FORM NO. G11-477 REV. 8
Supersedes Form No. G11-477 Rev. 7
90RJ SERIES
Models with Input Rates
from 45,000 to 120,000 BTU/HR
[13.19 to 35.17 kW]
(All Models 90% A.F.U.E.† or Above)
The Rheem Value Series 90 High Efficiency line of upflow
gas furnaces are designed for utility rooms, closets, or
alcoves. Because of the low-profile 34 inch height, the
90RJ model can be used vertically to satisfy most applications that traditionally call for a horizontal furnace.
The design is certified by the CSA.
Features
■ Low profile “34 inch” design is lighter and easier to handle
and leaves room for optional accessories.
■ Left or right side gas, electric, and condensate drainage
connections.
■ Integrated control board manages all operational func-
tions and provides accessory hookups for an electronic
air cleaner.
■ A slow-opening gas valve and a specially designed
inducer system make it one of the quietest furnaces on
the market today.
■ Textured galvanized steel cabinet with painted access
doors.
■ Optional indoor or outdoor combustion air. In addition,
combustion air may be piped to either the top or right side
of the cabinet on all upflow models. A special molded fitting is provided to ease installation.
■ Control board diagnostics.
A variety of cooling coils and plenums designed to use with
the Rheem Value Series 90 gas furnaces are available as
optional accessories for air conditioning models.
✝A.F.U.E. (Annual Fuel Utilization Efficiency) calculated in accordance with Department of
Energy test procedures.
90 HIGH EFFICIENCY
UPFLOW
GAS FURNACES
Annual Fuel Utilization Efficiency -
AFUE
THIS MODEL
97%78%
HIGH
MID
82% 88%
92.0%
ENER UIDE

2 ICECO
STANDARD EQUIPMENT
Completely assembled and wired; heat exchanger; primary: aluminized steel,
secondary: 29-4C stainless steel; induced draft; pressure switch; redundant main
gas control; blower compartment door safety switch; solid state time on/off blower
control; limit controls; manual shut-off valve; 100% safety lock out; cool fan off
delay; field selectable heat fan off delay; one hour automatic retry; self-test
diagnostics; flame sense current diagnostics; electronic air cleaner connections;
pressure regulator for natural and L.P. (propane) gases; transformer; direct drive,
multi-speed blower motor. (Please note: a thermostat is not included as standard
equipment.)
OPTIONAL EQUIPMENT
(See Accessory Page)
NOTE: Furnace is not listed for use with fuels other than natural or L.P.
(propane) gas.
All models can be converted by a qualified distributor or local service dealer to use
L.P. (propane) gas without changing burners. Factory approved kits must be used
to convert from natural to L.P. (propane) gas and may be ordered as optional
accessories from a parts distributor.
For L.P. (propane) operation, refer to Conversion Kit Index Form.
WARNING
THIS FURNACE IS NOT APPROVED
OR RECOMMENDED
FOR USE IN MOBILE HOMES
PRIMARY AND SECONDARY
HEAT EXCHANGER
REMOTE
SENSOR
GAS VALVE AND
MANIFOLD
HOT SURFACE IGNITOR
IN-SHOT BURNERS
PRESSURE SWITCH
DRAFT INDUCER
INTEGRATED
FURNACE
CONTROL
RHEEM 90 HIGH EFFICIENCY
UPFLOW GAS FURNACE

ICECO 3
BEFORE PURCHASING THIS APPLIANCE, READ IMPORTANT ENERGY COST AND EFFICIENCY INFORMATION AVAILABLE
FROM YOUR RETAILER.
PHYSICAL DATA AND SPECIFICATIONS
MODEL IDENTIFICATION
01SEE04RJ90
Rheem
Value Series
Fuel Code
S = 90 Plus Natural Gas
Variations
Blower Designation [mm]
Motor H.P.
E = Standard Cabinet
11 x 7 [279 x 178]
1
/2 H.P. – 4 Speed
F = Standard Cabinet
12 x 7 [305 x 178]
3
/4 H.P. – 3 Speed
G = Standard Cabinet
12 x 11 [305 x 279]
3
/4 H.P. – 3 Speed
H = Standard Cabinet
11 x 10 [279 x 254]
3
/4 H.P. – 3 Speed
J = Standard Cabinet
12 x 11 [305 x 279]
1
/2 H.P. – 3 Speed
Ignition
E = Electric Ignition
Heating Input
BTU/HR [kW]
04 = 45,000 [13]
06 = 60,000 [18]
07 = 75,000 [22]
09 = 90,000 [26]
10 = 105,000 [31]
12 = 120,000 [35]
Model
Designation
Efficiency
90 = 90 Plus
[ ] Designates Metric Conversions
NOTES: All models are 115V, 60HZ, 1
ø.
Gas connection size for all models is
1
/2
" [13 mm] N.P.T.
➀ See Conversion Kit Index Form for high altitude derate.
➁ Canadian installations only.
➂ In accordance with D.O.E. test procedures.
MODEL NUMBERS
90RJ- SERIES
Input-BTU/Hr [kW] ➀
Heating Capacity
BTU/Hr [kW]
High Altitude Input
[kW] ➁
High Altitude Output
Capacity [kW] ➁
Blower (D x W)
[mm]
Motor H.P. [W]
Speeds-Type
Motor Full Load Amps 6.8 6.8 6.8 9.5 9.5
Heating Speed Med-Low Low Med Low Low
Cooling Speed High High High High High
Minimum Ext. Static Pressure
(In. W.C.) [kPa]
Maximum Ext. Static Pressure
(In. W.C.) [kPa]
Heating C.F.M. @ .2" [.049 kPa]
W.C. E.S.P. [L/s]
Cooling C.F.M. @ .5" [.124 kPa]
W.C. E.S.P. [L/s]
Temperature Rise
Range °F [°C]
Return Air Cabinets (Opt.)
RXGRFilter Size
[mm]
Approx. Shipping Weight
(Lbs.) [kg]
AFUE ➂
California Seasonal
Efficiency ➂
90RJ04EES01 90RJ06EES01 90RJ07EES01 90RJ07EFS01 90RJ10EGS01
45,000
[13.19]
42,000
[12.31]
40,500
[11.87]
37,800
[11.07]
11 x 7
[279 x 178]
1/2 [373]
4-PSC
.10 [.025] .12 [.029] .12 [.029] .12 [.029] .20 [.049]
.50 [.12] .50 [.12] .50 [.12] .50 [.12] .50 [.12]
885 [417] 845 [398] 1050 [495] 1275 [600] 1445 [682]
1195 [564] 1100 [519] 1110 [524] 1540 [725] 1810 [854]
30-60
[16.7-33.3]
C17B
(2) 12" x 16"
[305 x 406]
111 [50.3] 117 [53.1] 123 [55.8] 123 [55.8] 152 [68.9]
93.5% 92.5% 92.8% 92.0% 92.0%
84.68% 86.44% 87.16% 85.16% 86.93%
60,000
[17.58]
56,000
[16.41]
54,000
[15.83]
50,400
[14.77]
11 x 7
[279 x 178]
1/2 [373]
3-PSC
40-70
[22.2-38.9]
C17B
(2) 12" x 16"
[305 x 406]
75,000
[21.98]
70,000
[20.51]
67,500
[19.78]
63,000
[18.46]
11 x 7
[279 x 178]
1/2 [373]
3-PSC
45-75
[25-41.7]
C17B
(2) 12" x 16"
[305 x 406]
75,000
[21.98]
70,000
[20.51]
67,500
[19.78]
63,000
[18.46]
12 x 7
[305 x 178]
3/4 [559]
3-PSC
40-70
[22.2-38.9]
C21B
(2) 12" x 20"
[305 x 508]
90RJ09EJS01
90,000
[26.37]
84,000
[24.61]
81,000
[23.73]
76,000
[22.27]
12 x 11
[305 x 279]
1/2 [373]
3-PSC
8.0
Med
High
.15 [.037]
.50 [.12]
1465 [691]
1580 [746]
35-65
[19.4-36.1]
C21B
(2) 12" x 16"
[305 x 406]
148 [67.1]
93.5%
85.96%
105,000
[30.77]
97,000
[28.43]
94,500
[27.70]
87,500
[25.64]
12 x 11
[305 x 279]
3/4 [559]
3-PSC
50-80
[27.8-44.4]
C21B
(2) 12" x 16"
[305 x 406]
90RJ12EHS01
120,000
[35.17]
113,000
[33.12]
108,000
[31.65]
100,000
[29.31]
11 x 10
[279 x 254]
3/4 [559]
3-PSC
9.5
Low
High
.20 [.049]
.50 [.12]
1580 [745]
1900 [897]
50-80
[27.8-44.4]
C24B
(2) 24" x 16"
[609 x 406]
160 [72.6]
93.5%
87.57%

MODEL
90RJ
A B C D E F
LEFT
SIDE
MINIMUM CLEARANCE (IN.) [mm]
SHIP
WGTS.
[kg]
RIGHT
SIDE
BACK TOP FRONT VENT
04 171/2 [445] 165/16 [414] 155/8 [397] 2 [51] 15 [422] 1313/16 [351] 0 0 0 1 [25] 2 [51] 0 111 [50]
06, 07EE 171/2 [445] 165/16 [414] 155/8 [397] 2 [51] 15 [422] 1313/16 [351] 0 0 0 1 [25] 2 [51] 0 117 [53]
07EF 21 [533] 1913/16 [503] 191/8 [487] 2 [51] 181/2 [511] 175/16 [440] 0 0 0 1 [25] 2 [51] 0 123 [56]
10 21 [533] 1913/16 [503] 191/8 [487] 2 [51] 181/2 [511] 175/16 [440] 0 0 0 1 [25] 2 [51] 0 152 [69]
12 241/2 [622] 235/16 [592] 225/8 [575] 2 [51] 22 [600] 2013/16 [529] 0 0 0 1 [25] 2 [51] 0 160 [73]
09 21 [533] 1927/32 [504] 191/8 [487] 2 [51] 181/2 [511] 179/32 [441] 0 0 0 1 [25] 2 [51] 0 148 [67]
[ ] Designates Metric Conversions

ICECO 5
BLOWER PERFORMANCE DATA—90RJ MODELS
GENERAL TERMS OF LIMITED WARRANTY
ICECOSMwill furnish a replacement for any part of this product which fails in normal use and service within the applicable
period stated, in accordance with the terms of the limited
warranty.
For Complete Details of the Limited Warranty, Including Applicable Terms
and Conditions, See Your Local Installer or visit www.ICECOhvac.com.
Primary and Secondary Heat Exchanger ....Twenty (20) Years
Any Other Part ..............................................Five (5) Years
[ ] Designates Metric Conversions
MODEL
NUMBER
90RJ
SERIES
04EES01
06EES01
07EES01
07EFS01
09EJS01
10EGS01
12EHS01
BLOWER
SIZE
[mm]
11 x 7
[279 x 178]
11 x 7
[279 x 178]
11 x 7
[279 x 178]
12 x 7
[305 x 178]
12 x 11
[305 x 279]
12 x 11
[305 x 279]
11 x 10
[279 x 245]
MOTOR
H.P.
[W]
1/2
[373]
1/2
[373]
1/2
[373]
3/4
[559]
1/2
[373]
3/4
[559]
3/4
[559]
BLOWER
SPEED
LOW
MED-LO
MED-HI
HIGH
LOW
MED
HIGH
LOW
MED
HIGH
LOW
MED
HIGH
LOW
MED
HIGH
LOW
MED
HIGH
LOW
MED
HIGH
EXTERNAL STATIC PRESSURE INCHES WATER COLUMN [kPa]
0.1 [.02] 0.2 [.05] 0.3 [.07] 0.4 [.10] 0.5 [.12] 0.6 [.15] 0.7 [.17]
805 [380]
920 [434]
1140 [538]
1360 [642]
880 [415]
1060 [500]
1260 [594]
880 [415]
1090 [514]
1300 [613]
1405 [668]
1595 [753]
1835 [866]
1235 [582]
1490 [703]
1720 [811]
1490 [703]
1710 [807]
2010 [949]
1610 [760]
1870 [882]
2115 [998]
780 [368]
885 [417]
1110 [524]
1320 [623]
845 [398]
1025 [483]
1215 [573]
850 [401]
1050 [495]
1255 [592]
1375 [649]
1560 [736]
1780 [840]
1210 [571]
1465 [691]
1670 [788]
1445 [682]
1665 [786]
1955 [923]
1580 [746]
1820 [860]
2050 [967]
CFM [L/s] AIR DELIVERY
760 [358]
850 [401]
1085 [512]
1280 [604]
815 [384]
990 [467]
1175 [554]
825 [389]
1010 [477]
1210 [571]
1350 [637]
1525 [720]
1730 [816]
1180 [559]
1445 [679]
1620 [764]
1405 [663]
1620 [764]
1900 [897]
1555 [734]
1775 [838]
1990 [939]
720 [340]
810 [382]
1045 [493]
1235 [583]
790 [373]
960 [453]
1135 [535]
785 [370]
970 [458]
1160 [547]
1310 [618]
1480 [698]
1675 [791]
1150 [543]
1405 [663]
1600 [755]
1375 [649]
1580 [746]
1855 [875]
1515 [715]
1715 [809]
1945 [917]
685 [323]
775 [365]
1010 [476]
1195 [564]
760 [358]
925 [436]
1100 [519]
750 [354]
925 [436]
1110 [524]
1270 [599]
1440 [679]
1625 [767]
1120 [528]
1375 [649]
1580 [746]
1350 [637]
1540 [727]
1810 [854]
1475 [696]
1660 [783]
1900 [897]
645 [304]
730 [344]
950 [448]
1140 [538]
715 [337]
880 [415]
1040 [491]
702 [331]
875 [413]
1055 [498]
1235 [583]
1380 [651]
1555 [734]
1075 [507]
1315 [620]
1520 [717]
1295 [611]
1475 [696]
1710 [807]
1415 [668]
1590 [750]
1795 [847]
605 [285]
690 [325]
890 [420]
1080 [500]
670 [316]
835 [394]
985 [465]
655 [309]
825 [389]
1005 [474]
1195 [564]
1325 [625]
1480 [698]
1035 [488]
1255 [592]
1460 [689]
1240 [585]
1410 [665]
1610 [859]
1355 [639]
1520 [717]
1690 [795]

6 ICECO
ACCESSORIES—UPFLOW
RXGP-F03
TWINNING KIT—is for use with Rheem Value Series 90 Gas
Furnaces for parallel operation requirements.
WARNING: IMPORTANT NOTICE
A SOLID METAL BASE PLATE (SEE TABLE) MUST BE IN PLACE WHEN THE FURNACE
IS INSTALLED WITH SIDE OR REAR AIR RETURN DUCTS. FAILURE TO INSTALL A
BASE PLATE COULD CAUSE PRODUCTS OF COMBUSTION TO BE CIRCULATED INTO
THE LIVING SPACE AND CREATE POTENTIALLY HAZARDOUS CONDITIONS.
FURNACE BASE
WIDTH
SOLID BOTTOM BASE
PLATE SIZE
IN. [mm]
KIT NO. PLATE NO.
IN. [mm]
17
1
/2 [445] RXGB-D17 AE-61874-02 151/8 x 239/16 [384 x 598]
21 [533] RXGB-D21 AE-61874-03 18
5
/8 x 239/16 [473 x 598]
24
1
/2 [622] RXGB-D24 AE-61874-04 255/8 x 239/16 [651 x 598]
PLENUM DATA FOR “A” COILS
Plenum adapters are required in some instances for use on upflow applications
when plenum and furnace size do not match.
VENT TERMINATION KITS
CONCENTRIC: Vertical/Horizontal = RXGY-E03
HORIZONTAL TWO PIPE: RXGY-D02, RXGY-D03, RXGY-D04
FOSSIL FUEL KIT: RXPF-F01
RXPF-F02 (TVA)
RETURN AIR PLENUM: RXGR-C17B
RXGR-C21B
RXGR-C24B
EXTERNAL BOTTOM FILTER RACK: RXGF-CB
EXTERNAL SIDE FILTER RACK: RXGF-CA
*Filter racks are shipped without filters.
Filters shipped with furnace may be used or a suitable 1" [25.4 mm] filter.
FOR HIGH ALTITUDES:
*HIGH ALTITUDE KIT:
RXGY-F04 (105 KBTU/H)
RXGY-F05 (120 KBTU/H)
RXGY-F06 (45 KBTU/H/60 KBTU/H/90 KBTU/H)
RXGY-F07 (75 KBTU/H)
*For installations over 5000 ft.
OPTION CODE FOR HIGH ALTITUDE: US & Canada – 278
NOTE: High altitude kits and options do NOT include additional
burner orifices. If a burner orifice change is necessary, they
must be ordered through PROSTOCK
®
. See Installation
Instructions for more information.
Option – 278 furnaces are shipped with #51 DMS orifices installed.
This is one drill size smaller than standard furnaces to account for
expected average elevations and heating values typically seen in
these areas.
CAUTION: Always follow National Fuel Gas Code (NFGC) guidelines
when converting for high altitudes.
For all installations above 2000 ft. (including all option – 278
models), the burner orifice size needs to be recalculated and
verified. A burner orifice change may still be required. See
Installation Instructions for more information.
NOTE: For Canadian installations only, an optional derate (manifold
gas pressure reduction) method may be used to adjust the
furnace for altitude. See Installation Instructions for more
information. This optional method may NOT be used for U.S.
installations.
[ ] Designates Metric Conversions
Note: See Form Number C11-207 for MultiFlex
®
coil data.
INTERNAL FILTER RACK FOR BOTTOM
OR SIDE RETURN: RXGF-DA*
Each order contains (1) one box of 10 filter racks supplied
without filters.
*Filters available through PROSTOCK
®
.
FILTER RACK FILTER SIZES* INCHES [mm]
MODEL
90RJ
04EE
06EE
07*EE
07*EF
09EJ
10EG
12EH
RXGF-CB
(BOTTOM)
153/4 x 25
[400 x 635]
153/4 x 25
[400 x 635]
153/4 x 25
[400 x 635]
191/4 x 25
[489 x 635]
191/4 x 25
[489 x 635]
191/4 x 25
[489 x 635]
223/4 x 25
[578 x 635]
RXGF-CA
(SIDE)
153/4 x 25
[400 x 635]
153/4 x 25
[400 x 635]
153/4 x 25
[400 x 635]
153/4 x 25
[400 x 635]
153/4 x 25
[400 x 635]
153/4 x 25
[400 x 635]
153/4 x 25
[400 x 635]
FURNACE
WIDTH
IN. [mm]
141/2 [356] 161/4 [413] RXAA-C171 RXAL-B16BU
141/2 [356] 201/4 [514] RXAA-C172 RXAL-B20BU
171/2 [445] 161/4 [413]
171/2 [445] 201/4 [514] RXAA-C173 RXAL-B20BU
171/2 [445] 215/8 [549] RXAA-C187 RXAL-B21BU
171/2 [445] 251/4 [641]
211/2 [533] 251/4 [641] RXAA-C175 RXAL-B25BU
211/2 [533] 221/4 [565]
211/2 [533] 215/8 [549] RXAA-C188 RXAL-B21BU
241/2 [622] 251/4 [641]
241/2
[622]
PLENUM
WIDTH
IN. [mm]
215/8
[549]
PLENUM ADAPTER
UPFLOW
RXAA-C185 RXAL-B16BU
RXAA-C174 RXAL-B25BU
RXAA-C176 RXAL-B22BU
RXAA-C177 RXAL-B25BU
RXAA-C187 RXAL-B21BU
PLENUM
COIL

“In keeping with its policy of continuous progress and product improvement, ICECO reserves the right to make changes without notice.”
PRINTED IN U.S.A. 3-07 DC FORM NO. G11-477 REV. 8
Supersedes Form No.G11-477 Rev. 7
Before proceeding with installation, refer
to installation instructions packaged
with each model, as well as complying
with all Federal, State, Provincial, and
Local codes, regulations, and practices.
RHEEM
AIR CONDITIONING
DIVISION
5600 Old Greenwood Road, Fort Smith, Arkansas 72908