17.00 13.10
24,800 [7.3] 17.00 13.15
24,600 [7.2] 16.50 12.95
24,400 [7.1] 16.50 12.85
24,800 [7.3] 17.00 13.25
24,400 [7.1] 17.00 13.15
24,600 [7.2] 16.50 12.95
24,400 [7.1] 16.50 12.85
24,800 [7.3] 17.00 13.25
24,400 [7.1] 17.00 13.15
24,600 [7.2] 16.50 13.15
24,600 [7.2] 16.00 12.95
24,600 [7.2] 16.50 13.05
24,400 [7.1] 17.50 13.55
24,800 [7.3] 17.50 13.70
24,800 [7.3] 17.00 13.35
24,800 [7.3] 17.00 13.10
24,000 [7.0] 14.50 11.80
24,400 [7.1] 16.00 12.65
24,400 [7.1] 16.00 12.75
24,600 [7.2] 16.50 12.95
24,400 [7.1] 16.50 12.85
AHRI Rating
SEER
EER
14.30 24,600 [7.2] 18.50
Indoor Airflow
CFM [L/s]
775 [366]
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
600 [283] 71
625 [295] 71
625 [295] 71
575 [271] 71
600 [283] 71
625 [295] 71
625 [295] 71
575 [271] 71
600 [283] 71
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
625 [295] 71
750 [354] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
625 [295] 71
Sound
Rating
db
71
74
74
Page 5
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Rheem Heating, Cooling and Water Heating 5
Performance Data @ AHRI Standard Conditions—Cooling
Outdoor
Unit
RASL-
Rev.
2/24/2010
RCFM-H*2417A*
RCFM-H*2417A*+RXMD-C06 Coil Only
024JEZ
RCFM-H*2421+RXMD-C06 Coil Only
Model Numbers
ID Coil
RCFM-H*2421
ID Air Mover
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGFD-06?MCK?
RGFD-07?MCK?
RGFE-06?MCK?
RGFE-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGGE-06?MCK?
RGGE-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGJF-06?MCK?
RGJF-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGRM-04?MAE?
RGRM-06?MAE?
RGRM-07?MAE?
RGTM-06?MAE?
Stage
1
2 17,650 [5.2] 6,950 [2.0]
1
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,500 [4.0] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,350 [3.9] 5,150 [1.5]
2 17,650 [5.2] 6,950 [2.0] 775 [366] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,050 [3.8] 5,050 [1.5]
2 17,200 [5.0] 6,800 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,500 [5.1] 6,900 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,600 [4.0] 5,200 [1.5]
2 17,550 [5.1] 7,050 [2.1] 800 [378] 74
1 13,600 [4.0] 5,200 [1.5]
2 17,900 [5.2] 7,100 [2.1] 825 [389] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,600 [4.0] 5,200 [1.5]
2 17,850 [5.2] 7,150 [2.1] 825 [389] 74
1 13,600 [4.0] 5,200 [1.5]
2 17,750 [5.2] 7,050 [2.1] 800 [378] 74
1
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378]
1 13,600 [4.0] 5,200 [1.5]
2 17,850 [5.2] 7,150 [2.1] 825 [389] 74
1 13,600 [4.0] 5,200 [1.5]
2 17,750 [5.2] 7,050 [2.1] 800 [378] 74
1 13,500 [4.0] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,350 [3.9] 5,150 [1.5]
2 17,650 [5.2] 6,950 [2.0] 775 [366] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1 13,550 [4.0] 5,050 [1.5]
2 17,850 [5.2] 6,950 [2.0] 850 [401] 74
1 14,200 [4.2] 5,400 [1.6]
2 17,900 [5.2] 7,100 [2.1] 825 [389] 74
1 13,050 [3.8] 5,050 [1.5]
2 17,200 [5.0] 6,800 [2.0] 800 [378] 74
Net
Sensible
BTU/H [kW]
13,400 [3.9] 5,200 [1.5] 600 [283]
13,400 [3.9] 5,200 [1.5]
13,400 [3.9] 5,200 [1.5]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
24,400 [7.1] 16.50 12.85
24,600 [7.2] 16.50 13.15
24,600 [7.2] 16.00 12.95
24,600 [7.2] 16.50 13.05
24,000 [7.0] 14.50 11.80
24,400 [7.1] 16.00 12.70
24,400 [7.1] 16.00 12.80
24,600 [7.2] 17.00 13.20
25,000 [7.3] 17.00 13.30
24,600 [7.2] 16.50 13.00
24,400 [7.1] 16.50 12.90
25,000 [7.3] 17.00 13.40
24,800 [7.3] 17.00 13.25
24,600 [7.2] 16.50 13.00
24,400 [7.1] 16.50 12.90
25,000 [7.3] 13.40
24,800 [7.3] 17.00 13.25
24,600 [7.2] 16.50 13.15
24,600 [7.2] 16.00 12.95
24,600 [7.2] 16.50 13.10
24,400 [7.1] 17.50 13.60
24,800 [7.3] 17.50 13.75
24,800 [7.3] 17.00 13.45
25,000 [7.3] 17.00 13.25
24,000 [7.0] 14.50 11.80
AHRI Rating
SEER
17.00
EER
12.95 24,600 [7.2] 16.50
Indoor Airflow
CFM [L/s]
800 [378]
625 [295] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
600 [283] 71
625 [295] 71
625 [295] 71
575 [271] 71
600 [283] 71
625 [295] 71
625 [295] 71
575 [271] 71
600 [283] 71
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
625 [295] 71
750 [354] 71
600 [283] 71
Sound
Rating
db
71
74
74
Page 6
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
6 Rheem Heating, Cooling and Water Heating
Performance Data @ AHRI Standard Conditions—Cooling
Outdoor
Unit
RASL-
Rev.
2/24/2010
RCFM-H*2421A*
RCFM-H*2421A*+RXMD-C06 Coil Only
024JEZ
Model Numbers
ID Coil
RCFN-H*2417
ID Air Mover
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGFD-06?MCK?
RGFD-07?MCK?
RGFE-06?MCK?
RGFE-07?MCK?
RGGD-07?MCK?
RGGE-06?MCK?
RGGE-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGJF-06?MCK?
RGJF-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGRM-04?MAE?
RGRM-06?MAE?
Stage
1
2 17,500 [5.1] 6,900 [2.0]
1
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,500 [4.0] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,350 [3.9] 5,150 [1.5]
2 17,650 [5.2] 6,950 [2.0] 775 [366] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,050 [3.8] 5,050 [1.5]
2 17,200 [5.0] 6,800 [2.0] 800 [378] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389]
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,700 [5.2] 6,900 [2.0] 775 [366] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
Net
Sensible
BTU/H [kW]
13,400 [3.9] 5,200 [1.5] 600 [283]
13,400 [3.9] 5,200 [1.5]
13,600 [4.0] 5,100 [1.5]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
24,400 [7.1] 16.00 12.80
24,600 [7.2] 16.50 13.00
24,400 [7.1] 16.50 12.90
24,600 [7.2] 16.50 13.00
24,400 [7.1] 16.50 12.90
24,600 [7.2] 16.50 13.15
24,600 [7.2] 16.00 12.95
24,600 [7.2] 16.50 13.10
24,000 [7.0] 14.50 11.80
24,400 [7.1] 17.50 13.50
24,400 [7.1] 17.50 13.60
24,600 [7.2] 18.00 13.80
24,800 [7.3] 17.50 13.85
24,400 [7.1] 17.50 13.70
24,800 [7.3] 18.00 13.95
24,600 [7.2] 18.00 13.85
24,600 [7.2] 18.00 13.85
24,400 [7.1] 17.50 13.70
24,800 [7.3] 18.00 13.95
24,600 [7.2] 18.00 13.85
24,600 [7.2] 18.00 14.00
24,600 [7.2] 17.50 13.80
24,600 [7.2] 18.00 13.90
24,400 [7.1] 17.50 13.55
24,800 [7.3] 17.50 13.70
AHRI Rating
SEER
EER
12.70 24,400 [7.1] 16.00
Indoor Airflow
CFM [L/s]
800 [378]
600 [283] 71
600 [283] 71
625 [295] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
625 [295] 71
625 [295] 71
575 [271] 71
600 [283] 71
625 [295] 71
625 [295] 71
575 [271] 71
600 [283] 71
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
Sound
Rating
db
71
74
74
Page 7
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Rheem Heating, Cooling and Water Heating 7
Performance Data @ AHRI Standard Conditions—Cooling
Outdoor
Unit
RASL-
Rev.
2/24/2010
RCFN-H*2417+RXMD-C06 Coil Only
RCFN-H*2417A*
RCFN-H*2417A*+RXMD-C06 Coil Only
024JEZ
Model Numbers
ID Coil
RCFN-H*2417
RCFN-H*2421
ID Air Mover
RGRM-07?MAE?
RGTM-06?MAE?
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGFD-06?MCK?
RGFD-07?MCK?
RGFE-06?MCK?
RGFE-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGGE-06?MCK?
RGGE-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGJF-06?MCK?
RGJF-07?MCK?
RGLR-07?AMK?
Stage
1
2 17,850 [5.2] 6,950 [2.0]
1
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1 13,250 [3.9] 4,950 [1.5]
2 17,250 [5.1] 6,750 [2.0] 775 [366] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,700 [5.2] 6,900 [2.0] 775 [366] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,250 [3.9] 4,950 [1.5]
2 17,250 [5.1] 6,750 [2.0] 775 [366] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378]
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,750 [5.2] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,750 [5.2] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
Net
Sensible
BTU/H [kW]
13,550 [4.0] 5,050 [1.5] 625 [295]
14,200 [4.2] 5,300 [1.6]
13,650 [4.0] 5,050 [1.5]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
24,800 [7.3] 17.50 13.80
24,000 [7.0] 15.50 12.55
24,400 [7.1] 17.50 13.50
24,400 [7.1] 17.50 13.60
24,600 [7.2] 18.00 13.85
24,400 [7.1] 17.50 13.70
24,600 [7.2] 18.00 13.85
24,400 [7.1] 17.50 13.70
24,600 [7.2] 18.00 14.00
24,600 [7.2] 17.50 13.80
24,600 [7.2] 18.00 13.90
24,000 [7.0] 15.50 12.55
24,400 [7.1] 17.50 13.50
24,400 [7.1] 17.50 13.65
24,600 [7.2] 17.50 13.80
24,800 [7.3] 17.50 13.90
24,600 [7.2] 18.00 13.85
24,600 [7.2] 17.50 13.75
24,800 [7.3] 18.00 14.00
24,600 [7.2] 18.00 13.90
24,600 [7.2] 18.00 13.85
24,600 [7.2] 17.50 13.75
24,800 [7.3] 18.00 14.00
24,600 [7.2] 18.00 13.90
24,600 [7.2] 18.00 14.05
AHRI Rating
SEER
EER
13.35 24,800 [7.3] 17.00
Indoor Airflow
CFM [L/s]
850 [401]
750 [354] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
625 [295] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
600 [283] 71
625 [295] 71
625 [295] 71
575 [271] 71
600 [283] 71
625 [295] 71
625 [295] 71
575 [271] 71
600 [283] 71
Sound
Rating
db
71
74
74
Page 8
8 Rheem Heating, Cooling and Water Heating
Performance Data @ AHRI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
Rev.
2/24/2010
RCFN-H*2421+RXMD-C06 Coil Only
024JEZ
RCFN-H*2421A*
RCFN-H*2421A*+RXMD-C06 Coil Only
Model Numbers
ID Coil
RCQD-2417
RCQD-2417
ID Air Mover
RGPE-05?BMK?
RGPE-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGRM-04?MAE?
RGRM-06?MAE?
RGRM-07?MAE?
RGTM-06?MAE?
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGFE-06?MCK?
RGFE-07?MCK?
RGJF-06?MCK?
RGJF-07?MCK?
RGPE-05?BMK?
RGRM-04?MAE?
RGRM-06?MAE?
Stage
1
2 17,700 [5.2] 6,900 [2.0]
1
2 17,800 [5.2] 7,000 [2.1] 825 [389] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,700 [5.2] 6,900 [2.0] 775 [366] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1 13,550 [4.0] 5,050 [1.5]
2 17,850 [5.2] 6,950 [2.0] 850 [401] 74
1 14,200 [4.2] 5,300 [1.6]
2 17,850 [5.2] 6,950 [2.0] 825 [389] 74
1 13,250 [3.9] 4,950 [1.5]
2 17,250 [5.1] 6,750 [2.0] 775 [366] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,750 [5.2] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1
2 17,750 [5.2] 6,850 [2.0] 800 [378] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378]
1 13,650 [4.0] 5,050 [1.5]
2 17,700 [5.2] 6,900 [2.0] 775 [366] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,250 [3.9] 4,950 [1.5]
2 17,250 [5.1] 6,750 [2.0] 775 [366] 74
1 14,100 [4.1] 4,700 [1.4]
2 18,250 [5.3] 6,350 [1.9] 800 [378] 74
1 14,100 [4.1] 4,700 [1.4]
2 18,600 [5.4] 6,400 [1.9] 825 [389] 74
1 14,100 [4.1] 4,700 [1.4]
2 18,600 [5.4] 6,400 [1.9] 825 [389] 74
1 14,100 [4.1] 4,700 [1.4]
2 18,450 [5.4] 6,350 [1.9] 800 [378] 74
1 14,100 [4.1] 4,700 [1.4]
2 18,450 [5.4] 6,350 [1.9] 800 [378] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 800 [378] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 825 [389] 74
Net
Sensible
BTU/H [kW]
13,600 [4.0] 5,100 [1.5] 575 [271]
13,700 [4.0] 5,100 [1.5]
13,600 [4.0] 5,100 [1.5]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
24,800 [7.3] 18.00 14.15
24,600 [7.2] 17.50 13.80
24,600 [7.2] 18.00 13.95
24,400 [7.1] 17.50 13.60
24,800 [7.3] 17.50 13.75
24,800 [7.3] 17.00 13.45
24,800 [7.3] 17.50 13.85
24,000 [7.0] 15.50 12.55
24,400 [7.1] 17.50 13.50
24,400 [7.1] 17.50 13.65
24,600 [7.2] 18.00 13.85
24,600 [7.2] 17.50 13.75
24,600 [7.2] 18.00 13.85
24,600 [7.2] 17.50 13.75
24,600 [7.2] 18.00 14.05
24,600 [7.2] 17.50 13.80
24,600 [7.2] 18.00 13.95
24,000 [7.0] 15.50 12.55
24,600 [7.2] 17.00 13.25
25,000 [7.3] 17.00 13.35
25,000 [7.3] 17.00 13.45
24,800 [7.3] 17.00 13.30
24,800 [7.3] 17.00 13.35
24,600 [7.2] 16.50 12.90
24,600 [7.2] 16.50 12.95
AHRI Rating
SEER
EER
13.95 24,600 [7.2] 18.00
Indoor Airflow
CFM [L/s]
800 [378]
625 [295] 71
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
625 [295] 71
750 [354] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
625 [295] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
625 [295] 71
575 [271] 71
575 [271] 71
575 [271] 71
600 [283] 71
Sound
Rating
db
71
74
74
Page 9
Rheem Heating, Cooling and Water Heating 9
Performance Data @ AHRI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
Rev.
2/24/2010
024JEZ
RCQD-2417A*+RXMD-C06 Coil Only
RCSM-H*2421A* RHPL-HM2421
RCSN-H*3624A* ➀
036JEZ
Model Numbers
ID Coil
RCQD-2417A
RCQD-2417A*
RCSM-H*2421 RHPL-HM2421
RCFM-H*3617
ID Air Mover
RGRM-07?MAE?
RBHM-17J*
RGFD-06?MCK?
RGFD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGPR-05?BMK?
RGPR-07?AMK?
RGRM-04?MAE?
RGRM-06?MAE?
RGRM-07?MAE?
RHPN-HM3624
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGFE-06?MCK?
RGFE-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGGE-06?MCK?
RGGE-07?MCK?
RGJD-06?MCK?
Stage
2 18,900 [5.5] 5,900 [1.7]
1
2 18,750 [5.5] 5,850 [1.7] 825 [389] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 800 [378] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 800 [378] 74
1 14,100 [4.1] 4,600 [1.3]
2 18,900 [5.5] 5,900 [1.7] 800 [378] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 800 [378] 74
1 14,050 [4.1] 4,550 [1.3]
2 18,950 [5.6] 5,850 [1.7] 775 [366] 74
1 14,100 [4.1] 4,600 [1.3]
2 18,900 [5.5] 5,900 [1.7] 800 [378] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 800 [378] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 825 [389] 74
1 14,050 [4.1] 4,550 [1.3]
2 18,900 [5.5] 5,900 [1.7] 850 [401] 74
1 13,750 [4.0] 4,450 [1.3]
2 18,450 [5.4] 5,750 [1.7] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,600 [5.2] 7,000 [2.1] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,600 [5.2] 7,000 [2.1] 800 [378] 74
2 26,750 [7.8] 10,250 [3.0] 1175 [554] 72
1 - dehumid 18,900 [5.5] 6,900 [2.0] 800 [378] 69
2 - dehumid 24,550 [7.2] 11,050 [3.2] 975 [460]172
1 16,700 [4.9] 7,100 [2.1]
2 22,450 [6.6] 11,150 [3.3] 1075 [507] 72
1 17,000 [5.0] 7,200 [2.1]
2 22,300 [6.5] 11,100 [3.3] 1175 [554] 72
1 17,000 [5.0] 7,200 [2.1]
2 22,300 [6.5] 11,100 [3.3] 1200 [566] 72
1 17,650 [5.2] 6,750 [2.0]
2 22,350 [6.5] 11,050 [3.2] 1200 [566] 72
1 17,650 [5.2] 6,750 [2.0]
2 22,500 [6.6] 11,100 [3.3] 1225 [578] 72
1 16,950 [5.0] 7,250 [2.1]
2 22,300 [6.5] 11,100 [3.3] 1225 [578] 72
1 16,950 [5.0] 7,250 [2.1]
2 22,300 [6.5] 11,100 [3.3] 1225 [578] 72
1 17,950 [5.3] 6,850 [2.0]
2 22,500 [6.6] 11,100 [3.3] 1200 [566] 72
1 17,650 [5.2] 6,750 [2.0]
2 22,500 [6.6] 11,100 [3.3] 1200 [566] 72
1 16,950 [5.0] 7,250 [2.1]
2 22,300 [6.5] 11,100 [3.3] 1225 [578] 72
Net
Sensible
BTU/H [kW]
14,050 [4.1] 4,550 [1.3] 625 [295]
14,150 [4.1] 4,550 [1.3]
20,450 [6.0] 6,150 [1.8]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
24,600 [7.2] 16.50 12.95
24,600 [7.2] 16.50 12.80
24,600 [7.2] 16.50 12.90
24,800 [7.3] 16.50 13.10
24,600 [7.2] 16.50 13.00
24,800 [7.3] 16.50 13.05
24,800 [7.3] 17.00 13.20
24,600 [7.2] 16.50 12.90
24,600 [7.2] 16.50 12.95
24,800 [7.3] 16.00 12.70
24,200 [7.1] 14.50 11.85
24,600 [7.2] 16.50 13.30
24,600 [7.2] 16.50 13.30
37,000 [10.8] 18.00 13.80
33,600 [9.8] 14.00 11.20
33,400 [9.8] 14.50 11.00
33,400 [9.8] 14.50 10.90
33,400 [9.8] 14.50 11.05
33,600 [9.8] 14.50 10.90
33,400 [9.8] 15.00 11.05
33,400 [9.8] 14.50 10.95
33,600 [9.8] 15.00 11.30
33,600 [9.8] 15.00 11.25
33,400 [9.8] 15.00 11.05
AHRI Rating
SEER
EER
12.70 24,800 [7.3] 16.00
Indoor Airflow
CFM [L/s]
850 [401]174
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
575 [271] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
600 [283] 71
950 [448] 69
900 [425] 69
875 [413] 69
900 [425] 69
875 [413] 69
875 [413] 69
900 [425] 69
925 [437] 69
925 [437] 69
875 [413] 69
900 [425] 69
Sound
Rating
db
71
Page 10
10 Rheem Heating, Cooling and Water Heating
Performance Data @ AHRI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
Rev.
2/24/2010
036JEZ
Model Numbers
ID Coil
RCFM-H*3617
RCFM-H*3621
ID Air Mover
RGJD-07?MCK?
RGJF-06?MCK?
RGJF-07?MCK?
RGLR-07?AMK?
RGPE-05?BMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGRM-04?MAE?
RGRM-06?MAE?
RGRM-07?MAE?
RGTM-06?MAE?
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFE-06?MCK?
RGFE-07?MCK?
RGFE-09?ZCM?
RGFE-10?ZCM?
RGGD-06?MCK?
RGGD-07?MCK?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGE-06?MCK?
RGGE-07?MCK?
Stage
2 22,300 [6.5] 11,100 [3.3]
1
2 22,500 [6.6] 11,100 [3.3] 1200 [566] 72
1 17,650 [5.2] 6,750 [2.0]
2 22,500 [6.6] 11,100 [3.3] 1200 [566] 72
1 17,150 [5.0] 7,250 [2.1]
2 22,600 [6.6] 11,200 [3.3] 1200 [566] 72
1 17,800 [5.2] 6,800 [2.0]
2 22,500 [6.6] 11,100 [3.3] 1200 [566] 72
1 17,000 [5.0] 7,200 [2.1]
2 22,300 [6.5] 11,100 [3.3] 1200 [566] 72
1 17,150 [5.0] 7,250 [2.1]
2 22,600 [6.6] 11,200 [3.3] 1200 [566] 72
1 16,750 [4.9] 7,050 [2.1]
2 22,050 [6.5] 10,950 [3.2] 1025 [484] 72
1 16,700 [4.9] 7,100 [2.1]
2 22,050 [6.5] 10,950 [3.2] 1000 [472] 72
1 16,700 [4.9] 7,100 [2.1]
2 22,100 [6.5] 10,900 [3.2] 1025 [484] 72
1 18,050 [5.3] 6,950 [2.0]
2 22,450 [6.6] 11,150 [3.3] 1225 [578] 72
1 16,950 [5.0] 7,050 [2.1]
2 22,550 [6.6] 11,050 [3.2] 1150 [543] 72
1 17,250 [5.1] 7,150 [2.1]
2 22,600 [6.6] 11,000 [3.2] 1175 [554] 72
1 17,250 [5.1] 7,150 [2.1]
2 22,400 [6.6] 11,000 [3.2] 1200 [566] 72
2 22,700 [6.7] 11,100 [3.3] 1150 [543] 72
1 17,250 [5.1] 7,150 [2.1]
2 22,850 [6.7] 11,150 [3.3] 1175 [554]172
1 19,600 [5.7] 5,800 [1.7]
2 25,550 [7.5] 10,050 [2.9] 1200 [566] 72
1 19,600 [5.7] 5,800 [1.7]
2 25,550 [7.5] 10,050 [2.9] 1225 [578] 72
1 19,800 [5.8] 5,800 [1.7]
2 25,850 [7.6] 10,150 [3.0] 1200 [566] 72
1 19,750 [5.8] 5,850 [1.7]
2 25,850 [7.6] 10,150 [3.0] 1225 [578] 72
1 17,200 [5.0] 7,200 [2.1]
2 22,550 [6.6] 11,050 [3.2] 1225 [578] 72
1 17,200 [5.0] 7,200 [2.1]
2 22,400 [6.6] 11,000 [3.2] 1225 [578] 72
1 17,100 [5.0] 7,100 [2.1]
2 22,800 [6.7] 11,200 [3.3] 1175 [554] 72
1 17,250 [5.1] 7,150 [2.1]
2 22,800 [6.7] 11,200 [3.3] 1175 [554] 72
1 19,900 [5.8] 5,900 [1.7]
2 25,700 [7.5] 10,100 [3.0] 1200 [566] 72
1 19,600 [5.7] 5,800 [1.7]
2 25,700 [7.5] 10,100 [3.0] 1200 [566] 72
Net
Sensible
BTU/H [kW]
16,950 [5.0] 7,250 [2.1] 925 [437]
17,950 [5.3] 6,850 [2.0]
17,250 [5.1] 7,150 [2.1]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
33,600 [9.8] 15.00 11.30
33,600 [9.8] 15.00 11.25
33,800 [9.9] 15.00 11.50
33,600 [9.8] 15.00 11.30
33,400 [9.8] 14.50 11.00
33,800 [9.9] 15.00 11.40
33,000 [9.7] 15.00 11.45
33,000 [9.7] 15.00 11.55
33,000 [9.7] 15.00 11.25
33,600 [9.8] 14.50 11.05
33,600 [9.8] 14.00 11.20
33,600 [9.8] 14.50 11.05
33,400 [9.8] 14.50 10.95
33,800 [9.9] 15.50 12.00
34,000 [10.0] 15.50 11.70
35,600 [10.4] 15.50 11.60
35,600 [10.4] 15.50 11.45
36,000 [10.5] 16.00 12.20
36,000 [10.5] 16.00 12.05
33,600 [9.8] 15.00 11.10
33,400 [9.8] 15.00 11.00
34,000 [10.0] 12.00
34,000 [10.0] 15.50 12.00
35,800 [10.5] 16.00 11.90
35,800 [10.5] 15.50 11.85
AHRI Rating
SEER
15.50
Indoor Airflow
EER
10.95 33,400 [9.8] 14.50
Sound
CFM [L/s]
1225 [578]172
925 [437] 69
875 [413] 69
925 [437] 69
900 [425] 69
900 [425] 69
900 [425] 69
750 [354] 69
775 [366] 69
800 [378] 69
1075 [507] 69
900 [425] 69
875 [413] 69
900 [425] 69
850 [401] 69
850 [401] 69
875 [413] 69
875 [413] 69
875 [413] 69
900 [425] 69
900 [425] 69
925 [437] 69
800 [378] 69
825 [389] 69
925 [437] 69
875 [413] 69
Rating
db
69
Page 11
Rheem Heating, Cooling and Water Heating 11
Performance Data @ AHRI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
Rev.
2/24/2010
036JEZ
Model Numbers
ID Coil
RCFM-H*3621
ID Air Mover
RGGE-09?ZCM?
RGGE-10?ZCM?
RGJD-06?MCK?
RGJD-07?MCK?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJF-06?MCK?
RGJF-07?MCK?
RGJF-09?ZCM?
RGJF-10?ZCM?
RGLR-07?AMK?
RGLR-07?BRQ?
RGLR-10?BRM?
RGPR-05?BMK?
RGPR-07?AMK?
RGPR-07?BRQ?
RGPR-10?BRM?
RGRM-04?MAE?
RGRM-06?MAE?
RGRM-07?MAE?
RGRM-07?YBG?
RGRM-09?ZAJ?
RGRM-10?ZAJ?
RGTM-06?MAE?
RGTM-07?RBG?
RGTM-09?ZAJ?
Stage
2 26,000 [7.6] 10,200 [3.0]
1
2 25,850 [7.6] 10,150 [3.0] 1200 [566] 72
1 17,200 [5.0] 7,200 [2.1]
2 22,550 [6.6] 11,050 [3.2] 1225 [578] 72
1 17,200 [5.0] 7,200 [2.1]
2 22,400 [6.6] 11,000 [3.2] 1225 [578] 72
1 17,100 [5.0] 7,100 [2.1]
2 22,800 [6.7] 11,200 [3.3] 1175 [554] 72
1 17,250 [5.1] 7,150 [2.1]
2 22,800 [6.7] 11,200 [3.3] 1175 [554] 72
1 19,900 [5.8] 5,900 [1.7]
2 25,700 [7.5] 10,100 [3.0] 1200 [566] 72
1 19,600 [5.7] 5,800 [1.7]
2 25,700 [7.5] 10,100 [3.0] 1200 [566] 72
1 19,800 [5.8] 5,800 [1.7]
2 26,000 [7.6] 10,200 [3.0] 1225 [578] 72
1 19,600 [5.7] 5,800 [1.7]
2 25,850 [7.6] 10,150 [3.0] 1200 [566] 72
1 17,400 [5.1] 7,200 [2.1]
2 22,650 [6.6] 11,150 [3.3] 1200 [566] 72
1 17,350 [5.1] 7,250 [2.1]
2 23,000 [6.7] 11,200 [3.3] 1225 [578] 72
1 17,350 [5.1] 7,250 [2.1]
2 22,950 [6.7] 11,250 [3.3] 1200 [566] 72
1 17,250 [5.1] 7,150 [2.1]
2 22,600 [6.6] 11,000 [3.2] 1200 [566] 72
2 22,700 [6.7] 11,100 [3.3] 1200 [566] 72
1 17,550 [5.1] 7,250 [2.1]
2 22,950 [6.7] 11,250 [3.3] 1200 [566]172
1 17,350 [5.1] 7,250 [2.1]
2 22,800 [6.7] 11,200 [3.3] 1225 [578] 72
1 17,000 [5.0] 7,000 [2.1]
2 22,100 [6.5] 10,900 [3.2] 1025 [484] 72
1 16,950 [5.0] 7,050 [2.1]
2 22,150 [6.5] 10,850 [3.2] 1000 [472] 72
1 16,950 [5.0] 7,050 [2.1]
2 22,150 [6.5] 10,850 [3.2] 1025 [484] 72
1 16,650 [4.9] 6,950 [2.0]
2 22,000 [6.4] 10,800 [3.2] 975 [460] 72
1 17,350 [5.1] 7,250 [2.1]
2 22,700 [6.7] 11,100 [3.3] 1225 [578] 72
1 17,400 [5.1] 7,200 [2.1]
2 22,550 [6.6] 11,050 [3.2] 1150 [543] 72
1 20,050 [5.9] 5,950 [1.7]
2 25,500 [7.5] 10,100 [3.0] 1225 [578] 72
1 19,900 [5.8] 5,900 [1.7]
2 26,150 [7.7] 10,250 [3.0] 1275 [602] 72
1 19,900 [5.8] 5,900 [1.7]
2 26,000 [7.6] 10,200 [3.0] 1225 [578] 72
Net
Sensible
BTU/H [kW]
19,800 [5.8] 5,800 [1.7] 875 [413]
19,600 [5.7] 5,800 [1.7]
17,400 [5.1] 7,200 [2.1]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
36,000 [10.5] 16.00 12.20
33,600 [9.8] 15.00 11.10
33,400 [9.8] 15.00 11.00
34,000 [10.0] 15.50 12.00
34,000 [10.0] 15.50 12.00
35,800 [10.5] 16.00 11.90
35,800 [10.5] 15.50 11.85
36,200 [10.6] 16.00 12.30
36,000 [10.5] 16.00 12.20
33,800 [9.9] 15.50 11.55
34,200 [10.0] 15.50 12.00
34,200 [10.0] 15.50 12.00
33,600 [9.8] 14.50 11.05
33,800 [9.9] 15.00 11.50
34,200 [10.0] 16.00 12.05
34,000 [10.0] 15.50 12.00
33,000 [9.7] 15.00 11.50
33,000 [9.7] 15.00 11.60
33,000 [9.7] 15.00 11.25
32,800 [9.6] 15.00 11.40
33,800 [9.9] 15.00 11.45
33,600 [9.8] 15.00 11.55
35,600 [10.4] 15.00 11.60
36,400 [10.7] 16.00 12.25
36,200 [10.6] 16.00 12.25
AHRI Rating
SEER
Indoor Airflow
EER
12.30 36,200 [10.6] 16.00
Sound
CFM [L/s]
1225 [578]172
875 [413] 69
900 [425] 69
925 [437] 69
800 [378] 69
825 [389] 69
925 [437] 69
875 [413] 69
875 [413] 69
875 [413] 69
925 [437] 69
900 [425] 69
925 [437] 69
900 [425] 69
900 [425] 69
875 [413] 69
925 [437] 69
750 [354] 69
775 [366] 69
800 [378] 69
700 [330] 69
950 [448] 69
875 [413] 69
1075 [507] 69
950 [448] 69
975 [460] 69
Rating
db
69
Page 12
12 Rheem Heating, Cooling and Water Heating
Performance Data @ AHRI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
Rev.
2/24/2010
036JEZ
Model Numbers
ID Coil
RCFN-H*3624
ID Air Mover
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGFE-09?ZCM?
RGFE-10?ZCM?
RGFE-12?RCM?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
RGRM-07?YBG?
RGRM-09?ZAJ?
RGRM-10?ZAJ?
RGRM-12?RAJ?
RGTM-07?RBG?
RGTM-09?ZAJ?
RGTM-10?RBJ?
Stage
2 26,200 [7.7] 10,000 [2.9]
1
2 26,600 [7.8] 10,200 [3.0] 1150 [543] 72
1 20,000 [5.9] 6,000 [1.8]
2 26,450 [7.7] 10,150 [3.0] 1175 [554] 72
1 20,150 [5.9] 6,050 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 20,450 [6.0] 6,150 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1275 [602] 72
1 20,450 [6.0] 6,150 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1250 [590] 72
1 20,600 [6.0] 6,200 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1250 [590] 72
1 19,850 [5.8] 5,950 [1.7]
2 26,600 [7.8] 10,200 [3.0] 1175 [554] 72
1 19,800 [5.8] 6,000 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1175 [554] 72
1 20,150 [5.9] 6,050 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 19,850 [5.8] 5,950 [1.7]
2 26,600 [7.8] 10,200 [3.0] 1175 [554] 72
1 19,800 [5.8] 6,000 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1175 [554] 72
1 20,150 [5.9] 6,050 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 20,150 [5.9] 6,050 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
2 26,600 [7.8] 10,200 [3.0] 1200 [566] 72
1 20,600 [6.0] 6,200 [1.8]
2 26,900 [7.9] 10,300 [3.0] 1225 [578]172
1 20,150 [5.9] 6,050 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1200 [566] 72
1 20,300 [5.9] 6,100 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 20,450 [6.0] 6,150 [1.8]
2 26,900 [7.9] 10,300 [3.0] 1250 [590] 72
1 19,850 [5.8] 5,950 [1.7]
2 26,000 [7.6] 10,000 [2.9] 1200 [566] 72
1 20,300 [5.9] 6,100 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1225 [578] 72
1 20,000 [5.9] 6,000 [1.8]
2 26,450 [7.7] 10,150 [3.0] 1150 [543] 72
1 20,300 [5.9] 6,100 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 20,300 [5.9] 6,100 [1.8]
2 26,900 [7.9] 10,300 [3.0] 1275 [602] 72
1 20,300 [5.9] 6,100 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 20,300 [5.9] 6,100 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
Net
Sensible
BTU/H [kW]
19,850 [5.8] 5,950 [1.7] 950 [448]
20,000 [5.9] 6,000 [1.8]
20,450 [6.0] 6,150 [1.8]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
36,800 [10.8] 17.50 13.35
36,600 [10.7] 17.00 13.15
37,000 [10.8] 17.50 13.30
37,000 [10.8] 17.00 12.95
36,800 [10.8] 17.00 12.85
37,000 [10.8] 17.00 13.15
36,800 [10.8] 17.50 13.30
36,800 [10.8] 17.50 13.30
37,000 [10.8] 17.50 13.50
36,800 [10.8] 17.50 13.30
36,800 [10.8] 17.50 13.30
37,000 [10.8] 17.50 13.50
37,000 [10.8] 17.50 13.50
36,800 [10.8] 17.50 13.50
37,200 [10.9] 18.00 13.60
36,800 [10.8] 17.50 13.50
37,000 [10.8] 17.50 13.35
37,200 [10.9] 17.50 13.50
36,000 [10.5] 16.50 12.10
36,800 [10.8] 17.00 12.90
36,600 [10.7] 17.00 13.05
37,000 [10.8] 17.50 13.20
37,200 [10.9] 17.00 13.20
37,000 [10.8] 17.00 13.25
37,000 [10.8] 17.50 13.50
AHRI Rating
SEER
Indoor Airflow
EER
12.30 36,200 [10.6] 15.00
Sound
CFM [L/s]
1175 [554]172
850 [401] 69
850 [401] 69
900 [425] 69
1025 [484] 69
1025 [484] 69
1025 [484] 69
800 [378] 69
825 [389] 69
900 [425] 69
800 [378] 69
825 [389] 69
900 [425] 69
900 [425] 69
925 [437] 69
1000 [472] 69
875 [413] 69
925 [437] 69
1000 [472] 69
850 [401] 69
950 [448] 69
875 [413] 69
925 [437] 69
950 [448] 69
975 [460] 69
975 [460] 69
Rating
db
69
Page 13
Rheem Heating, Cooling and Water Heating 13
Performance Data @ AHRI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
Rev.
2/24/2010
036JEZ
Model Numbers
ID Coil
RCQD-3621
RCQD-3621A*
ID Air Mover
RGFE-06?MCK?
RGFE-07?MCK?
RGFE-09?ZCM?
RGFE-10?ZCM?
RGJF-06?MCK?
RGJF-07?MCK?
RGJF-09?ZCM?
RGJF-10?ZCM?
RGRM-04?MAE?
RGRM-06?MAE?
RGRM-07?MAE?
RGRM-07?YBG?
RGRM-09?ZAJ?
RGRM-10?ZAJ?
RGFD-06?MCK?
RGFD-07?MCK?
RGFD-09?ZCM?
RGFD-10?ZCM?
RGJD-06?MCK?
RGJD-07?MCK?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGPR-05?BMK?
RGPR-07?AMK?
RGPR-07?BRQ?
RGPR-10?BRM?
Stage
2 25,400 [7.4] 10,000 [2.9]
1
2 25,550 [7.5] 10,050 [2.9] 1225 [578] 72
1 20,250 [5.9] 5,950 [1.7]
2 25,950 [7.6] 10,250 [3.0] 1275 [602] 72
1 20,050 [5.9] 5,950 [1.7]
2 25,800 [7.6] 10,200 [3.0] 1250 [590] 72
1 19,900 [5.8] 5,900 [1.7]
2 25,500 [7.5] 10,100 [3.0] 1200 [566] 72
1 19,600 [5.7] 5,800 [1.7]
2 25,550 [7.5] 10,050 [2.9] 1200 [566] 72
1 19,750 [5.8] 5,850 [1.7]
2 25,950 [7.6] 10,250 [3.0] 1225 [578] 72
1 19,750 [5.8] 5,850 [1.7]
2 25,650 [7.5] 10,150 [3.0] 1200 [566] 72
1 19,050 [5.6] 5,950 [1.7]
2 25,100 [7.4] 9,300 [2.7] 1025 [484] 72
1 19,050 [5.6] 5,950 [1.7]
2 24,900 [7.3] 9,300 [2.7] 1000 [472] 72
1 19,250 [5.6] 5,950 [1.7]
2 24,900 [7.3] 9,300 [2.7] 1025 [484] 72
1 18,700 [5.5] 5,900 [1.7]
2 24,750 [7.3] 9,250 [2.7] 975 [460] 72
1 19,650 [5.8] 6,150 [1.8]
2 25,650 [7.5] 9,550 [2.8] 1225 [578] 72
1 19,500 [5.7] 6,100 [1.8]
2 25,500 [7.5] 9,500 [2.8] 1150 [543] 72
2 27,100 [7.9] 9,700 [2.8] 1175 [554] 72
1 19,800 [5.8] 6,200 [1.8]
2 27,250 [8.0] 9,750 [2.9] 1200 [566]172
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1150 [543] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,400 [8.0] 9,800 [2.9] 1175 [554] 72
1 19,950 [5.8] 6,250 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1225 [578] 72
1 19,800 [5.8] 6,200 [1.8]
2 27,400 [8.0] 9,800 [2.9] 1225 [578] 72
1 19,450 [5.7] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,800 [5.8] 6,200 [1.8]
2 27,400 [8.0] 9,800 [2.9] 1200 [566] 72
1 19,950 [5.8] 6,250 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1200 [566] 72
1 19,800 [5.8] 6,200 [1.8]
2 27,850 [8.2] 9,950 [2.9] 1200 [566] 72
1 19,950 [5.8] 6,250 [1.8]
2 27,850 [8.2] 9,950 [2.9] 1225 [578] 72
Net
Sensible
BTU/H [kW]
19,600 [5.7] 5,800 [1.7] 875 [413]
19,600 [5.7] 5,800 [1.7]
19,650 [5.8] 6,150 [1.8]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
35,600 [10.4] 15.50 11.70
36,200 [10.6] 16.00 12.25
36,000 [10.5] 16.00 12.15
35,600 [10.4] 16.00 12.15
35,600 [10.4] 16.00 12.00
36,200 [10.6] 16.50 12.60
35,800 [10.5] 16.50 12.45
34,400 [10.1] 16.00 11.95
34,200 [10.0] 16.50 12.05
34,200 [10.0] 16.00 11.75
34,000 [10.0] 16.00 11.90
35,200 [10.3] 16.00 12.00
35,000 [10.3] 16.50 12.10
36,800 [10.8] 16.00 12.05
37,000 [10.8] 16.00 12.05
37,400 [11.0] 17.00 12.95
37,200 [10.9] 17.00 12.75
37,400 [11.0] 16.50 12.30
37,200 [10.9] 16.50 12.15
37,400 [11.0] 17.00 12.95
37,400 [11.0] 17.00 12.95
37,200 [10.9] 16.00 12.15
37,400 [11.0] 17.00 12.65
37,800 [11.1] 17.00 13.20
37,800 [11.1] 17.00 13.00
AHRI Rating
SEER
Indoor Airflow
EER
11.80 35,400 [10.4] 16.00
Sound
CFM [L/s]
1200 [566]172
875 [413] 69
1025 [484] 69
1025 [484] 69
925 [437] 69
875 [413] 69
875 [413] 69
875 [413] 69
750 [354] 69
775 [366] 69
800 [378] 69
700 [330] 69
950 [448] 69
875 [413] 69
875 [413] 69
900 [425] 69
850 [401] 69
850 [401] 69
900 [425] 69
925 [437] 69
800 [378] 69
825 [389] 69
900 [425] 69
900 [425] 69
875 [413] 69
925 [437] 69
Rating
db
69
Page 14
14 Rheem Heating, Cooling and Water Heating
Performance Data @ AHRI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
Rev.
2/24/2010
RCQD-3621A*+RXMD-C06 Coil Only
036JEZ
Model Numbers
ID Coil
RCQD-3621A*
RCQD-3624
RCQD-3624A*
ID Air Mover
RGRM-04?MAE?
RGRM-06?MAE?
RGRM-07?MAE?
RGRM-07?YBG?
RGRM-09?ZAJ?
RGRM-10?ZAJ?
RGFE-09?ZCM?
RGFE-10?ZCM?
RGFE-12?RCM?
RGJF-09?ZCM?
RGJF-10?ZCM?
RGJF-12?RCM?
RGRM-07?YBG?
RGRM-09?ZAJ?
RGRM-10?ZAJ?
RGRM-12?RAJ?
RBHM-24J*
RBHN-24J*
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGPR-07?BRQ?
Stage
2 25,100 [7.4] 9,300 [2.7]
1
2 24,900 [7.3] 9,300 [2.7] 1000 [472] 72
1 19,250 [5.6] 5,950 [1.7]
2 24,900 [7.3] 9,300 [2.7] 1025 [484] 72
1 18,700 [5.5] 5,900 [1.7]
2 24,750 [7.3] 9,250 [2.7] 975 [460] 72
1 19,650 [5.8] 6,150 [1.8]
2 25,650 [7.5] 9,550 [2.8] 1225 [578] 72
1 19,500 [5.7] 6,100 [1.8]
2 25,500 [7.5] 9,500 [2.8] 1150 [543] 72
1 19,500 [5.7] 6,100 [1.8]
2 27,100 [7.9] 9,700 [2.8] 1150 [543] 72
1 19,750 [5.8] 5,850 [1.7]
2 25,650 [7.5] 10,150 [3.0] 1200 [566] 72
1 19,950 [5.8] 5,850 [1.7]
2 26,000 [7.6] 10,200 [3.0] 1225 [578] 72
1 19,750 [5.8] 5,850 [1.7]
2 25,950 [7.6] 10,250 [3.0] 1225 [578] 72
1 19,750 [5.8] 5,850 [1.7]
2 25,950 [7.6] 10,250 [3.0] 1225 [578] 72
1 19,750 [5.8] 5,850 [1.7]
2 25,850 [7.6] 10,150 [3.0] 1200 [566] 72
1 19,750 [5.8] 5,850 [1.7]
2 26,000 [7.6] 10,200 [3.0] 1200 [566] 72
1 18,700 [5.5] 5,900 [1.7]
2 25,300 [7.4] 9,500 [2.8] 975 [460] 72
2 26,000 [7.6] 9,800 [2.9] 1225 [578] 72
1 19,450 [5.7] 6,150 [1.8]
2 25,850 [7.6] 9,750 [2.9] 1150 [543]172
1 19,650 [5.8] 6,150 [1.8]
2 26,150 [7.7] 9,850 [2.9] 1225 [578] 72
1 20,100 [5.9] 6,300 [1.8]
2 28,000 [8.2] 10,000 [2.9] 1200 [566] 72
1 20,100 [5.9] 6,300 [1.8]
2 28,000 [8.2] 10,000 [2.9] 1175 [554] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1150 [543] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,950 [5.8] 6,250 [1.8]
2 27,850 [8.2] 9,950 [2.9] 1225 [578] 72
1 19,450 [5.7] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,950 [5.8] 6,250 [1.8]
2 28,000 [8.2] 10,000 [2.9] 1225 [578] 72
1 19,800 [5.8] 6,200 [1.8]
2 27,850 [8.2] 9,950 [2.9] 1200 [566] 72
Net
Sensible
BTU/H [kW]
19,050 [5.6] 5,950 [1.7] 750 [354]
19,050 [5.6] 5,950 [1.7]
19,600 [5.7] 6,200 [1.8]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
34,200 [10.0] 16.50 12.05
34,200 [10.0] 16.00 11.75
34,000 [10.0] 16.00 11.90
35,200 [10.3] 16.00 12.00
35,000 [10.3] 16.50 12.10
36,800 [10.8] 15.00 12.10
35,800 [10.5] 16.50 12.50
36,200 [10.6] 16.50 12.45
36,200 [10.6] 16.50 12.75
36,200 [10.6] 16.50 12.70
36,000 [10.5] 16.50 12.50
36,200 [10.6] 16.50 12.85
34,800 [10.2] 16.00 12.15
35,800 [10.5] 16.00 12.30
35,600 [10.4] 16.50 12.40
36,000 [10.5] 16.50 12.55
38,000 [11.1] 17.50 13.55
38,000 [11.1] 17.50 13.90
37,400 [11.0] 17.00 13.00
37,400 [11.0] 17.00 12.85
37,800 [11.1] 17.00 13.05
37,400 [11.0] 17.00 13.00
37,400 [11.0] 17.00 13.00
38,000 [11.1] 17.00 13.20
37,800 [11.1] 17.50 13.25
AHRI Rating
SEER
Indoor Airflow
EER
11.95 34,400 [10.1] 16.00
Sound
CFM [L/s]
1025 [484]172
775 [366] 69
800 [378] 69
700 [330] 69
950 [448] 69
875 [413] 69
925 [437] 69
875 [413] 69
900 [425] 69
875 [413] 69
875 [413] 69
875 [413] 69
875 [413] 69
700 [330] 69
950 [448] 69
875 [413] 69
925 [437] 69
900 [425] 69
925 [437] 69
850 [401] 69
850 [401] 69
900 [425] 69
800 [378] 69
825 [389] 69
900 [425] 69
875 [413] 69
Rating
db
69
Page 15
Rheem Heating, Cooling and Water Heating 15
Performance Data @ AHRI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
Rev.
2/24/2010
036JEZ
RCQD-3624A*+RXMD-C06 Coil Only
Model Numbers
ID Coil
RCQD-364A*
RCSM-H*3621 RHPL-HM3621
ID Air Mover
RGPR-10?BRM?
RGPR-12?ARM?
RGRM-07?YBG?
RGRM-09?ZAJ?
RGRM-10?ZAJ?
RGRM-12?RAJ?
Stage
2 27,850 [8.2] 9,950 [2.9]
1
2 28,000 [8.2] 10,000 [2.9] 1250 [590] 72
1 18,700 [5.5] 5,900 [1.7]
2 25,300 [7.4] 9,500 [2.8] 975 [460] 72
1 19,600 [5.7] 6,200 [1.8]
2 26,000 [7.6] 9,800 [2.9] 1225 [578] 72
1 19,450 [5.7] 6,150 [1.8]
2 25,850 [7.6] 9,750 [2.9] 1150 [543] 72
1 19,650 [5.8] 6,150 [1.8]
2 26,150 [7.7] 9,850 [2.9] 1225 [578] 72
1 19,500 [5.7] 6,100 [1.8]
2 27,100 [7.9] 9,700 [2.8] 1150 [543] 72
1 17,350 [5.1] 7,250 [2.1]
2 22,950 [6.7] 11,250 [3.3] 1225 [578] 72
Net
Sensible
BTU/H [kW]
19,950 [5.8] 6,250 [1.8] 925 [437]
20,250 [5.9] 6,350 [1.9]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
AHRI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total Capacity
BTU/H [kW]
38,000 [11.1] 17.00 13.20
34,800 [10.2] 16.00 12.15
35,800 [10.5] 16.00 12.30
35,600 [10.4] 16.50 12.40
36,000 [10.5] 16.50 12.55
36,800 [10.8] 15.00 12.10
34,200 [10.0] 16.00 12.10
AHRI Rating
SEER
Indoor Airflow
EER
13.10 37,800 [11.1] 17.00
Sound
CFM [L/s]
1225 [578] 72
1000 [472] 69
700 [330] 69
950 [448] 69
875 [413] 69
925 [437] 69
925 [437] 69
925 [437] 69
Rating
db
69 1
Page 16
16 Rheem Heating, Cooling and Water Heating
Rheem will furnish a replacement for any part of this product
which fails in normal use and service within the applicable
period stated, in accordance with the terms of the limited
warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms
and Conditions, See Your Local Installer or Contact the Manufacturer for
a Copy.
Limited Parts Warranty:
Rheem Prestige Series™ equipment features a 10-year
limited parts warranty.*
*This ten-year limited parts warranty is applicable only to single-phase
products installed in residential applications.
Electrical and Physical Data
RASL- JEZ Conditional Replacement Warranty:
Rheem will provide a replacement model (if an exact replacement is not available, an equivalent product will be provided)
to the original purchaser if the compressor fails within 10
years (providing the unit is installed with a new Rheem
Air Handler OR Rheem Indoor Coil with a Rheem Gas
Furnace, and is properly matched as specified by Rheem
and/or listed in the AHRI published rating, and if additional
conditions are satisfied. See product warranty card for
additional information.
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE
FROM YOUR RETAILER.
Model Number
RASL-
Height “H”
(Inches) [mm]
Length “L”
(Inches) [mm]
Width “W”
(Inches) [mm]
024JEZ/036JEZ 33 [838] 443/8 [1127] 311/2 [800]
Unit Dimensions
[ ] Designates Metric Conversions
GENERAL TERMS OF LIMITED WARRANTY
ELECTRICAL
Model
Number
Rev. 2/24/2009
RASL-
Frequency (Hz)
Voltage (Volts)
Phase
Compressor
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Min.
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Min.
Amperes
Amperes
Max.
Face Area
Sq. Ft. [m
Outdoor Coil
2
024JEZ 1-60-208/230 10.3/10.3 52 0.5 14/14 20/20 20/20 15.8 [1.47] 1
036JEZ 1-60-208/230 16.7/16.7 82 2.8 24/24 30/30 40/40 23.01 [2.14] 1
AIR DISCHARGE
ALLOW 60 [1524 mm] CLEARANCE
W
L
H
]
Rows
No.
PHYSICAL
CFM
[L/s]
2200/2500
[1038/1180]
2800/3400
[1321/1604]
Refrig.
Per
Circuit
Oz. [g]
Net
Lbs. [kg]
Weight
Shipping
Lbs. [kg]
144 [4082] 236 [107] 263.5 [119.5]
150 [4252] 250.5 [113.6] 260.5 [118.2]
ACCESS
PANEL
ALTERNATE HIGH VOLTAGE
CONNECTION (KNOCKOUT)
11
/32 [34 mm]
1
ALLOW 24 [610 mm]
ACCESS CLEARANCE
AIR INLETS
(LOUVERS)
ALLOW 6 [152 mm]
MIN. CLEARANCE
3 SIDES
SERVICE
FITTINGS
3
0
0
0
0
-
A
HIGH PRESSURE
CONTROL
MANUAL RESET
(FIELD INSTALLED
ACCESSORY)
VAPOR LINE
CONNECTION
LOW VOLTAGE
CONNECTION
7
/8 0 [22 mm]
LIQUID LINE
CONNECTION
7
/8 0 [73 mm] DIA.
2
ACCESSORY
KNOCKOUTS
HIGH VOLTAGE
CONNECTION
11
/32 0 [34 mm]
1
SERVICE ACCESS
TO ELECTRICAL &
VALVES ALLOW
240 [610 mm]
CLEARANCE
ONE SIDE
Page 17
Rheem Heating, Cooling and Water Heating 17
Condensing Unit Refrigerant Line Size Information
NOTES:
*Standard line size.
N/A = Application not recommended.
Note: Using suction line larger than shown in chart will result in poor oil return.
[ ] Designates Metric Conversions
Liquid Line Sizing (2-Stage R-410A)
Liquid Line Size
Total Equivalent Length—Feet [m] Total Equivalent Length—Feet [m]
100
[30.48]
125
[38.10]
150
[45.72]25[7.62]50[15.24]75[22.86]
3 Ton
3/4" [19.05] I.D.
5
/
8" [15.88 mm]O.D. Optional
3
/4 " [19.05 mm]O.D. Standard
—
1.00
1.00
—
.99
1.00
—
.97
.98
—
.95
.97
99
1.00
—
.98
.99
—
.95
.97
—
.91
.95
—
System
Capacity
(2nd
Stage)
Liquid Line
Connection
Size
(Inch I.D.)
[mm]
Line Size
(Inch O.D.)
[mm]
Outdoor Unit above Indoor Coil (Cooling Only)
25
[7.62]50[15.24]75[22.86]
Minimum Vertical Separation—Feet [m] Maximum Vertical Separation—Feet [m]
1/4* [7.94] 0 0 17 [5.18] 43 [13.11] 70 [21.34] 95 [28.96] 25 [7.62] 10 [3.05] N/A N/A N/A N/A
″
3/8
2 Ton
[9.53]
5/16 [7.94] 0 0 0 0 0 0 25 [7.62] 50 [15.24] 40 [12.19] 35 [10.67] 29 [8.84] 22 [6.71]
3/8* [9.53] 0 0 0 0 0 0 25 [7.62] 50 [15.24] 45 [13.72] 42 [12.80] 39 [11.89] 37 [11.28]
5/16 [7.94] 0 0 0 0 0 7 [2.13] 25 [7.62] 39 [11.89] 28 [8.53] 16 [4.88] 5 [1.52] N/A
″
3 Ton
3/8
[9.53]
3/8* [9.53] 0 0 0 0 0 0 25 [7.62] 50 [15.24] 51 [15.54] 48 [14.63] 44 [13.41] 40 [12.19]
Suction Line Length/Size versus Capacity Multiplier (2-Stage R-410A)
Unit Size 2 Ton
Suction Line Connection Size
Suction Line Run
Feet [m]
25'
[7.62]
50'
[15.24]
100'
[30.48]
150'
[45.72]
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
Optional
Standard
Optional
3/4" [19.05] I.D.
5
/
8" [15.88 mm]O.D. Optional
3
/4 " [19.05 mm]O.D. Standard
Liquid Line Size
Outdoor Unit Below Indoor Coil
100
[30.48]
125
[38.10]
150
[45.72]
Page 18
18 Rheem Heating, Cooling and Water Heating
NOTES
Page 19
Rheem Heating, Cooling and Water Heating 19
NOTES
Page 20
Before proceeding with installation, refer
to installation instructions packaged
with each model, as well as complying
with all Federal, State, Provincial, and
Local codes, regulations, and practices.
Rheem Heating,
Cooling and
Water Heating
P.O. Box 17010, Fort Smith, AR 72917
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A. 5-10 DC FORM NO. A11-189 REV. 5