Rudd RARL-024JEC Installation Manual

Page 1
FORM NO. A11-197 REV. 1
Supersedes Form No. A11-197
CONDENSING UNITS
RARL- JEC
16 Seer Two-Stage Cooling Efficiencies up to 17 SEER/13.80 EER Nominal Size 2 to 5 Tons [7.03 kW] to [17.6 kW]
Cooling Capacities 24,200 to 59,000 BTU/HR [8.51 kW] to [17.29 kW]
The Rheem Prestige Series™ High Efficiency Two-Stage RARL­JEC Condensing Unit was designed with performance in mind. These units offer comfort, energy conservation and dependability for single, multi-family and light commercial applications. The Rheem Prestige Series™ Two-Stage RARL- JEC Condensing Units are the result of an ongoing development program for improved efficiencies. With system SEER’s as high as 17 SEER/ 13 EER, these units continue a tradition of delivering high efficiency.
Industry’s lowest profile design: 33" maximum height
The Comfort Control
2
System™ provides over 32+ on-board
diagnostics and fault history codes for condensing units with single-phase compressors by detecting system and electrical problems. The integrated diagnostics with Active Protection™ prevents compressor operation when potentially harmful condi­tions are detected. Sends “Call for Service” alert notification to the thermostat to alert the homeowner of required service.
Serial Communication Enhanced – When installed with a Serial Communicating Air Handler (RHPL/RHPN-HM****JC) and user interface control (RHC-TST501CMMS) Series 500 thermostat this unit offers 4 or 2 wire installation, auto-configuration, and diagnostic messaging with full communicating capability.
Legacy Enabled – Unit can be conventionally wired using 24VAC with non-communicating Rheem Prestige air-handlers or furnaces with non-communicating thermostat.
Features a 10-year conditional unit replacement warranty and 10-year parts warranty when properly installed with a new Rheem air handler or Rheem indoor coil with a Rheem gas fur­nace. See product warranty card for additional information.
Reliable Two-Stage operation for precise temperature control with On-Demand dehumidification feature. When matched with ECM gas furnace or air-handler, the system adjusts airflow to help con­trol humidity for unsurpassed comfort in the cooling mode.
All controls are accessible by removing one service panel.
Removable top grille provides access to the condenser fan motor and condenser coil.
Attractive, louvered wrap-around jacket protects the coil from
yard hazards and weather extremes. Top grille is steel rein­forced for extra strength. Cabinet is powder painted for all weather protection.
For quiet operation and improved efficiency, models feature an
ECM two-speed condenser fan motor with a 3-blade outdoor fan.
All models meet or exceed a 1000-hour salt spray test per ASTM
B117 Standard Practice for Operating Salt Spray Testing Apparatus.
Equipped with
Comfort Control
2
System
• Serial communication enabled
• Increased system reliability and efficiency
• 32+ on-board diagnostic and operating codes
Active Protection
with homeowner “Call for Service” alert
• Exclusive Design with dual 7-segment LED display
“Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps
must be matched with appropriate coil components to meet ENERGY STAR criteria. Ask your Contractor for details or visit
www.energystar.gov <http://www.energystar.gov/>.”
earth friendly refrigerant
16.0
Page 2
2 Rheem Heating, Cooling and Water Heating
The Rheem exclusive Dual 7-Segment LED Display easily shows system operating status codes and diagnostic codes.
A Sealed Switch replaces the standard
contactor and features optical control and latching mecha­nism. The sealed
switch prevents infiltration of insects and dust. A minimal switching arc, by the optical control, offers greater relia­bility. The latching mechanism consumes less power while reducing chatter.
The Status Indication and System Diagnostics feature ther­mostat communication capability, built-in diagnostics, cur­rent sensing and high & low pressure switch monitoring. The
thermostat communication capability alerts the homeowner to any necessary service requirements. Faster, more accurate service is pro­vided by the built-in diagnostics, by providing the HVAC professional with dependable information. In addition, high and low pressure-switch monitor­ing prevents the system from operat­ing outside of its normal parameters.
The fault recall feature will allow for the last six fault-codes to be displayed, and will retain these codes even if power failure occurs.
Built-in short-cycle protection allows the compressor to restart easily without oil removal.
A 30-second minimum run-time for every compressor call allows the oil to return to the compressor.
Active Protection monitors the system to prevent nuisance lockouts and prevents compressor operation when poten­tially harmful conditions are detected.
The compressor and fan are controlled independently, which reduces the starting load and light dimming.
A manual push-button is offered to operate the compres­sor and fan for 5 seconds to allow for an operation check.
In order to save time and money, replacement automo­tive fuses can be utilized instead of replacing the entire control board.
STANDARD FEATURES
RARL- JEC Condensing Units
1. Scroll compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor windings. It is externally mounted on rubber grommets to reduce vibration and noise.
2. Compressors have an internal pressure relief assembly to protect against excessive pressure differential.
3. All refrigerant connections are on the exterior of the unit, located close to the ground for neat appearing installations.
4. Cabinet is constructed of powder painted galvanized steel. The full wrap-around louvered grille protects the coil from damage.
5. Sound Blanket-enhanced compressor sound blanket is standard.
6. Copper tube—aluminum fin coils are used on all models.
7. The control box is located in the top corner of the cabinet
providing for easy access through a service panel.
8. Service valves are standard on all models.
9. Field connections for power and control wiring are kept
separate.
10. Every unit is factory charged and run-tested.
11. Separate compressor compartment for easy service access.
12. Drawn, painted base pan for extra corrosion resistance and
sound reduction.
13. The RARL- JEC has a 10-year limited parts warranty, plus a 10-year conditional unit replacement warranty. Refer to the General Terms of Limited Warranty for details.
14. Hard Start Kits—Standard on all JEC models.
15. Control Box Cover.
16. The RARL- JEC is shipped with a liquid line filter drier, and
also features factory-installed low and high pressure controls, and time delay control.
17. The 2, 3 and 4 ton models feature an 8-pole motor with a 3-blade outdoor fan. The 5 ton model features the GE
®
ECM
two-speed motor with a 3-blade outdoor fan.
FEATURES & BENEFITS OF THE COMFORT CONTROL SYSTEM
SCROLL TWO-STAGE ULTRA TECH
COMPRESSOR
The 2-Stage Scroll UltraTech™ compressor is the key to efficiency for this Rheem model. It’s the latest in high-efficiency compressor technology. The advanced scroll compressor offers low noise and vibration characteristics and features tolerance to liquid refrigerant and system contamination. The Scroll UltraTech™ also has low start torque, eliminating start problems in the field. And its unique design enables the RARL- JEC condensing unit to perform efficiently, quietly and reliably.
All controls and compressor
are accessible for servicing by
removal of the service panel.
Page 3
Rheem Heating, Cooling and Water Heating 3
R A R L 024
COOLING
CAPACITY
024 = 24,000 BTU/HR [7.03 kW] 036 = 36,000 BTU/HR [10.55 kW] 048 = 48,000 BTU/HR [14.07 kW] 060 = 60,000 BTU/HR [17.6 kW]
J EC
RHEEM REMOTE
CONDENSING
UNIT
16-SEER DESIGN
SERIES
DESIGN SERIES
ELECTRICAL
DESIGNATION
J = 208/230V-1-60
EC = EQUIPPED WITH
THE COMFORT
CONTROL
2
SYSTEM
Model Number Identification
Field Installed Accessories
Low Ambient Control—Cycles outdoor fan to maintain adequate condensing pressures assuring liquid refrigerant flow to the coil. Allows indoor cooling with outdoor temperatures down to 0°F [–17.8°C]. (Model No. RXAD-A08)
It is recommended that this control be installed in units to be operated at outdoor ambient temperatures under 45°F [7°C].
Thermostats
Compressor Crankcase Heater (CCH)—While scroll compressors usually do not require crankcase heaters, there are instances when a heater should be added. Refrigerant migration during the off cycle can result in a noisy start up. Add a crankcase heater to minimize refrigeration migration, and to hep eliminate any start up noise or bearing “wash out.”
[ ] Designates Metric Conversions
IMPORTANT:
The Comfort Control2Systems™ require a communicating RHPL/RHPN-HM***JC Air Handler and a 500-Series Thermostat.
Page 4
4 Rheem Heating, Cooling and Water Heating
Performance Data @ ARI Standard Conditions—Cooling
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
RCSN-H*2421A*
RCFM-H*2417A*
024JEC
RCFM-H*2421A*
RCFN-H*2417A*
Model Numbers
ID Coil
ID Air Mover
RHPN-HM2421
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
Stage
1
2 18,100 [5.3] 7,100 [2.1] 800 [378] 74
1 - dehumid 12,700 [3.7] 5,400 [1.6] 500 [236] 71
2 - dehumid 16,000 [4.7] 7,400 [2.2] 650 [307] 74
1
2 17,150 [5.0] 7,050 [2.1]
1 13,500 [4.0] 5,200 [1.5] 600 [283]
2 17,450 [5.1] 7,150 [2.1] 800 [378]
1
2 17,400 [5.1] 7,200 [2.1]
1 13,500 [4.0] 5,200 [1.5] 600 [283]
2 17,600 [5.2] 7,200 [2.1] 800 [378]
1
2 17,400 [5.1] 7,200 [2.1]
1 13,500 [4.0] 5,200 [1.5] 600 [283]
2 17,600 [5.2] 7,200 [2.1] 800 [378]
2 17,400 [5.1] 7,200 [2.1]
1 13,600 [4.0] 5,200 [1.5] 600 [283]
2 17,600 [5.2] 7,200 [2.1] 800 [378]
1
2 17,600 [5.2] 7,200 [2.1]
1 13,500 [4.0] 5,200 [1.5] 600 [283]
2 17,600 [5.2] 7,200 [2.1] 800 [378]
1
2 17,550 [5.1] 7,050 [2.1]
1 13,600 [4.0] 5,200 [1.5]
2 17,850 [5.2] 7,150 [2.1] 800 [378]
1
2 17,800 [5.2] 7,200 [2.1]
1 13,600 [4.0] 5,200 [1.5] 600 [283]
2 18,000 [5.3] 7,200 [2.1] 800 [378]
1
2 17,800 [5.2] 7,200 [2.1]
1 13,600 [4.0] 5,200 [1.5] 600 [283]
2 18,000 [5.3] 7,200 [2.1] 800 [378]
1
2 17,800 [5.2] 7,200 [2.1]
1 13,700 [4.0] 5,200 [1.5]
2 18,000 [5.3] 7,200 [2.1] 800 [378]
1
2 18,000 [5.3] 7,200 [2.1]
1 13,600 [4.0] 5,200 [1.5] 600 [283]
2 18,000 [5.3] 7,200 [2.1] 800 [378]
2 17,700 [5.2] 6,900 [2.0]
1 13,950 [4.1] 5,150 [1.5]
2 17,950 [5.3] 7,050 [2.1] 800 [378]
1
2 17,950 [5.3] 7,050 [2.1]
1 13,900 [4.1] 5,200 [1.5] 600 [283] 2 17,950 [5.3] 7,050 [2.1] 800 [378]
Net
Sensible
BTU/H [kW]
14,000 [4.1] 5,200 [1.5] 600 [283]
13,150 [3.9] 5,050 [1.5] 600 [283]
13,500 [4.0] 5,200 [1.5] 600 [283]
13,500 [4.0] 5,200 [1.5] 625 [295]
13,500 [4.0] 5,200 [1.5] 625 [295]
13,450 [3.9] 5,150 [1.5] 600 [283]
13,250 [3.9] 5,050 [1.5] 600 [283]
13,600 [4.0] 5,200 [1.5] 600 [283]
13,600 [4.0] 5,200 [1.5] 625 [295]
13,600 [4.0] 5,200 [1.5] 625 [295]
13,550 [4.0] 5,150 [1.5] 600 [283]
13,550 [4.0] 5,050 [1.5] 600 [283]
13,950 [4.1] 5,150 [1.5] 600 [283]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
24,600 [7.2]7415.50
24,800 [7.3]7415.50
24,800 [7.3]7415.50
24,800 [7.3]7416.00
24,800 [7.3]7415.50
25,000 [7.3]7415.50
25,200 [7.4]7415.50
25,200 [7.4]7415.50
25,200 [7.4]7416.00
25,200 [7.4]7416.00
25,000 [7.3]7416.00
25,000 [7.3]7416.00
SEER
EER
13.0025,200 [7.4] 16.50
11.4024,200 [7.1] 13.50
12.25
12.3024,600 [7.2] 15.50
12.50
12.4024,600 [7.2] 15.50
12.50
12.4024,600 [7.2] 15.50
12.65
12.5024,800 [7.3] 15.50
12.60
11.6024,600 [7.2] 14.00
12.45
12.5525,000 [7.3] 15.50
12.75
12.6525,000 [7.3] 15.50
12.75
12.6525,000 [7.3] 15.50
12.90
12.7025,200 [7.4] 15.50
12.80
11.7024,600 [7.2] 14.00
12.60
12.7025,000 [7.3] 16.00
12.90
Indoor Airflow
CFM [L/s]
800 [378] 74
800 [378]
800 [378] 74
800 [378]
775 [366] 74
800 [378]
600 [283]
800 [378] 74
800 [378] 74
800 [378]
600 [283]
775 [366] 74
800 [378]
600 [283]
800 [378] 74
Sound Rating
db
71
71
71
71
74
71
71
71
711
74
71
71
71
71
74
71
71
71
71
71
71
74
71
71
71
711
74
71
71
71
Page 5
Rheem Heating, Cooling and Water Heating 5
Performance Data @ ARI Standard Conditions—Cooling (cont.)
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
RCFN-H*2417A*
RCFN-H*2421A*
024JEC
RCQD-2417A*+RXMD-C04
RCSM-H*2421A*
Model Numbers
ID Coil
RCQD-2417A*
Stage
ID Air Mover
RGGD-07?MCK?
RGJD-06?MCK? 25,000 [7.3] 16.00 12.90
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
RBHM-17J*
RGFD-06?MCK?
RGFD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGPR-05?BMK?
RGPR-07?AMK?
Coil Only
RHPL-HM2421
1
2 17,950 [5.3] 7,050 [2.1] 800 [378] 74
1 13,900 [4.1] 5,200 [1.5] 600 [283] 71
2 17,950 [5.3] 7,050 [2.1] 800 [378] 74
1
2 17,950 [5.3] 7,050 [2.1]
1 14,000 [4.1] 5,200 [1.5] 600 [283]
2 18,100 [5.3] 7,100 [2.1] 800 [378]
1
2 17,950 [5.3] 7,050 [2.1]
1 13,900 [4.1] 5,200 [1.5] 600 [283]
2 18,100 [5.3] 7,100 [2.1] 800 [378]
1
2 17,700 [5.2] 6,900 [2.0]
1 13,950 [4.1] 5,150 [1.5] 600 [283]
2 17,950 [5.3] 7,050 [2.1] 800 [378]
2 17,950 [5.3] 7,050 [2.1]
1 13,900 [4.1] 5,200 [1.5] 600 [283]
2 18,150 [5.3] 7,050 [2.1] 800 [378]
1
2 17,950 [5.3] 7,050 [2.1]
1 13,900 [4.1] 5,200 [1.5] 600 [283]
2 18,150 [5.3] 7,050 [2.1] 800 [378]
1
2 17,950 [5.3] 7,050 [2.1]
1 14,000 [4.1] 5,200 [1.5]
2 18,100 [5.3] 7,100 [2.1] 800 [378]
1
2 17,950 [5.3] 7,050 [2.1]
1 13,900 [4.1] 5,200 [1.5] 600 [283]
2 18,100 [5.3] 7,100 [2.1] 800 [378]
1
2 18,750 [5.5] 6,450 [1.9]
1 13,800 [4.0] 4,600 [1.3] 600 [283]
2 18,600 [5.4] 6,400 [1.9] 800 [378]
1
2 18,750 [5.5] 6,450 [1.9]
1 13,800 [4.0] 4,600 [1.3]
2 18,750 [5.5] 6,450 [1.9] 800 [378]
1
2 18,750 [5.5] 6,450 [1.9]
1 13,700 [4.0] 4,600 [1.3] 600 [283]
2 18,600 [5.4] 6,400 [1.9] 775 [366]
2 18,750 [5.5] 6,450 [1.9]
1 13,450 [3.9] 4,450 [1.3]
2 18,300 [5.4] 6,300 [1.8] 825 [389]
1 2 17,950 [5.3] 7,250 [2.1]
Net
Sensible
BTU/H [kW]
13,950 [4.1] 5,150 [1.5] 625 [295]
13,950 [4.1] 5,150 [1.5] 625 [295]
13,950 [4.1] 5,150 [1.5] 600 [283]
13,550 [4.0] 5,050 [1.5] 600 [283]
13,950 [4.1] 5,150 [1.5] 600 [283]
13,950 [4.1] 5,150 [1.5] 625 [295]
13,950 [4.1] 5,150 [1.5] 625 [295]
13,950 [4.1] 5,150 [1.5] 600 [283]
13,800 [4.0] 4,600 [1.3] 600 [283]
13,800 [4.0] 4,600 [1.3] 600 [283]
13,800 [4.0] 4,600 [1.3] 625 [295]
13,800 [4.0] 4,600 [1.3] 600 [283]
13,600 [4.0] 5,200 [1.5] 600 [283]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
25,200 [7.4]7416.50
25,200 [7.4]7416.00
25,000 [7.3]7416.00
25,200 [7.4]7416.00
25,200 [7.4]7416.00
25,200 [7.4]7416.50
25,200 [7.4]7416.00
25,000 [7.3]7416.00
25,200 [7.4]7416.00
25,000 [7.3]7416.00
24,600 [7.2]7414.00
SEER
EER
12.8025,000 [7.3] 16.00
12.8025,000 [7.3] 16.00
13.05
12.8525,000 [7.3] 16.00
12.95
11.7024,600 [7.2] 14.00
12.65
12.7525,000 [7.3] 16.00
12.90
12.8525,000 [7.3] 16.00
12.90
12.8525,000 [7.3] 16.00
13.10
12.9025,000 [7.3] 16.00
13.00
12.5525,200 [7.4] 16.00
12.40
12.5025,200 [7.4] 16.00
12.70
12.6025,200 [7.4] 16.00
12.50
12.7525,200 [7.4] 16.00
11.45
13.0025,200 [7.4] 16.00
Indoor Airflow
CFM [L/s]
800 [378] 74
775 [366]
800 [378] 74
800 [378]
800 [378] 74
800 [378]
600 [283]
775 [366] 74
825 [389] 74
800 [378]
600 [283]
800 [378] 74
800 [378]
625 [295]
800 [378] 74
Sound Rating
db
71
71
71
71
74
71
71
71
711
74
71
71
71
71
74
71
71
71
71
71
71
74
71
71
71
711
74
71
71
Page 6
6 Rheem Heating, Cooling and Water Heating
Performance Data @ ARI Standard Conditions—Cooling (cont.)
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
RCSN-H*3624A*
RCFM-H*3617A*
036JEC
RCFM-H*3621A*
Model Numbers
ID Coil
ID Air Mover
RHPN-HM3624
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGGD-06?MCK?
RGGD-07?MCK?
RGJD-06?MCK?
RGJD-07?MCK?
RGLR-07?AMK?
RGPR-05?BMK?
RGPR-07?AMK?
Coil Only
RGFD-06?MCK?
RGFD-07?MCK?
RGFD-09?ZCM?
RGFD-10?ZCM?
RGGD-06?MCK?
RGGD-07?MCK?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGJD-06?MCK?
RGJD-07?MCK?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGLR-07?AMK?
Stage
1
2 27,250 [8.0] 10,950 [3.2] 1175 [554] 72
1 - dehumid 20,300 [5.9] 6,700 [2.0] 825 [389] 71
2 - dehumid 26,150 [7.7] 11,050 [3.2] 1000 [472] 72
1
2 23,100 [6.8] 12,100 [3.5]
1 17,000 [5.0] 7,600 [2.2] 875 [413]
2 22,950 [6.7] 12,050 [3.5] 1175 [554]
1
2 22,950 [6.7] 12,050 [3.5]
1 16,950 [5.0] 7,650 [2.2] 900 [425]
2 22,950 [6.7] 12,050 [3.5] 1225 [578]
2 22,950 [6.7] 12,050 [3.5]
1 16,950 [5.0] 7,650 [2.2] 900 [425]
2 22,950 [6.7] 12,050 [3.5] 1225 [578]
2 22,950 [6.7] 12,050 [3.5]
1 17,100 [5.0] 7,700 [2.3] 925 [437]
2 23,250 [6.8] 12,150 [3.6] 1200 [566]
2 22,950 [6.7] 12,050 [3.5]
1 17,150 [5.0] 7,650 [2.2] 900 [425]
2 23,250 [6.8] 12,150 [3.6] 1200 [566]
1
2 23,300 [6.8] 12,100 [3.5]
1 17,100 [5.0] 7,500 [2.2]
2 23,350 [6.8] 12,050 [3.5] 1175 [554]
2 23,150 [6.8] 12,050 [3.5]
1 17,100 [5.0] 7,500 [2.2] 850 [401]
2 23,450 [6.9] 12,150 [3.6] 1150 [543]
1
2 23,600 [6.9] 12,200 [3.6]
1 17,050 [5.0] 7,550 [2.2] 900 [425]
2 23,300 [6.8] 12,100 [3.5] 1225 [578]
1
2 23,150 [6.8] 12,050 [3.5]
1 16,950 [5.0] 7,450 [2.2]
2 23,550 [6.9] 12,250 [3.6] 1175 [554]
2 23,550 [6.9] 12,250 [3.6]
1 17,050 [5.0] 7,550 [2.2] 900 [425]
2 23,300 [6.8] 12,100 [3.5] 1225 [578]
2 23,150 [6.8] 12,050 [3.5]
1 16,950 [5.0] 7,450 [2.2]
2 23,550 [6.9] 12,250 [3.6] 1175 [554]
2 23,550 [6.9] 12,250 [3.6]
1 17,200 [5.0] 7,600 [2.2] 925 [437] 2 23,400 [6.9] 12,200 [3.6] 1200 [566]
Net
Sensible
BTU/H [kW]
20,400 [6.0] 6,600 [1.9] 950 [448]
16,700 [4.9] 7,500 [2.2] 900 [425]
17,000 [5.0] 7,600 [2.2] 900 [425]
16,950 [5.0] 7,650 [2.2] 925 [437]
16,950 [5.0] 7,650 [2.2] 925 [437]
17,000 [5.0] 7,600 [2.2] 900 [425]
16,800 [4.9] 7,400 [2.2] 900 [425]
17,050 [5.0] 7,550 [2.2] 900 [425]
17,100 [5.0] 7,500 [2.2] 850 [401]
17,050 [5.0] 7,550 [2.2] 925 [437]
17,100 [5.0] 7,500 [2.2] 825 [389]
17,050 [5.0] 7,550 [2.2] 925 [437]
17,100 [5.0] 7,500 [2.2] 825 [389]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
35,000 [10.3]7213.50
35,000 [10.3]7214.00
35,000 [10.3]7214.00
35,400 [10.4]7214.00
35,400 [10.4]7214.00
35,400 [10.4]7213.50
35,600 [10.4]7214.50
35,400 [10.4]7214.00
35,800 [10.5]7214.50
35,400 [10.4]7214.00
35,800 [10.5]7214.50
35,600 [10.4]7214.50
SEER
Indoor Airflow
EER
13.0038,000 [11.1] 16.50
11.4035,200 [10.3] 13.00
11.25
11.1035,000 [10.3] 13.50
11.30
11.1535,000 [10.3] 13.50
11.30
11.1535,000 [10.3] 13.50
11.75
11.2535,000 [10.3] 13.50
11.65
11.4535,400 [10.4] 13.00
11.35
11.2535,200 [10.3] 14.00
12.10
12.0035,800 [10.5] 14.50
11.40
11.3035,200 [10.3] 14.00
12.15
12.2035,800 [10.5] 14.50
11.40
11.3035,200 [10.3] 14.00
12.15
12.2035,800 [10.5] 14.50
11.85
Sound
CFM [L/s]
1075 [507] 72
1200 [566]172
1225 [578] 72
1225 [578]172
1200 [566] 72
1150 [543]172
875 [413]
1200 [566] 72
1175 [554] 72
1225 [578]172
800 [378]
1175 [554] 72
1225 [578]172
800 [378]
1175 [554] 72
Rating
db
71
71
71
71
71
71
71
711
71
71
71
71
71
71
71
71
71
71
71
71
71
711
71
71
71
Page 7
Rheem Heating, Cooling and Water Heating 7
Performance Data @ ARI Standard Conditions—Cooling (cont.)
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
RCFM-H*3621A*
036JEC
RCFN-H*3624A*
Model Numbers
ID Coil
RCQD-3621A*
Stage
ID Air Mover
RGLR-07?BRQ?
RGLR-10?BRM? 36,000 [10.5] 14.50 12.30
RGPR-05?BMK?
RGPR-07?AMK?
RGPR-07?BRQ?
RGPR-10?BRM?
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
RGFD-06?MCK?
RGFD-07?MCK?
RGFD-09?ZCM?
RGFD-10?ZCM?
1
2 23,750 [7.0] 12,250 [3.6] 1225 [578] 72
1 17,200 [5.0] 7,600 [2.2] 925 [437] 71
2 23,700 [6.9] 12,300 [3.6] 1200 [566] 72
1
2 23,350 [6.8] 12,050 [3.5]
1 17,250 [5.1] 7,550 [2.2] 900 [425]
2 23,450 [6.9] 12,150 [3.6] 1200 [566]
1
2 23,700 [6.9] 12,300 [3.6]
1 17,200 [5.0] 7,600 [2.2] 925 [437]
2 23,550 [6.9] 12,250 [3.6] 1225 [578]
2 26,500 [7.8] 10,700 [3.1]
1 19,950 [5.8] 6,450 [1.9] 850 [401]
2 26,950 [7.9] 10,850 [3.2] 1150 [543]
2 27,000 [7.9] 10,800 [3.2]
1 20,100 [5.9] 6,500 [1.9] 900 [425]
2 27,100 [7.9] 10,900 [3.2] 1225 [578]
2 26,950 [7.9] 10,850 [3.2]
1 19,800 [5.8] 6,400 [1.9] 825 [389]
2 26,950 [7.9] 10,850 [3.2] 1175 [554]
1
2 27,250 [8.0] 10,950 [3.2]
1 19,800 [5.8] 6,400 [1.9]
2 26,950 [7.9] 10,850 [3.2] 1175 [554]
2 26,950 [7.9] 10,850 [3.2]
1 20,100 [5.9] 6,500 [1.9] 900 [425]
2 27,250 [8.0] 10,950 [3.2] 1225 [578]
1
2 27,250 [8.0] 10,950 [3.2]
1 20,250 [5.9] 6,550 [1.9] 925 [437]
2 27,100 [7.9] 10,900 [3.2] 1200 [566]
1
2 27,250 [8.0] 10,950 [3.2]
1 20,100 [5.9] 6,500 [1.9]
2 27,100 [7.9] 10,900 [3.2] 1200 [566]
2 27,250 [8.0] 10,950 [3.2]
1 20,400 [6.0] 6,600 [1.9] 1000 [472]
2 27,400 [8.0] 11,000 [3.2] 1250 [590]
2 27,300 [8.0] 9,100 [2.7]
1 20,250 [5.9] 5,950 [1.7]
2 27,300 [8.0] 9,100 [2.7] 1200 [566]
2 27,750 [8.1] 9,250 [2.7]
1 20,250 [5.9] 5,950 [1.7] 850 [401] 2 27,600 [8.1] 9,200 [2.7] 1175 [554]
Net
Sensible
BTU/H [kW]
17,200 [5.0] 7,600 [2.2] 900 [425]
17,100 [5.0] 7,500 [2.2] 900 [425]
17,400 [5.1] 7,600 [2.2] 875 [413]
19,650 [5.8] 6,350 [1.9] 950 [448]
19,950 [5.8] 6,450 [1.9] 850 [401]
19,800 [5.8] 6,400 [1.9] 800 [378]
20,100 [5.9] 6,500 [1.9] 900 [425]
19,800 [5.8] 6,400 [1.9] 825 [389]
20,100 [5.9] 6,500 [1.9] 900 [425]
20,550 [6.0] 6,650 [1.9] 1000 [472]
20,250 [5.9] 6,550 [1.9] 925 [437]
20,250 [5.9] 5,950 [1.7] 875 [413]
20,250 [5.9] 5,950 [1.7] 850 [401]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
35,600 [10.4]7214.00
35,800 [10.5]7214.50
37,800 [11.1]7216.00
38,000 [11.1]7216.00
37,800 [11.1]7216.00
37,800 [11.1]7216.00
38,000 [11.1]7216.00
38,000 [11.1]7216.50
38,000 [11.1]7216.50
38,500 [11.3]7216.50
36,400 [10.7]7215.50
36,800 [10.8]7216.00
SEER
EER
12.2536,000 [10.5] 14.50
11.3535,400 [10.4] 13.50
11.75
12.3036,000 [10.5] 14.50
12.10
11.7537,200 [10.9] 14.00
12.60
12.4537,800 [11.1] 16.00
12.60
12.6037,800 [11.1] 16.00
12.60
12.7538,000 [11.1] 16.00
12.60
12.6037,800 [11.1] 16.00
12.75
12.7538,000 [11.1] 16.50
12.75
12.8538,000 [11.1] 16.50
12.75
12.6538,000 [11.1] 16.50
12.75
12.0036,400 [10.7] 15.50
11.90
12.9037,000 [10.8] 16.50
12.70
Indoor Airflow
CFM [L/s]
1200 [566] 72
1200 [566]172
1175 [554] 72
1175 [554]172
1175 [554] 72
1225 [578]172
800 [378]
1175 [554] 72
1225 [578] 72
1225 [578]172
875 [413]
1225 [578] 72
1175 [554]172
900 [425]
1150 [543] 72
Sound Rating
db
71
71
71
71
71
71
71
711
71
71
71
71
71
71
71
71
71
71
71
71
71
711
71
71
71
Page 8
8 Rheem Heating, Cooling and Water Heating
Performance Data @ ARI Standard Conditions—Cooling (cont.)
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
RCQD-3621A*+RXMD-C06
036JEC
RCQD-3624A*+RXMD-C06
RCSM-H*3621A*
048JEC
RCSN-H*4824A*
Model Numbers
ID Coil
RCQD-3621A*
RCQD-3624A*
Stage
ID Air Mover
RGJD-06?MCK?
RGJD-07?MCK? 36,800 [10.8] 15.50 12.05
RGJD-09?ZCM?
RGJD-10?ZCM?
RGPR-05?BMK?
RGPR-07?AMK?
RGPR-07?BRQ?
RGPR-10?BRM?
Coil Only
RBHM-24J*
RBHN-24J*
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
RHPL-HM3621
RHPN-HM4824
Coil Only
RGFD-09?ZCM?
1
2 27,600 [8.1] 9,200 [2.7] 1225 [578] 72
1 20,250 [5.9] 5,950 [1.7] 925 [437] 71
2 27,600 [8.1] 9,200 [2.7] 1225 [578] 72
1
2 27,750 [8.1] 9,250 [2.7]
1 20,050 [5.9] 5,950 [1.7] 825 [389]
2 27,750 [8.1] 9,250 [2.7] 1175 [554]
1
2 27,300 [8.0] 9,100 [2.7]
1 20,400 [6.0] 6,000 [1.8] 900 [425]
2 27,600 [8.1] 9,200 [2.7] 1200 [566]
2 27,750 [8.1] 9,250 [2.7]
1 20,400 [6.0] 6,000 [1.8] 925 [437]
2 27,900 [8.2] 9,300 [2.7] 1225 [578]
2 27,300 [8.0] 9,100 [2.7]
1 20,550 [6.0] 6,050 [1.8] 900 [425]
2 28,050 [8.2] 9,350 [2.7] 1200 [566]
2 28,200 [8.3] 9,400 [2.8]
1 20,250 [5.9] 5,950 [1.7] 850 [401]
2 27,750 [8.1] 9,250 [2.7] 1150 [543]
1
2 27,750 [8.1] 9,250 [2.7]
1 20,400 [6.0] 6,000 [1.8]
2 27,900 [8.2] 9,300 [2.7] 1225 [578]
2 27,750 [8.1] 9,250 [2.7]
1 20,050 [5.9] 5,950 [1.7] 825 [389]
2 27,750 [8.1] 9,250 [2.7] 1175 [554]
1
2 28,050 [8.2] 9,350 [2.7]
1 20,400 [6.0] 6,000 [1.8] 875 [413]
2 27,900 [8.2] 9,300 [2.7] 1200 [566]
1
2 27,900 [8.2] 9,300 [2.7]
1 20,900 [6.1] 6,100 [1.8]
2 28,050 [8.2] 9,350 [2.7] 1250 [590]
2 27,300 [8.0] 9,100 [2.7]
1 17,200 [5.0] 7,600 [2.2] 925 [437]
2 23,700 [6.9] 12,300 [3.6] 1225 [578]
2 35,050 [10.3] 12,950 [3.8] 1600 [755]172
1 - dehumid 24,650 [7.2] 9,750 [2.9]
2 - dehumid 32,850 [9.6] 13,750 [4.0] 1350 [637]
2 29,950 [8.8] 14,650 [4.3]
1 23,300 [6.8] 10,700 [3.1] 1150 [543] 2 29,800 [8.7] 14,600 [4.3] 1600 [755]
Net
Sensible
BTU/H [kW]
20,250 [5.9] 5,950 [1.7] 900 [425]
20,100 [5.9] 5,900 [1.7] 800 [378]
20,250 [5.9] 5,950 [1.7] 900 [425]
20,400 [6.0] 6,000 [1.8] 875 [413]
19,950 [5.8] 5,850 [1.7] 900 [425]
20,550 [6.0] 6,050 [1.8] 925 [437]
20,250 [5.9] 5,950 [1.7] 850 [401]
20,100 [5.9] 5,900 [1.7] 800 [378]
20,400 [6.0] 6,000 [1.8] 900 [425]
20,400 [6.0] 6,000 [1.8] 925 [437]
19,950 [5.8] 5,850 [1.7] 900 [425]
27,200 [8.0] 9,200 [2.7] 1200 [566]
23,000 [6.7] 10,600 [3.1] 1200 [566]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
37,000 [10.8]7216.50
36,800 [10.8]7216.00
37,200 [10.9]7216.50
37,400 [11.0]7217.00
37,000 [10.8]7216.50
37,200 [10.9]7216.50
37,000 [10.8]7216.50
37,200 [10.9]7216.50
37,400 [11.0]7216.50
36,000 [10.5]7214.50
44,500 [13.0]7214.00
SEER
EER
12.2036,800 [10.8] 16.00
12.8537,000 [10.8] 16.50
12.90
12.0036,400 [10.7] 15.50
12.45
13.0537,000 [10.8] 16.50
12.90
11.9536,400 [10.7] 14.50
13.40
13.8037,600 [11.0] 17.00
12.95
12.7537,000 [10.8] 16.00
12.95
12.9537,000 [10.8] 16.50
12.95
13.1037,400 [11.0] 16.50
13.10
12.9537,200 [10.9] 16.50
13.10
11.9536,400 [10.7] 14.50
12.40
12.3548,000 [14.1] 16.00
10.9544,500 [13.0] 13.50
10.75
Indoor Airflow
CFM [L/s]
1175 [554] 72
1200 [566]172
1200 [566] 72
1175 [554]172
1175 [554] 72
1175 [554]172
900 [425]
1175 [554] 72
1225 [578] 72
1225 [578]172
1000 [472]
1175 [554] 72
1000 [472] 71
1475 [696] 72
Sound Rating
db
71
71
71
71
71
71
71
711
71
71
71
71
71
71
71
71
71
71
71
71
71
711
72
71
71
Page 9
Rheem Heating, Cooling and Water Heating 9
Performance Data @ ARI Standard Conditions—Cooling (cont.)
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
RCFM-H*4821A*
048JEC
RCFM-H*4824A*
RCFN-H*4824A*
Model Numbers
ID Coil
Stage
ID Air Mover
RGFD-10?ZCM?
RGGD-06?MCK? 43,000 [12.6] 14.00 10.95
RGGD-07?MCK?
RGGD-10?ZCM?
RGJD-06?MCK?
RGJD-07?MCK?
RGJD-10?ZCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGPR-07?BRQ?
RGPR-10?BRM?
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
RGFD-09?ZCM?
1
2 29,700 [8.7] 14,500 [4.2] 1625 [767] 72
1 22,450 [6.6] 10,350 [3.0] 900 [425] 71
2 29,050 [8.5] 14,150 [4.1] 1225 [578] 72
1
2 28,850 [8.5] 14,150 [4.1]
1 23,400 [6.9] 10,800 [3.2] 1175 [554]
2 29,650 [8.7] 14,550 [4.3] 1625 [767]
1
2 29,050 [8.5] 14,150 [4.1]
1 22,600 [6.6] 10,400 [3.0] 925 [437]
2 28,850 [8.5] 14,150 [4.1] 1225 [578]
2 29,650 [8.7] 14,550 [4.3]
1 23,400 [6.9] 10,800 [3.2] 1225 [578]
2 30,100 [8.8] 14,700 [4.3] 1625 [767]
2 30,050 [8.8] 14,750 [4.3]
1 23,400 [6.9] 10,800 [3.2] 1225 [578]
2 30,100 [8.8] 14,700 [4.3] 1625 [767]
2 29,950 [8.8] 14,650 [4.3]
1 23,050 [6.8] 10,350 [3.0] 1200 [566]
2 30,250 [8.9] 14,350 [4.2] 1475 [696]
1
2 30,100 [8.8] 14,300 [4.2]
1 23,300 [6.8] 10,500 [3.1]
2 30,000 [8.8] 14,200 [4.2] 1625 [767]
2 30,550 [9.0] 14,450 [4.2]
1 23,450 [6.9] 10,550 [3.1] 1175 [554]
2 29,950 [8.8] 14,250 [4.2] 1625 [767]
1
2 30,400 [8.9] 14,400 [4.2]
1 23,450 [6.9] 10,550 [3.1] 1225 [578]
2 30,400 [8.9] 14,400 [4.2] 1650 [779]
1
2 30,400 [8.9] 14,400 [4.2]
1 23,450 [6.9] 10,550 [3.1]
2 30,350 [8.9] 14,450 [4.2] 1575 [743]
2 30,350 [8.9] 14,450 [4.2]
1 23,450 [6.9] 10,550 [3.1] 1225 [578]
2 30,400 [8.9] 14,400 [4.2] 1625 [767]
2 30,250 [8.9] 14,350 [4.2]
1 23,550 [6.9] 10,650 [3.1]
2 30,550 [9.0] 14,450 [4.2] 1575 [743]
2 34,600 [10.1] 12,800 [3.8]
1 26,750 [7.8] 9,050 [2.7] 1150 [543] 2 34,650 [10.2] 12,750 [3.7] 1600 [755]
Net
Sensible
BTU/H [kW]
23,250 [6.8] 10,750 [3.1] 1175 [554]
22,600 [6.6] 10,400 [3.0] 925 [437]
22,450 [6.6] 10,350 [3.0] 900 [425]
23,400 [6.9] 10,800 [3.2] 1175 [554]
23,400 [6.9] 10,800 [3.2] 1200 [566]
23,400 [6.9] 10,800 [3.2] 1200 [566]
23,350 [6.8] 10,450 [3.1] 1150 [543]
21,800 [6.4] 9,800 [2.9] 725 [342]
23,450 [6.9] 10,550 [3.1] 1225 [578]
23,450 [6.9] 10,550 [3.1] 1225 [578]
23,650 [6.9] 10,550 [3.1] 1200 [566]
23,450 [6.9] 10,550 [3.1] 1200 [566]
26,450 [7.7] 8,950 [2.6] 1200 [566]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
44,000 [12.9]7214.00
43,000 [12.6]7214.00
45,000 [13.2]7214.50
45,000 [13.2]7214.50
44,500 [13.0]7213.50
44,000 [12.9]7214.00
44,000 [12.9]7214.00
45,000 [13.2]7214.50
45,000 [13.2]7214.50
45,000 [13.2]7214.50
45,000 [13.2]7214.50
47,500 [13.9]7215.00
SEER
EER
10.4544,000 [12.9] 14.00
10.9043,000 [12.6] 14.00
10.60
11.0043,000 [12.6] 14.00
10.90
10.6044,000 [12.9] 14.00
11.05
11.1545,000 [13.2] 14.50
11.15
10.9044,500 [13.0] 14.50
10.95
10.7544,500 [13.0] 14.00
10.45
11.0545,000 [13.2] 13.50
10.55
10.8545,000 [13.2] 14.50
10.90
11.0545,000 [13.2] 14.50
11.15
11.2045,000 [13.2] 14.50
11.15
10.9044,500 [13.0] 14.50
11.25
11.5547,500 [13.9] 14.00
11.50
Indoor Airflow
CFM [L/s]
1225 [578] 72
1225 [578]172
1625 [767] 72
1575 [743]172
1625 [767] 72
1600 [755]172
1175 [554]
1650 [779] 72
1650 [779] 72
1625 [767]172
1200 [566]
1600 [755] 72
1625 [767]172
1250 [590]
1600 [755] 72
Sound Rating
db
71
71
71
71
71
71
71
711
71
71
71
71
71
71
71
71
71
71
71
71
71
711
71
71
71
Page 10
10 Rheem Heating, Cooling and Water Heating
Performance Data @ ARI Standard Conditions—Cooling (cont.)
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
RCFN-H*4824A*
048JEC
RCQD-4821A*+RXMD-C06
Model Numbers
ID Coil
RCQD-4821A*
RCQD-4824A*
Stage
ID Air Mover
RGFD-10?ZCM?
RGFD-12?RCM? 48,000 [14.1] 14.50 11.75
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
RGFD-09?ZCM?
RGFD-10?ZCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGPR-07?BRQ?
RGPR-10?BRM?
Coil Only
RBHM-25J*
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGJD-09?ZCM?
1
2 34,300 [10.0] 12,700 [3.7] 1625 [767] 72
1 24,950 [7.3] 8,450 [2.5] 725 [342] 71
2 34,900 [10.2] 12,900 [3.8] 1650 [779] 72
1
2 34,600 [10.1] 12,800 [3.8]
1 26,900 [7.9] 9,100 [2.7] 1175 [554]
2 34,450 [10.1] 12,750 [3.7] 1625 [767]
1
2 34,750 [10.2] 12,850 [3.8]
1 26,900 [7.9] 9,100 [2.7] 1175 [554]
2 34,600 [10.1] 12,800 [3.8] 1675 [790]
2 34,450 [10.1] 12,750 [3.7]
1 26,900 [7.9] 9,100 [2.7] 1225 [578]
2 34,750 [10.2] 12,850 [3.8] 1650 [779]
2 34,750 [10.2] 12,850 [3.8]
1 27,050 [7.9] 9,150 [2.7] 1200 [566]
2 34,950 [10.2] 12,850 [3.8] 1575 [743]
2 34,900 [10.2] 12,900 [3.8]
1 27,050 [7.9] 9,150 [2.7] 1225 [578]
2 34,750 [10.2] 12,850 [3.8] 1625 [767]
1
2 34,600 [10.1] 12,800 [3.8]
1 27,200 [8.0] 9,200 [2.7]
2 34,900 [10.2] 12,900 [3.8] 1575 [743]
2 35,800 [10.5] 11,000 [3.2]
1 27,300 [8.0] 7,700 [2.3] 1175 [554]
2 35,450 [10.4] 10,950 [3.2] 1625 [767]
1
2 35,750 [10.5] 11,050 [3.2]
1 27,450 [8.0] 7,750 [2.3] 1175 [554]
2 35,650 [10.4] 10,950 [3.2] 1625 [767]
1
2 36,100 [10.6] 11,100 [3.3]
1 27,450 [8.0] 7,750 [2.3]
2 35,750 [10.5] 11,050 [3.2] 1625 [767]
2 35,750 [10.5] 11,050 [3.2]
1 27,750 [8.1] 7,850 [2.3] 1200 [566]
2 36,550 [10.7] 11,250 [3.3] 1600 [755]
2 35,750 [10.5] 11,050 [3.2]
1 27,250 [8.0] 7,750 [2.3]
2 35,650 [10.4] 10,950 [3.2] 1625 [767]
2 36,250 [10.6] 11,150 [3.3]
1 27,450 [8.0] 7,750 [2.3] 1175 [554] 2 35,950 [10.5] 11,050 [3.2] 1675 [790]
Net
Sensible
BTU/H [kW]
26,900 [7.9] 9,100 [2.7] 1175 [554]
26,900 [7.9] 9,100 [2.7] 1175 [554]
26,900 [7.9] 9,100 [2.7] 1225 [578]
26,900 [7.9] 9,100 [2.7] 1175 [554]
26,900 [7.9] 9,100 [2.7] 1225 [578]
27,050 [7.9] 9,150 [2.7] 1200 [566]
26,900 [7.9] 9,100 [2.7] 1200 [566]
27,100 [7.9] 7,700 [2.3] 1150 [543]
27,450 [8.0] 7,750 [2.3] 1175 [554]
27,450 [8.0] 7,750 [2.3] 1225 [578]
27,000 [7.9] 7,600 [2.2] 1200 [566]
27,100 [7.9] 7,700 [2.3] 1150 [543]
27,450 [8.0] 7,750 [2.3] 1225 [578]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
47,000 [13.8]7215.00
47,500 [13.9]7215.00
47,500 [13.9]7215.00
48,000 [14.1]7215.50
47,500 [13.9]7215.50
48,000 [14.1]7215.50
46,500 [13.6]7214.50
46,500 [13.6]7214.50
47,000 [13.8]7214.50
48,000 [14.1]7216.00
46,500 [13.6]7214.50
47,000 [13.8]7215.00
SEER
Indoor Airflow
EER
11.2047,000 [13.8] 15.00
11.3047,500 [13.9] 15.00
11.35
11.6547,500 [13.9] 15.00
11.30
11.3547,000 [13.8] 15.00
11.65
11.8547,500 [13.9] 15.50
11.95
12.0048,000 [14.1] 15.50
11.90
11.6547,500 [13.9] 15.00
12.00
11.4547,000 [13.8] 14.50
11.10
11.2547,000 [13.8] 14.50
11.30
11.8547,000 [13.8] 15.00
11.60
11.6047,000 [13.8] 13.50
12.60
11.5547,000 [13.8] 14.50
11.25
11.8547,500 [13.9] 15.00
11.40
Sound
CFM [L/s]
1675 [790] 72
1650 [779]172
1625 [767] 72
1625 [767]172
1600 [755] 72
1625 [767]172
1250 [590]
1600 [755] 72
1675 [790] 72
1625 [767]172
1200 [566]
1600 [755] 72
1600 [755]172
1175 [554]
1650 [779] 72
Rating
db
71
71
71
71
71
71
71
711
71
71
71
71
71
71
71
71
71
71
71
71
71
711
71
71
71
Page 11
Rheem Heating, Cooling and Water Heating 11
Performance Data @ ARI Standard Conditions—Cooling (cont.)
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
048JEC
RCQD-4824A*+RXMD-C06
RCSM-H*4824A*
RCSN-H*6024A*
060JEC
RCFM-H*6024A*
RCFN-H*6024A*
Model Numbers
ID Coil
RCQD-4824A*
Stage
ID Air Mover
RGJD-10?ZCM?
RGJD-12?RCM? 47,000 [13.8] 15.00 11.70
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
RHPL-HM4824
RHPN-HM6024
Coil Only
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
Coil Only
1
2 35,800 [10.5] 11,000 [3.2] 1625 [767] 72
1 27,450 [8.0] 7,750 [2.3] 1225 [578] 71
2 36,100 [10.6] 11,100 [3.3] 1650 [779] 72
1
2 36,100 [10.6] 11,100 [3.3]
1 26,950 [7.9] 7,650 [2.2] 1075 [507]
2 35,650 [10.4] 10,950 [3.2] 1425 [672]
1
2 36,250 [10.6] 11,150 [3.3]
1 27,000 [7.9] 7,600 [2.2] 1200 [566]
2 35,750 [10.5] 11,050 [3.2] 1600 [755]
2 30,800 [9.0] 14,600 [4.3]
1 30,550 [9.0] 11,850 [3.5] 1275 [602]
2 40,500 [11.9] 17,900 [5.2] 1700 [802]
2 - dehumid 36,650 [10.7] 16,950 [5.0]
1 29,800 [8.7] 12,000 [3.5] 1275 [602]
2 40,000 [11.7] 18,200 [5.3] 1675 [790]
2 39,750 [11.6] 18,050 [5.3]
1 29,800 [8.7] 12,000 [3.5] 1175 [554]
2 39,600 [11.6] 18,000 [5.3] 1625 [767]
1
2 40,100 [11.7] 18,300 [5.4]
1 29,800 [8.7] 12,000 [3.5]
2 39,850 [11.7] 18,150 [5.3] 1675 [790]
2 39,750 [11.6] 18,050 [5.3]
1 30,100 [8.8] 12,100 [3.5] 1225 [578]
2 40,150 [11.8] 18,250 [5.3] 1650 [779]
1
2 39,850 [11.7] 18,150 [5.3]
1 29,800 [8.7] 12,000 [3.5] 1175 [554]
2 39,750 [11.6] 18,050 [5.3] 1625 [767]
1
2 40,150 [11.8] 18,250 [5.3]
1 30,100 [8.8] 12,100 [3.5]
2 40,000 [11.7] 18,200 [5.3] 1625 [767]
2 39,850 [11.7] 18,150 [5.3]
1 30,100 [8.8] 12,100 [3.5] 1200 [566]
2 40,000 [11.7] 18,200 [5.3] 1600 [755]
2 40,000 [11.7] 18,200 [5.3]
1 29,900 [8.8] 12,100 [3.5]
2 39,850 [11.7] 18,150 [5.3] 1625 [767]
2 39,850 [11.7] 18,150 [5.3]
1 29,800 [8.7] 11,600 [3.4] 1275 [602] 2 40,050 [11.7] 17,750 [5.2] 1700 [802]
Net
Sensible
BTU/H [kW]
27,450 [8.0] 7,750 [2.3] 1175 [554]
27,400 [8.0] 7,800 [2.3] 1225 [578]
27,550 [8.1] 7,850 [2.3] 1250 [590]
23,700 [6.9] 10,700 [3.1] 1250 [590]
27,600 [8.1] 13,000 [3.8] 1025 [484] 761 - dehumid
29,800 [8.7] 12,000 [3.5] 1150 [543]
30,100 [8.8] 12,100 [3.5] 1225 [578]
29,800 [8.7] 12,000 [3.5] 1175 [554]
29,800 [8.7] 12,000 [3.5] 1175 [554]
30,100 [8.8] 12,100 [3.5] 1225 [578]
30,100 [8.8] 12,100 [3.5] 1200 [566]
30,050 [8.8] 12,150 [3.6] 1225 [578]
30,400 [8.9] 12,200 [3.6] 1250 [590]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
46,500 [13.6]7215.00
47,000 [13.8]7213.50
58,500 [17.1]7816.00
58,000 [17.0]7814.00
57,500 [16.8]7814.50
58,000 [17.0]7814.50
58,500 [17.1]7814.50
58,000 [17.0]7814.50
58,000 [17.0]7815.00
58,000 [17.0]7815.00
58,000 [17.0]7814.50
58,000 [17.0]7814.50
SEER
15.00
EER
11.4547,000 [13.8] 15.00
11.9547,000 [13.8] 15.00
12.05
12.0547,500 [13.9] 15.00
11.60
11.7545,500 [13.3] 15.00
12.55
11.70
11.6558,000 [17.0] 14.50
11.45
11.9558,500 [17.1] 14.50
11.55
11.6058,000 [17.0] 14.50
11.85
11.5558,000 [17.0] 14.50
11.60
11.8558,500 [17.1] 14.50
12.00
12.0058,000 [17.0] 15.00
12.10
12.0558,000 [17.0] 15.00
11.80
12.0558,000 [17.0]
11.90
Indoor Airflow
CFM [L/s]
1625 [767] 72
1575 [743]172
1625 [767] 72
1400 [661]178
1600 [755] 78
1650 [779]178
1175 [554]
1625 [767] 78
1675 [790] 78
1650 [779]178
1225 [578]
1575 [743] 78
1625 [767]178
1200 [566]
1575 [743] 78
Sound Rating
db
71
71
71
71
71
71
76
76
76
76
76
76
76
76
76
76
76
76
76
76
761
76
76
76
Page 12
12 Rheem Heating, Cooling and Water Heating
Performance Data @ ARI Standard Conditions—Cooling (cont.)
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
RCFN-H*6024A*
060JEC
Model Numbers
ID Coil
RCQD-6024A*
Stage
ID Air Mover
RGFD-09?ZCM?
RGFD-10?ZCM? 57,000 [16.7] 15.00 11.60
RGFD-12?RCM?
RGGD-09?ZCM?
RGGD-10?ZCM?
RGGD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGLR-07?BRQ?
RGLR-10?BRM?
RGLR-12?ARM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
RBHM-26J*
RGFD-09?ZCM?
RGFD-10?ZCM?
RGFD-12?RCM?
RGJD-09?ZCM?
RGJD-10?ZCM?
RGJD-12?RCM?
RGPR-07?BRQ?
RGPR-10?BRM?
RGPR-12?ARM?
1
2 39,650 [11.6] 17,550 [5.1] 1600 [755] 78
1 29,800 [8.7] 11,600 [3.4] 1175 [554] 76
2 39,700 [11.6] 17,500 [5.1] 1625 [767] 78
1
2 40,100 [11.7] 17,700 [5.2]
1 30,000 [8.8] 11,600 [3.4] 1175 [554]
2 39,950 [11.7] 17,650 [5.2] 1675 [790]
1
2 39,650 [11.6] 17,550 [5.1]
1 30,300 [8.9] 11,700 [3.4] 1225 [578]
2 39,950 [11.7] 17,650 [5.2] 1650 [779]
2 39,950 [11.7] 17,650 [5.2]
1 30,000 [8.8] 11,600 [3.4] 1175 [554]
2 39,650 [11.6] 17,550 [5.1] 1625 [767]
2 39,950 [11.7] 17,650 [5.2]
1 30,300 [8.9] 11,700 [3.4] 1225 [578]
2 40,100 [11.7] 17,700 [5.2] 1625 [767]
2 39,800 [11.7] 17,600 [5.2]
1 30,100 [8.8] 11,700 [3.4] 1200 [566]
2 40,100 [11.7] 17,700 [5.2] 1600 [755]
1
2 40,100 [11.7] 17,700 [5.2]
1 30,150 [8.8] 11,650 [3.4]
2 39,950 [11.7] 17,650 [5.2] 1625 [767]
2 39,950 [11.7] 17,650 [5.2]
1 30,650 [9.0] 11,550 [3.4] 1275 [602]
2 41,250 [12.1] 16,550 [4.8] 1675 [790]
1
2 40,400 [11.8] 16,200 [4.7]
1 29,950 [8.8] 11,250 [3.3] 1175 [554]
2 40,250 [11.8] 16,150 [4.7] 1625 [767]
1
2 40,800 [12.0] 16,400 [4.8]
1 29,900 [8.8] 11,300 [3.3]
2 40,550 [11.9] 16,250 [4.8] 1675 [790]
2 40,400 [11.8] 16,200 [4.7]
1 30,200 [8.8] 11,400 [3.3] 1225 [578]
2 40,850 [12.0] 16,350 [4.8] 1650 [779]
2 40,650 [11.9] 16,350 [4.8]
1 30,050 [8.8] 11,350 [3.3]
2 40,500 [11.9] 16,300 [4.8] 1625 [767]
2 40,550 [11.9] 16,250 [4.8]
Net
Sensible
BTU/H [kW]
29,800 [8.7] 11,600 [3.4] 1150 [543]
30,100 [8.8] 11,700 [3.4] 1225 [578]
30,000 [8.8] 11,600 [3.4] 1175 [554]
30,000 [8.8] 11,600 [3.4] 1175 [554]
30,300 [8.9] 11,700 [3.4] 1225 [578]
30,100 [8.8] 11,700 [3.4] 1200 [566]
30,250 [8.9] 11,750 [3.4] 1225 [578]
30,400 [8.9] 11,800 [3.5] 1250 [590]
29,950 [8.8] 11,250 [3.3] 1150 [543]
30,250 [8.9] 11,350 [3.3] 1225 [578]
29,900 [8.8] 11,300 [3.3] 1175 [554]
30,200 [8.8] 11,400 [3.3] 1225 [578]
30,500 [8.9] 11,500 [3.4] 1250 [590]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
57,500 [16.8]7815.00
57,500 [16.8]7815.50
57,000 [16.7]7815.00
58,000 [17.0]7815.50
58,000 [17.0]7815.50
57,500 [16.8]7815.50
58,000 [17.0]7815.50
56,500 [16.6]7814.50
57,000 [16.7]7815.00
57,000 [16.7]7815.00
57,000 [16.7]7815.00
SEER
EER
11.8557,000 [16.7] 15.00
12.1058,000 [17.0] 15.00
11.75
11.7557,000 [16.7] 15.00
12.00
11.7557,500 [16.8] 15.00
11.75
12.0057,500 [16.8] 15.50
12.20
12.2057,500 [16.8] 15.50
12.30
12.2558,000 [17.0] 15.50
12.00
12.2557,500 [16.8] 15.50
12.20
11.4056,500 [16.6] 15.00
11.20
11.7057,000 [16.7] 15.00
11.30
11.3556,500 [16.6] 15.00
11.60
11.8057,000 [16.7] 15.00
11.60
11.8057,000 [16.7] 15.00
Indoor Airflow
CFM [L/s]
1650 [779] 78
1625 [767]178
1675 [790] 78
1650 [779]178
1575 [743] 78
1625 [767]178
1200 [566]
1575 [743] 78
1600 [755] 78
1650 [779]178
1175 [554]
1625 [767] 78
1625 [767]178
1200 [566]
1575 [743] 78
Sound
Rating
db
76
76
76
76
76
76
76
761
76
76
76
76
76
76
76
76
76
76
76
76
76
761
76
76
Page 13
Rheem Heating, Cooling and Water Heating 13
Performance Data @ ARI Standard Conditions—Cooling (cont.)
Highest sales volume tested combination required by DOE test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RARL-
Rev.
3/12/2009
060JEC
RCQD-6024A*+RXMD-C06
RCSM-H*6024A*
Model Numbers
ID Coil
ID Air Mover
Coil Only
RHPL-HM6024
Stage
1 29,950 [8.8] 11,250 [3.3] 1275 [602]
2 40,700 [11.9] 16,300 [4.8] 1675 [790]
1 30,950 [9.1] 12,450 [3.6] 1400 [661] 2 40,550 [11.9] 18,450 [5.4] 1700 [802]
Net
Sensible
BTU/H [kW]
80°F [26.5°C] DB / 67°F [19.5°C] WB Indoor Air
Net
Latent
BTU/H [kW]
ARI Cooling Performance
95°F [35°C] DB Outdoor Air
ARI Rating
Total Capacity
BTU/H [kW]
57,000 [16.7]7814.00
59,000 [17.3]7815.00
SEER EER
11.45
12.45
Indoor Airflow
CFM [L/s]
Sound
Rating
db
76
76
Page 14
14 Rheem Heating, Cooling and Water Heating
Electrical and Physical Data
[ ] Designates Metric Conversions
Unit Dimensions
GENERAL TERMS OF LIMITED WARRANTY
Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms and Conditions, See Your Local Installer or Contact the Manufacturer for a Copy.
Limited Parts Warranty:
Rheem Prestige Series™ equipment features a 10-year limited parts warranty.*
*This ten-year limited parts warranty is applicable only to single-phase
products installed in residential applications.
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE FROM YOUR RETAILER.
RARL- JEC Conditional Replacement Warranty:
Rheem will provide a replacement model (if an exact replacement is not available, an equivalent product will be provided) to the original purchaser if the compressor fails within 10 years (providing the unit is installed with a new Rheem Air Handler OR Rheem Indoor Coil with a Rheem Gas Furnace, and is properly matched as specified by Rheem and/or listed in the Air Conditioning Institute (ARI) published rating, and if additional conditions are satisfied. See product warranty card for additional information.
ELECTRICAL
Model
Number
Frequency (Hz)
RARL-
Voltage (Volts)
Rev. 10/17/2008
Phase
Compressor
Rated Load
Amperes
(RLA)
Locked Rotor
Amperes
(LRA)
Fan Motor
Full Load
Amperes
(FLA)
Min.
Circuit Ampacity Amperes
Fuse or HACR
Circuit Breaker
Min.
Amperes
Amperes
Max.
Face Area
Sq. Ft. [m
Outdoor Coil
No.
2
Rows
]
024JEC 1-60-208/230 10.3/10.3 52 0.75 14/14 20/20 20/20 15.82 [1.47] 1 2285 [1078] 115 [3260] 190 [86.2] 200 [90.7] 036JEC 1-60-208/230 16.7/16.7 82 1.0 22/22
30/30 35/35 23.01 [2.14] 1 3400 [1604] 150 [4252]
048JEC 1-60-208/230 21.2/21.2 96 1.0 28/28 35/35 45/45 23.01 [2.14] 2 3400 [1604] 150 [4252] 250 [113.4] 260 [117.9]
060JEC 1-60-208/230 25.6/25.6 118 2.8 35/35 45/45 60/60 23.01 [2.14] 2
PHYSICAL
CFM [L/s]
2800/3500
[1321/1652]
R-410a
Oz. [g]
Weight
Net
Lbs. [kg]
236 [107.0]
Shipping Lbs. [kg]
246 [111.6]
220 [6237] 305 [138.3] 315 [142.9]
AIR DISCHARGE
ALLOW 60 [1524 mm] CLEARANCE
W
SERVICE FITTINGS
LOW VOLTAGE CONNECTION
7
/80 [22 mm]
L
ACCESS PANEL
ALTERNATE HIGH VOLTAGE CONNECTION (KNOCKOUT)
11
/32[34 mm]
1
ALLOW 24 [610 mm] ACCESS CLEARANCE
H
AIR INLETS (LOUVERS) ALLOW 6 [152 mm] MIN. CLEARANCE 3 SIDES
HIGH VOLTAGE CONNECTION
11
/320 [34 mm]
1
LIQUID LINE CONNECTION
SERVICE ACCESS TO ELECTRICAL & VALVES ALLOW 240 [610 mm] CLEARANCE ONE SIDE
Width “W”
(Inches) [mm]
Model Number
RARL-
3
0
0
0
0
-
A
HIGH PRESSURE CONTROL MANUAL RESET (FIELD INSTALLED ACCESSORY)
VAPOR LINE CONNECTION
Height “H”
(Inches) [mm]
7
/80 [73 mm] DIA.
2 ACCESSORY KNOCKOUTS
Length “L”
(Inches) [mm]
024JEC 23 [584] 443/8 [1127] 311/2 [800]
036JEC/048JEC/060JEC 33 [838] 443/8 [1127] 311/2 [800]
Page 15
Rheem Heating, Cooling and Water Heating 15
Condensing Unit Refrigerant Line Size Information
*Standard line size.
NOTE: N/A = Application not recommended. Using suction line larger than recommended will result in poor oil return. [ ] Designates Metric Conversions
*Standard line size.
NOTE: N/A = Application not recommended.
LIQUID LINE SIZE - OUTDOOR UNIT ABOVE INDOOR COIL
R-410A System
Capacity
Model
-024
-036
-048
-060
R-410A System
Capacity
Model
-024
-036
-048
-060
Line Size
Connection
Size
(Inch I.D.)
[mm]
3/8
[9.53]
3/8
[9.53]
3/8
[9.53]
3/8
[9.53]
Line Size
Connection
Size
(Inch I.D.)
[mm]
3/8
[9.53]
3/8
[9.53]
3/8
[9.53]
3/8
[9.53]
Line Size
(Inch O.D.)
[mm]
1/4" [6.35]* 0 1 [0.31] 24 [7.32] 50 [15.24] 76 [23.17] 102 [31.09]
5/16" [7.93]* 0 0 0 0 0 0
3/8" [9.52]* 0 0 0 0 0 0 5/16" [7.93]* 0 0 0 5 [1.52] 13 [3.96] 20 [6.10] 3/8" [9.52]* 0 0 0 0 0 0 1/2" [12.70]* 5/16" [7.93]* 0 0 0 7 [2.13] 28 [8.53] 50 [15.24] 3/8" [9.52]* 0 0 0 0 0 0 1/2" [12.70]* 3/8" [9.52]* 0 0 0 0 0 0 1/2" [12.70]* 0 0 0 0 0 0
LIQUID LINE SIZE - OUTDOOR UNIT BELOW INDOOR COIL
Line Size
(Inch O.D.)
[mm]
1/4" [6.35]* 13 [3.96] N/A N/A N/A N/A N/A
5/16" [7.93]* 25 [7.62] 21 [6.40] 17 [5.18] 13 [3.96] 9 [2.74] N/A
3/8" [9.52]* 25 [8.23] 26 [7.93] 25 [7.62] 23 [7.01] 22 [6.71] 20 [6.10] 5/16" [7.93]* 15 [4.57] N/A N/A N/A N/A N/A 3/8" [9.52]* 19 [5.79] 17 [5.18] 15 [4.57] 12 [3.66] 10 [3.05] N/A 1/2" [12.70]* 5/16" [7.93]* 25 [9.14] 17 [5.18] N/A N/A N/A N/A 3/8" [9.52]* 25 [11.89] 34 [10.36] 30 [9.14] 25 [7.62] 21 [6.40] 17 [5.18] 1/2" [12.70]* 3/8" [9.52]* 25 [17.98] 49 [14.94] 40 [12.19] 30 [9.14] 20 [6.10] 10 [3.05] 1/2" [12.70]* 25 [19.51] 50 [18.90] 61 [18.59] 60 [18.29] 59 [17.98] 57 [17.37]
25
[7.62]
0 0 0 0 0 0
0 0 0 0 0 0
[7.62]
21 [6.40] 21 [6.40] 20 [6.10] 20 [6.10] 19 [5.79] 19 [5.79]
25 [12.80] 41 [12.50] 41 [12.50] 40 [12.19] 39 [11.89] 38 [11.58]
50
[15.24]
25
(Cooling Only - Does not apply to Heat Pumps)
Total Equivalent Length—Feet [m]
75
[22.86]
Minimum Vertical Separation—Feet [m]
(Cooling Only - Does not apply to Heat Pumps)
50
[15.24]
Maximum Vertical Separation—Feet [m]
Liquid Line Size
Outdoor Unit Above Indoor Coil
100
[30.48]
Liquid Line Size
Outdoor Unit Below Indoor Coil
Total Equivalent Length—Feet [m]
75
[22.86]
100
[30.48]
125
[38.10]
125
[38.10]
150
[45.72]
150
[45.72]
SUCTION LINE SIZE - OUTDOOR UNIT ABOVE INDOOR COIL
R-410A System
Capacity
Model
-024
-036
-048
-060
Line Size
Connection Size
(Inch I.D.) [mm]
3/4"
[19.05]
3/4"
[19.05]
7/8"
[22.22]
7/8"
[22.22]
Line Size
(Inch O.D.)
[mm]
25 [7.62] 50 [15.24] 75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72]
5/8" [15.88]* Same as Liquid Line Size Table 3/4" [19.05]* 7/8" [22.23]* 5/8" [15.88]* Same as Liquid Line Size Table 3/4" [19.05]* NA 7/8" [22.23]* 5/8" [15.88]* Same as Liquid Line Size Table 3/4" [19.05]* Same as Liquid Line Size Table 7/8" [22.23]* 3/4" [19.05]* Same as Liquid Line Size Table 7/8" [22.23]* Same as Liquid Line Size Table
1-1/8" [28.58]*
Outdoor Unit ABOVE Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Suction Line Size
Total Equivalent Length - Feet [m]
NA NA
NA
Same as Liquid Line Size Table
Same as Liquid Line Size Table
NA
Page 16
Before proceeding with installation, refer to installation instructions packaged with each model, as well as complying with all Federal, State, Provincial, and Local codes, regulations, and practices.
Rheem Heating, Cooling and Water Heating
P.O. Box 17010, Fort Smith, AR 72917
“In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice.”
PRINTED IN U.S.A. 3-09 DC FORM NO. A11-197 REV. 1
Supersedes Form No. A11-197
Vapor Line Capacity Multiplier
NOTES:
1. Do NOT exceed the limits in the liquid and suction line sizing charts.
2. Do NOT use 7/8 OD suction lines in 2 or 3-ton applications.
3. Do NOT use 1-1/8 OD suction line in ANY application.
4. 2 and 3-ton line sets over 75 feet MUST use the optional suction line.
[ ] Designates Metric Conversions
Condensing Unit Refrigerant Line Size Information (Cont.)
*Standard line size.
NOTE: N/A = Application not recommended. Using suction line larger than recommended will result in poor oil return.
SUCTION LINE SIZE - OUTDOOR UNIT BELOW INDOOR COIL
R-410A System
Capacity
Model
-024
-036
-048
-060
Line Size Connection Size (Inch I.D.) [mm]
3/4"
[19.05]
3/4"
[19.05]
7/8"
[22.23]
7/8"
[22.23]
Line Size
(Inch O.D.)
[mm]
25 [7.62] 50 [15.24]
5/8" [15.88]* Same as Liquid Line Size Table 3/4" [19.05]* 7/8" [22.23]* 5/8" [15.88]* Same as Liquid Line Size Table 3/4" [19.05]* 7/8" [22.23]* 5/8" [15.88]* Same as Liquid Line Size Table 3/4" [19.05]* Same as Liquid Line Size Table 7/8" [22.23]* 3/4" [19.05]* Same as Liquid Line Size Table 7/8" [22.23]*
1-1/8" [28.58]*
Outdoor Unit BELOW Indoor Coil (Cooling Only - Does not apply to Heat Pumps)
Same as Liquid Line Size Table
Suction Line Size
Total Equivalent Length - Feet [m]
75 [22.86] 100 [30.48] 125 [45.72] 150 [45.72]
N/A
Same as Liquid Line Size Table
N/A
Same as Liquid Line Size Table
Same as Liquid Line Size Table
N/A
RARL-
Connection Size (Inches I.D.) [mm]
Unit Vapor Line
Vapor Line Run Feet [m]
25' [7.62]
50' [15.24]
75' [22.86]
100' [30.48]
125' [38.10]
150' [45.72]
Optional Standard Optional
Optional Standard Optional
Optional Standard Optional
Optional Standard Optional
Optional Standard Optional
Optional Standard Optional
024
3/4" [19.05]
I.D. Sweat
5/8" [15.88]
Optional
3/4" [19.05]
Standard
——
1.00
1.00 N/A
0.99
1.00 N/A
0.98
0.99 N/A
0.97 N/A N/A
0.97 N/A N/A
0.96 N/A N/A
036
3/4" [19.05]
I.D. Sweat Vapor Line Diameter (inches O.D.) [mm]
5/8" [15.88]
Optional
3/4" [19.05]
Standard
0.98
1.00 N/A
0.96
0.99 N/A
0.96
0.98 N/A
0.94 N/A N/A
0.93 N/A N/A
0.92 N/A N/A
048
7/8" [22.23]
I.D. Sweat
5/8" [15.88]
Optional
3/4" [19.05]
Standard
7/8" [22.23]
Optional
0.98
1.00
1.02
0.96
0.99
1.00
0.94
0.96
1.00
0.92
0.98 N/A
0.90
0.97 N/A
0.88
0.96 N/A
N/A
060
7/8" [22.23]
I.D. Sweat
3/4" [19.05]
Optional
7/8" [22.23]
Standard
0.99
1.00 N/A
0.97
0.99 N/A
0.96
0.99 N/A
0.95
0.98 N/A
0.94
0.97 N/A
0.93
0.97
N/A