Rudd RAPM-018JEZ Installation Manual

The Rheem Prestige Series™ High Efficiency RAPM- JEZ Con­densing Units were designed with performance in mind. These units offer comfort, energy conservation and dependability for sin­gle, multi-family and light commercial applications. These units also contain the most advanced alternate refrigerant which contains no chlorofluorocarbons (CFCs), or hydrochloroflu­orocarbons (HCFCs), or other compounds that may leak from air­conditioning systems and potentially harm the protective ozone layer of the Earth’s atmosphere. The Rheem Prestige Series™ RAPM- JEZ Condensing Units are the result of an ongoing development program for improved efficien­cies. These units are flexible enough to achieve up to 16.00 SEER in specific match-ups, continuing a tradition of high efficiency.
The Comfort Control System™ provides on-board diagnostics and fault history for condensing units with single-phase com­pressors by detecting system and electrical problems without adding sensors. It can also communicate “fault codes” to enabled “L terminal” thermostats. The integrated diagnostics with Active Protection™ prevents compressor operation when potentially harmful conditions are detected.
7-Segment LED Display is exclusive only to Rheem products. The information-display quickly and accurately shows technicians the source of malfunctions.
Features a five-year conditional unit replacement warranty when properly installed with a new Rheem Air Handler or Rheem Indoor Coil with a Rheem Gas Furnace. See product warranty card for additional information.
Compressor sound blanket is standard to provide quiet operation.
Attractive, louvered wrap-around jacket protects the coil from yard hazards and weather extremes. Top grille is steel rein­forced for extra strength. Cabinet is powder painted for all­weather protection.
Air is discharged upward away from bushes and shrubs. The dis­charge pattern of the top grille provides minimum air restriction.
Combination Grille/Motor Mount secures the motor to the underside of the discharge grille. The grille protects the motor windings and bearings from rain and snow.
Removable top grille provides access to the condenser fan motor and condenser coil.
Single speed 8-pole fan motor designed for low speed, quiet, energy-saving operation.
All models meet or exceed a 1000-hour salt spray test per ASTM B117 Standard Practice for Operating Salt Spray Testing Apparatus.
CONDENSING UNITS
FORM NO. A11-200 REV. 2
Supersedes Form No. A11-200 Rev. 1
Equipped with
Comfort Control System
• Increased Reliability
• On-Board Diagnostics
• Fault Recall
Active Protection
(IN CERTAIN MATCHED SYSTEMS)
RAPM- JEZ
14.5 SEER Models Efficiencies up to 16.00 SEER Nominal Sizes 1
1
/2 to 5 Tons
[5.28 kW] to [17.6 kW]
Eight Models
Cooling Capacities 18,800 to 62,500 BTU/HR [5.50 kW] to [18.32 kW]
“Proper sizing and installation of equipment is critical to achieve optimal performance. Split system air conditioners and heat pumps must be matched with
appropriate coil components to meet ENERGY STAR criteria. Ask your Contractor for details or visit www.energystar.gov.”
“Visit www.Rheem.com
for complete details.”
2 Rheem Heating, Cooling and Water Heating
The Rheem exclusive 7-Segment LED Display easily shows system operating status codes and diagnostic codes.
A Sealed Switch replaces the standard
contactor and features optical control and latching mecha­nism. The sealed
switch prevents infiltration of insects and dust. A minimal switching arc, by the optical control, offers greater relia­bility. The latching mechanism consumes less power while reducing chatter.
The Status Indication and System Diagnostics feature ther­mostat communication capability, built-in diagnostics, high & low voltage monitoring and high & low pressure switch monitoring. The thermostat communication capability alerts
the homeowner to any necessary service requirements. Faster, more accurate service is provided by the built-in diagnostics, by providing the HVAC professional with dependable information. With the high and low voltage monitoring feature, the control provides alerts for out-of­range conditions. In addition, high and low pressure-switch monitoring prevents the system from operating outside of its normal parameters.
The fault recall feature will allow for the last six fault-codes to be displayed, and will retain these codes even if power failure occurs.
Built-in short-cycle protection allows the compressor to restart easily without oil removal.
A 30-second minimum run-time for every compressor call enables the oil return to the compressor.
Active Protection monitors the system to prevent nuisance lockouts and prevents compressor operation when poten­tially harmful conditions are detected.
The compressor and fan are controlled independently, which reduces the starting load and light dimming.
A push-button is offered to operate the compressor and fan for 5 seconds to allow for an operation check.
In order to save time and money, replacement automo­tive fuses can be utilized instead of replacing the entire control board.
STANDARD FEATURES
RAPM- JEZ Condensing Units
1. This unit contains a special scroll compressor that is designed specifically to operate with R-410A refrigerants and polyolester (POE) oils. The compressor is hermetically sealed and incorporates internal high temperature motor overload protection and durable insulation on the motor windings. It is externally mounted on rubber grommets to reduce vibration and noise.
2. Scroll compressor is hermetically sealed and incorporates internal high temperature motor overload protection, and durable insulation on the motor windings. It is externally mounted on rubber grommets to reduce vibration and noise.
3. Compressors have an internal pressure relief assembly to protect against excessive pressure differential.
4. All refrigerant connections are on the exterior of the unit, located close to the ground for neat appearing installations.
5. Cabinet is constructed of powder painted galvanized steel. The full wrap-around louvered grille protects the coil from damage.
6. Enhanced compressor sound blanket is standard.
7. Copper tube—aluminum fin coils are used on all models.
8. The control box is located in the top corner of the cabinet
providing for easy access through a service panel.
9. Service valves are standard on all models.
10. Field connections for power and control wiring are kept
separate.
11. Every unit is factory charged and run-tested.
12. Separate compressor compartment for easy service access.
13. Drawn, painted base pan for extra corrosion resistance and
sound reduction.
14. The RAPM- JEZ has a 10 year limited compressor warranty, plus a 5 year conditional unit replacement warranty. See General Terms of Limited Warranty for more details.
15. Hard Start Kits—Standard on all JEZ models.
16. Control Box Cover.
17. Automatic reset high and low pressure controls are standard
on all JEZ models.
18. Liquid line filter drier is standard on all models (shipped – not installed).
FEATURES & BENEFITS OF THE COMFORT CONTROL SYSTEM
SCROLL® COMPRESSOR
The scroll compressor is the key to efficiency for this Rheem model. It’s the latest in high-efficiency compressor technology. The advanced scroll compressor offers low noise and vibration characteristics and features tolerance to liquid refrigerant and system contamination. The scroll compressor also has low start torque, eliminating start problems in the field. And its unique design enables the RAPM- JEZ condensing units to perform efficiently, quietly and dependably.
All controls and compressor
are accessible for servicing by
removal of the service panel.
Rheem Heating, Cooling and Water Heating 3
Field Installed Accessories
Low Ambient Control—Cycles outdoor fan to maintain adequate condensing pressures assuring liquid refrigerant flow to the coil. Allows indoor cooling with outdoor temperatures down to 0°F [–17.8°C]. (Model No. RXAD-A08)
It is recommended that this control be installed in units to be operated at outdoor ambient temperatures under 70°F [21°C].
Thermostats
Compressor Crankcase Heater (CCH)—While scroll compressors usually do not require crankcase heaters, there are instances when a heater should be added. Refrigerant migration during the off cycle can result in a noisy start up. Add a crankcase heater to minimize refrigeration migration, and to help eliminate any start up noise or bearing “wash out.”
Model Number Identification
[ ] Designates Metric Conversions
R A P M 018 J E Z
RHEEM REMOTE
CONDENSING
UNIT
P = 14 SEER DESIGN
SERIES
M = R-410A
(2ND DESIGN
SERIES)
018 = 18,000 BTU/HR [5.28 kW] 024 = 24,000 BTU/HR [7.03 kW] 030 = 30,000 BTU/HR [8.79 kW] 036 = 36,000 BTU/HR [10.55 kW] 042 = 42,000 BTU/HR [12.31 kW] 048 = 48,000 BTU/HR [14.07 kW] 056 = 56,000 BTU/HR [16.41 kW] 060 = 60,000 BTU/HR [17.58 kW]
A*
VARIATIONS
A = STANDARD
COOLING
CAPACITY
ELECTRICAL
DESIGNATION
J = 208/230V-1-60
VARIATIONS
EQUIPPED WITH
THE COMFORT
CONTROL SYSTEM
COOLING
CONNECTION
FITTING
Z = SWEAT W/SCROLL
4 Rheem Heating, Cooling and Water Heating
Performance Data @ AHRI Standard Conditions—Cooling: RAPM- JEZ
Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RAPM-
Rev.
3/11/2010
018JEZ
RCFL-H*2417+RXMD-C04 RCFL-A*2414+RXMD-C04 18,800 [5.5] 13,800 [4.0] 5,000 [1.5] 12.15 14.50 74 650 [307] RCFL-A*2417 (RGFD-06?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.50 16.00 74 600 [283] RCFL-A*2417 (RGFD-07?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.55 16.00 74 600 [283] RCFL-A*2417 (RGFE-06?MCK?) 18,900 [5.5] 13,650 [4.0] 5,250 [1.5] 13.00 16.00 74 575 [271] RCFL-A*2417 (RGFE-07?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.00 16.00 74 600 [283] RCFL-A*2417 (RGGD-06?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.70 16.00 74 600 [283] RCFL-A*2417 (RGGD-07?MCK?) 19,400 [5.7] 14,250 [4.2] 5,150 [1.5] 13.80 16.00 74 625 [295] RCFL-A*2417 (RGGE-06?MCK?) 19,300 [5.7] 14,150 [4.1] 5,150 [1.5] 13.00 16.00 74 625 [295] RCFL-A*2417 (RGGE-07?MCK?) 19,000 [5.6] 13,700 [4.0] 5,300 [1.6] 13.00 16.00 74 575 [271] RCFL-A*2417 (RGLR-07?AMK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.75 16.00 74 600 [283] RCFL-A*2417 (RGPR-05?BMK?) 19,000 [5.6] 13,800 [4.0] 5,200 [1.5] 13.40 16.00 74 600 [283] RCFL-A*2417 (RGPR-07?AMK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.70 16.00 74 600 [283] RCFL-A*2417 (RGRM-04?MAE?) 18,900 [5.5] 13,650 [4.0] 5,250 [1.5] 13.00 16.00 74 575 [271] RCFL-A*2417 (RGRM-06?MAE?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.00 16.00 74 600 [283] RCFL-A*2417 (RGRM-07?MAE?) 19,300 [5.7] 14,200 [4.2] 5,100 [1.5] 13.00 16.00 74 625 [295] RCFL-A*2417 (RGTM-06?MAE?) 19,300 [5.7] 14,200 [4.2] 5,100 [1.5] 13.00 16.00 74 625 [295] RCFL-A*2417+RXMD-C04 18,800 [5.5] 13,800 [4.0] 5,000 [1.5] 12.15 14.50 74 650 [307] RCFL-H*2414+RXMD-C04 18,800 [5.5] 13,800 [4.0] 5,000 [1.5] 12.15 14.50 74 650 [307] RCFL-H*2417 (RGFD-06?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.50 16.00 74 600 [283] RCFL-H*2417 (RGFD-07?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.55 16.00 74 600 [283] RCFL-H*2417 (RGFE-06?MCK?) 18,900 [5.5] 13,650 [4.0] 5,250 [1.5] 13.00 16.00 74 575 [271] RCFL-H*2417 (RGFE-07?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.00 16.00 74 600 [283] RCFL-H*2417 (RGGD-06?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.70 16.00 74 600 [283] RCFL-H*2417 (RGGD-07?MCK?) 19,400 [5.7] 14,250 [4.2] 5,150 [1.5] 13.80 16.00 74 625 [295] RCFL-H*2417 (RGGE-06?MCK?) 19,300 [5.7] 14,150 [4.1] 5,150 [1.5] 13.00 16.00 74 625 [295] RCFL-H*2417 (RGGE-07?MCK?) 19,000 [5.6] 13,700 [4.0] 5,300 [1.6] 13.00 16.00 74 575 [271] RCFL-H*2417 (RGJD-06?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.70 16.00 74 600 [283] RCFL-H*2417 (RGJD-07?MCK?) 19,400 [5.7] 14,250 [4.2] 5,150 [1.5] 13.80 16.00 74 625 [295] RCFL-H*2417 (RGJF-06?MCK?) 19,300 [5.7] 14,150 [4.1] 5,150 [1.5] 13.00 16.00 74 625 [295] RCFL-H*2417 (RGJF-07?MCK?) 19,000 [5.6] 13,700 [4.0] 5,300 [1.6] 13.00 16.00 74 575 [271] RCFL-H*2417 (RGLR-07?AMK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.75 16.00 74 600 [283] RCFL-H*2417 (RGPR-05?BMK?) 19,000 [5.6] 13,800 [4.0] 5,200 [1.5] 13.40 16.00 74 600 [283] RCFL-H*2417 (RGPR-07?AMK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.70 16.00 74 600 [283] RCFL-H*2417 (RGRM-04?MAE?) 18,900 [5.5] 13,650 [4.0] 5,250 [1.5] 13.00 16.00 74 575 [271] RCFL-H*2417 (RGRM-06?MAE?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.00 16.00 74 600 [283] RCFL-H*2417 (RGRM-07?MAE?) 19,300 [5.7] 14,200 [4.2] 5,100 [1.5] 13.00 16.00 74 625 [295] RCFL-H*2417 (RGTM-06?MAE?) 19,300 [5.7] 14,200 [4.2] 5,100 [1.5] 13.00 16.00 74 625 [295] RBHP-17 (RCHL-24A2) 19,000 [5.6] 13,500 [4.0] 5,500 [1.6] 13.55 16.00 74 650 [307] RCQD-2417 (RGFE-06?MCK?) 19,500 [5.7] 14,400 [4.2] 5,100 [1.5] 13.00 16.00 74 575 [271] RCQD-2417 (RGFE-07?MCK?) 19,600 [5.7] 14,550 [4.3] 5,050 [1.5] 13.00 16.00 74 600 [283] RCQD-2417 (RGJF-06?MCK?) 19,800 [5.8] 14,800 [4.3] 5,000 [1.5] 13.00 16.00 74 625 [295] RCQD-2417 (RGJF-07?MCK?) 19,500 [5.7] 14,400 [4.2] 5,100 [1.5] 13.00 16.00 74 575 [271] RCQD-2417 (RGRM-04?MAE?) 19,800 [5.8] 14,850 [4.4] 4,950 [1.5] 13.00 16.50 74 575 [271] RCQD-2417 (RGRM-06?MAE?) 19,900 [5.8] 15,000 [4.4] 4,900 [1.4] 13.00 16.00 74 600 [283] RCQD-2417 (RGRM-07?MAE?) 20,200 [5.9] 15,400 [4.5] 4,800 [1.4] 13.00 16.00 74 625 [295] RCQD-2417A* (RGFD-06?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.65 16.00 74 600 [283] RCQD-2417A* (RGFD-07?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.65 16.00 74 600 [283] RCQD-2417A* (RGJD-06?MCK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.80 16.00 74 600 [283] RCQD-2417A* (RGJD-07?MCK?) 19,400 [5.7] 14,250 [4.2] 5,150 [1.5] 13.95 16.00 74 625 [295] RCQD-2417A* (RGPR-05?BMK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.55 16.00 74 600 [283] RCQD-2417A* (RGPR-07?AMK?) 19,100 [5.6] 13,850 [4.1] 5,250 [1.5] 13.80 16.00 74 600 [283] RCQD-2417A*+RXMD-C04 18,800 [5.5] 13,800 [4.0] 5,000 [1.5] 12.15 14.50 74 650 [307]
Model Numbers
Indoor Coil and/or Air Handler
Total
Capacity
BTU/H [kW]
18,800 [5.5] 13,800 [4.0] 5,000 [1.5]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
BTU/H [kW]
Net
Latent
EER SEER
12.15 14.50 74
Sound Rating
dB
Indoor
CFM [L/s]
650 [307]
Rheem Heating, Cooling and Water Heating 5
Performance Data @ AHRI Standard Conditions—Cooling: RAPM- JEZ
(continued)
Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RAPM-
Rev.
3/11/2010
018JEZ
024JEZ
024JEZ
RHKL-HM2417 (RCSL-H*2417) 19,400 [5.7] 14,250 [4.2] RHLL-HM2417 (RCSL-H*2417) 19,400 [5.7] 14,250 [4.2] 5,150 [1.5] 13.85 16.00 74 RHSL-HM1817 (RCSL-H*2417) 18,800 [5.5] 13,650 [4.0] 5,150 [1.5] 12.65 15.00 74 600 [283] RCFL-H*2417+RXMD-C04 RCFL-A*2414+RXMD-C04 25,000 [7.3] 18,450 [5.4] 6,550 [1.9] 12.55 14.50 73 800 [378] RCFL-A*2417 (RGFD-06?MCK?) 25,200 [7.4] 18,600 [5.4] 6,600 [1.9] 13.40 15.10 73 800 [378] RCFL-A*2417 (RGFD-07?MCK?) 25,200 [7.4] 18,600 [5.4] 6,600 [1.9] 13.50 15.50 73 RCFL-A*2417 (RGFE-06?MCK?) 25,200 [7.4] 18,550 [5.4] 6,650 [1.9] 13.00 15.50 73 800 [378] RCFL-A*2417 (RGFE-07?MCK?) 25,200 [7.4] 18,550 [5.4] 6,650 [1.9] RCFL-A*2417 (RGGD-06?MCK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.70 15.50 73 800 [378] RCFL-A*2417 (RGGD-07?MCK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.60 15.50 73 800 [378] RCFL-A*2417 (RGGE-06?MCK?) 25,400 [7.4] 18,700 [5.5] 6,700 [2.0] 13.00 16.00 73 RCFL-A*2417 (RGGE-07?MCK?) 25,200 [7.4] 18,500 [5.4] 6,700 [2.0] 13.00 15.50 RCFL-A*2417 (RGLR-07?AMK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.90 16.00 RCFL-A*2417 (RGPR-05?BMK?) 25,200 [7.4] 18,550 [5.4] 6,650 [1.9] 13.50 15.50 73 775 [366] RCFL-A*2417 (RGPR-07?AMK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.80 RCFL-A*2417 (RGRM-04?MAE?) 25,200 [7.4] 18,600 [5.4] 6,600 [1.9] 13.45 15.50 73 800 [378] RCFL-A*2417 (RGRM-06?MAE?) 25,200 [7.4] 18,600 [5.4] 6,600 [1.9] 13.45 15.50 73 825 [389] RCFL-A*2417 (RGRM-07?MAE?) 25,400 [7.4] 18,950 [5.6] 6,450 [1.9] 13.20 15.10 73 850 [401] RCFL-A*2417+RXMD-C04 25,000 [7.3] 18,450 [5.4] 6,550 [1.9] 12.55 14.50 73 800 [378] RCFL-H*2414+RXMD-C04 25,000 [7.3] 18,450 [5.4] 6,550 [1.9] 12.55 14.50 73 800 [378] RCFL-H*2417 (RGFD-06?MCK?) 25,200 [7.4] 18,600 [5.4] 6,600 [1.9] 13.40 15.10 73 800 [378] RCFL-H*2417 (RGFD-07?MCK?) 25,200 [7.4] 18,600 [5.4] 6,600 [1.9] 13.50 15.50 73 800 [378] RCFL-H*2417 (RGFE-06?MCK?) 25,200 [7.4] 18,550 [5.4] 6,650 [1.9] 13.00 15.50 73 800 [378] RCFL-H*2417 (RGFE-07?MCK?) 25,200 [7.4] 18,550 [5.4] 6,650 [1.9] 13.00 15.50 73 825 [389] RCFL-H*2417 (RGGD-06?MCK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.70 15.50 73 800 [378] RCFL-H*2417 (RGGD-07?MCK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.60 15.50 73 800 [378] RCFL-H*2417 (RGGE-06?MCK?) 25,400 [7.4] 18,700 [5.5] 6,700 [2.0] 13.00 16.00 73 825 [389] RCFL-H*2417 (RGGE-07?MCK?) 25,200 [7.4] 18,500 [5.4] 6,700 [2.0] 13.00 15.50 73 800 [378] RCFL-H*2417 (RGJD-06?MCK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.70 15.50 73 800 [378] RCFL-H*2417 (RGJD-07?MCK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.60 15.50 73 800 [378] RCFL-H*2417 (RGJF-06?MCK?) 25,400 [7.4] 18,700 [5.5] 6,700 [2.0] 13.00 16.00 73 825 [389] RCFL-H*2417 (RGJF-07?MCK?) 25,200 [7.4] 18,500 [5.4] 6,700 [2.0] 13.00 15.50 73 800 [378] RCFL-H*2417 (RGLR-07?AMK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.90 16.00 73 800 [378] RCFL-H*2417 (RGPR-05?BMK?) 25,200 [7.4] 18,550 [5.4] 6,650 [1.9] 13.50 15.50 73 775 [366] RCFL-H*2417 (RGPR-07?AMK?) 25,400 [7.4] 18,750 [5.5] 6,650 [1.9] 13.80 16.00 73 800 [378] RCFL-H*2417 (RGRM-04?MAE?) 25,200 [7.4] 18,600 [5.4] 6,600 [1.9] 13.45 15.50 73 800 [378] RCFL-H*2417 (RGRM-06?MAE?) 25,200 [7.4] 18,600 [5.4] 6,600 [1.9] 13.45 15.50 73 825 [389] RCFL-H*2417 (RGRM-07?MAE?) 25,400 [7.4] 18,950 [5.6] 6,450 [1.9] 13.20 15.10 73 850 [401] RCFL-H*2417 (RGTM-06?MAE?) 25,200 [7.4] 18,400 [5.4] 6,800 [2.0] 13.00 16.00 73 750 [354] RBHP-17 (RCHL-24A2) 23,200 [6.8] 16,550 [4.8] 6,650 [1.9] 12.15 14.00 73 800 [378] RCQD-2417 (RGFE-06?MCK?) 24,600 [7.2] 18,600 [5.4] 6,000 [1.8] 12.50 15.00 73 800 [378] RCQD-2417 (RGFE-07?MCK?) 24,600 [7.2] 18,600 [5.4] 6,000 [1.8] 12.50 15.00 73 825 [389] RCQD-2417 (RGJF-06?MCK?) 24,600 [7.2] 18,550 [5.4] 6,050 [1.8] 12.50 15.00 73 825 [389] RCQD-2417 (RGJF-07?MCK?) 24,600 [7.2] 18,600 [5.4] 6,000 [1.8] 12.50 15.00 73 800 [378] RCQD-2417 (RGRM-04?MAE?) 25,600 [7.5] 20,050 [5.9] 5,550 [1.6] 13.65 15.50 73 800 [378] RCQD-2417 (RGRM-06?MAE?) 25,600 [7.5] 20,050 [5.9] 5,550 [1.6] 13.65 15.50 73 825 [389] RCQD-2417 (RGRM-07?MAE?) 25,800 [7.6] 20,400 [6.0] 5,400 [1.6] 13.45 15.00 73 850 [401] RCQD-2417A* 24,800 [7.3] 18,750 [5.5] 6,050 [1.8] 12.05 14.00 73 800 [378] RCQD-2417A* (RGFD-06?MCK?) 24,400 [7.1] 18,450 [5.4] 5,950 [1.7] 12.60 14.50 73 800 [378] RCQD-2417A* (RGFD-07?MCK?) 24,400 [7.1] 18,450 [5.4] 5,950 [1.7] 12.70 15.00 73 800 [378] RCQD-2417A* (RGJD-06?MCK?) 24,600 [7.2] 18,650 [5.5] 5,950 [1.7] 12.90 15.00 73 800 [378] RCQD-2417A* (RGJD-07?MCK?) 24,600 [7.2] 18,650 [5.5] 5,950 [1.7] 12.80 15.00 73 800 [378]
Model Numbers
Indoor Coil and/or Air Handler
Total
Capacity
BTU/H [kW]
25,000 [7.3] 18,450 [5.4] 6,550 [1.9] 12.55 14.50 73 800 [378]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
BTU/H [kW]
5,150 [1.5]
Net
Latent
EER SEER
13.80
13.00 15.50 73 825 [389]
16.00
16.00 73
Sound Rating
dB
74
73 73 800 [378]
Indoor
CFM [L/s]
650 [307] 650 [307]
800 [378]
825 [389] 800 [378]
800 [378]
6 Rheem Heating, Cooling and Water Heating
Performance Data @ AHRI Standard Conditions—Cooling: RAPM- JEZ
(continued)
Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RAPM-
Rev.
3/11/2010
024JEZ
030JEZ
030JEZ
RCQD-2417A* (RGPR-05?BMK?) 24,400 [7.1] 18,400 [5.4] RCQD-2417A* (RGPR-07?AMK?) 24,600 [7.2] 18,650 [5.5] 5,950 [1.7] 13.00 15.00 73 RHKL-HM2417 (RCSL-H*2417) 25,600 [7.5] 19,100 [5.6] 6,500 [1.9] 13.85 16.00 73 850 [401] RHLL-HM2417 (RCSL-H*2417) 25,600 [7.5] 18,900 [5.5] 6,700 [2.0] 14.25 16.00 73 775 [366] RHSL-HM2417 (RCSL-H*2417) 25,000 [7.3] 18,450 [5.4] 6,550 [1.9] 12.95 14.50 73 800 [378] RCFL-H*3617+RXMD-C04 RCFL-A*3617 (RGFD-06?MCK?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.55 14.50 73 RCFL-A*3617 (RGFD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.10 15.10 73 1,000 [472] RCFL-A*3617 (RGFE-06?MCK?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] RCFL-A*3617 (RGFE-07?MCK?) 29,200 [8.6] 21,150 [6.2] 8,050 [2.4] 12.50 14.50 73 1,025 [484] RCFL-A*3617 (RGGD-06?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.15 15.10 73 1,000 [472] RCFL-A*3617 (RGGD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.05 15.00 73 RCFL-A*3617 (RGGE-06?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 RCFL-A*3617 (RGGE-07?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 RCFL-A*3617 (RGLR-07?AMK?) 29,400 [8.6] 21,200 [6.2] 8,200 [2.4] 13.45 15.50 73 1,025 [484] RCFL-A*3617 (RGPR-05?BMK?) 29,200 [8.6] 21,050 [6.2] 8,150 [2.4] 13.00 RCFL-A*3617 (RGPR-07?AMK?) 29,400 [8.6] 21,200 [6.2] 8,200 [2.4] 13.40 15.10 73 1,000 [472] RCFL-A*3617 (RGRM-04?MAE?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.85 14.50 73 1,025 [484] RCFL-A*3617 (RGRM-06?MAE?) 28,800 [8.4] 20,000 [5.9] 8,800 [2.6] 13.45 15.50 73 825 [389] RCFL-A*3617 (RGRM-07?MAE?) 28,800 [8.4] 20,100 [5.9] 8,700 [2.5] 13.20 15.10 73 850 [401] RCFL-A*3617 (RGTM-06?MAE?) 29,000 [8.5] 20,450 [6.0] 8,550 [2.5] 13.00 15.50 73 900 [425] RCFL-A*3617+RXMD-C04 29,000 [8.5] 20,950 [6.1] 8,050 [2.4] 12.55 14.50 73 1,000 [472] RCFL-A*3621 (RGFD-06?MCK?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.55 14.50 73 1,000 [472] RCFL-A*3621 (RGFD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.15 15.10 73 1,000 [472] RCFL-A*3621 (RGFD-09?ZCM?) 29,000 [8.5] 20,300 [5.9] 8,700 [2.5] 13.00 15.50 73 850 [401] RCFL-A*3621 (RGFE-06?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,000 [472] RCFL-A*3621 (RGFE-07?MCK?) 29,200 [8.6] 21,150 [6.2] 8,050 [2.4] 13.00 15.00 73 1,025 [484] RCFL-A*3621 (RGFE-09?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 975 [460] RCFL-A*3621 (RGFE-10?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 1,000 [472] RCFL-A*3621 (RGGD-06?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.25 15.10 73 1,000 [472] RCFL-A*3621 (RGGD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.10 15.10 73 1,025 [484] RCFL-A*3621 (RGGE-06?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-A*3621 (RGGE-07?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-A*3621 (RGGE-09?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 1,000 [472] RCFL-A*3621 (RGGE-10?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 1,000 [472] RCFL-A*3621 (RGLR-07?AMK?) 29,600 [8.7] 21,400 [6.3] 8,200 [2.4] 13.50 15.50 73 1,025 [484] RCFL-A*3621 (RGLR-07?BRQ?) 29,600 [8.7] 21,350 [6.3] 8,250 [2.4] 13.85 16.00 73 1,000 [472] RCFL-A*3621 (RGPR-05?BMK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.10 15.10 73 1,000 [472] RCFL-A*3621 (RGPR-07?AMK?) 29,400 [8.6] 21,200 [6.2] 8,200 [2.4] 13.45 15.50 73 1,000 [472] RCFL-A*3621 (RGPR-07?BRQ?) 29,800 [8.7] 21,550 [6.3] 8,250 [2.4] 13.90 16.00 73 1,000 [472] RCFL-A*3621 (RGRM-04?MAE?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.90 14.50 73 1,025 [484] RCFL-A*3621 (RGRM-06?MAE?) 28,800 [8.4] 20,000 [5.9] 8,800 [2.6] 13.50 15.50 73 825 [389] RCFL-A*3621 (RGRM-07?MAE?) 28,800 [8.4] 20,100 [5.9] 8,700 [2.5] 13.25 15.10 73 850 [401] RCFL-A*3621 (RGRM-07?YBG?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.85 14.50 73 975 [460] RCFL-A*3621 (RGRM-09?ZAJ?) 29,200 [8.6] 20,900 [6.1] 8,300 [2.4] 13.00 15.50 73 950 [448] RCFL-A*3621 (RGRM-10?ZAJ?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-A*3621 (RGTM-06?MAE?) 29,000 [8.5] 20,450 [6.0] 8,550 [2.5] 13.00 15.50 73 900 [425] RCFL-A*3621 (RGTM-07?RBG?) 29,400 [8.6] 21,000 [6.2] 8,400 [2.5] 13.00 15.50 73 950 [448] RCFL-A*3621 (RGTM-09?ZAJ?) 29,600 [8.7] 21,400 [6.3] 8,200 [2.4] 13.00 16.00 73 975 [460] RCFL-A*3621+RXMD-C04 29,000 [8.5] 20,950 [6.1] 8,050 [2.4] 12.55 14.50 73 1,000 [472] RCFL-H*3617 (RGFD-06?MCK?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.55 14.50 73 1,000 [472] RCFL-H*3617 (RGFD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.10 15.10 73 1,000 [472] RCFL-H*3617 (RGFE-06?MCK?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 13.00 15.00 73 1,000 [472]
Model Numbers
Indoor Coil and/or Air Handler
Total
Capacity
BTU/H [kW]
29,000 [8.5] 20,950 [6.1] 8,050 [2.4] 12.55 14.60 73 1,000 [472]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
BTU/H [kW]
6,000 [1.8]
Net
Latent
EER SEER
12.65
13.00 15.00 73 1,000 [472]
14.50
15.00 73
Sound
Rating
dB
73
73 73 1,025 [484]
Indoor
CFM [L/s]
775 [366] 800 [378]
1,000 [472]
1,025 [484] 1,025 [484]
1,000 [472]
Rheem Heating, Cooling and Water Heating 7
Performance Data @ AHRI Standard Conditions—Cooling: RAPM- JEZ
(continued)
Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RAPM-
Rev.
3/11/2010
030JEZ
RCFL-H*3617 (RGFE-07?MCK?) 29,200 [8.6] 21,150 [6.2] RCFL-H*3617 (RGGD-06?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.15 15.10 73 RCFL-H*3617 (RGGD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.05 15.00 73 1,025 [484] RCFL-H*3617 (RGGE-06?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-H*3617 (RGGE-07?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-H*3617 (RGJD-06?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.15 15.10 73 1,000 [472] RCFL-H*3617 (RGJD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.05 15.00 73 RCFL-H*3617 (RGJF-06?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-H*3617 (RGJF-07?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] RCFL-H*3617 (RGLL-07?BRQ?) 29,600 [8.7] 21,350 [6.3] 8,250 [2.4] 13.80 16.00 73 1,000 [472] RCFL-H*3617 (RGLR-07?AMK?) 29,400 [8.6] 21,200 [6.2] 8,200 [2.4] 13.45 15.50 73 1,025 [484] RCFL-H*3617 (RGPR-05?BMK?) 29,200 [8.6] 21,050 [6.2] 8,150 [2.4] 13.00 15.00 73 RCFL-H*3617 (RGPR-07?AMK?) 29,400 [8.6] 21,200 [6.2] 8,200 [2.4] 13.40 15.10 RCFL-H*3617 (RGRM-04?MAE?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.85 14.50 RCFL-H*3617 (RGRM-06?MAE?) 28,800 [8.4] 20,000 [5.9] 8,800 [2.6] 13.45 15.50 73 825 [389] RCFL-H*3617 (RGRM-07?MAE?) 28,800 [8.4] 20,100 [5.9] 8,700 [2.5] 13.20 RCFL-H*3617 (RGTM-06?MAE?) 29,000 [8.5] 20,450 [6.0] 8,550 [2.5] 13.00 15.50 73 900 [425] RCFL-H*3621 (RGFD-06?MCK?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.55 14.50 73 1,000 [472] RCFL-H*3621 (RGFD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.15 15.10 73 1,000 [472] RCFL-H*3621 (RGFD-09?ZCM?) 29,000 [8.5] 20,300 [5.9] 8,700 [2.5] 13.00 15.50 73 850 [401] RCFL-H*3621 (RGFE-06?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,000 [472] RCFL-H*3621 (RGFE-07?MCK?) 29,200 [8.6] 21,150 [6.2] 8,050 [2.4] 13.00 15.00 73 1,025 [484] RCFL-H*3621 (RGFE-09?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 975 [460] RCFL-H*3621 (RGFE-10?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 1,000 [472] RCFL-H*3621 (RGGD-06?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.25 15.10 73 1,000 [472] RCFL-H*3621 (RGGD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.05 15.10 73 1,025 [484] RCFL-H*3621 (RGGE-06?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-H*3621 (RGGE-07?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-H*3621 (RGGE-09?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 1,000 [472] RCFL-H*3621 (RGGE-10?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 1,000 [472] RCFL-H*3621 (RGJD-06?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.25 15.10 73 1,000 [472] RCFL-H*3621 (RGJD-07?MCK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.10 15.10 73 1,025 [484] RCFL-H*3621 (RGJF-06?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-H*3621 (RGJF-07?MCK?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-H*3621 (RGJF-09?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 1,000 [472] RCFL-H*3621 (RGJF-10?ZCM?) 29,600 [8.7] 21,450 [6.3] 8,150 [2.4] 13.00 15.50 73 1,000 [472] RCFL-H*3621 (RGLL-07?BRQ?) 29,600 [8.7] 21,350 [6.3] 8,250 [2.4] 13.85 16.00 73 1,000 [472] RCFL-H*3621 (RGLR-07?AMK?) 29,600 [8.7] 21,400 [6.3] 8,200 [2.4] 13.50 15.50 73 1,025 [484] RCFL-H*3621 (RGLR-07?BRQ?) 29,600 [8.7] 21,350 [6.3] 8,250 [2.4] 13.85 16.00 73 1,000 [472] RCFL-H*3621 (RGPR-05?BMK?) 29,400 [8.6] 21,250 [6.2] 8,150 [2.4] 13.10 15.10 73 1,000 [472] RCFL-H*3621 (RGPR-07?AMK?) 29,400 [8.6] 21,200 [6.2] 8,200 [2.4] 13.45 15.50 73 1,000 [472] RCFL-H*3621 (RGPR-07?BRQ?) 29,800 [8.7] 21,550 [6.3] 8,250 [2.4] 13.90 16.00 73 1,000 [472] RCFL-H*3621 (RGRM-04?MAE?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.90 14.50 73 1,025 [484] RCFL-H*3621 (RGRM-06?MAE?) 28,800 [8.4] 20,000 [5.9] 8,800 [2.6] 13.50 15.50 73 825 [389] RCFL-H*3621 (RGRM-07?MAE?) 28,800 [8.4] 20,100 [5.9] 8,700 [2.5] 13.25 15.10 73 850 [401] RCFL-H*3621 (RGRM-07?YBG?) 29,200 [8.6] 21,100 [6.2] 8,100 [2.4] 12.85 14.50 73 975 [460] RCFL-H*3621 (RGRM-09?ZAJ?) 29,200 [8.6] 20,900 [6.1] 8,300 [2.4] 13.00 15.50 73 950 [448] RCFL-H*3621 (RGRM-10?ZAJ?) 29,400 [8.6] 21,300 [6.2] 8,100 [2.4] 13.00 15.10 73 1,025 [484] RCFL-H*3621 (RGTM-06?MAE?) 29,000 [8.5] 20,450 [6.0] 8,550 [2.5] 13.00 15.50 73 900 [425] RCFL-H*3621 (RGTM-07?RBG?) 29,400 [8.6] 21,000 [6.2] 8,400 [2.5] 13.00 15.50 73 950 [448] RCFL-H*3621 (RGTM-09?ZAJ?) 29,600 [8.7] 21,400 [6.3] 8,200 [2.4] 13.00 16.00 73 975 [460] RCFL-H*3621+RXMD-C04 29,000 [8.5] 20,950 [6.1] 8,050 [2.4] 12.55 14.50 73 1,000 [472] RCFL-H*3821 29,800 [8.7] 21,950 [6.4] 7,850 [2.3] 12.00 14.50 73 995 [470]
Model Numbers
Indoor Coil and/or Air Handler
Total
Capacity
BTU/H [kW]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
BTU/H [kW]
8,050 [2.4]
Net
Latent
EER SEER
12.50
13.00 15.10 73 1,025 [484]
14.50
15.10 73
Sound Rating
dB
73
73 73 1,025 [484]
Indoor
CFM [L/s]
1,025 [484] 1,000 [472]
1,025 [484]
1,000 [472] 1,000 [472]
850 [401]
8 Rheem Heating, Cooling and Water Heating
Performance Data @ AHRI Standard Conditions—Cooling: RAPM- JEZ
(continued)
Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
Outdoor
Unit
RAPM-
Rev.
3/11/2010
030JEZ
RCFL-H*3821 (RGFD-06?MCK?) 29,800 [8.7] 21,900 [6.4] RCFL-H*3821 (RGFD-07?MCK?) 30,000 [8.8] 22,100 [6.5] 7,900 [2.3] 13.00 15.10 73 RCFL-H*3821 (RGFD-09?ZCM?) 29,600 [8.7] 21,050 [6.2] 8,550 [2.5] 13.00 16.00 73 850 [401] RCFL-H*3821 (RGFD-10?ZCM?) 29,600 [8.7] 21,100 [6.2] 8,500 [2.5] 13.00 16.00 73 850 [401] RCFL-H*3821 (RGFE-06?MCK?) 30,000 [8.8] 22,050 [6.5] 7,950 [2.3] 13.00 15.10 73 1,000 [472] RCFL-H*3821 (RGFE-07?MCK?) 30,200 [8.8] 22,400 [6.6] 7,800 [2.3] 13.00 15.10 73 1,025 [484] RCFL-H*3821 (RGFE-09?ZCM?) 30,200 [8.8] 22,200 [6.5] 8,000 [2.3] 13.00 16.00 73 RCFL-H*3821 (RGFE-10?ZCM?) 30,200 [8.8] 22,200 [6.5] 8,000 [2.3] 13.00 16.00 73 1,000 [472] RCFL-H*3821 (RGGD-06?MCK?) 29,800 [8.7] 21,500 [6.3] 8,300 [2.4] RCFL-H*3821 (RGGD-07?MCK?) 29,800 [8.7] 21,600 [6.3] 8,200 [2.4] 13.00 15.50 73 925 [437] RCFL-H*3821 (RGGE-06?MCK?) 30,200 [8.8] 22,350 [6.5] 7,850 [2.3] 13.00 15.10 73 1,025 [484] RCFL-H*3821 (RGGE-07?MCK?) 30,200 [8.8] 22,350 [6.5] 7,850 [2.3] 13.00 15.50 73 RCFL-H*3821 (RGGE-09?ZCM?) 30,200 [8.8] 22,200 [6.5] 8,000 [2.3] 13.00 16.00 RCFL-H*3821 (RGGE-10?ZCM?) 30,200 [8.8] 22,200 [6.5] 8,000 [2.3] 13.00 16.00 RCFL-H*3821 (RGJD-06?MCK?) 30,000 [8.8] 22,050 [6.5] 7,950 [2.3] 13.00 15.10 73 1,000 [472] RCFL-H*3821 (RGJD-07?MCK?) 30,200 [8.8] 22,400 [6.6] 7,800 [2.3] 13.00 RCFL-H*3821 (RGJF-06?MCK?) 30,200 [8.8] 22,350 [6.5] 7,850 [2.3] 13.00 15.50 73 1,025 [484] RCFL-H*3821 (RGJF-07?MCK?) 30,200 [8.8] 22,350 [6.5] 7,850 [2.3] 13.00 15.50 73 1,025 [484] RCFL-H*3821 (RGJF-09?ZCM?) 30,400 [8.9] 22,550 [6.6] 7,850 [2.3] 13.00 16.00 73 1,025 [484] RCFL-H*3821 (RGJF-10?ZCM?) 30,200 [8.8] 22,200 [6.5] 8,000 [2.3] 13.00 16.00 73 1,000 [472] RCFL-H*3821 (RGLR-07?AMK?) 30,000 [8.8] 21,750 [6.4] 8,250 [2.4] 13.00 16.00 73 925 [437] RCFL-H*3821 (RGLR-07?BRQ?) 30,400 [8.9] 22,400 [6.6] 8,000 [2.3] 13.00 16.00 73 1,000 [472] RCFL-H*3821 (RGLR-10?BRM?) 30,000 [8.8] 21,700 [6.4] 8,300 [2.4] 13.00 16.00 73 925 [437] RCFL-H*3821 (RGPR-05?BMK?) 30,000 [8.8] 22,100 [6.5] 7,900 [2.3] 13.00 15.10 73 1,000 [472] RCFL-H*3821 (RGPR-07?AMK?) 30,200 [8.8] 22,250 [6.5] 7,950 [2.3] 13.00 15.10 73 1,000 [472] RCFL-H*3821 (RGPR-07?BRQ?) 30,400 [8.9] 22,400 [6.6] 8,000 [2.3] 13.00 16.00 73 1,000 [472] RCFL-H*3821 (RGPR-10?BRM?) 30,000 [8.8] 21,750 [6.4] 8,250 [2.4] 13.00 16.00 73 925 [437] RCFL-H*3821 (RGRM-04?MAE?) 29,800 [8.7] 21,600 [6.3] 8,200 [2.4] 13.00 15.10 73 925 [437] RCFL-H*3821 (RGRM-06?MAE?) 30,000 [8.8] 22,100 [6.5] 7,900 [2.3] 13.00 15.10 73 1,000 [472] RCFL-H*3821 (RGRM-07?MAE?) 29,600 [8.7] 21,550 [6.3] 8,050 [2.4] 13.00 15.00 73 950 [448] RCFL-H*3821 (RGRM-07?YBG?) 30,000 [8.8] 22,100 [6.5] 7,900 [2.3] 13.00 15.00 73 975 [460] RCFL-H*3821 (RGRM-09?ZAJ?) 30,000 [8.8] 21,850 [6.4] 8,150 [2.4] 13.00 15.50 73 950 [448] RCFL-H*3821 (RGRM-10?ZAJ?) 30,200 [8.8] 22,350 [6.5] 7,850 [2.3] 13.00 15.50 73 1,025 [484] RCFL-H*3821 (RGTM-06?MAE?) 29,800 [8.7] 21,450 [6.3] 8,350 [2.4] 13.00 16.00 73 900 [425] RCFL-H*3821 (RGTM-07?RBG?) 30,000 [8.8] 21,850 [6.4] 8,150 [2.4] 13.00 16.00 73 950 [448] RCFL-H*3821 (RGTM-09?ZAJ?) 30,400 [8.9] 22,400 [6.6] 8,000 [2.3] 13.00 16.00 73 975 [460] RCFL-H*3824 29,800 [8.7] 21,950 [6.4] 7,850 [2.3] 12.00 14.50 73 995 [470] RCFL-H*3824 (RGFD-09?ZCM?) 29,600 [8.7] 21,050 [6.2] 8,550 [2.5] 13.00 16.00 73 850 [401] RCFL-H*3824 (RGFD-10?ZCM?) 29,600 [8.7] 21,100 [6.2] 8,500 [2.5] 13.00 16.00 73 850 [401] RCFL-H*3824 (RGFD-12?RCM?) 29,800 [8.7] 21,450 [6.3] 8,350 [2.4] 13.00 16.00 73 900 [425] RCFL-H*3824 (RGFE-09?ZCM?) 30,400 [8.9] 22,550 [6.6] 7,850 [2.3] 13.00 15.50 73 1,025 [484] RCFL-H*3824 (RGFE-10?ZCM?) 29,800 [8.7] 21,450 [6.3] 8,350 [2.4] 13.00 16.00 73 900 [425] RCFL-H*3824 (RGFE-12?RCM?) 30,400 [8.9] 22,400 [6.6] 8,000 [2.3] 13.00 16.00 73 975 [460] RCFL-H*3824 (RGGD-12?RCM?) 29,800 [8.7] 21,450 [6.3] 8,350 [2.4] 13.00 16.00 73 900 [425] RCFL-H*3824 (RGGE-09?ZCM?) 30,200 [8.8] 22,200 [6.5] 8,000 [2.3] 13.00 16.00 73 1,000 [472] RCFL-H*3824 (RGGE-10?ZCM?) 30,200 [8.8] 22,200 [6.5] 8,000 [2.3] 13.00 16.00 73 1,000 [472] RCFL-H*3824 (RGGE-12?RCM?) 30,600 [9.0] 22,800 [6.7] 7,800 [2.3] 13.00 16.00 73 1,050 [495] RCFL-H*3824 (RGJF-09?ZCM?) 30,400 [8.9] 22,550 [6.6] 7,850 [2.3] 13.00 16.00 73 1,025 [484] RCFL-H*3824 (RGJF-10?ZCM?) 30,400 [8.9] 22,650 [6.6] 7,750 [2.3] 13.00 15.50 73 1,050 [495] RCFL-H*3824 (RGJF-12?RCM?) 30,600 [9.0] 22,800 [6.7] 7,800 [2.3] 13.00 16.00 73 1,050 [495] RCFL-H*3824 (RGLR-07?BRQ?) 30,000 [8.8] 21,650 [6.3] 8,350 [2.4] 13.00 16.00 73 900 [425] RCFL-H*3824 (RGLR-10?BRM?) 30,600 [9.0] 22,800 [6.7] 7,800 [2.3] 13.00 16.00 73 1,050 [495] RCFL-H*3824 (RGLR-12?ARM?) 30,400 [8.9] 22,350 [6.5] 8,050 [2.4] 13.00 16.00 73 1,000 [472]
Model Numbers
Indoor Coil and/or Air Handler
Total
Capacity
BTU/H [kW]
80°F [26.5°C] DB/67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
BTU/H [kW]
7,900 [2.3]
Net
Latent
EER SEER
13.00
13.00 15.50 73 900 [425]
15.00
15.10 73
Sound Rating
dB
73
73 73 1,000 [472]
Indoor
CFM [L/s]
1,000 [472] 1,000 [472]
975 [460]
1,025 [484] 1,000 [472]
1,025 [484]