Page 1
FORM NO. A11-196
Supersedes Form No. A11-189 Rev. 2
CONDENSING UNITS
RASL- JEC
18 Seer Two-Stage Cooling
Efficiencies up to 19.50 SEER/14.30 EER
Nominal Size 2 to 5 Tons [7.03 kW] to [17.6 kW]
Five Models
Cooling Capacity
24,600 to 57,200 BTU/HR
[7.21 kW] to [16.76 kW]
The Rheem Prestige Series™ High Efficiency Two-Stage RASLJEC Condensing Unit was designed with performance in mind.
These units offer comfort, energy conservation and dependability
for single, multi-family and light commercial applications. The
Rheem Prestige Series™ Two-Stage RASL- JEC Condensing
Units are the result of an ongoing development program for
improved efficiencies. With system SEER’s as high as 19.5, these
units continue a tradition of delivering high efficiency.
■ Industry’s lowest profile design: 33" maximum height
■ The Comfort Control
2
System™ provides over 32+ on-board
diagnostics and fault history codes for condensing units with
single-phase compressors by detecting system and electrical
problems. The integrated diagnostics with Active Protection™
prevents compressor operation when potentially harmful conditions are detected. Sends “Call for Service” alert notification to
the thermostat to alert the homeowner of required service.
■
Serial Communication Enhanced – When installed with a Serial
Communicating Air Handler (RHPL/RHPN-HM****JC) and user
interface control (RHC-TST501CMMS) Series 500 thermostat
this unit offers 4 or 2 wire installation, auto-configuration, and
diagnostic messaging with full communicating capability.
■
Legacy Enabled – Unit can be conventionally wired using
24VAC with non-communicating Rheem Prestige air-handlers or
furnaces with non-communicating thermostat.
■
Features a 10-year conditional unit replacement warranty and
10-year parts warranty when properly installed with a new
Rheem air handler or Rheem indoor coil with a Rheem gas furnace. See product warranty card for additional information.
■
Reliable Two-Stage operation for precise temperature control with
On-Demand dehumidification feature. When matched with ECM
gas furnace or air-handler, the system adjusts airflow to help control humidity for unsurpassed comfort in the cooling mode.
■ All controls are accessible by removing one service panel.
Removable top grille provides access to the condenser fan
motor and condenser coil.
■ Attractive, louvered wrap-around jacket protects the coil from
yard hazards and weather extremes. Top grille is steel reinforced for extra strength. Cabinet is powder painted for allweather protection.
■ For quiet operation and improved efficiency, models feature an
ECM two-speed condenser fan motor with a 3-blade outdoor fan.
■ All models meet or exceed a 1000-hour salt spray test per ASTM
B117 Standard Practice for Operating Salt Spray Testing
Apparatus.
Equipped with
Comfort Control
2
System
™
• Serial communication enabled
• Increased system reliability and efficiency
• 32+ on-board diagnostic and operating codes
• Active Protection
™
with homeowner “Call for Service” alert
• Exclusive Design with dual 7-segment LED display
“Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps
must be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your Contractor for details or visit
www.energystar.gov <http://www.energystar.gov/>.”
earth friendly refrigerant
18.0
Page 2
2 Rheem Heating, Cooling and Water Heating
■
The Rheem exclusive Dual 7-Segment LED Display easily
shows system operating status codes
and diagnostic codes.
■
A Sealed Switch replaces the standard
contactor and
features optical
control and
latching mechanism. The sealed
switch prevents
infiltration of
insects and dust. A minimal switching arc,
by the optical control, offers greater reliability. The latching mechanism consumes
less power while reducing chatter.
■
The Status Indication and System Diagnostics feature thermostat communication capability, built-in diagnostics, current sensing and high & low pressure switch monitoring. The
thermostat communication capability alerts the homeowner to
any necessary service requirements.
Faster, more accurate service is provided by the built-in diagnostics, by
providing the HVAC professional with
dependable information. In addition,
high and low pressure-switch monitoring prevents the system from operating outside of its normal parameters.
■
The fault recall feature will allow for the last six fault-codes
to be displayed, and will retain these codes even if power
failure occurs.
■
Built-in short-cycle protection allows the compressor to
restart easily without oil removal.
■
A 30-second minimum run-time for every compressor call
allows the oil to return to the compressor.
■
Active Protection monitors the system to prevent nuisance
lockouts and prevents compressor operation when potentially harmful conditions are detected.
■
The compressor and fan are
controlled independently,
which reduces the starting load
and light dimming.
■
A manual push-button is
offered to operate the compressor and fan for 5 seconds to
allow for an operation check.
■
In order to save time and
money, replacement automotive fuses can be utilized instead of replacing the entire
control board.
STANDARD FEATURES
RASL- JEC Condensing Units
1. Scroll compressor is hermetically sealed and incorporates
internal high temperature motor overload protection, and
durable insulation on the motor windings. It is externally
mounted on rubber grommets to reduce vibration and noise.
2. Compressors have an internal pressure relief assembly to
protect against excessive pressure differential.
3. All refrigerant connections are on the exterior of the unit,
located close to the ground for neat appearing installations.
4. Cabinet is constructed of powder painted galvanized
steel. The full wrap-around louvered grille protects the coil
from damage.
5. Sound Blanket-enhanced compressor sound blanket is
standard.
6. Copper tube—aluminum fin coils are used on all models.
7. The control box is located in the top corner of the cabinet
providing for easy access through a service panel.
8. Service valves are standard on all models.
9. Field connections for power and control wiring are kept
separate.
10. Every unit is factory charged and run-tested.
11. Separate compressor compartment for easy service access.
12. Drawn, painted base pan for extra corrosion resistance and
sound reduction.
13. The RASL- JEC has a 10-year limited parts warranty, plus a
10-year conditional unit replacement warranty. Refer to the
General Terms of Limited Warranty for more details.
14. Hard Start Kits—Standard on all JEC models.
15. Control Box Cover.
16. The RASL- JEC is shipped with a liquid line filter drier, and
also features factory-installed low and high pressure
controls.
FEATURES & BENEFITS OF THE COMFORT CONTROL 2SYSTEM
™
SCROLL COMPRESSOR
024 & 036 nominal capacities
— Single scroll Ultra-Tech two-stage
compressor
— Operates at 50% capacity in non
peak condiions to improve efficiency
and comfort (humidity control)
039, 048 & 60 nominal capacities
— Dual Drive scroll compressors –
Tandem
— Operates at 50% capacity on first
compressor in non peak conditions to
improve efficiency and comfort
(humidity control)
— Compressor “A” operated by control
board “A” Compressor “B” operated
by control board “B”.
Page 3
Rheem Heating, Cooling and Water Heating 3
Accessories
■
Low Ambient Control —Cycles outdoor fan to maintain
adequate condensing pressures assuring liquid refrigerant
flow to the coil. Allows indoor cooling with outdoor
temperatures down to 0°F [–17.8°C]. (Model No. RXADA08). It is recommended that this control be installed in units
to be operated at outdoor ambient temperatures under 70°F
[21°C].
■
Thermostats
■
Compressor Crankcase Heater (Model No. 44-1740244CCH) Add to minimize refrigeration migration and to help
eliminate any startup noise or bearing “wash out”.
[ ] Designates Metric Conversions
IMPORTANT:
The Comfort Control 2System™requires a communicating
RHPL/RHPN-HM***JC Air Handler and a 500-Series Thermostat.
Page 4
4 Rheem Heating, Cooling and Water Heating
R A S L 024
COOLING
CAPACITY
024 = 24,000 BTU/HR [7.03 kW]
036 = 36,000 BTU/HR [10.55 kW]
039 = 39,000 BTU/HR [11.43 kW]
048 = 48,000 BTU/HR [14.07 kW]
060 = 60,000 BTU/HR [17.6 kW]
J EC
RHEEM REMOTE
CONDENSING
UNIT
18-SEER DESIGN
SERIES
L = FIRST DESIGN
SERIES
ELECTRICAL
DESIGNATION
J = 208/230V-1-60
EC = EQUIPPED WITH
THE
COMFORT
CONTROL
2
SYSTEM
™
—
Model Number Identification
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCSN-H*2421A* ➀
RCFM-H*2417A*
024JEC
RCFM-H*2417A*+RXMD-C06 Coil Only
RCFM-H*2421A*
RCFM-H*2421A*+RXMD-C06 Coil Only
Model Numbers
ID
Coil
Air Mover
RHPN-HM2421
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
ID
Stage
1
1 13,400 [3.9] 5,200 [1.5]
2 17,500 [5.1] 6,900 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,500 [5.1] 6,900 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,500 [4.0] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,350 [3.9] 5,150 [1.5]
2 17,650 [5.2] 6,950 [2.0] 775 [366] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,050 [3.8] 5,050 [1.5]
2 17,200 [5.0] 6,800 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,500 [5.1] 6,900 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,450 [5.1] 6,950 [2.0] 800 [378] 74
1 13,500 [4.0] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,350 [3.9] 5,150 [1.5]
2 17,650 [5.2] 6,950 [2.0] 775 [366] 74
1 13,400 [3.9] 5,200 [1.5]
2 17,650 [5.2] 6,950 [2.0] 800 [378] 74
1 13,050 [3.8] 5,050 [1.5]
2 17,200 [5.0] 6,800 [2.0] 800 [378] 74
Net
Sensible
BTU/H [kW]
13,700 [4.0] 5,100 [1.5] 600 [283]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total
Capacity
BTU/H [kW]
24,400 [7.1] 16.00 12.65
24,400 [7.1] 16.00 12.75
24,600 [7.2] 16.50 12.95
24,400 [7.1] 16.50 12.85
24,600 [7.2] 16.50 12.95
24,400 [7.1] 16.50 12.85
24,600 [7.2] 16.50 13.15
24,600 [7.2] 16.00 12.95
24,600 [7.2] 16.50 13.05
24,000 [7.0] 14.50 11.80
24,400 [7.1] 16.00 12.70
24,400 [7.1] 16.00 12.80
24,600 [7.2] 16.50 13.00
24,400 [7.1] 16.50 12.90
24,600 [7.2] 16.50 13.00
24,400 [7.1] 16.50 12.90
24,600 [7.2] 16.50 13.15
24,600 [7.2] 16.00 12.95
24,600 [7.2] 16.50 13.10
24,000 [7.0] 14.50 11.80
ARI Ratings
SEER EER
Indoor
Airflow
14.30 24,600 [7.2] 18.50
600 [283] 71
600 [283] 71
600 [283] 71
625 [295] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
625 [295] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
CFM
[L/s]
Sound
Rating
db
71
74 2 17,700 [5.2] 6,900 [2.0] 775 [366]
71 1 - dehumid 12,600 [3.7] 5,700 [1.7] 500 [236]
74 2 - dehumid 16,750 [4.9] 7,650 [2.2] 650 [307]
Page 5
Rheem Heating, Cooling and Water Heating 5
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCFN-H*2417A*
RCFN-H*2417A*+RXMD-C06 Coil Only
024JEC
RCFN-H*2421A*
RCFN-H*2421A*+RXMD-C06 Coil Only
Model Numbers
ID
Coil
RCQD-2417A*
ID
Air Mover
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RBHM-17J*
RGFD-06?MCK?
RGFD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGPR-05?BMK?
RGPR-07?AMK?
Stage
1
2
1
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,700 [5.2] 6,900 [2.0] 775 [366] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,250 [3.9] 4,950 [1.5]
2 17,250 [5.1] 6,750 [2.0] 775 [366] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,550 [5.1] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,750 [5.2] 6,850 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,600 [4.0] 5,100 [1.5]
2 17,750 [5.2] 6,850 [2.0] 800 [378] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,650 [4.0] 5,050 [1.5]
2 17,700 [5.2] 6,900 [2.0] 775 [366] 74
1 13,700 [4.0] 5,100 [1.5]
2 17,700 [5.2] 6,900 [2.0] 800 [378] 74
1 13,250 [3.9] 4,950 [1.5]
2 17,250 [5.1] 6,750 [2.0] 775 [366] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 825 [389] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 800 [378] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 800 [378] 74
1 14,100 [4.1] 4,600 [1.3]
2 18,900 [5.5] 5,900 [1.7] 800 [378] 74
1 14,150 [4.1] 4,550 [1.3]
2 18,750 [5.5] 5,850 [1.7] 800 [378] 74
1 14,050 [4.1] 4,550 [1.3]
2 18,950 [5.6] 5,850 [1.7] 775 [366] 74
1 14,100 [4.1] 4,600 [1.3]
2 18,900 [5.5] 5,900 [1.7] 800 [378] 74
Net
Sensible
BTU/H [kW]
13,650 [4.0] 5,050 [1.5] 600 [283]
17,550 [5.1] 6,850 [2.0] 800 [378]
13,650 [4.0] 5,050 [1.5] 600 [283]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
ARI Ratings
Total
Capacity
BTU/H [kW]
24,400 [7.1]
24,400 [7.1]
24,600 [7.2] 18.00 13.85
24,400 [7.1] 17.50 13.70
24,600 [7.2] 18.00 13.85
24,400 [7.1] 17.50 13.70
24,600 [7.2] 18.00 14.00
24,600 [7.2] 17.50 13.80
24,600 [7.2] 18.00 13.90
24,000 [7.0] 15.50 12.55
24,400 [7.1] 17.50 13.50
24,400 [7.1] 17.50 13.65
24,600 [7.2] 18.00 13.85
24,600 [7.2] 17.50 13.75
24,600 [7.2] 18.00 13.85
24,600 [7.2] 17.50 13.75
24,600 [7.2] 18.00 14.05
24,600 [7.2] 17.50 13.80
24,600 [7.2] 18.00 13.95
24,000 [7.0] 15.50 12.55
24,600 [7.2] 16.50 12.95
24,600 [7.2] 16.50 12.80
24,600 [7.2] 16.50 12.90
24,800 [7.3] 16.50 13.10
24,600 [7.2] 16.50 13.00
24,800 [7.3] 16.50 13.05
24,800 [7.3] 17.00 13.20
SEER
17.50
17.50
EER
13.50
13.60
Indoor
Airflow
CFM
[L/s]
600 [283] 71
625 [295] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
625 [295] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
600 [283] 71
625 [295] 71
600 [283] 71
600 [283] 71
Sound
Rating
db
71
74
71
Page 6
6 Rheem Heating, Cooling and Water Heating
Net
Sensible
BTU/H [kW]
Outdoor
Unit
RASL-
ARI Cooling Performance
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Model Numbers
71
RHPL-HM2421
1
EER
RCSM-H*2421A*
13,750 [4.0] 4,450 [1.3] 600 [283]
Sound
Rating
db
RCQD-2417A*+RXMD-C06
Total
Capacity
BTU/H [kW]
ID
Coil
Coil Only
71
Stage
ARI Ratings
1
024JEC
13,400 [3.9] 5,200 [1.5] 600 [283]
24,600 [7.2]
24,200 [7.1]
74
16.50
2
14.50
18,450 [5.4] 5,750 [1.7] 800 [378]
13.30
11.85
ID
Air Mover
2 17,600 [5.2] 7,000 [2.1] 800 [378] 74
036JEC
RCSN-H*3624A* ➀
RHPN-HM3624
1 20,450 [6.0] 6,150 [1.8]
37,000 [10.8] 18.00 13.80
950 [448] 69
Indoor
Airflow
CFM
[L/s]
2 26,750 [7.8] 10,250 [3.0] 1175 [554] 72
1 - dehumid 18,900 [5.5] 6,900 [2.0] 800 [378] 69
2 - dehumid 24,550 [7.2] 11,050 [3.2] 975 [460] 72
Net
Latent
BTU/H [kW]
SEER
RCFM-H*3617A*
Coil Only
1 16,700 [4.9] 7,100 [2.1]
33,600 [9.8] 14.00 11.20
900 [425] 69
2 22,450 [6.6] 11,150 [3.3] 1075 [507] 72
RGFD-06?MCK?
1 17,000 [5.0] 7,200 [2.1]
33,400 [9.8] 14.50 11.00
875 [413] 69
2 22,300 [6.5] 11,100 [3.3] 1175 [554] 72
RGFD-07?MCK?
1 17,000 [5.0] 7,200 [2.1]
33,400 [9.8] 14.50 10.90
900 [425] 69
2 22,300 [6.5] 11,100 [3.3] 1200 [566] 72
RGGD-06?MCK?
1 16,950 [5.0] 7,250 [2.1]
33,400 [9.8] 15.00 11.05
900 [425] 69
2 22,300 [6.5] 11,100 [3.3] 1225 [578] 72
RGGD-07?MCK?
1 16,950 [5.0] 7,250 [2.1]
33,400 [9.8] 14.50 10.95
925 [437] 69
2 22,300 [6.5] 11,100 [3.3] 1225 [578] 72
RGJD-06?MCK?
1 16,950 [5.0] 7,250 [2.1]
33,400 [9.8] 15.00 11.05
900 [425] 69
2 22,300 [6.5] 11,100 [3.3] 1225 [578] 72
RGJD-07?MCK?
1 16,950 [5.0] 7,250 [2.1]
33,400 [9.8] 14.50 10.95
925 [437] 69
2 22,300 [6.5] 11,100 [3.3] 1225 [578] 72
RGLR-07?AMK?
1 17,150 [5.0] 7,250 [2.1]
33,800 [9.9] 15.00 11.50
925 [437] 69
2 22,600 [6.6] 11,200 [3.3] 1200 [566] 72
RGPR-05?BMK?
1 17,000 [5.0] 7,200 [2.1]
33,400 [9.8] 14.50 11.00
900 [425] 69
2 22,300 [6.5] 11,100 [3.3] 1200 [566] 72
RGPR-07?AMK?
1 17,150 [5.0] 7,250 [2.1]
33,800 [9.9] 15.00 11.40
900 [425] 69
2 22,600 [6.6] 11,200 [3.3] 1200 [566] 72
RCFM-H*3621A*
Coil Only
1 16,950 [5.0] 7,050 [2.1]
33,600 [9.8] 14.00 11.20
900 [425] 69
2 22,550 [6.6] 11,050 [3.2] 1150 [543] 72
RGFD-06?MCK?
1 17,250 [5.1] 7,150 [2.1]
33,600 [9.8] 14.50 11.05
875 [413] 69
2 22,600 [6.6] 11,000 [3.2] 1175 [554] 72
RGFD-07?MCK?
1 17,250 [5.1] 7,150 [2.1]
33,400 [9.8] 14.50 10.95
900 [425] 69
2 22,400 [6.6] 11,000 [3.2] 1200 [566] 72
RGFD-09?ZCM?
1 17,250 [5.1] 7,150 [2.1]
33,800 [9.9] 15.50 12.00
850 [401] 69
2 22,700 [6.7] 11,100 [3.3] 1150 [543] 72
RGFD-10?ZCM?
1 17,250 [5.1] 7,150 [2.1]
34,000 [10.0] 15.50 11.70
850 [401] 69
2 22,850 [6.7] 11,150 [3.3] 1175 [554] 72
RGGD-06?MCK?
1 17,200 [5.0] 7,200 [2.1]
33,600 [9.8] 15.00 11.10
900 [425] 69
2 22,550 [6.6] 11,050 [3.2] 1225 [578] 72
RGGD-07?MCK?
1 17,200 [5.0] 7,200 [2.1]
33,400 [9.8] 15.00 11.00
925 [437] 69
2 22,400 [6.6] 11,000 [3.2] 1225 [578] 72
RGGD-09?ZCM?
1 17,100 [5.0] 7,100 [2.1]
34,000 [10.0] 15.50 12.00
800 [378] 69
2 22,800 [6.7] 11,200 [3.3] 1175 [554] 72
RGGD-10?ZCM?
1 17,250 [5.1] 7,150 [2.1]
34,000 [10.0] 15.50 12.00
825 [389] 69
2 22,800 [6.7] 11,200 [3.3] 1175 [554] 72
RGJD-06?MCK?
1 17,200 [5.0] 7,200 [2.1]
33,600 [9.8] 15.00 11.10
900 [425] 69
2 22,550 [6.6] 11,050 [3.2] 1225 [578] 72
RGJD-07?MCK?
1 17,200 [5.0] 7,200 [2.1]
33,400 [9.8] 15.00 11.00
925 [437] 69
2 22,400 [6.6] 11,000 [3.2] 1225 [578] 72
RGJD-09?ZCM?
1 17,100 [5.0] 7,100 [2.1]
34,000 [10.0] 15.50 12.00
800 [378] 69
2 22,800 [6.7] 11,200 [3.3] 1175 [554] 72
RGJD-10?ZCM?
1 17,250 [5.1] 7,150 [2.1]
34,000 [10.0] 15.50 12.00
825 [389] 69
2 22,800 [6.7] 11,200 [3.3] 1175 [554] 72
REV.
10/8/2008
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Page 7
Rheem Heating, Cooling and Water Heating 7
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCFM-H*3621A*
036JEC
RCFN-H*3624A*
Model Numbers
ID
Coil
RCQD-3621A*
ID
Air Mover
RGLR-07?AMK?
RGLR-07?BRQ?
RGLR-10?BRM?
RGPR-05?BMK?
RGPR-07?AMK?
RGPR-07?BRQ?
RGPR-10?BRM?
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
RGFD-06?MCK?
RGFD-07?MCK?
RGFD-09?ZCM?
RGFD-10?ZCM?
Stage
1
2
1
2 23,000 [6.7] 11,200 [3.3] 1225 [578] 72
1 17,350 [5.1] 7,250 [2.1]
2 22,950 [6.7] 11,250 [3.3] 1200 [566] 72
1 17,250 [5.1] 7,150 [2.1]
2 22,600 [6.6] 11,000 [3.2] 1200 [566] 72
1 17,400 [5.1] 7,200 [2.1]
2 22,700 [6.7] 11,100 [3.3] 1200 [566] 72
1 17,550 [5.1] 7,250 [2.1]
2 22,950 [6.7] 11,250 [3.3] 1200 [566] 72
1 17,350 [5.1] 7,250 [2.1]
2 22,800 [6.7] 11,200 [3.3] 1225 [578] 72
1 19,850 [5.8] 5,950 [1.7]
2 26,200 [7.7] 10,000 [2.9] 1175 [554] 72
1 20,000 [5.9] 6,000 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1150 [543] 72
1 20,000 [5.9] 6,000 [1.8]
1 20,150 [5.9] 6,050 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 19,850 [5.8] 5,950 [1.7]
2 26,600 [7.8] 10,200 [3.0] 1175 [554] 72
1 19,800 [5.8] 6,000 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1175 [554] 72
1 20,150 [5.9] 6,050 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 19,850 [5.8] 5,950 [1.7]
2 26,600 [7.8] 10,200 [3.0] 1175 [554] 72
1 19,800 [5.8] 6,000 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1175 [554] 72
1 20,150 [5.9] 6,050 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 20,150 [5.9] 6,050 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 20,450 [6.0] 6,150 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1200 [566] 72
1 20,600 [6.0] 6,200 [1.8]
2 26,900 [7.9] 10,300 [3.0] 1225 [578] 72
1 20,150 [5.9] 6,050 [1.8]
2 26,600 [7.8] 10,200 [3.0] 1200 [566] 72
1 20,300 [5.9] 6,100 [1.8]
2 26,750 [7.8] 10,250 [3.0] 1225 [578] 72
1 20,450 [6.0] 6,150 [1.8]
2 26,900 [7.9] 10,300 [3.0] 1250 [590] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,100 [7.9] 9,700 [2.8] 1175 [554] 72
1 19,800 [5.8] 6,200 [1.8]
2 27,250 [8.0] 9,750 [2.9] 1200 [566] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1150 [543] 72
1 19,650 [5.8]
2 27,400 [8.0] 9,800 [2.9] 1175 [554] 72
Net
Sensible
BTU/H [kW]
17,400 [5.1] 7,200 [2.1] 925 [437]
22,650 [6.6] 11,150 [3.3] 1200 [566]
17,350 [5.1] 7,250 [2.1] 900 [425]
26,450 [7.7] 10,150 [3.0] 1175 [554] 72
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
6,150 [1.8]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
ARI Ratings
Total
Capacity
BTU/H [kW]
33,800 [9.9]
34,200 [10.0]
34,200 [10.0] 15.50 12.00
33,600 [9.8] 14.50 11.05
33,800 [9.9] 15.00 11.50
34,200 [10.0] 16.00 12.05
34,000 [10.0] 15.50 12.00
36,200 [10.6] 15.00 12.30
36,800 [10.8] 17.50 13.35
36,600 [10.7] 17.00 13.15
37,000 [10.8] 17.50 13.30
36,800 [10.8] 17.50 13.30
36,800 [10.8] 17.50 13.30
37,000 [10.8] 17.50 13.50
36,800 [10.8] 17.50 13.30
36,800 [10.8] 17.50 13.30
37,000 [10.8] 17.50 13.50
37,000 [10.8] 17.50 13.50
36,800 [10.8] 17.50 13.50
37,200 [10.9] 18.00 13.60
36,800 [10.8] 17.50 13.50
37,000 [10.8] 17.50 13.35
37,200 [10.9] 17.50 13.50
36,800 [10.8] 16.00 12.05
37,000 [10.8] 16.00 12.05
37,400 [11.0] 17.00 12.95
37,200 [10.9]6917.00212.75
SEER
15.50
15.50
EER
11.55
12.00
Indoor
Airflow
CFM
[L/s]
925 [437] 69
900 [425] 69
900 [425] 69
875 [413] 69
925 [437] 69
950 [448] 69
850 [401] 69
850 [401]
900 [425] 69
800 [378] 69
825 [389] 69
900 [425] 69
800 [378] 69
825 [389] 69
900 [425] 69
900 [425] 69
925 [437] 69
1000 [472] 69
875 [413] 69
925 [437] 69
1000 [472] 69
875 [413] 69
900 [425] 69
850 [401] 69
850 [401] 69
Sound
Rating
db
69
72
69
Page 8
8 Rheem Heating, Cooling and Water Heating
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCQD-3621A*+RXMD-C06 Coil Only
036JEC
RCQD-3624A*+RXMD-C06 Coil Only
RCSM-H*3621A* RHPL-HM3621
RCSN-H*3624A* ➀
039JEC
RCFM-H*3617A*
Model Numbers
ID
Coil
RCQD-3621A*
RCQD-3624A*
ID
Air Mover
RGJD-06?MCK?
RGJD-07?MCK?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGPR-05?BMK?
RGPR-07?AMK?
RGPR-07?BRQ?
RGPR-10?BRM?
RBHM-24J*
RBHN-24J*
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
RHPN-HM3624
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
Stage
1
2
1
2 27,400 [8.0] 9,800 [2.9] 1225 [578] 72
1 19,450 [5.7] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,800 [5.8] 6,200 [1.8]
2 27,400 [8.0] 9,800 [2.9] 1200 [566] 72
1 19,950 [5.8] 6,250 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1200 [566] 72
1 19,800 [5.8] 6,200 [1.8]
2 27,850 [8.2] 9,950 [2.9] 1200 [566] 72
1 19,950 [5.8] 6,250 [1.8]
2 27,850 [8.2] 9,950 [2.9] 1225 [578] 72
1 19,500 [5.7] 6,100 [1.8]
2 27,100 [7.9] 9,700 [2.8] 1150 [543] 72
1 20,100 [5.9] 6,300 [1.8]
1 20,100 [5.9] 6,300 [1.8]
2 28,000 [8.2] 10,000 [2.9] 1175 [554] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1150 [543] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,950 [5.8] 6,250 [1.8]
2 27,850 [8.2] 9,950 [2.9] 1225 [578] 72
1 19,450 [5.7] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,650 [5.8] 6,150 [1.8]
2 27,550 [8.1] 9,850 [2.9] 1175 [554] 72
1 19,950 [5.8] 6,250 [1.8]
2 28,000 [8.2] 10,000 [2.9] 1225 [578] 72
1 19,800 [5.8] 6,200 [1.8]
2 27,850 [8.2] 9,950 [2.9] 1200 [566] 72
1 19,950 [5.8] 6,250 [1.8]
2 27,850 [8.2] 9,950 [2.9] 1225 [578] 72
1 20,250 [5.9] 6,350 [1.9]
2 28,000 [8.2] 10,000 [2.9] 1250 [590] 72
1 19,500 [5.7] 6,100 [1.8]
2 27,100 [7.9] 9,700 [2.8] 1150 [543] 72
1 17,350 [5.1] 7,250 [2.1]
2 22,950 [6.7] 11,250 [3.3] 1225 [578] 72
1 17,100 [5.0] 4,700 [1.4]
2 28,000 [8.2] 11,600 [3.4] 1175 [554] 73
1 - dehumid 17,150 [5.0] 5,050 [1.5] 725 [342] 69
2 - dehumid 26,250 [7.7] 12,350 [3.6] 975 [460] 73
1 14,100 [4.1] 5,400 [1.6]
2 23,400 [6.9] 12,200 [3.6] 1075 [507] 73
1 14,450 [4.2] 5,550 [1.6]
2 23,250 [6.8] 12,150 [3.6] 1175 [554] 73
1 14,600 [4.3]
2 23,250 [6.8] 12,150 [3.6] 1200 [566] 73
Net
Sensible
BTU/H [kW]
19,950 [5.8] 6,250 [1.8] 900 [425]
27,550 [8.1] 9,850 [2.9] 1225 [578]
19,800 [5.8] 6,200 [1.8] 925 [437]
28,000 [8.2] 10,000 [2.9] 1200 [566] 72
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
5,600 [1.6]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total
Capacity
BTU/H [kW]
37,400 [11.0]
37,200 [10.9]
37,400 [11.0] 17.00 12.95
37,400 [11.0] 17.00 12.95
37,200 [10.9] 16.00 12.15
37,400 [11.0] 17.00 12.65
37,800 [11.1] 17.00 13.20
37,800 [11.1] 17.00 13.00
36,800 [10.8] 15.00 12.10
38,000 [11.1] 17.50 13.55
38,000 [11.1] 17.50 13.90
37,400 [11.0] 17.00 13.00
37,400 [11.0] 17.00 12.85
37,800 [11.1] 17.00 13.05
37,400 [11.0] 17.00 13.00
37,400 [11.0] 17.00 13.00
38,000 [11.1] 17.00 13.20
37,800 [11.1] 17.50 13.25
37,800 [11.1] 17.00 13.10
38,000 [11.1] 17.00 13.20
36,800 [10.8] 15.00 12.10
34,200 [10.0] 16.00 12.10
39,500 [11.6] 19.50 13.85
35,600 [10.4] 14.00 11.35
35,400 [10.4] 15.00 11.15
35,400 [10.4]6915.00211.05
ARI Ratings
SEER
16.50
16.50
EER
12.30
12.15
Indoor
Airflow
CFM
[L/s]
800 [378] 69
825 [389] 69
900 [425] 69
900 [425] 69
875 [413] 69
925 [437] 69
925 [437] 69
900 [425]
925 [437] 69
850 [401] 69
850 [401] 69
900 [425] 69
800 [378] 69
825 [389] 69
900 [425] 69
875 [413] 69
925 [437] 69
1000 [472] 69
925 [437] 69
925 [437] 69
825 [389] 69
800 [378] 69
875 [413] 69
900 [425] 69
Sound
Rating
db
69
72
69
Page 9
Rheem Heating, Cooling and Water Heating 9
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCFM-H*3617A*
039JEC
RCFM-H*3621A*
Model Numbers
ID
Coil
ID
Air Mover
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGFD-09?ZCM?
RGFD-10?ZCM?
RGGD-06?MCK?
RGGD-07?MCK?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGJD-06?MCK?
RGJD-07?MCK?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGLR-07?AMK?
RGLR-07?BRQ?
RGLR-10?BRM?
RGPR-05?BMK?
RGPR-07?AMK?
RGPR-07?BRQ?
RGPR-10?BRM?
Stage
1
2
1
2 23,250 [6.8] 12,150 [3.6] 1225 [578] 73
1 14,800 [4.3] 5,600 [1.6]
2 23,250 [6.8] 12,150 [3.6] 1225 [578] 73
1 14,750 [4.3] 5,650 [1.7]
2 23,250 [6.8] 12,150 [3.6] 1225 [578] 73
1 14,900 [4.4] 5,700 [1.7]
2 23,550 [6.9] 12,250 [3.6] 1200 [566] 73
1 14,600 [4.3] 5,600 [1.6]
2 23,250 [6.8] 12,150 [3.6] 1200 [566] 73
1 14,750 [4.3] 5,650 [1.7]
2 23,550 [6.9] 12,250 [3.6] 1200 [566] 73
1 14,100 [4.1] 5,400 [1.6]
2 23,400 [6.9] 12,200 [3.6] 1150 [543] 73
1 14,300 [4.2] 5,500 [1.6]
2 23,450 [6.9] 12,150 [3.6] 1175 [554] 73
1 14,400 [4.2] 5,500 [1.6]
1 14,650 [4.3] 5,550 [1.6]
2 23,550 [6.9] 12,250 [3.6] 1150 [543] 73
1 14,650 [4.3] 5,550 [1.6]
2 23,700 [6.9] 12,300 [3.6] 1175 [554] 73
1 14,450 [4.2] 5,550 [1.6]
2 23,400 [6.9] 12,200 [3.6] 1225 [578] 73
1 14,650 [4.3] 5,550 [1.6]
2 23,250 [6.8] 12,150 [3.6] 1225 [578] 73
1 14,400 [4.2] 5,500 [1.6]
2 23,650 [6.9] 12,350 [3.6] 1175 [554] 73
1 14,450 [4.2] 5,550 [1.6]
2 23,650 [6.9] 12,350 [3.6] 1175 [554] 73
1 14,450 [4.2] 5,550 [1.6]
2 23,400 [6.9] 12,200 [3.6] 1225 [578] 73
1 14,650 [4.3] 5,550 [1.6]
2 23,250 [6.8] 12,150 [3.6] 1225 [578] 73
1 14,400 [4.2] 5,500 [1.6]
2 23,650 [6.9] 12,350 [3.6] 1175 [554] 73
1 14,450 [4.2] 5,550 [1.6]
2 23,650 [6.9] 12,350 [3.6] 1175 [554] 73
1 14,600 [4.3] 5,600 [1.6]
2 23,500 [6.9] 12,300 [3.6] 1200 [566] 73
1 14,600 [4.3] 5,600 [1.6]
2 23,850 [7.0] 12,350 [3.6] 1225 [578] 73
1 14,750 [4.3] 5,650 [1.7]
2 23,800 [7.0] 12,400 [3.6] 1200 [566] 73
1 14,300 [4.2] 5,500 [1.6]
2 23,450 [6.9] 12,150 [3.6] 1200 [566] 73
1 14,450 [4.2] 5,550 [1.6]
2 23,550 [6.9] 12,250 [3.6] 1200 [566] 73
1 14,600 [4.3] 5,600 [1.6]
2 23,800 [7.0] 12,400 [3.6] 1200 [566] 73
1 14,600 [4.3]
2 23,650 [6.9] 12,350 [3.6] 1225 [578] 73
Net
Sensible
BTU/H [kW]
14,800 [4.3] 5,600 [1.6] 900 [425]
23,250 [6.8] 12,150 [3.6] 1225 [578]
14,750 [4.3] 5,650 [1.7] 925 [437]
23,250 [6.8] 12,150 [3.6] 1200 [566] 73
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
5,600 [1.6]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
ARI Ratings
Total
Capacity
BTU/H [kW]
35,400 [10.4]
35,400 [10.4]
35,400 [10.4] 15.50 11.20
35,400 [10.4] 15.00 11.10
35,800 [10.5] 16.00 11.65
35,400 [10.4] 15.00 11.15
35,800 [10.5] 15.50 11.55
35,600 [10.4] 14.00 11.35
35,600 [10.4] 15.00 11.20
35,400 [10.4] 15.50 11.10
35,800 [10.5] 16.50 11.90
36,000 [10.5] 16.50 11.85
35,600 [10.4] 15.50 11.25
35,400 [10.4] 15.50 11.15
36,000 [10.5] 16.50 12.00
36,000 [10.5] 16.50 12.05
35,600 [10.4] 15.50 11.25
35,400 [10.4] 15.50 11.15
36,000 [10.5] 16.50 12.00
36,000 [10.5] 16.50 12.05
35,800 [10.5] 16.00 11.70
36,200 [10.6] 16.50 12.05
36,200 [10.6] 16.50 12.15
35,600 [10.4] 15.00 11.20
35,800 [10.5] 16.00 11.60
36,200 [10.6] 16.50 12.15
36,000 [10.5]6916.50211.90
SEER
15.50
15.00
EER
11.20
11.10
Indoor
Airflow
CFM
[L/s]
900 [425] 69
925 [437] 69
925 [437] 69
900 [425] 69
900 [425] 69
875 [413] 69
875 [413] 69
900 [425]
850 [401] 69
850 [401] 69
900 [425] 69
925 [437] 69
800 [378] 69
825 [389] 69
900 [425] 69
925 [437] 69
800 [378] 69
825 [389] 69
925 [437] 69
900 [425] 69
925 [437] 69
900 [425] 69
900 [425] 69
875 [413] 69
925 [437] 69
Sound
Rating
db
69
73
69
Page 10
10 Rheem Heating, Cooling and Water Heating
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCFN-H*3624A*
039JEC
Model Numbers
ID
Coil
RCQD-3621A*
ID
Air Mover
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGFD-09?ZCM?
RGFD-10?ZCM?
RGJD-06?MCK?
RGJD-07?MCK?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGPR-05?BMK?
RGPR-07?AMK?
Stage
1
2
1
2 27,700 [8.1] 11,500 [3.4] 1150 [543] 73
1 16,950 [5.0] 4,650 [1.4]
2 27,750 [8.1] 11,450 [3.4] 1175 [554] 73
1 17,250 [5.1] 4,750 [1.4]
2 28,050 [8.2] 11,550 [3.4] 1225 [578] 73
1 16,950 [5.0] 4,650 [1.4]
2 27,700 [8.1] 11,500 [3.4] 1175 [554] 73
1 16,950 [5.0] 4,650 [1.4]
2 27,700 [8.1] 11,500 [3.4] 1175 [554] 73
1 17,250 [5.1] 4,750 [1.4]
2 28,000 [8.2] 11,600 [3.4] 1225 [578] 73
1 16,950 [5.0] 4,650 [1.4]
2 27,700 [8.1] 11,500 [3.4] 1175 [554] 73
1 16,950 [5.0] 4,650 [1.4]
2 27,700 [8.1] 11,500 [3.4] 1175 [554] 73
1 17,250 [5.1] 4,750 [1.4]
1 17,250 [5.1] 4,750 [1.4]
2 28,000 [8.2] 11,600 [3.4] 1225 [578] 73
1 17,250 [5.1] 4,750 [1.4]
2 27,900 [8.2] 11,500 [3.4] 1200 [566] 73
1 17,550 [5.1] 4,850 [1.4]
2 28,000 [8.2] 11,600 [3.4] 1225 [578] 73
1 17,100 [5.0] 4,700 [1.4]
2 27,850 [8.2] 11,550 [3.4] 1200 [566] 73
1 17,250 [5.1] 4,750 [1.4]
2 28,000 [8.2] 11,600 [3.4] 1225 [578] 73
1 17,550 [5.1] 4,850 [1.4]
2 28,150 [8.2] 11,650 [3.4] 1250 [590] 73
1 15,850 [4.6] 4,550 [1.3]
2 26,700 [7.8] 10,700 [3.1] 1200 [566] 73
1 16,300 [4.8] 4,700 [1.4]
2 26,700 [7.8] 10,700 [3.1] 1175 [554] 73
1 16,450 [4.8] 4,750 [1.4]
2 26,700 [7.8] 10,700 [3.1] 1200 [566] 73
1 16,450 [4.8] 4,750 [1.4]
2 27,000 [7.9] 10,800 [3.2] 1150 [543] 73
1 16,450 [4.8] 4,750 [1.4]
2 26,950 [7.9] 10,850 [3.2] 1175 [554] 73
1 16,650 [4.9] 4,750 [1.4]
2 26,850 [7.9] 10,750 [3.1] 1225 [578] 73
1 16,650 [4.9] 4,750 [1.4]
2 26,700 [7.8] 10,700 [3.1] 1225 [578] 73
1 16,300 [4.8] 4,700 [1.4]
2 27,150 [8.0] 10,850 [3.2] 1175 [554] 73
1 16,300 [4.8] 4,700 [1.4]
2 27,150 [8.0] 10,850 [3.2] 1175 [554] 73
1 16,450 [4.8] 4,750 [1.4]
2 26,700 [7.8] 10,700 [3.1] 1200 [566] 73
1 16,650 [4.9]
2 27,000 [7.9] 10,800 [3.2] 1200 [566] 73
Net
Sensible
BTU/H [kW]
16,800 [4.9] 4,400 [1.3] 875 [413]
27,300 [8.0] 11,300 [3.3] 1175 [554]
16,950 [5.0] 4,650 [1.4] 850 [401]
28,000 [8.2] 11,600 [3.4] 1225 [578] 73
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
4,750 [1.4]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total
Capacity
BTU/H [kW]
38,500 [11.3]
39,000 [11.4]
39,000 [11.4] 18.00 13.20
39,500 [11.6] 18.50 13.35
39,000 [11.4] 18.50 13.35
39,000 [11.4] 18.50 13.35
39,500 [11.6] 18.50 13.50
39,000 [11.4] 18.50 13.35
39,000 [11.4] 18.50 13.35
39,500 [11.6] 18.50 13.50
39,500 [11.6] 18.50 13.55
39,500 [11.6] 18.50 13.50
39,500 [11.6] 19.00 13.65
39,500 [11.6] 18.50 13.50
39,500 [11.6] 18.50 13.40
40,000 [11.7] 18.50
37,400 [11.0] 14.50 11.95
37,400 [11.0] 16.00 12.00
37,400 [11.0] 16.00 11.90
37,800 [11.1] 17.00 12.75
37,800 [11.1] 17.00 12.70
37,600 [11.0] 16.50 12.10
37,400 [11.0] 16.00 12.00
38,000 [11.1] 17.00 12.85
38,000 [11.1] 17.00 12.85
37,400 [11.0] 16.00 12.05
37,800 [11.1]6916.50212.45
ARI Ratings
SEER
15.50
18.00
EER
12.40
13.40
18.50
Indoor
Airflow
CFM
[L/s]
850 [401] 69
900 [425] 69
800 [378] 69
825 [389] 69
900 [425] 69
800 [378] 69
825 [389] 69
900 [425]
900 [425] 69
925 [437] 69
1000 [472] 69
875 [413] 69
925 [437] 69
1000 [472] 69
800 [378] 69
875 [413] 69
900 [425] 69
850 [401] 69
850 [401] 69
900 [425] 69
925 [437] 69
800 [378] 69
825 [389] 69
900 [425] 69
900 [425] 69
Sound
Rating
db
69
73
69
Page 11
Rheem Heating, Cooling and Water Heating 11
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCQD-3621A*
039JEC
048JEC
RCQD-3624A*
RCSM-H*3621A*
RCSN-H*4824A* ➀
RCFM-H*4821A*
Model Numbers
ID
Coil
ID
Air Mover
RGPR-07?BRQ?
RGPR-10?BRM?
Coil Only
RBHM-24J*
RBHN-24J*
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
RHPL-HM3621
RHPN-HM4824
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGGD-06?MCK?
RGGD-07?MCK?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGJD-06?MCK?
RGJD-07?MCK?
Stage
1
2
1
2 27,150 [8.0] 10,850 [3.2] 1225 [578] 73
1 15,850 [4.6] 4,550 [1.3]
2 26,700 [7.8] 10,700 [3.1] 1200 [566] 73
1 16,800 [4.9] 4,800 [1.4]
2 27,450 [8.0] 10,950 [3.2] 1200 [566] 73
1 16,750 [4.9] 4,850 [1.4]
2 27,550 [8.1] 11,050 [3.2] 1175 [554] 73
1 16,450 [4.8] 4,750 [1.4]
2 27,000 [7.9] 10,800 [3.2] 1150 [543] 73
1 16,450 [4.8] 4,750 [1.4]
2 27,150 [8.0] 10,850 [3.2] 1175 [554] 73
1 16,600 [4.9] 4,800 [1.4]
2 27,150 [8.0] 10,850 [3.2] 1225 [578] 73
1 16,300 [4.8] 4,700 [1.4]
2 27,100 [7.9] 10,900 [3.2] 1175 [554] 73
1 16,300 [4.8] 4,700 [1.4]
1 16,600 [4.9] 4,800 [1.4]
2 27,100 [7.9] 10,900 [3.2] 1225 [578] 73
1 16,600 [4.9] 4,800 [1.4]
2 27,300 [8.0] 10,900 [3.2] 1200 [566] 73
1 16,800 [4.9] 4,800 [1.4]
2 27,100 [7.9] 10,900 [3.2] 1225 [578] 73
1 17,100 [5.0] 4,900 [1.4]
2 27,450 [8.0] 10,950 [3.2] 1250 [590] 73
1 14,100 [4.1] 5,400 [1.6]
2 23,400 [6.9] 12,200 [3.6] 1150 [543] 73
1 14,750 [4.3] 5,650 [1.7]
2 23,800 [7.0] 12,400 [3.6] 1225 [578] 73
1 20,750 [6.1] 5,850 [1.7]
2 35,700 [10.5] 12,700 [3.7] 1600 [755] 74
1 - dehumid 19,200 [5.6] 6,800 [2.0] 825 [389] 73
2 - dehumid 33,000 [9.7] 14,200 [4.2] 1300 [613] 74
1 17,300 [5.1] 7,100 [2.1]
2 29,950 [8.8] 15,050 [4.4] 1475 [696] 74
1 17,900 [5.2] 7,300 [2.1]
2 29,800 [8.7] 15,000 [4.4] 1600 [755] 74
1 17,900 [5.2] 7,300 [2.1]
2 29,700 [8.7] 14,900 [4.4] 1625 [767] 74
1 17,300 [5.1] 7,100 [2.1]
2 29,050 [8.5] 14,550 [4.3] 1225 [578] 74
1 17,300 [5.1] 7,100 [2.1]
2 28,900 [8.5] 14,500 [4.2] 1225 [578] 74
1 17,850 [5.2] 7,350 [2.2]
2 30,000 [8.8] 15,000 [4.4] 1675 [790] 74
1 17,850 [5.2] 7,350 [2.2]
2 29,650 [8.7] 14,950 [4.4] 1625 [767] 74
1 17,300 [5.1] 7,100 [2.1]
2 29,050 [8.5] 14,550 [4.3] 1225 [578] 74
1 17,300 [5.1]
2 28,850 [8.5] 14,550 [4.3] 1225 [578] 74
Net
Sensible
BTU/H [kW]
16,650 [4.9] 4,750 [1.4] 875 [413]
27,100 [7.9] 10,900 [3.2] 1200 [566]
16,800 [4.9] 4,800 [1.4] 925 [437]
27,100 [7.9] 10,900 [3.2] 1175 [554] 73
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
7,100 [2.1]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
ARI Ratings
Total
Capacity
BTU/H [kW]
38,000 [11.1]
38,000 [11.1]
37,400 [11.0] 14.50 11.95
38,500 [11.3] 17.50 13.40
38,500 [11.3] 18.00 13.75
37,800 [11.1] 17.00 12.85
38,000 [11.1] 17.00 12.75
38,000 [11.1] 17.00 12.85
38,000 [11.1] 17.00 12.90
38,000 [11.1] 17.00 12.90
38,000 [11.1] 17.00 13.00
38,000 [11.1] 17.50 13.10
38,000 [11.1] 17.00 12.90
38,500 [11.3] 17.00 13.05
35,600 [10.4] 14.00 11.35
36,200 [10.6] 17.00 12.20
48,500 [14.2] 18.00 13.00
45,000 [13.2] 14.00 11.65
45,000 [13.2] 15.50 11.45
44,500 [13.0] 15.00 11.10
43,500 [12.7] 16.00 11.70
43,500 [12.7] 16.00 11.60
45,000 [13.2] 15.50 11.20
44,500 [13.0] 15.50 11.25
43,500 [12.7] 16.00 11.75
43,500 [12.7]6916.00211.65
SEER
17.50
17.00
EER
13.00
12.80
Indoor
Airflow
CFM
[L/s]
800 [378] 69
900 [425] 69
925 [437] 69
850 [401] 69
850 [401] 69
900 [425] 69
800 [378] 69
825 [389]
900 [425] 69
875 [413] 69
925 [437] 69
1000 [472] 69
875 [413] 69
925 [437] 69
1000 [472] 73
1100 [519]
1150 [543] 73
1175 [554] 73
900 [425] 73
925 [437] 73
1175 [554] 73
1175 [554] 73
900 [425] 73
925 [437] 73
Sound
Rating
db
69
73
69
73
Page 12
12 Rheem Heating, Cooling and Water Heating
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCFM-H*4821A*
048JEC
RCFM-H*4824A*
RCFN-H*4824A*
Model Numbers
ID
Coil
ID
Air Mover
RGJD-09?ZCM?
RGJD-10?ZCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGPR-07?BRQ?
RGPR-10?BRM?
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGGD-09?ZCM?
Stage
1
2
1
2 29,650 [8.7] 14,950 [4.4] 1625 [767] 74
1 18,000 [5.3] 7,400 [2.2]
2 30,100 [8.8] 15,100 [4.4] 1625 [767] 74
1 18,000 [5.3] 7,400 [2.2]
2 30,050 [8.8] 15,150 [4.4] 1575 [743] 74
1 18,150 [5.3] 7,450 [2.2]
2 30,100 [8.8] 15,100 [4.4] 1625 [767] 74
1 18,050 [5.3] 7,350 [2.2]
2 29,950 [8.8] 15,050 [4.4] 1625 [767] 74
1 17,800 [5.2] 6,800 [2.0]
2 30,350 [8.9] 14,650 [4.3] 1475 [696] 74
1 18,400 [5.4] 7,000 [2.1]
2 30,200 [8.8] 14,600 [4.3] 1600 [755] 74
1 18,400 [5.4] 7,000 [2.1]
2 30,100 [8.8] 14,500 [4.2] 1625 [767] 74
1 18,550 [5.4] 7,050 [2.1]
1 18,400 [5.4] 7,000 [2.1]
2 30,400 [8.9] 14,600 [4.3] 1675 [790] 74
1 18,400 [5.4] 7,000 [2.1]
2 30,050 [8.8] 14,550 [4.3] 1625 [767] 74
1 18,500 [5.4] 7,100 [2.1]
2 30,500 [8.9] 14,700 [4.3] 1650 [779] 74
1 18,350 [5.4] 7,050 [2.1]
2 30,350 [8.9] 14,650 [4.3] 1675 [790] 74
1 18,350 [5.4] 7,050 [2.1]
2 30,050 [8.8] 14,550 [4.3] 1625 [767] 74
1 18,500 [5.4] 7,100 [2.1]
2 30,500 [8.9] 14,700 [4.3] 1650 [779] 74
1 18,500 [5.4] 7,100 [2.1]
2 30,500 [8.9] 14,700 [4.3] 1625 [767] 74
1 18,500 [5.4] 7,100 [2.1]
2 30,450 [8.9] 14,750 [4.3] 1575 [743] 74
1 18,500 [5.4] 7,100 [2.1]
2 30,450 [8.9] 14,750 [4.3] 1600 [755] 74
1 18,700 [5.5] 7,100 [2.1]
2 30,500 [8.9] 14,700 [4.3] 1625 [767] 74
1 18,550 [5.4] 7,050 [2.1]
2 30,350 [8.9] 14,650 [4.3] 1625 [767] 74
1 18,650 [5.5] 7,150 [2.1]
2 30,650 [9.0] 14,750 [4.3] 1575 [743] 74
1 21,450 [6.3] 4,950 [1.5]
2 35,100 [10.3] 12,500 [3.7] 1600 [755] 74
1 21,100 [6.2] 5,900 [1.7]
2 35,150 [10.3] 12,450 [3.6] 1600 [755] 74
1 21,100 [6.2] 5,900 [1.7]
2 34,800 [10.2] 12,400 [3.6] 1625 [767] 74
1 21,200 [6.2] 6,000 [1.8]
2 35,400 [10.4] 12,600 [3.7] 1650 [779] 74
1 21,050 [6.2]
2 35,100 [10.3] 12,500 [3.7] 1675 [790] 74
Net
Sensible
BTU/H [kW]
17,850 [5.2] 7,350 [2.2] 1175 [554]
29,950 [8.8] 15,050 [4.4] 1675 [790]
17,850 [5.2] 7,350 [2.2] 1175 [554]
30,650 [9.0] 14,750 [4.3] 1650 [779] 74
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
5,950 [1.7]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total
Capacity
BTU/H [kW]
45,000 [13.2]
44,500 [13.0]
45,000 [13.2] 16.00 11.80
45,000 [13.2] 16.00 11.90
45,000 [13.2] 16.00 11.90
45,000 [13.2] 11.60
45,000 [13.2] 14.50 11.65
45,000 [13.2] 15.50 11.45
44,500 [13.0] 15.50 11.10
45,500 [13.3] 16.00 11.80
45,000 [13.2] 15.50 11.20
44,500 [13.0] 15.50 11.25
45,000 [13.2] 16.00 11.60
45,000 [13.2] 15.50 11.25
44,500 [13.0] 15.50 11.30
45,000 [13.2] 16.00 11.60
45,000 [13.2] 16.00 11.80
45,000 [13.2] 16.00 11.90
45,000 [13.2] 16.00 11.95
45,000 [13.2] 16.00 11.90
45,000 [13.2] 16.00 11.60
45,500 [13.3] 16.00 12.00
47,500 [13.9] 15.00 12.05
47,500 [13.9] 17.00 12.00
47,000 [13.8] 16.50 11.65
48,000 [14.1] 17.00 12.30
47,500 [13.9]7316.50211.80
ARI Ratings
SEER
15.50
15.50
15.50
EER
11.25
11.30
Indoor
Airflow
CFM
[L/s]
1225 [578] 73
1200 [566] 73
1225 [578] 73
1200 [566] 73
1100 [519] 73
1150 [543] 73
1175 [554] 73
1225 [578]
1175 [554] 73
1175 [554] 73
1225 [578] 73
1175 [554] 73
1175 [554] 73
1225 [578] 73
1225 [578] 73
1200 [566] 73
1200 [566] 73
1225 [578] 73
1200 [566] 73
1250 [590] 73
1200 [566] 73
1150 [543] 73
1175 [554] 73
1225 [578] 73
1175 [554] 73
Sound
Rating
db
73
74
73
Page 13
Rheem Heating, Cooling and Water Heating 13
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCFN-H*4824A*
048JEC
RCQD-4821A*
RCQD-4824A*
Model Numbers
ID
Coil
ID
Air Mover
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGPR-07?BRQ?
RGPR-10?BRM?
Coil Only
RBHM-25J*
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGPR-07?BRQ?
Stage
1
2
1
2 35,250 [10.3] 12,550 [3.7] 1650 [779] 74
1 21,050 [6.2] 5,950 [1.7]
2 35,100 [10.3] 12,500 [3.7] 1675 [790] 74
1 21,050 [6.2] 5,950 [1.7]
2 34,950 [10.2] 12,450 [3.6] 1625 [767] 74
1 21,400 [6.3] 6,000 [1.8]
2 35,250 [10.3] 12,550 [3.7] 1650 [779] 74
1 21,400 [6.3] 6,000 [1.8]
2 35,250 [10.3] 12,550 [3.7] 1625 [767] 74
1 20,900 [6.1] 5,900 [1.7]
2 34,850 [10.2] 12,350 [3.6] 1375 [649] 74
1 20,900 [6.1] 5,900 [1.7]
2 34,950 [10.2] 12,450 [3.6] 1425 [672] 74
1 20,900 [6.1] 5,900 [1.7]
2 34,800 [10.2] 12,400 [3.6] 1400 [661] 74
1 21,200 [6.2] 6,000 [1.8]
1 21,350 [6.3] 6,050 [1.8]
2 35,400 [10.4] 12,600 [3.7] 1575 [743] 74
1 19,300 [5.7] 5,500 [1.6]
2 33,650 [9.9] 12,350 [3.6] 1550 [731] 74
1 19,750 [5.8] 5,650 [1.7]
2 33,500 [9.8] 12,300 [3.6] 1600 [755] 74
1 19,800 [5.8] 5,600 [1.6]
2 33,350 [9.8] 12,250 [3.6] 1625 [767] 74
1 19,750 [5.8] 5,650 [1.7]
2 33,650 [9.9] 12,350 [3.6] 1675 [790] 74
1 19,750 [5.8] 5,650 [1.7]
2 33,500 [9.8] 12,300 [3.6] 1625 [767] 74
1 20,100 [5.9] 5,700 [1.7]
2 33,800 [9.9] 12,400 [3.6] 1625 [767] 74
1 19,750 [5.8] 5,650 [1.7]
2 33,650 [9.9] 12,350 [3.6] 1625 [767] 74
1 19,300 [5.7] 5,500 [1.6]
2 34,050 [10.0] 12,150 [3.6] 1600 [755] 74
1 20,500 [6.0] 5,900 [1.7]
2 34,800 [10.2] 12,400 [3.6] 1600 [755] 74
1 20,250 [5.9] 5,750 [1.7]
2 34,050 [10.0] 12,150 [3.6] 1600 [755] 74
1 20,250 [5.9] 5,750 [1.7]
2 33,750 [9.9] 12,050 [3.5] 1625 [767] 74
1 20,400 [6.0] 5,800 [1.7]
2 34,350 [10.1] 12,250 [3.6] 1650 [779] 74
1 20,200 [5.9] 5,800 [1.7]
2 34,200 [10.0] 12,200 [3.6] 1675 [790] 74
1 20,200 [5.9] 5,800 [1.7]
2 33,900 [9.9] 12,100 [3.5] 1625 [767] 74
1 20,550 [6.0] 5,850 [1.7]
2 34,350 [10.1] 12,250 [3.6] 1650 [779] 74
1 20,550 [6.0]
2 34,350 [10.1] 12,250 [3.6] 1625 [767] 74
Net
Sensible
BTU/H [kW]
21,050 [6.2] 5,950 [1.7] 1175 [554]
34,950 [10.2] 12,450 [3.6] 1625 [767]
21,400 [6.3] 6,000 [1.8] 1225 [578]
35,100 [10.3] 12,500 [3.7] 1625 [767] 74
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
5,850 [1.7]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
ARI Ratings
Total
Capacity
BTU/H [kW]
47,500 [13.9]
48,000 [14.1]
47,500 [13.9] 16.50 11.80
47,500 [13.9] 16.50 11.85
48,000 [14.1] 17.00 12.15
48,000 [14.1] 17.00 12.40
47,000 [13.8] 18.00 12.80
47,500 [13.9] 18.00 12.80
47,000 [13.8] 18.00 12.75
47,500 [13.9] 17.00 12.15
48,000 [14.1] 17.50 12.55
46,000 [13.5] 15.00 11.90
46,000 [13.5] 16.50 11.75
45,500 [13.3] 16.00 11.40
46,000 [13.5] 16.00 11.50
46,000 [13.5] 16.00 11.60
46,000 [13.5] 17.00 12.15
46,000 [13.5] 16.50 11.90
46,000 [13.5] 15.00 11.90
47,000 [13.8] 17.50 13.15
46,000 [13.5] 16.00 11.85
46,000 [13.5] 16.00 11.55
46,500 [13.6] 16.00 12.15
46,500 [13.6] 16.00 11.65
46,000 [13.5] 16.00 11.75
46,500 [13.6] 16.50 12.05
46,500 [13.6]7316.50212.30
SEER
16.50
17.00
EER
11.85
12.15
Indoor
Airflow
CFM
[L/s]
1175 [554] 73
1175 [554] 73
1225 [578] 73
1225 [578] 73
1050 [495] 73
1050 [495] 73
1050 [495] 73
1200 [566]
1250 [590] 73
1175 [554] 73
1150 [543] 73
1175 [554] 73
1175 [554] 73
1175 [554] 73
1225 [578] 73
1200 [566] 73
1000 [472] 73
1200 [566] 73
1150 [543] 73
1175 [554] 73
1225 [578] 73
1175 [554] 73
1175 [554] 73
1225 [578] 73
1225 [578] 73
Sound
Rating
db
73
74
73
Page 14
14 Rheem Heating, Cooling and Water Heating
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
048JEC
RCSM-H*4824A* RHPL-HM4824
RCSN-H*6024A* ➀
RCFM-H*6024A*
060JEC
RCFN-H*6024A*
Model Numbers
ID
Coil
RCQD-4824A*
ID
Air Mover
RGPR-10?BRM?
RGPR-12?ARM?
RHPN-HM6024
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGGD-09?ZCM?
RGGD-10?ZCM?
Stage
1
2
1
2 34,350 [10.1] 12,250 [3.6] 1575 [743] 74
1 18,800 [5.5] 7,200 [2.1]
2 30,900 [9.1] 14,900 [4.4] 1625 [767] 74
1 23,550 [6.9] 8,850 [2.6]
2 39,200 [11.5] 18,000 [5.3] 1700 [802] 72
1 - dehumid 22,500 [6.6] 10,300 [3.0] 925 [437] 67
2 - dehumid 37,400 [11.0] 20,800 [6.1] 1325 [625] 72
1 20,950 [6.1] 9,450 [2.8]
2 38,600 [11.3] 17,800 [5.2] 1700 [802] 72
1 23,550 [6.9] 8,850 [2.6]
2 38,400 [11.3] 17,600 [5.2] 1600 [755] 72
1 23,550 [6.9] 8,850 [2.6]
2 38,250 [11.2] 17,550 [5.1] 1625 [767] 72
1 21,950 [6.4] 8,250 [2.4]
2 38,650 [11.3] 17,750 [5.2] 1650 [779] 72
1 23,700 [6.9] 8,900 [2.6]
1 23,700 [6.9] 8,900 [2.6]
2 38,400 [11.3] 17,600 [5.2] 1625 [767] 72
1 24,000 [7.0] 9,000 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1650 [779] 72
1 23,700 [6.9] 8,900 [2.6]
2 38,700 [11.3] 17,700 [5.2] 1675 [790] 72
1 23,700 [6.9] 8,900 [2.6]
2 38,400 [11.3] 17,600 [5.2] 1625 [767] 72
1 24,000 [7.0] 9,000 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1650 [779] 72
1 24,000 [7.0] 9,000 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1625 [767] 72
1 23,850 [7.0] 8,950 [2.6]
2 38,500 [11.3] 17,700 [5.2] 1575 [743] 72
1 23,800 [7.0] 9,000 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1600 [755] 72
1 24,000 [7.0] 9,000 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1625 [767] 72
1 23,850 [7.0] 8,950 [2.6]
2 38,500 [11.3] 17,700 [5.2] 1625 [767] 72
1 23,950 [7.0] 9,050 [2.7]
2 38,500 [11.3] 17,700 [5.2] 1575 [743] 72
1 24,750 [7.3] 7,650 [2.2]
2 38,600 [11.3] 17,800 [5.2] 1700 [802] 72
1 23,550 [6.9] 8,850 [2.6]
2 38,400 [11.3] 17,600 [5.2] 1600 [755] 72
1 23,550 [6.9] 8,850 [2.6]
2 38,250 [11.2] 17,550 [5.1] 1625 [767] 72
1 23,850 [7.0] 8,950 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1650 [779] 72
1 23,700 [6.9] 8,900 [2.6]
2 38,700 [11.3] 17,700 [5.2] 1675 [790] 72
1 23,700 [6.9]
2 38,400 [11.3] 17,600 [5.2] 1625 [767] 72
Net
Sensible
BTU/H [kW]
20,400 [6.0] 5,800 [1.7] 1200 [566]
34,200 [10.0] 12,200 [3.6] 1625 [767]
20,550 [6.0] 5,850 [1.7] 1250 [590]
38,700 [11.3] 17,700 [5.2] 1675 [790] 72
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
8,900 [2.6]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total
Capacity
BTU/H [kW]
46,500 [13.6]
46,500 [13.6]
46,000 [13.5] 17.00 12.60
57,000 [16.7] 18.00 12.30
56,500 [16.6] 14.50 11.35
56,000 [16.4] 16.00 11.30
56,000 [16.4] 15.50 11.05
56,500 [16.6] 15.00 11.55
56,500 [16.6] 15.50 11.20
56,000 [16.4] 15.50 11.20
56,500 [16.6] 16.00 11.45
56,500 [16.6] 15.50 11.20
56,000 [16.4] 15.50 11.20
56,500 [16.6] 16.00 11.45
56,500 [16.6] 16.00 11.60
56,000 [16.4] 16.50 11.65
56,500 [16.6] 16.50 11.70
56,500 [16.6] 16.50 11.65
56,000 [16.4] 16.00 11.45
56,000 [16.4] 16.50 11.70
56,500 [16.6] 15.00 11.65
56,000 [16.4] 16.50 11.60
56,000 [16.4] 16.00 11.35
56,500 [16.6] 16.50 11.85
56,500 [16.6] 16.00 11.50
56,000 [16.4]6716.00211.50
ARI Ratings
SEER
16.50
16.50
EER
12.05
12.40
Indoor
Airflow
CFM
[L/s]
1250 [590] 73
1050 [495] 67
1050 [495] 67
1150 [543] 67
1175 [554] 67
725 [342] 67
1175 [554]
1175 [554] 67
1225 [578] 67
1175 [554] 67
1175 [554] 67
1225 [578] 67
1225 [578] 67
1200 [566] 67
1200 [566] 67
1225 [578] 67
1200 [566] 67
1250 [590] 67
1275 [602] 67
1150 [543] 67
1175 [554] 67
1225 [578] 67
1175 [554] 67
1175 [554] 67
Sound
Rating
db
73
74
73
Page 15
Rheem Heating, Cooling and Water Heating 15
Performance Data @ ARI Standard Conditions—Cooling
➀ Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RASL-
REV.
10/8/2008
RCFN-H*6024A*
060JEC
RCQD-6024A*
RCSM-H*6024A* RHPL-HM6024
Model Numbers
ID
Coil
ID
Air Mover
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
RBHM-26J*
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Stage
1
2
1
2 38,700 [11.3] 17,700 [5.2] 1675 [790] 72
1 23,700 [6.9] 8,900 [2.6]
2 38,400 [11.3] 17,600 [5.2] 1625 [767] 72
1 24,000 [7.0] 9,000 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1650 [779] 72
1 24,000 [7.0] 9,000 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1625 [767] 72
1 23,850 [7.0] 8,950 [2.6]
2 38,500 [11.3] 17,700 [5.2] 1575 [743] 72
1 23,800 [7.0] 9,000 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1600 [755] 72
1 24,000 [7.0] 9,000 [2.6]
2 38,650 [11.3] 17,750 [5.2] 1625 [767] 72
1 23,850 [7.0] 8,950 [2.6]
2 38,500 [11.3] 17,700 [5.2] 1625 [767] 72
1 23,950 [7.0] 9,050 [2.7]
2 38,500 [11.3] 17,700 [5.2] 1575 [743] 72
1 21,050 [6.2] 8,750 [2.6]
2 36,100 [10.6] 17,300 [5.1] 1700 [802] 72
1 22,500 [6.6] 9,300 [2.7]
2 36,800 [10.8] 17,600 [5.2] 1700 [802] 72
1 21,750 [6.4] 9,050 [2.7]
2 35,850 [10.5] 17,150 [5.0] 1600 [755] 72
1 21,750 [6.4] 9,050 [2.7]
2 35,700 [10.5] 17,100 [5.0] 1625 [767] 72
1 22,050 [6.5] 9,150 [2.7]
2 36,100 [10.6] 17,300 [5.1] 1650 [779] 72
1 21,900 [6.4] 9,100 [2.7]
2 35,950 [10.5] 17,250 [5.1] 1675 [790] 72
1 21,900 [6.4] 9,100 [2.7]
2 35,850 [10.5] 17,150 [5.0] 1625 [767] 72
1 22,050 [6.5] 9,150 [2.7]
2 36,150 [10.6] 17,250 [5.1] 1650 [779] 72
1 22,000 [6.4] 9,200 [2.7]
2 36,100 [10.6] 17,300 [5.1] 1625 [767] 72
1 21,900 [6.4] 9,100 [2.7]
2 35,950 [10.5] 17,250 [5.1] 1625 [767] 72
1 22,200 [6.5] 9,200 [2.7]
2 35,950 [10.5] 17,250 [5.1] 1575 [743] 72
1 24,750 [7.3] 9,250 [2.7]
2 39,350 [11.5] 18,050 [5.3] 1700 [802] 72
Net
Sensible
BTU/H [kW]
24,000 [7.0] 9,000 [2.6] 1225 [578]
38,650 [11.3] 17,750 [5.2] 1650 [779]
23,700 [6.9] 8,900 [2.6] 1175 [554]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
Net
Total
Capacity
BTU/H [kW]
56,500 [16.6]
56,500 [16.6]
56,000 [16.4] 16.00 11.50
56,500 [16.6] 16.50 11.75
56,500 [16.6] 16.50 11.90
56,000 [16.4] 17.00 11.95
56,500 [16.6] 17.00 12.00
56,500 [16.6] 17.00 11.95
56,000 [16.4] 16.50 11.75
56,000 [16.4] 17.00 12.00
53,500 [15.7] 14.00 11.10
54,500 [16.0] 16.50 12.00
53,000 [15.5] 15.50 11.10
53,000 [15.5] 15.00 10.85
53,500 [15.7] 15.50 11.35
53,000 [15.5] 15.50 11.00
53,000 [15.5] 15.50 11.00
53,500 [15.7] 15.50 11.25
53,500 [15.7] 16.00 11.45
53,000 [15.5] 15.50 11.25
53,000 [15.5] 16.00 11.50
57,500 [16.8] 17.00 12.45
ARI Ratings
SEER
16.50
16.00
EER
11.75
11.50
Indoor
Airflow
CFM
[L/s]
1175 [554] 67
1225 [578] 67
1225 [578] 67
1200 [566] 67
1200 [566] 67
1225 [578] 67
1200 [566] 67
1250 [590] 67
1050 [495] 67
1275 [602] 67
1150 [543] 67
1175 [554] 67
1225 [578] 67
1175 [554] 67
1175 [554] 67
1225 [578] 67
1225 [578] 67
1200 [566] 67
1250 [590] 67
1400 [661] 67
Sound
Rating
db
67
72
67
Page 16
16 Rheem Heating, Cooling and Water Heating
Electrical and Physical Data
Unit Dimensions
[ ] Designates Metric Conversions
ELECTRICAL
Model
Number
Frequency (Hz)
RASL-
Voltage (Volts)
REV. 10/8/2008
Phase
Compressor
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Min.
Circuit
Ampacity
Amperes
Fuse or HACR
Circuit Breaker
Min.
Amperes
Amperes
Max.
Face Area
Sq. Ft. [m
Outdoor Coil
2
]
024JEC 1-60-208/230 10.3/10.3 52 0.5 14/14 20/20 20/20 15.8 [1.47] 1
036JEC 1-60-208/230 16.7/16.7 82 2.8 24/24 30/30 40/40 23.01 [2.14] 1
039JEC 1-60-208/230 17.9/17.9 96 2.8 26/26 30/30 40/40 23.00 [2.14] 2
048JEC 1-60-208/230 26.9/26.9 117 2.8 37/37 45/45 60/60 23.00 [2.14] 2
060JEC 1-60-208/230 28.2/28.2 146 2.8 39/39 50/50 60/60 23.00 [2.14] 2
AIR DISCHARGE
ALLOW 60 [1524 mm] CLEARANCE
No.
Rows
PHYSICAL
CFM
[L/s]
2200/2500
[1038/1180]
2800/3400
[1321/1604]
2800/3500
[1321/1652]
2800/3500
[1321/1652]
2800/3500
[1321/1652]
Refrig.
Per
Circuit
Oz. [g]
Net
Lbs. [kg]
Weight
Shipping
Lbs. [kg]
144 [4082] 236 [107.0] 256 [116.1]
150 [4252] 251 [113.6] 261 [118.2]
268 [7598] 326 [147.9] 336 [152.4]
253 [7173] 326 [148.0] 336 [152.4]
241 [6832] 328 [149.0] 338 [153.3]
L
ACCESS
PANE L
ALLOW 24 [610 mm]
ACCESS CLEARANCE
Model Number
RASL-
024JEC/036JEC/039JEC/
048JEC/060JEC
Height “H”
(Inches) [mm]
33 [838]
W
H
AIR INLETS
(LOUVERS)
ALLOW 6 [152 mm]
MIN. CLEARANCE
ALTERNATE HIGH VOLTAGE
CONNECTION (KNOCKOUT)
1
Length “L”
(Inches) [mm]
3 SIDES
11
/32 [34 mm]
Width “W”
(Inches) [mm]
443/8 [1127] 311/2 [800]
SERVICE
FITTINGS
3
0
0
0
0
-
A
HIGH PRESSURE
CONTROL
MANUAL RESET
(FIELD INSTALLED
ACCESSORY)
VAPOR LINE
CONNECTION
LOW VOLTAGE
CONNECTION
7
/8 0 [22 mm]
LIQUID LINE
CONNECTION
7
/8 0 [73 mm] DIA.
2
ACCESSORY
KNOCKOUTS
HIGH VOLTAGE
CONNECTION
11
/32 0 [34 mm]
1
SERVICE ACCESS
TO ELECTRICAL &
VALVES ALLOW
240 [610 mm]
CLEARANCE
ONE SIDE
Page 17
Rheem Heating, Cooling and Water Heating 17
Condensing Unit Refrigerant Line Size Information
NOTES: N/A = Application not recommended.
*Standard line size.
[ ] Designates Metric Conversions
Liquid Line Sizing (2-Stage R-410A)
R-410A
System
Capacity
Model
-024
-036
-039
-048
-060
Line Size
Connection
Size
(Inch I.D.)
[mm]
″
3/8
[9.53]
″
3/8
[9.53]
″
3/8
[9.53]
″
3/8
[9.53]
″
3/8
[9.53]
Line Size
(Inch O.D.)
[mm]
1/4" [6.35]* 0 0 10 [3.05] 34 [10.36] 58 [17.68] 82 [24.99]
5/16" [7.93]* 0 0 0 0 0 0
3/8" [9.52]* 0 0 0 0 0 0
5/16" [7.93]* 0 0 6 [1.83] 14 [4.27] 21 [6.40] 28 [8.53]
3/8" [9.52]* 0 0 0 0 0 0
1/2" [12.70]*
5/16" [7.93]* 0 0 0 0 10 [3.05] 24 [7.32]
3/8" [9.52]* 0 0 0 0 0 0
1/2" [12.70]*
5/16" [7.93]* 0 0 0 18 [5.49] 40 [12.19] 62 [18.90]
3/8" [9.52]* 0 0 0 0 0 0
1/2" [12.70]* 0 0 0 0 0 0
3/8" [9.52]* 0 0 0 0 0 0
1/2" [12.70]* 0 0 0 0 0 0
25
[7.62]
0 0 0 0 0 0
0 0 0 0 0 0
[15.24]
(Cooling Only - Does not apply to Heat Pumps)
Total Equivalent Length—Feet [m]
50
[22.86]
Minimum Vertical Separation—Feet [m]
Liquid Line Size
Outdoor Unit Above Indoor Coil
75
100
[30.48]
125
[38.10]
150
[45.72]
R-410A
System
Capacity
Model
-024
-036
-039
-048
-060
Line Size
Connection
Size
(Inch I.D.)
[mm]
″
3/8
[9.53]
″
3/8
[9.53]
″
3/8
[9.53]
″
3/8
[9.53]
″
3/8
[9.53]
Line Size
(Inch O.D.)
[mm]
1/4" [6.35]* 25 [11.28] 13 [3.96] N/A N/A N/A N/A
5/16" [7.93]* 25 [14.33] 44 [13.41] 40 [12.19] 36 [10.97] 30 [9.14] 24 [7.32]
3/8" [9.52]*
5/16" [7.93]* N/A N/A N/A N/A N/A N/A
3/8" [9.52]*
1/2" [12.70]*
5/16" [7.93]* 15 [4.57] 11 [3.35] N/A N/A N/A N/A
3/8" [9.52]* 18 [5.49] 17 [5.18] 15 [4.57] 13 [3.96] 12 [3.66] 10 [3.05]
1/2" [12.70]*
5/16" [7.93]* 25 [10.36] 24 [7.32] N/A N/A N/A N/A
3/8" [9.52]* 25 [11.89]
1/2" [12.70]* 25 [12.50] 40 [12.19] 40 [12.19] 39 [11.89] 39 [11.89] 38 [11.58]
3/8" [9.52]* 25 [11.28] 33 [10.06] 30 [9.14] 25 [7.62] 15 [4.57] N/A
1/2" [12.70]* 25 [11.89] 39 [11.89] 38 [11.58] 37 [11.28] 37 [11.28] 36 [10.97]
Liquid Line Sizing (2-Stage R-410A)
Liquid Line Size
(Cooling Only - Does not apply to Heat Pumps)
25
[7.62]
25 [15.24] 48 [14.63]
12 [3.66]
14 [4.27] 13 [3.96] 13 [3.96] 12 [3.66] 12 [3.66] 11 [3.35]
20 [6.10] 19 [5.79] 19 [5.79] 19 [5.79] 18 [5.49] 18 [5.49]
50
[15.24]
9 [2.74] N/A N/A N/A N/A
36 [10.97] 34 [10.36] 32 [9.75] 29 [8.84] 23 [7.01]
Outdoor Unit Below Indoor Coil
Total Equivalent Length—Feet [m]
75
[22.86]
Maximum Vertical Separation—Feet [m]
47 [14.33] 46 [14.02] 45 [13.72]
100
[30.48]
125
[38.10]
150
[45.72]
43 [13.11]
Page 18
18 Rheem Heating, Cooling and Water Heating
NOTES: Using suction line larger than shown in chart will result in poor oil return. N/A = Application not recommended.
*Standard line size.
[ ] Designates Metric Conversions
Condensing Unit Refrigerant Line Size Information (Con’t.)
SUCTION LINE SIZE - OUTDOOR UNIT ABOVE INDOOR COIL
R-410A
System
Capacity
Model
-024
-036 & -039
-048
-060
R-410A
System
Capacity
Model
-024
-036 & -039
-048
-060
Line Size
Connection Size
(Inch I.D.) [mm]
3/4"
[19.05]
3/4"
[19.05]
7/8"
[22.23]
7/8"
[22.23]
Line Size
Connection Size
(Inch I.D.) [mm]
3/4"
[19.05]
3/4"
[19.05]
7/8"
[22.23]
7/8"
[22.23]
Line Size
(Inch O.D.)
[mm]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72]
5/8" [15.88]* Same as Liquid Line Size Table
3/4" [19.05]*
7/8" [22.23]*
5/8" [15.88]* Same as Liquid Line Size Table
3/4" [19.05]* N/A
7/8" [22.23]*
5/8" [15.88]* Same as Liquid Line Size Table
3/4" [19.05]* Same as Liquid Line Size Table
7/8" [22.23]*
3/4" [19.05]* Same as Liquid Line Size Table
7/8" [22.23]* N/A
1-1/8" [28.58]*
SUCTION LINE SIZE - OUTDOOR UNIT BELOW INDOOR COIL
Line Size
(Inch O.D.)
[mm]
25 [7.62] 50 [15.24]
5/8" [15.88]* Same as Liquid Line Size Table
3/4" [19.05]*
7/8" [22.23]*
5/8" [15.88]* Same as Liquid Line Size Table
3/4" [19.05]*
7/8" [22.23]*
5/8" [15.88]* Same as Liquid Line Size Table
3/4" [19.05]* Same as Liquid Line Size Table
7/8" [22.23]*
3/4" [19.05]* Same as Liquid Line Size Table
7/8" [22.23]* Same as Liquid Line Size Table
1-1/8" [28.58]*
Outdoor Unit ABOVE Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Outdoor Unit BELOW Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Same as Liquid Line Size Table
Same as Liquid Line Size Table
Suction Line Size
Total Equivalent Length - Feet [m]
N/A
N/A
N/A
N/A
N/A
Suction Line Size
Total Equivalent Length - Feet [m]
75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72]
N/A
Same as Liquid Line Size Table
N/A
N/A
N/A
N/A
Page 19
Rheem Heating, Cooling and Water Heating 19
Vapor Line Capacity Multiplier
NOTES:
1. Do NOT exceed the limits in the liquid and suction line sizing charts.
2. Do NOT use 7/8 OD suction lines in 2, 3, or 4-ton applications.
3. Do NOT use 1-1/8 OD suction line in ANY application.
4. Line sets over 75 feet MUST use the optional suction line.
[ ] Designates Metric Conversions
Unit Vapor Line Connection Size
Vapor Line Run Feet [m]
25' [7.62]
50'[15.24]
75' [22.86]
100' [22.86]
125' [38.10]
150' [45.72]
RASL
(Inches I.D.) [mm]
Optional
Standard
Optional
Standard
Optional
Standard
Optional
Standard
Optional
Standard
Optional
Standard
024
3/4" [19.05]
I.D. Sweat
5/8" [15.88]
Optional
3/4" [19.05]
Standard
1.00
1.00
0.98
1.00
0.98
1.00
0.98
N/A
0.96
N/A
0.96
N/A
036
3/4" [19.05]
I.D. Sweat
5/8" [15.88]
Optional
3/4" [19.05]
Standard
0.99
1.00
0.98
1.00
0.96
0.99
0.95
N/A
0.94
N/A
0.92
N/A
039
7/8" [22.23]
I.D. Sweat
Vapor Line Diameter (inches O.D.) [mm]
5/8" [15.88]
Optional
3/4" [19.05]
Standard
0.99
1.00
0.97
0.99
0.96
0.99
0.95
N/A
0.93
N/A
0.91
N/A
048
7/8" [22.23]
I.D. Sweat
5/8" [15.88]
Optional
3/4" [19.05]
Standard
0.98
1.00
0.96
0.99
0.94
0.98
0.92
N/A
0.90
N/A
0.88
N/A
060
7/8" [22.23]
I.D. Sweat
3/4" [19.05]
Optional
7/8" [22.23]
Standard
0.99
1.00
0.98
0.99
0.96
0.96
0.95
N/A
0.94
N/A
0.93
N/A
Page 20
Before proceeding with installation, refer
to installation instructions packaged
with each model, as well as complying
with all Federal, State, Provincial, and
Local codes, regulations, and practices.
Rheem Heating,
Cooling and
Water Heating
P.O. Box 17010, Fort Smith, AR 72917
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A. 11-08 DC FORM NO. A11-196
Supersedes Form No. A11-189 Rev. 2
Rheem will furnish a replacement for any part of this product
which fails in normal use and service within the applicable
period stated, in accordance with the terms of the limited
warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms
and Conditions, See Your Local Installer or Contact the Manufacturer for
a Copy.
Limited Parts Warranty:
Rheem Prestige Series™ equipment features a 10-year
limited parts warranty.*
*This ten-year limited parts warranty is applicable only to single-phase
products installed in residential applications.
RASL- JEC Conditional Replacement Warranty:
Rheem will provide a replacement model (if an exact replacement is not available, an equivalent product will be provided)
to the original purchaser if the compressor fails within 10
years (providing the unit is installed with a new Rheem Air
Handler OR Rheem Indoor Coil with a Rheem Gas Furnace,
and is properly matched as specified by Rheem and/or listed
in the Air Conditioning Institute (ARI) published rating, and if
additional conditions are satisfied. See product warranty card
for additional information.
GENERAL TERMS OF LIMITED WARRANTY
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE
FROM YOUR RETAILER.