Rudd 40 GALLON Installation Manual

Page 1
VACATION
WARNING
VERY HOT
WARM
A B C
COOLER
VACATION
WARNING
VERY HOT
WARM
A B C
COOLER
!
Warning: This water heater is not
suitable for use in manufactured (mobile) homes!
Residential Gas
Use & Care Manual
With Installation Instructions for the Installer
PowerDirectVent
Residential 40, 50, 65 & 75 Gallon Models
The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations for the proper installation and adjustment of the water heater; and two, for the owner–operator, to explain the features, operation, safety precautions, maintenance and troubleshooting of the water heater. This manual also includes a parts list.
It is very important that all persons who are expected to install, operate or adjust this water heater read the instructions carefully so they may understand how to perform these operations. If you do not understand these instructions or any terms within it, seek professional assistance.
Any questions regarding the operation, maintenance, service or warranty of this water heater should be directed to the seller from whom it was purchased. If additional information is required, refer to the section on “If you need service.”
Do not destroy this manual. Please read carefully and keep in a safe place for future reference.
Recognize this symbol as an indication of Important Safety Information!
!
California Proposition 65 Warning: This product contains chemicals known to the
!
State of California to cause cancer, birth defects or other reproductive harm.
Water Heaters
!
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
!
FOR YOUR SAFETY!
Do not store or use gasoline or other
flammable vapors or liquids or other combustible materials in the vicinity of this or any other appliance. To do so may result in an explosion or fire.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not
use any phone in your building.
Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s instructions.
Printed in USA
If you cannot reach your gas supplier, call
the fire department.
Do not return to your home until authorized
by the gas supplier or fire department.
Improper installation, adjustment, alteration,
service or maintenance can cause property damage, personal injury, or death. Refer to this manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
I
S
G
E
N
D
C
E
D
R
E
I
T
F
I
®
AP14896-1 (01/10)
Page 2
Safety Information
Safety Precautions . . . . . . . 3–6
LP Gas Models . . . . . . . . . . . 5
Installing the Water Heater
Location . . . . . . . . . . . . . . . . . 7
Water Supply Connections . . 8
Gas Supply . . . . . . . . . . . . . . 10
Vent and Combustion
Air-Inlet . . . . . . . . . . . . . .11-22
Wiring Diagram . . . . . . . . . . .23
Pipe Insulation . . . . . . . . . . . .24
Heat Traps . . . . . . . . . . . . . . .25
Installation Checklist . . . . . . .26
Potable/Space Heating . . . . 27
Operating Instructions
Lighting Instructions . . . . . . 28
Water Temperature . . . . 29, 30
FOR YOUR RECORDS
Write the model and serial numbers here:
#
#
You can find them on a label on the appliance.
Staple sales slip or cancelled check here.
Proof of the original purchase date is needed to obtain service under the warranty.
READ THIS MANUAL
Inside you will find many helpful hints on how to use and maintain your water heater properly. A little preventive care on your part can save you time and money over the life of your water heater.
You’ll find many answers to common problems in the Troubleshooting Guide. If you review the chart of Troubleshooting Tips first, you may not need to call for service.
Care and Cleaning
Draining . . . . . . . . . . . . . . . . 32
Maintenance . . . . . . . . . . . . . 32
Vent System Inspection . . . . 33
Burner Inspection . . . . . . . . 33
Extended Shut-Down . . . . . .33
Troubleshooting Tips
Before You Call
For Service . . . . . . . . . . . 34, 35
Customer Service
Parts List . . . . . . . . . . . . . . . . 37
If You Need Service . . . . . . .38
READ THE SAFETY INFORMATION
Your safety and the safety of others are very important. There are many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol. Recognize this symbol as an indication of Important Safety Information!
!
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word “DANGER”, “WARNING”, “CAUTION” or “NOTICE”.
These words mean:
!
DANGER
WARNING
!
!
CAUTION
Notice:
An imminently hazardous situation that will result in death or serious injury.
A potentially hazardous situation that could result in death or serious injury and/or damage to property.
A potentially hazardous situation that may result in minor moderate injury.
Attention is called to observe a specified procedure or maintain a specific condition.
2
Page 3
IMPORTANT SAFETY INFORMATION READ ALL INSTRUCTIONS BEFORE USING
Be sure to read and understand the entire Use and Care Manual before attempting to install or operate this water heater. It may save you time and money. Pay particular attention to the Safety Instructions. Failure to follow these warnings could result in serious bodily injury or death. Should you have problems understanding the instructions in this manual, or have any questions, STOP, and get help from a qualified service technician, or the local gas utility.
NOTICE: This water heater is equipped with a flammable vapor sensor that will automatically shut down the water heater in the presence of gasoline vapors and some other flammable vapors. If the flammable vapor sensor shuts down the water heater, contact a qualified service technician. Clear any hazardous materials and ventilate the area around the water heater. Do not turn off the appliance or adjust the ON/OFF switch in any way. Do not tamper with the flammable vapor sensor. Do not submerse the flammable vapor sensor in water. Do not allow the flammable vapor sensor to come into contact with any substances such as bleach or cleaners. See the “Gas Valve LED Code” Section of this manual for a list of diagnostic codes.
DANGER!
PROPERLY VENT THE WATER HEATER
Failure to properly vent the water heater as outlined in the Vent and Combustion Air-Inlet Section of the Installation Instructions in this manual can result in unsafe operation of the water heater. To avoid the risk of fire, explosion, or asphyxiation from carbon monoxide, never operate this water heater unless both the vent and combustion air-inlet systems are properly installed. Be sure to inspect both the vent and combustion air-inlet for proper installation at initial start-up; and at least periodically thereafter. Refer to the Care and Cleaning section of this manual for more information regarding vent and combustion air­inlet system inspection.
WARNING!
Gasoline, as well as other flammable materials and liquids (which include but are not limited to adhesives, solvents, paint thinners etc.), and the vapors they produce are extremely dangerous. DO NOT handle, use or store gasoline or other flammable or combustible materials anywhere near or in the vicinity of a water heater or any other appliance. Be sure to read and follow warning label pictured below and other labels on the water heater, as well as the warnings printed in this manual. Failure to do so can result in property damage, bodily injury or death.
W A R N I N G
!
FLA MMABLE S
!
Do not store or use gasoline or other flammable vapors and liquids
in the vicinity of this or any other appliance. Storage of or use of gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance can result in serious injury or death.
Flammable Vapors
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death.
3
Page 4
!
IMPORTANT SAFETY INFORMATION. READ ALL INSTRUCTIONS BEFORE USING
DANGER!
WATER TEMPERATURE SETTING
Safety and energy conservation are factors to be considered when selecting the water temperature setting of a water heater’s gas control. Water temperatures above 125°F (52°C) can cause severe burns or death from scalding. Be sure to read and follow the warnings outlined on the label pictured below. This label is also located on the water heater.
Time/Temperature Relationship in Scalds
!
D A N G E R
HOT
Water Temperature Time To Produce a Serious Burn
120°F (49°C) More than 5 minutes
125°F (52°C) 11/2 to 2 minutes
130°F (54°C) About 30 seconds
135°F (57°C) About 10 seconds
140°F (60°C) Less than 5 seconds
145°F (63°C) Less than 3 seconds
150°F (66°C) About 11/2 seconds
155°F (68°C) About 1 second
Table courtesy of Shriners Burn Institute
The chart shown above may be used as a guide in determining the proper water temperature for your home.
!
DANGER: Households with small children, disabled, or elderly persons may require a 120°F (49 control (thermostat) setting to prevent contact with "HOT" water.
°C) or lower gas
BURN
Water temperature over 125°
can
cause severe burns
instantly or
death from scalds.
Children, disabled and elderly are at highest risk of being scalded.
See instruction manual before setting temperature at water heater.
Feel water before bathing or showering.
Temperature limiting valves are available, see manual.
Notice: Mixing valves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines. Contact a licensed plumber or the local plumbing authority for further information.
4
F
Maximum water temperatures occur just after the burner has shut off. To find water temperature being delivered, turn on a hot water faucet and place a thermometer in the water stream and read the thermometer. (See pages 29 and 30 for more details.)
The temperature of the water in the heater can be regulated by pressing the "COOLER" or "HOTTER"
arrow buttons on the front of the combination
gas control. To comply with safety regulations the combination gas control was set at its lowest setting before the water heater was shipped from the factory. The desired water temperature must be set.
The illustration below details the approximate water temperature for each LED indicator of the
VACATION
WARM
COOLER
WARM = approx. 70°F (21°C)
▼ = approx. 120°F (49°C)
A = approx. 130°F (54°C)
B = approx. 140°F (60°C)
C = approx. 150°F (66°C)
C-Flashing = approx. 160°F (71°C)
A B C
VERY HOT
HOTTER
WARNING
Temperature Setting
Combination Gas Control's display.
DANGER: Hotter water
increases the potential for Hot Water SCALDS.
Display
▼ A B C
● ○ ○ ○ ○ ○ ○ ○ ● ○ ○ ○ ○ ○ ○ ● ○ ○ ○ ○ ○ ○ ● ○ ○ ○ ○ ○ ○ ● ○ ○ ○ ○ ○ ●
Burns on Adult Skin
--------------------
More than 5 minutes
About 30 seconds
Less than 5 seconds
About 1-1/2 seconds
About 1/2 seconds
Page 5
DANGER!
!
LIQUEFIED PETROLEUM (LP PROPANE OR BUTANE) AND NATURAL GAS MODELS
LP and Natural gas have an odorant added to aid in detecting a gas leak. Some people may not physically be able to smell or recognize this odorant. If you are unsure or unfamiliar with the smell of LP or natural gas, ask the gas supplier. Other conditions, such as “odorant fade”, which causes the odorant to diminish in intensity, can also hide or camouflage a gas leak.
Water heaters utilizing LP gas are
different from natural gas models. A natural gas water heater will not function safely on LP gas and vice versa.
No attempt should ever be made to
convert the water heater from natural gas to LP gas. To avoid possible equipment damage, personal injury or fire, do not connect the water heater to a fuel type not in accordance with the unit data plate. LP for LP units. Natural gas for natural gas units. These units are not certified for any other fuel type.
LP appliances should not be installed
below grade (for example, in a basement) if such installation is prohibited by federal, state and/or local laws, rules, regulations or customs.
LP gas must be used with great caution.
It is heavier than air and will collect first in lower areas making it hard to detect at nose level.
DANGER: If a gas leak is present or
suspected:
Do not attempt to find the cause
yourself.
Do not try to light any appliance.
Do not touch any electrical switch.
Do not use any phone in your building.
Leave the house immediately and make
sure your family and pets leave also.
Leave the doors open for ventilation
and contact the gas supplier, a qualified service agency or the fire department.
Stay away from the house (or building)
until the service call has been made, the leak is corrected and a qualified agency has determined the area to be safe.
Before attempting to light the water
heater, make sure to look and smell for gas leaks. Use a soapy solution to check all gas fittings and connections. Bubbling at a connection indicates a leak that must be corrected. When smelling to detect a gas leak, be sure to sniff near the floor also.
Gas detectors are recommended in LP
& natural gas applications and their installation should be in accordance with the detector manufacturer’s recommendations and/or local laws, rules, regulations or customs.
It is recommended that more than one
method, such as soapy solution, gas detectors, etc., be used to detect leaks in gas applications.
5
Page 6
IMPORTANT SAFETY INFORMATION.
!
READ ALL INSTRUCTIONS BEFORE USING
WARNING!
For your safety, the information in this manual must be followed to minimize the risk of fire or explosion, electric shock, or to prevent property damage, personal injury, or loss of life.
FOR INSTALLATIONS IN THE STATE OF CALIFORNIA
California Law requires that residential water heaters must be braced, anchored or strapped to resist falling or horizontal displacement due to earthquake motions. For residential water heaters up to 52-gallon capacity, a brochure with generic earthquake bracing instructions can be obtained from: Office of the State Architect, 1102 Q Street, Suite 5100, Sacramento, CA 95814 or you may call 916-445-8100 or ask a water heater dealer.
SAFETY PRECAUTIONS
Have the installer show you the location of the gas shut-off valve and how to shut it off if necessary. Turn off the manual shut-off valve if the water heater has been subjected to overheating, fire, flood, physical damage or if the gas supply fails to shut off.
Read this manual entirely before installing
or operating the water heater.
Use this appliance only for its intended
purpose as described in this Use and Care Manual.
Be sure your appliance is properly installed
in accordance with local codes and the provided installation instructions.
Do not attempt to repair or replace any part
of your water heater unless it is specifically recommended in this manual. All other servicing should be referred to a qualified technician.
READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY.
SAVE THESE INSTRUCTIONS
IMPORTANT
Carefully inspect the water heater for damage before proceeding with the installation. Of specific
interest should be any dents in the long blue cover panel for the combustion air-inlet, PVC pipe; or
damages to the blower and the combustion air-inlet, PVC pipe assembly. If you find damage, DO
NOT install or attempt any repair to the water heater. Contact the manufacturer as detailed under "IF
YOU NEED SERVICE" on page 36
6
Page 7
Installing the Water Heater
!
This water heater must be installed in accordance with these instructions, local codes, utility company requirements, and/or in the absence of local codes, use the latest edition of the American National Standard/National Fuel Gas Code. A copy can be purchased from either the American Gas Association, 400 N. Capitol Street NW, Washington, DC 20001 as ANSI standard Z223.1 or National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269 as booklet NFPA 54.
Location
Max.
2.75 in.
(7 cm)
Flammable Vapor Sensor
The auxiliary catch pan installation MUST conform with local codes.
Diameter of water
heater plus 2 in.
(5.1 cm) min.
Notice: DO NOT allow the catch pan to obstuct the flammable vapor sensor.
Notice: DO NOT allow the flammable vapor sensor to become submerged in water. Make sure the catch pan is properly drained.
WARNING: Combustible construction refers to adjacent walls and ceilings and should not be confused with combustible or flammable products and materials. Combustible and/or flammable products and materials should never be stored in the vicinity of this or any gas appliance.
The water heater should not be located in an area where leakage from the tank or connections will result in damage to the area adjacent to the heater or to lower floors of the structure.
When such areas cannot be avoided it is recom­mended that a suitable catch pan, adequately drained, must be installed under the water heater.
The water heater must be centered in the catch pan.
Catch pan kits are available from the store where the water heater was purchased, or any water heater distributor.
Make certain the floor underneath the water heater is strong enough to sufficiently support the weight of the water heater once it is filled with water.
This gas fired water heater or any other appli­ance should not be installed in a space where liquids which give off flammable vapors are to be used or stored. Such liquids include gasoline, LP gas (butane or propane), paint or adhesives, thinners, solvents and/or combustible removers.
DO NOT obstruct or block the Flammable Vapor Sensor.
Because of natural air movement in a room or other enclosed space, flammable vapors can be carried some distance from where liquids which give off flammable vapors are to be used or stored. The open flame of the water heater’s main burner can ignite these vapors creating a shut down condition which will not allow the water heater to ignite.
The water heater must be located so it is not subject to physical damage, for example, by moving vehicles, area flooding, etc.
Rheem Water Heating FVIR certified gas water heaters can be installed on a residential garage floor without the use of an 18-inch stand in accordance with the National Fuel Gas Code, NFPA 54, ANSI Z223.1, unless otherwise direct­ed by State and Local code requirements. The water heater must be located so it is not subject
to physical damage, for example, by moving vehicles, area flooding, etc
● The water heater should be installed so as
to minimize the length of plastic vent pipe and the number of vent connection fittings required.
● Hot water lines should be insulated to con­serve water and energy.
● Protect the water heater and water lines from
exposure to freezing temperatures.
● Do not install this water heater outdoors.
● Minimum clearances from combustible con-
struction:
Front
5 in.
(12.7 cm)
"Front" Clearance dimension is measured
from the water heater jacket to the closet door.
✶✶ "Top" clearance dimension is measured
from the jacket top of the water heater to the ceiling.
● If the water heater is to be installed directly on
carpeting , the water heater shall be installed on a metal or wood panel extending beyond the full width and depth of the water heater by at least 3 in. (7.6 cm) in all directions or, if the water heater is to be installed in an alcove or closet, the entire floor must be covered by a wood or metal panel.
Sides Rear
0 in.
(0 cm)
0 in.
(0 cm)
Top✶✶
12 in.
(30.5 cm)
7
Page 8
Installing the Water Heater
Corrosive Atmospheres
NOTICE: The water heater must not be installed near an air supply containing halogenated hydrocarbons.
The air in beauty shops, dry cleaning establishments, photo processing labs, and storage areas for liquid and powdered bleaches or swimming pool chemicals often contain halogenated hydrocarbons.
An air supply containing halogenated hydrocarbons may be safe to breathe, but when it passes through a gas flame corrosive elements are released that
Thermal Expansion
Determine if a check valve exists in the inlet water line. Check with your local water util­ity company. It may have been installed in the cold water line as a separate back flow preventer, or it may be part of a pressure reducing valve, water meter or water softener. A check valve located in the cold water inlet line can cause what is referred to as a “closed water system”. A cold water inlet line with no check valve or back flow prevention device is referred to as an “open” water system.
As water is heated, it expands in volume and creates an increase in the pressure within the water system. This action is referred to as “thermal expansion”. In an “open” water sys­tem, expanding water which exceeds the capac­ity of the water heater flows back into the city main where the pressure is easily dissipated.
A “closed water system”, however, prevents the expanding water from flowing back into the main supply line, and the result of “thermal expansion” can create a rapid and dangerous pressure increase in the water heater and sys-
will shorten the life of any gas burning appliance.
Propellants from common spray cans or gas leaks from A/C and refrigeration equipment are highly corrosive after pass­ing through a flame.
The water heater warranty is voided when failure of the heater is due to operation in a corrosive atmosphere.
tem piping. This rapid pressure increase can quickly reach the safety setting of the relief valve, causing it to operate during each heating cycle. Thermal expansion, and the resulting rapid, and repeated expansion and contraction of components in the water heater and piping system can cause premature failure of the relief valve, and possibly the heater itself. Replacing the relief valve will not correct the problem!
The suggested method of controlling thermal expansion is to install an expansion tank in the cold water line between the water heater and the check valve (see illustration on page
9). The expansion tank is designed with an air cushion built in that compresses as the system pressure increases, thereby relieving the over pressure condition and eliminating the repeated operation of the relief valve. Other methods of controlling thermal expansion are also avail­able. Contact your installing contractor, water supplier or plumbing inspector for additional information regarding this subject.
IMPORTANT: Do not apply heat to the HOT or COLD water connections. If sweat connections are used, sweat tubing to adapter before fitting adapter to the cold water connections on heater. Any heat applied to the cold water supply fittings will permanently damage the dip tube and heat traps.
8
Water Supply Connections
Refer to the illustration below for suggested typical installation. The installation of unions or flexible copper connectors are recommended on the hot and cold water connections so that the water heater may be easily disconnected
for servicing if necessary. The HOT and COLD water connections are clearly marked and are 3/4” NPT on all models. Install a shut-off valve in the cold water line near the water heater.
Page 9
NOTICE: The National Fuel Gas Code (NFGC) mandates a manual gas shut-off valve: See (NFGC) for complete instructions. Local codes or plumbing authority requirements may vary from the instruc­tions or diagrams provided and take precedent over these instructions.
Typical Installation
Vent connector
Union (Optional)
Heat trap
6 in. (15.2 cm) min.
Hot water outlet to
fixtures
Water Heater Jacket
Temperature and pressure
relief valve
Manual gas shut-off
To gas supply
Union
Sediment trap
Cap
Thermostatic gas valve
Jacket door
Flammable Vapor Sensor
Optional catch pan
(if required).
Drain Pan Pipe to suitable drain.
1/8 in. per foot (10 mm per meter) maximum slope down for horizontal venting.
Combustion Air-In Connector
Blower assembly
Union (Optional)
Heat trap 6 in. (15.2 cm) min.
Shut-off valve
Thermal expansion tank (if required)
Drain valve
6 in. (15.2 cm) min. Air gap
To cold water supply
Shut-off valve
Relief valve discharge line to suitable open drain.
A new combination temperature and pressure relief valve, complying with the Standard for Relief Valves and Automatic Gas Shut-Off Devices for Hot Water Supply Systems, ANSI Z21.22 /CSA 4.4, is factory installed and must remain in the opening provided and marked for the purpose on the water heater. No valve of any type should be installed between the relief valve and the tank. Local codes shall govern the installation of relief valves.
Relief Valve
The pressure rating of the relief valve must not exceed 150 PSI psi (1,034 kPA), the maximum working pressure of the water heater as marked on the rating plate.
The Btuh rating of the relief valve must equal or exceed the Btuh input of the water heater as marked on its rating plate.
Position the outlet of the relief valve above a suitable open drain to eliminate potential water damage. Piping used should be of a type approved for hot water distribution.
The discharge line must be no smaller than the outlet of the valve and must pitch downward from the valve to allow com­plete drainage (by gravity) of the relief valve and discharge line.
The end of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction, or reducer coupling must be installed in the discharge line.
9
Page 10
Installing the Water Heater
To Fill the Water Heater
WARNING: The tank must be full of water before the water heater is turned on. The water heater warranty does not cover damage or failure resulting from operation with an empty or partially empty tank.
Make certain that the drain valve is closed, then open the shut-off valve in the cold water supply line.
Open each hot water faucet slowly to allow the air to vent from the water heater and piping.
Condensation
Condensation can form on the tank when it is first filled with water. Condensation might also occur with a heavy water draw and very cold inlet water temperatures.
Drops of water falling on the burner can produce a sizzling or pinging sound.
This condition is not unusual, and will disappear after the water becomes heated.
A steady flow of water from all hot water faucet(s) indicates a full water heater.
Do not allow the flammable vapor sensor to become submerged in water.
If, however, the condensation continues, examine the piping and fittings for pos­sible leaks.
NOTICE: Additional information on this subject may be found at www.rheem.com, under Rheem Water Heating, "Support", scroll down to the Technical Service Section and to Bulletins 1400 Series Section and choose Bulletin #1402.
WARNING: Do not attempt to convert this water heater for use with a different type of gas other than the type shown on the rating plate. Such conversion could result in hazardous operating conditions.
Gas Supply
The branch gas supply line to the water heater should be clean properly sized steel pipe or other approved gas piping mate­rial.
A union or ANSI design certified semi­rigid or flexible gas appliance connector should be installed in the gas line close to the water heater. The National Fuel Gas Code (NFGC) mandates a manual gas shut-off valve: See (NFGC) for complete instructions.
If flexible connectors are used, the maxi­mum length shall not exceed 36" (91.4 cm) and must meet the require­ments in ANSI Z21.24/CSA 6.10­Connectors for Gas Appliances.
Compound used on the threaded joints of the gas piping must be of the type resistant to the action of LP gas. Use compound sparingly on male threads only.
Where a sediment trap is not incorpo­rated as part of the appliance, a sediment
trap shall be installed downstream of the equipment shutoff valve as close to the inlet of the appliance as practical at the time of the appliance installation.
The sediment trap shall be either a tee fit­ting with a capped nipple in the bottom outlet or other device recognized as an effective sediment trap.
”Do not use excessive force over 31.5 ft. lbs. (42.7 Nm) in tightening the pipe joint at the combination gas control inlet, par­ticularly if teflon pipe compound is used, as the valve body may be damaged.
The inlet gas pressure to the water heater must not exceed 14.0 in. w.c. (3.5 kPa) w.c. for natural gas, or 14.0 in. w.c. (3.5 kPa) w.c. for LP gas. For purposes of input adjustment, the minimum inlet gas pressure (with main burner on) is shown on the water heater rating plate. If high or low gas pressures are present, contact your gas supplier for correction.
10
Page 11
WARNING: Never use
!
an open flame to test for gas leaks, as property damage, personal injury, or death could result.
Leak Testing
The water heater and its gas connections must be leak tested at normal operating pressures before it is placed in operation.
Turn on the manual gas shut-off
valve near the water heater.
Use a soapy water solution to test for
leaks at all connections and fittings.
Bubbles indicate a gas leak that must be corrected.
The factory connections to the combina­tion gas control should also be leak tested after the water heater is placed in opera­tion.
Pressure Testing the Gas Supply System
The water heater and its individual shut­off valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess 1/2 psi (3.5 kPA).
The water heater must be isolated from the gas supply piping system by closing its individual manual gas shutoff valve during any pressure testing of the gas supply at test pressures equal to or less than 1/2 psi (3.5 kPa).
WARNING: Failure to install a water heater suitable for the altitude at the location it is intended to serve, can result in improper operation of the appliance resulting in property damage and/or producing carbon monoxide gas, which could result in personal injury, or death.
DANGER: Failure to
properly install the vent and combustion air-inlet systems as outlined in the Vent and Combustion Air-Inlet section of this manual will result in unsafe operation of the water heater causing bodily injury, explosion, fire or death.
To avoid the risk of fire, explosion, or asphyxiation from carbon monoxide, NEVER operate the water heater unless it is properly vented and the vent and combustion air-inlet systems are properly installed as detailed in the "Vent and Combustion Air-Inlet" section of this manual.
The vent and combustion air inlet pipes must overlap a minimum of 1/2 in. (1.3 cm) at each joint. It is important that the vent and combustion air-inlet pipes engage fully into any pipe fitting and be kept in that position until the adhesive has fully cured. DO NOT drill or punch holes in the plastic pipe or fittings.
High Altitude
Input rating of this water heater is based on sea level operation. At higher eleva­tions the actual input rate may be lower than the value listed on the rating label due to the derating of Natural Gas and LP Gas. For Power Direct Vent models listed in the venting tables that do not show
Vent and Combustion Air-Inlet
This water heater is a direct vent appli­ance and must be installed so that all air for combustion is derived directly from the outside atmosphere and all flue gases are discharged to the outside atmosphere. For proper installation of the vent and combustion air-inlet systems, follow the instructions as detailed in this manual. DO NOT connect this water heater to an existing vent or chimney - it must be vented separately from all other appli­ances.
NOTICE: This water heater is approved to use the following materials for pipe of the vent and Combustion Air-Inlet sys­tems:
PVC (Schedule 40, Cellular Core, ASTM-F891)
PVC (DWV, ASTM-D2665 or CSA B181.2)
PVC (Schedule 40, ASTM-D1785 or CSA B137.3)
PVC (SDR Series, ASTM-D2241 or CSA B137.3)
venting configurations above 7,700 ft. (2,347 m), contact the water heater manu­facturer for a required High Altitude Kit that will allow the specific water heater model to operate at altitudes between 7,700 ft. (2,347 m) and 10,200 ft. (3,109 m),(see page 40).
CPVC (CPVC 4120, ASTM-D2846 or CSA B137.6)
CPVC (Schedule 40, ASTM-F441 or CSA B137.3)
CPVC (SDR Series, ASTM-F442)
ABS (Schedule 40, DWV, ASTM-D2661 or CSA B181.1)
ABS (Schedule 40, DWV, Cellular Core, ASTM-F628)
This water heater is approved to use the following materials for the fittings of the vent and combustion air-intake systems:
PVC (Schedule 40 DWV, ASTM D2665)
CPVC (Schedule 40, ASTM F438)
ABS (Schedule 40 DWV, ASTM D2661)
DO NOT mix ABS pipe and fittings with PVC or CPVC pipe fittings. Note: It is acceptable to interchange PVC and CPVC pipe and fittings.
Vent and combustion air-inlet systems must be adequately supported along both vertical and horizontal lengths.
11
Page 12
Installing the Water Heater
Vent and Combustion Air-Inlet continued -
The vent and combustion air-inlet
NOTICE: This unit is equipped with a Flammable Vapor Sensor. Do not supply electrical power to the water heater until enough time has passed to allow the vapors from the primer and cement to dissapate.
systems of this water heater may be installed horizontally through a wall or vertically through the roof
Maximum unsupported length is rec­ommended to be no more than 4 feet (1.22 m).
It is imperative that the first hanger be located on the horizontal length imme­diately adjacent to the first 90-degree elbow from the vertical rise of vent pipe connected to the water heater.
The support method used should isolate the vent and combustion air­inlet pipes from floor joists or other structural members to help prevent the transmission of noise and vibration.
Do not support, pin or otherwise secure the vent and combustion air-inlet sys­tems in a way that restricts the normal thermal expansion and contraction of the chosen venting material.
If the water heater is being installed as a replacement for an existing power direct vent water heater, a thorough inspection of the existing vent and combustion air-inlet systems must be
performed prior to any installation work.
.
Verify that the correct materials as
specified in this manual have been used, and that the minimum or maxi­mum vent and combustion air-inlet lengths and terminal locations as detailed in this manual have been met.
Carefully inspect the entire vent and
combustion air-inlet systems for any signs of cracks or fractures, particu­larly at the joints between elbows or other fittings and the straight length of vent pipe.
Check the vent and combustion air-
inlet for signs of sagging or other stresses in the joints as a result of misalignment of any components in the systems.
If any of the conditions above are
found, they must be corrected in accordance with the instructions in this manual before completing the installation and putting the water heater into service.
Additional installation information for The Com­monwealth of Massachusetts is located on the back page of this manual.
12
Maximum and Minimum Vent and Combustion Air-Inlet Lengths for Power Direct Vent Models: 40 Gallon with Inputs of 40,000 & 38,000 BTU/Hr. 50 Gallon with Input of 40,000 BTU/Hr.
Connect the vent system piping to the blower assembly using the already installed 2 in. (5.1 cm) diameter rub­ber coupling and clamps. Connect the combustion air-inlet system pip­ing to the combustion air-inlet piping tee using the 2 in. (5.1 cm) already installed rubber coupling and clamps (See Figure 1). For vent and combus­tion air-inlet terminals, use the two (2), 2 in. (5.1 cm) diameter, Schedule 40, PVC, 90°, 1/4 standard bend elbows and wire mesh screen assemblies sup­plied with the water heater.
This water heater may also be installed with 3 in. (7.6 cm) diameter pipe and fittings for the vent and combustion
air-inlet systems. When using 3 in. (7.6 cm) diameter pipe, two (2), 2 in. (5.1 cm) to 3 in. (7.6 cm) diameter pipe increaser fittings are required for connection of the vent system piping to the blower assembly and combustion air-inlet system piping to the combus­tion air-inlet piping tee couplings (See Figure 2). For vent and combustion air-inlet terminals, 3 in. (7.6 cm) diameter, Schedule 40, PVC, 90°, 1/4 standard bend elbows (not supplied) along with the two (2) wire mesh screens (supplied) must be installed.
DO NOT use unequal sizes except as defined previously for the vent and combustion air-inlet systems.
Page 13
IMPORTANT: Ensure that all the coupling clamps are firmly tight, then leak test the vent system joints using a soap and water solution. Repair any leak before allowing the water heater to operate.
When using CPVC or ABS pipe and fittings, use 90° elbows of the corresponding size and material for the vent and combustion air-inlet terminals. Install supplied wire mesh screens into the CPVC or ABS vent and combustion air-inlet terminal elbows.
The vent and combustion air-inlet terminals of the water heater must be installed in the same atmospheric pressure zone.
The minimum and maximum equivalent lengths for the vent and combustion air-inlet systems are shown in Table 1. Maintain a minimum vertical height of 1 foot (3.5 cm) of pipe from the blower exhaust before transi­tioning in any elbow. The vent and combus­tion air-inlet terminations are not included in the equivalency calculations.
Notice: One (1), 90°, 1/4 standard bend elbow is equivalent to 5 feet (1.52 meters) of straight pipe and quantity one (1), 45°, 1/8 standard bend elbow is equivalent to 2.5 feet (0.76 meters) of straight pipe.
DO NOT use short bend elbows.
2 in. (5.1cm)
Figure 1
2 in. (5.1 cm)
Vent
Vent
3 in. (7.6 cm)
Combustion Air-Inlet
2 in. (5.1cm)
Combustion Air-Inlet
3 in. (7.6 cm)
2 in. (5.1cm)
Figure 2
13
Page 14
Installing the Water Heater
Table 1
From Sea Level through 5,999 Ft. (1,828 m) Above Sea Level
Model
40 Gallon, 40,000
& 38,000 Btu/hr.
Models
Vent & Combus-
tion Air-Inlet
System Diameter
Inches Feet Meters Feet Meters
2 7 2 30 9 90° Elbows Concentric
3 7 2 60 18 90° Elbows Concentric
Min. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Max. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Vent and Combustion Air-Inlet System
Termination(s)
50 Gallon, 40,000
Btu/hr. Models
Model
40 Gallon, 40,000
& 38,000 Btu/hr.
Models
50 Gallon, 40,000
Btu/hr. Models
Model
40 Gallon, 40,000
& 38,000 Btu/hr.
Models
2 7 2 30 9 90° Elbows Concentric
3 7 2 60 18 90° Elbows Concentric
From 6,000 Ft. (1,828 m) Above Sea Level through 7,700 Ft. (2,347 m) Above Sea Level
Vent & Combus-
tion Air-Inlet
System Diameter
Inches Feet Meters Feet Meters
2 7 2 15 4.5 90° Elbows
2 7 2 30 9 Concentric
3 7 2 60 18 90° Elbows Concentric
2 7 2 15 4.5
3 7 2 60 18 90° Elbows Concentric
From 7,701 Ft. (2,347 m) Above Sea Level through 10,200 Ft. (3,109 m) Above Sea Level
Vent & Combus-
tion Air-Inlet
System Diameter
Inches Feet Meters Feet Meters
2 7 2 15 4.5 Concentric
3 7 2 60 18 90° Elbows Concentric
Min. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Min. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Max. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Max. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Vent and Combustion Air-Inlet System
Termination(s)
Vent and Combustion Air-Inlet System
Termination(s)
50 Gallon, 40,000
Btu/hr. Models
14
3 7 2 60 18 90° Elbows Concentric
Page 15
Maximum and Minimum Vent and Combustion Air-Inlet Lengths For Power Direct Vent Models:
50 Gallon With Inputs of 65,000 & 47,000 BTU/Hr. 65 Gallon With Inputs of 65,000 & 56,000 BTU/Hr. 75 Gallon With Inputs of 75,100 & 70,000 BTU/Hr.
Connect the vent system piping to the blower assembly using the already installed 3 in. (7.6 cm) diameter rubber coupling and clamps. Connect the combustion air-inlet system piping to the combustion air-inlet piping tee using the 3 in. (7.6 cm) already installed rubber coupling and clamps (See Figure 3). For vent and combustion air-inlet terminals, use the two (2), 3 in. (7.6 cm) diameter, Schedule 40, PVC, 90°, 1/4 standard bend elbows and wire mesh screen assemblies supplied with the water heater.
This water heater may also be installed with 4 in. (10.2 cm) diameter pipe and fittings for the vent and combustion air-inlet systems. When using 4 in. (10.2 cm) diameter pipe, two (2), 3 in. (7.6 cm) to 4 in. (10.1 cm) diameter pipe increaser fittings are required for connection of the vent system piping to the blower assembly and combustion air-inlet system piping to the combustion air-inlet piping tee couplings (See Figure 4). For vent and combustion air-inlet terminals, 4 in. (10.1 cm) diameter, Schedule 40, PVC, 90°, 1/4 standard bend elbows (not supplied) along with the two (2) wire mesh screens (supplied) must be installed.
DO NOT use unequal sizes except as defined previously for the vent and combustion air-inlet systems.
IMPORTANT: Ensure that all the coupling clamps are firmly tight, then leak test the vent sys­tem joints using a soap and water solution. Repair any leak before allowing the water heater to oper­ate.
When using CPVC or ABS pipe and fittings, use 90° elbows of the corresponding size and material for the vent and combustion air-inlet terminals. Install supplied wire mesh screens into the CPVC or ABS vent and combustion air-inlet terminal elbows.
The vent and combustion air-inlet terminals of the water heater must be installed in the same atmo­spheric pressure zone.
The minimum and maximum equivalent lengths for the vent and combustion air-inlet systems are shown in Table 2. Maintain a minimum vertical height of 1 foot (3.5 cm) of pipe from the blower exhaust before transitioning in any elbow. The vent and combustion air-inlet terminations are not included in the equivalency calculations.
Notice: One (1), 90°, 1/4 standard bend elbow is equivalent to 5 feet (1.52 meters) of straight pipe and quantity one (1), 45°, 1/8 standard bend elbow is equivalent to 2.5 feet (0.76 meters) of straight pipe.
DO NOT use short bend elbows.
3 in.
(7.6 cm)
Figure 3
Vent
Combustion Air-Inlet
3 in.
(7.6 cm)
3 in. (7.6 cm)
Figure 4
Vent
4 in. (10.2 cm)
Combustion Air-Inlet
4 in. (10.2 cm)
3 in. (7.6 cm)
15
Page 16
Installing the Water Heater
Table 2
Model
50 Gallon, 65,000 &
47,000 Btu/hr. Models
65 Gallon, 65,000 &
56,000 Btu/hr. Models
75 Gallon, 75,100
&70,000 Btu/hr. Models
From Sea Level through 2,000 ft. (609 m) Above Sea Level
Vent &
Combustion
Air-Inlet System
Diameter
3 7 2 55 17 90° Elbows Concentric
4 7 2 100 30 90° Elbows
3 8 2.5 60 18 90° Elbows
3 8 2.5 50 15 Concentric
4 8 2.5 100 30 90° Elbows
3 8 2.5 50 15 90° Elbows
3 8 2.5 40 12 Concentric
4 8 2.5 100 30 90° Elbows
Min. Allowed
Equivalent Vent &
Combustion Air-Inlet
Lengths (Each Pipe
Run)
Max. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Vent and Combustion Air-Inlet
System Termination(s)Inches Feet Meters Feet Meters
From 2,000 Ft. (609 m) Above Sea Level through 5,999 Ft. (1,828 m) Above Sea Level
Model
50 Gallon, 65,000 &
47,000 Btu/hr. Models
65 Gallon, 65,000 &
56,000 Btu/hr. Models
75 Gallon, 75,100 &
70,000 Btu/hr. Models
Vent &
Combustion
Air-Inlet System
Diameter
3 7 2 55 17 90° Elbows Concentric
4 7 2 100 30 90° Elbows
3 8 3 40 12 90° Elbows
3 8 3 30 9 Concentric
4 8 3 100 30 90° Elbows
3 8 3 25 8 90° Elbows
3 8 3 20 6 Concentric
4 8 3 100 30 90° Elbows
Min. Allowed
Equivalent Vent &
Combustion Air-Inlet
Lengths (Each Pipe
Run)
Max. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Vent and Combustion Air-Inlet
System Termination(s)Inches Feet Meters Feet Meters
16
Page 17
Table 2 - Continued
From 6,000 Ft. (1,829 m) Above Sea Level through 7,700 Ft. (2,347 m) Above Sea Level
Model
50 Gallon, 65,000 &
47,000 Btu/hr. Models
65 Gallon, 65,000 &
56,000 Btu/hr. Models
75 Gallon, 75,100
&70,000 Btu/hr. Models
From 7,701 Ft. (2347 m) Above Sea Level through 10,200 Ft. (3,109 m) Above Sea Level
Model
50 Gallon, 65,000 &
47,000 Btu/hr. Models
Vent &
Combustion
Air-Inlet System
Diameter
3 7 2 55 16.5 90° Elbows
3 7 2 45 13.5 Concentric
4 7 2 100 30 90° Elbows
4 8 3 50 15 90° Elbows
4 8 3 50 15 90° Elbows
Vent &
Combustion
Air-Inlet System
Diameter
3 7 2 70 12 90° Elbow
3 7 2 35 10.5 Concentric
4 7 2 100 30 90° Elbow
Min. Allowed
Equivalent Vent &
Combustion Air-Inlet
Lengths (Each Pipe
Run)
Min. Allowed
Equivalent Vent &
Combustion Air-Inlet
Lengths (Each Pipe
Run)
Max. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Max. Allowed Equivalent
Vent & Combustion Air-
Inlet Lengths (Each Pipe
Run)
Vent and Combustion Air-Inlet
System Termination(s)Inches Feet Meters Feet Meters
Vent and Combustion Air-Inlet
System Termination(s)Inches Feet Meters Feet Meters
17
Page 18
Installing the Water Heater
Direct Vent Terminal Clearances
D
E
V
B
V
L
F
V Vent Terminal X Air Supply Inlet Area Where Terminal Is Not Permitted
A = Clearance above grade, veranda, porch,
deck or balcony
B = Clearance to window or door that may be
opened
C = Clearance to permanately closed window *
D = Vertical clearance to ventilated soft lo-
cated above the terminal within a horizontal distance of 2 feet (61 cm) from the center line of the terminal
E - Clearance to unventilated soft *
F - Clearance to outside corner *
G - Clearance to inside corner *
H - Clearance to each side of centerline extend-
ed above meter/regulator assembly
I - Clearance to service regulator vent outlet *
J - Clearance to nonmechanical air supply inlet
to building or the combustion air inlet to any other appliance
K - Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m) horizontally
L - Clearance above paved sidewalk or paved
driveway located on public property
M - Clearance under veranda, porch, deck, or
balcony
1
In accordance with the current ANSI Z223.1/ NFPA 54 National Fuel Gas Code
* For clearances not specied in ANSI Z223.1/ NFPA 54 the following statement shall be included:
"Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's installation
instructions".
G
v
A
B
C
FIXED
v
CLOSED
ERAB
P
O
v
B
B
LE
US Installations
B
FIXED
CLOSED
PERABLE
O
v
v
J
B
A
1
H
X
v
I
X
v
K
M
12 inches (30 cm)
6 inches (15 cm) for appliances ≤ 10,000 Btuh (3 kW), 9 inches (23 cm) for appliances > 10,000 Btuh (3kW) and ≤
50,000 Btuh (15 KW), 12 inches (30 cm) for appliances> 50,000 Btuh (15 kW)
*
*
6 inches (15 cm) for appliances ≤ 10,000 Btuh (3 kW), 9 inches (23 cm) for appliances > 10,000 Btuh (3kW) and ≤
50,000 Btuh (15 KW), 12 inches (30 cm) for appliances> 50,000 Btuh (15 kW)
*
*
18
Page 19
Additional Considerations
If soffit vent is too close, block off and install new vent at another location
Inside corner
Caulk
Caulk
Caulk
6 ft. (1.8 m) Caulk zone or to edge of window etc., starting within 6 ft. (1.8 m)
Rising moisture will collect under eves
4 ft.'
6 ft. (1.8 m) Caulk zone
6 ft. (1.8 m)
Vent
Combustion
DO NOT install the vent terminal under any patio or deck.
To help prevent moisture from freezing on walls and under
eaves, do not locate the vent terminal on the side of a build­ing with prevailing winter winds.
When terminating the vent and combustion air-inlet pipes
through brick or masonry surfaces, the installation of a rust­resistant sheet metal backing plates behind the vent and com­bustion air-inlet terminals are recommended.
DO NOT locate the vent terminal too close to shrubbery, as
flue gasses may damage them.
Caulk all cracks, seams and joints within six feet (1.83
meters) of the vent and combustion air-inlet terminals.
Insulate vent pipe exposed to cold conditions (attics, crawl
WARNING: Moisture in the flue gas will condense as it leaves the vent terminal. In cold weather this condensate can freeze on the exterior wall, under the eaves and on surrounding objects. Some discoloration to the exterior of the building is to be expected. However, improper location or installation can result in severe damage to the structure or exterior finish of the building
spaces, etc.) with inflammable material to help prevent moisture from accumulating in the vent pipe.
Support horizontal sections of the vent and combustion
air-inlet pipe every 4 feet (1.22 meters). DO NOT rigidly secure the vent system. Provisions must be made to allow for expansion and contraction of the vent system.
Horizontal Vent and Combustion Air-Inlet Terminal Installation
Determine the locations for the vent and combustion air-inlet termi­nals then make two (2) holes through the exterior wall to accommo­date the vent and combustion air-inlet pipes. Maintain a minimum distance of 12 in. (30.5 cm) between the vent and combustion air-inlet terminal centerlines.
Insert lengths of vent and combustion air-inlet pipes through the wall as shown. Allow sufficient length of pipe to extend beyond the exte­rior wall of the building for attachment of the vent and combustion air-inlet terminals.
Place the supplied ½ in. (1.3 cm) mesh metal screens inside each ter­minal fitting and connect the terminals to the vent and combustion air­inlet pipes which are extending out of the building. Ensure that the back of the supplied terminals are flush with the outside wall surface.
Complete the installation of the remainder of the vent system and attach it to the vent connector fitting on the water heater’s blower assembly. Horizontal lengths of the vent system must slope down­ward away from the water heater a minimum of 1/8 in. per foot (10 mm per meter).
Complete the installation of the remainder of the combustion air-inlet system and attach it to the combustion air-inlet connector fitting on the water heater’s combustion air-inlet tube assembly. Horizontal lengths of the combustion air-inlet system must slope downward away from the water heater a minimum of 1/8 in. per foot (10 mm per meter).
Support vertical and horizontal lengths of the vent and combustion air-inlet systems as previously mentioned.
For 75 Gallon Power Direct Vent Models ONLY:
These water heater models are supplied with two (2) vent and com­bustion air-inlet termination restrictors. These restrictors help the water heater achieve peak efficiency when the water heater is installed using 3 in. (7.6 cm) diameter pipe at the minimum equivalent vent
and combustion air-inlet lengths specified in Table 2. The termination restrictors must be installed in the same location as the supplied vent and combustion air-intake terminal screens. IMPORTANT: Do not install the termination restrictors in equivalent vent and/or combus­tion air-inlet lengths longer than 8 feet (2.44 meters) or on any other Power Direct Vent model.
Vent and/or combustion air inlet
Pipe
From Water Heater
Inside of Building
12 in. (30.5 cm) Min.
Exhaust Vent Terminal
Outside of Building
2' x 2' (60 m x 60 m) Sheet Metal Shield on Brick or Masonry Walls
Terminals with ½” Mesh Protective Screen and Termination Restrictor Inside. Note: Termination Restrictors used on 75 Gallon models ONLY.
Combustion Air­Inlet Terminal
19
Page 20
Installing the Water Heater
Vertical Vent and Combustion Air-Inlet Installation
Combustion Air-Inlet
Min. 12 in. (30.5 cm) Above Roof
Min. 12 in .(30.5 cm ) Above Anticipated Snow Level.
Max. 24 in. (61 cm) Above Roof (Without Additional Support)
Exhaust Vent
Terminals with ½” Mesh Protective Screen and Termination Restrictor Inside. Note: Termination Restrictors used on 75 Gallon models ONLY.
Short Piece of Pipe
Vent Pipe or Combustion
Air-Inlet
Through Roof
Elbow
Vent and/or Combustion Air-Inlet Terminal
The location of the vent and combustion air-inlet termi­nals depends on the following minimum clearances and considerations.
Minimum 12 in. (30.5 cm) above roof.
Minimum 12 in. (30.5 cm) above anticipated snow
level.
Maximum 24 in. (61cm) above roof level without
additional support for vent.
Four (4) ft. (1.22 m) from any gable, dormer or other
roof structure with building interior access (i.e., vent, window, etc.).
Ten (10) ft. (3.05m) from any forced air inlet to the
building. Any fresh or make-up air inlet such as a dryer or furnace area is considered to be a forced air inlet.
Maintain a minimum distance of 12 in. (30.5 cm)
between the vent and combustion air-inlet terminal cen­terlines.
Important: The vent terminal must not terminate below the combustion air-inlet terminal.
20
Determine the locations for the vent and com­bustion air-inlet terminals then make two (2) holes through the roof and interior ceiling(s) to accommodate the vent and combustion air­inlet pipes. Maintain a minimum distance of 16 in. (40.6 cm) between the vent and com­bustion air-inlet terminals.
Install the vent system and attach it to the vent connector fitting on the water heater’s blower assembly. Horizontal lengths of the vent system must slope downward away from the water heater a minimum of 1/8 in. per foot (10 mm per meter).
Install the combustion air-inlet system and attach it to the combustion air-inlet connector fitting on the water heater’s combustion air­inlet tube assembly. Horizontal lengths of the combustion air-inlet system must slope down­ward from the water heater a minimum of 1/8 in. per foot (10 mm per meter).
Support vertical and horizontal lengths of the vent and combustion air-inlet systems as pre­viously mentioned.
Determine the vent and combustion air-inlet terminal heights and cut the pipe accordingly.
Insert lengths of vent and combustion air­inlet pipes through the ceiling wall as shown. Install adequate flashing where the vent and combustion air-inlet pipes pass through the roof.
Place the supplied ½ in. (1.3 cm) mesh metal screens inside each terminal fitting then con­nect a short piece of pipe approximately 3 in. (7.6 cm) to the terminals and elbows.
For 75 Gallon Power Direct Vent Models ONLY:
These water heater models are supplied with two (2) vent and combustion air-inlet termina­tion restrictors. These restrictors help main­tain the efficiency of the water heater when installed using 3 in. (7.6 cm) diameter pipe at the minimum equivalent vent and combus­tion air-inlet lengths specified in Table 2. The termination restrictors must be installed in the same location as the supplied vent and combustion air-intake terminal screens. IMPORTANT: Do not install the termination restrictors in equivalent vent and/or combus­tion air-inlet lengths longer than 8 feet (2.44 meters) or on any other Power Direct Vent model.
Page 21
Horizontal Vent- Alternate Concentric, and Combustion Air-Inlet Terminal Installation:
Kit information, see If You Need Service section.
Determine the location for the concentric vent and com­bustion air-inlet terminal then make a hole through the exterior wall to accommodate the terminal (see Figure 5).
Insert the concentric vent and combustion air-inlet ter­minal assembly through the wall as shown. Ensure that
the back of the supplied terminal is ush with the outside
wall surface.
Complete the installation of the remainder of the vent
system and attach it to the vent connector tting on the
water heater’s blower assembly. Horizontal lengths of the vent system must slope downward away from the water heater a minimum of 1/8 in. per foot (10 mm per meter).
Contact Manufacturer's National Service Department for
Complete the installation of the remainder of the combus­tion air-inlet system and attach it to the combustion air-inlet connector tting on the water heater’s combus­tion air-inlet tube assembly. Horizontal lengths of the combustion air-inlet system must slope downward away from the water heater a minimum of 1/8 in. per foot (10 mm per meter). The terminal may be installed with the Combustion Air-inlet Connection orientated in any posi­tion from upward vertical (see Figure 5) to 90° horizontal (see Figure 6). DO NOT install the terminal with the Combustion Air-Inlet Connection angled downward.
Support vertical and horizontal lengths of the vent and combustion air-inlet systems as previously mentioned.
Combustion Air-Inlet
Connection
Vent
Connections
Figure 5
Combustion Air-Inlet
Connection
Vent
Connections
Figure 6
Vertical Vent - Alternate Concentric, and Combustion Air-Inlet Installation:
Contact Manufacturer's National Service Department for Kit information, see If You Need Service
section.
Terminals with ½” Mesh Protective Screen and Termination Restrictor Inside. Note: Termination Restrictors used on 75 Gallon models ONLY.
Short Piece of Pipe
NOTICE: All pipe, fittings, solvent cement, primers and procedures must conform to American National Standards Institute and American Society for Testing and Materials (ANSI/ASTM) standards.
The location of the vent and combustion air-inlet terminals depends on the following minimum clearances and considerations.
Vent
Min. 12 in. (30.5m) Above Roof
Min. 12 in. (30.5m) Above Above Anticipated Snow Level
Max. 24 in. (61 cm) Above Roof (Without Additional Support)
18
Concentric Vent and
Combustion Air-Inlet
Through Roof
Minimum 12 in. (30.5 cm) above roof.
Minimum 12 in. (30.5 cm) above anticipated snow level.
Maximum 24 in. (61 cm) above roof level without additional
support for vent.
Four feet (1.22 m) from any gable, dormer or other roof struc-
ture with building interior access (i.e., vent, window, etc.).
Ten (10) ft. (3.05 m) from any forced air inlet to the building.
Any fresh or make-up air inlet such as a dryer or furnance area is considered to be a forced air inlet.
Important: The vent terminal must not terminate below the combustion air-inlet terminal.
21
Page 22
Installing the Water Heater
Determine the location for the concentric vent and combustion air-inlet terminal then make a hole through the roof and interior ceiling(s) to accommodate the terminal, vent and combustion air-inlet system pipes. Insert the concentric vent and combustion air-inlet terminal assem­bly through the roof and interior ceiling(s) as shown. Install the vent system and at-
tach it to the vent connector tting on the
water heater’s blower assembly. Horizon­tal lengths of the vent system must slope downward away from the water heater a minimum of 1/8 in. per foot (10 mm per meter). Install the combustion air-inlet system and attach it to the combustion
air-inlet connector tting on the water
heater’s combustion air-inlet tube assem­bly. Horizontal lengths of the combustion air-inlet system must slope downward
from the water heater a minimum of 1/8 in. per foot (10 mm per meter). Support vertical and horizontal lengths of the vent and combustion air-inlet systems as previ­ously mentioned. Determine the vent and combustion air-inlet terminal heights and cut the pipe accordingly. Refer to Figure 9 for the proper terminal heights. Insert lengths of vent and combustion air-inlet pipes through the ceiling wall as shown.
Install adequate ashing where the vent
and combustion air-inlet pipe passes through the roof. Place the supplied ½ in. (1.3 cm) mesh metal screens inside the
terminal tting then connect a short piece
of pipe approximately 3 in. (7.6 cm) to the terminal and elbows.
WARNING: DANGER OF FIRE OR BODILY INJURY - Solvent cements and primers are highly flammable. Provide adequate ventilation and do not assemble near heat source or open flame. Do not smoke. Avoid skin or eye contact. Observe all cautions and warnings on material containers.
CAUTION: For proper installation:
DO NOT use solvent cement that has become curdled, lumpy or thickened.
DO NOT thin solvent cement. Observe shelf precautions printed on the containers.
For applications below 32°F (0°C) use only low temperature type solvent cement.
Appropriate solvent and cleaner must be used for the type of pipe used (PVC, CPVC or ABS).
Cementing Joints
All joints in the vent piping must be properly sealed and the following materials are recommended:
PVC materials should use ASTM D2564 grade cement.
CPVC materials should use ASTM F493 grade cement.
ABS materials should use ASTM D2235 grade cement.
Cleaner-Primer and Medium Body Solvent Cement:
Cut pipe end square, remove jagged
edges and burrs. Chamfer end of pipe, then clean fitting socket and pipe joint area of all dirt, grease or moisture.
After checking pipe and socket for
proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of primer to inside surface of socket and outside of pipe. Do not allow primer to dry before applying cement.
Apply a thin coat of cement evenly
in the socket. Quickly apply a
heavy coat of cement to the pipe end and insert pipe into fitting with a slight twisting motion until it bot­toms out.
NOTICE: Cement must be fluid; if not, recoat.
Hold the pipe fitting for 30 seconds
to prevent the tapered socket from pushing the pipe out of the fitting.
Wipe all excess cement from the
joint with a rag. Allow 15 minutes before handling. Cure time will vary according to fit, temperature and humidity.
NOTICE: Stir the solvent cement frequently while using. Use a natural bristle brush or the dauber supplied with the can.
NOTICE: This unit is equipped with a Flammable Vapor Sensor. Do not apply power until enough time has passed to allow the vapors from the primer and cement to dissipate.
22
Page 23
Wiring
If local codes permit, the water heater may be connected to electric service with the power cord provided (DO NOT use an extension cord). A grounding receptacle is required.
If local codes do not permit the use of cord connections, a 120 V, 50/60 Hz power supply, with suitable disconnecting means, must be connected to the black and white leads in the heater control enclosure.
The maximum current draw is less than
5.0 amps.
The water heater must be electrically grounded in accordance with local codes, or, in the absence of local codes, in accor­dance with latest edition of the National Electric Code ANSI/NFPA No. 70. Refer to the figures below for water heater inter­nal wiring.
CONNECTOR DIAGRAM SCHÉMA DES CONNEXIONS
120 VAC PLUG FOR POWERVENT BLOWER ASSEMBLY PRISE DE 120 VCA POUR L’ENSEMBLE DE SOUFFLEUR D’ÉVENT MÉCHANIQUE
BLOWER SOUFFLEUR
POWER VENT BLOWER ASSEMBLY ENSEMBLE DU SOUFFLEUR D’ÉVENT MÉCANIQUE
GAS VALVE
SOUPAPE DE GAZ
GND
INTELLI-VENT ELECTRONIC CONTROL
ANY REPLACEMENT IGNITOR CABLE MUST BE RATED AT 250º C TOUT CÂBLE D’ALLUMAGE DE REMPLACEMENT DOIT ÊTRE ÉTALONNÉ Á 250º C
H G N
TEMPERATURE SWITCH NC CHANGEMENT DE
MOT
TEMPÉRATURE
SCREW GND VIS DE MISE À LA TERRE
FLAMMABLE VAPOR SENSOR DÉTECTEUR DE VAPEUR INFLAMMABLE
FV
W
1
BK
2
BK
3
W
4
J2
BL
1
1
2
2
R
3
3
R
4
4
Y
5
5
W
6
6
CONTRÔLE ÉLECTRONIQUE INTELLI-VENT
G
BK G W
VAC
VAC
SW NO
SW NC CONTACTEUR À DÉPRESSION
6 PIN CONNECTOR CONNECTEUR À 6 BROCHES
IGNITER AND FLAME SENSOR ALLUMEUR ET CAPTEUR DE FLAMME
W
N/C
WIRE HARNESS THAT RUNS FROM BLOWER ASSEMBLY TO WIPER CONTROL GAS VALVE FAISCEAU DE CÂBLAGE ENTRE L’ENSEMBLE DU SOUFFLEUR ET LA INTELLI-VENT DE LA SOUPAPE DE CONTRÔLE DU GAZ
ON/OFF SWITCH CONTACTEUR MARCHE/ARRÉT
BK R Y BL G
W
1 2 3 4 5 6
1 2 3 4 5 6
W R R Y BL G
H
ON/OFF SWITCH CONTACTEUR MARCHE/ARRÉT
NOTE: IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH A 18 GA, 600 V, 105º C WIRE. REMARQUE: SI UNE PARTIE QUELCONQUE DU CÂBLAGE ORIGINAL
H N
FOURNI AVEC L’APPAREIL DOIT ÊTRE REMPLACÉE, ELLE DOIT ÊTRE REMPLACÉE AVEC UN FIL DE CALIBRE 18, 600 VCA, 105º C.
SCHEMATIC DIAGRAM SCHÉMA DE CABLÂGE
120 VAC
IGNITER ALLUMEUR
W
1
W
BK
2
3
4
BL
1
N/C
2
R
3
GAS VALVE
SOUPAPE DE GAZ
R
4
Y
5
W
INTELLI-VENT ELECTRONIC CONTROL
CONTRÔLE ÉLECTRONIQE INTELLI-VENT
6
BK = BLACK/NOIR BL = BLUE/BLEU G = GREEN/VERT R = RED/ROUGE W = WHITE/BLANC Y = YELLOW/JAUNE
FLAMMABLE VAPOR SENSOR
BK
DÉTECTEUR DE VAPEUR INFLAMMABLE
W
TEMPERATURE SWITCH NC CHANGEMENT DE TEMPÉRATURE
MOT
FLAME SENSOR CAPTEUR DE FLAMME
VAC SW NO
CONTACTEUR À DÉPRESSION
BLOWER SOUFFLEUR
GND
VAC SW NC
N
CAUTION! Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING!
23
Page 24
Installing the Water Heater
Insulation Blankets
Insulation blankets, available to
WARNING: If local codes require external application of insulation blanket kits the manufacturer’s instructions included with the kit must be carefully followed.
the general public, for external use on gas water heaters are not neces­sary. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. This water heater meets or exceeds the National Appliance Energy Conservation Act standards with respect to insulation and stand­by loss requirements making an insulation blanket unnecessary.
The manufacturer’s warranty does not cover any damage or defect caused by installation, attachment or use of any type of energy saving or other unapproved devices (other than those authorized by the manufactur­er) into, onto or in conjunction with the water heater. The use of unau­thorized energy saving devices may shorten the life of the water heater and may endanger life and property.
The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unau­thorized devices.
CAUTION: If local codes require the application of an external insulation blanket to this water heater, pay careful attention to the following so as not to restrict the proper function and operation of the water heater:
Do not cover the operating or
warning labels attached to the water heater or attempt to relo­cate them on the exterior of insu­lation blanket.
Do not apply insulation to the top
of the water heater. This will inter­fere with the safe operation of the blower assembly.
Do not cover the burner access
door, jacket door, gas control (thermostat)/gas valve or pressure and temperature relief valve.
Do not apply insulation to the
area where the Flammable Vapor Sensor is located. This area must be unobstructed so as not to restrict air flow to the sensor.
Inspect the insulation blanket fre-
quently making certain it has not sagged and it is not restricting the air flow to the Flammable Vapor sensor located around the lower perimeter of the water heater jack­et. This could result in an unsafe operating condition.
24
Hot and Cold Pipe Insulation Installation
Typical vertical piping arrangement
For increased energy efficiency, some water heaters have been sup­plied with two 24 in. (61 cm) long sections of
Typical horizontal piping arrangement
pipe insulation. Please install the insulation, accord­ing to the illustrations above, that best meets your requirements.
Page 25
Heat Traps
VACATION
VERY HOT
WARM
A B C
COOLER
HOTTER
For increased energy efficiency, some water heaters have been supplied with fac­tory installed 3/4” NPT heat traps in the hot outlet line and cold water inlet line.
These heat traps may require a minimum of one (1) 90° 3/4” NPT elbow and may require an additional 90° 3/4” NPT elbow or a 3/4” coupling depending on your installation needs. See Illustration of nipples and heat traps on page 35.
During Installation of this water heater...........
DO
DO check inlet gas pressure to ensure
that it is within the range specified on the rating plate.
DO maintain proper clearances to com-
bustibles as specified on the rating plate.
DO allow enough time for joint cement vapors to dissipate BEFORE applying power to the water heater.
DO ensure that the venting system com­plies with the guidelines found in the Use and Care Manual and National Fuel Gas Code.
DO contact a qualified service techni­cian if the main burner will not stay lit. The burner chamber is designed to be sealed uti­lizing a gasket and tamper resistant screws.
Burner Access Door Grommet
Flammable Vapor Sensor
Sight Glass
DON’T
DON’T block or restrict the Flammable Vapor Sensor located around the lower por­tion of the water heater jacket.
DON’T remove the Burner Access Door unless absolutely necessary. This should only be done by a qualified service techni­cian. A new burner access door gasket must be installed on any burner access door that has been removed.
DON’T install this water heater where standing water may occur. The base of the water heater is meant to be mounted on a dry surface.
❑ DON’T allow cleaners, solvents, or other
materials to come into contact with the Flammable Vapor Sensor.
❑ DON’T operate the water heater if the
sight glass or burner access door grommet is damaged or broken (see to the left).
25
Page 26
Installation Checklist
A. Water Heater Location
In a location where the vent and combustion
air-inlet systems will be within the requirements specified in this manual.
Indoors and protected from freezing tempera­tures.
Proper clearance from combustible surfaces observed and water heater not installed on car­peted floor.
Air supply free of corrosive elements and flam­mable vapors.
B. Water Supply
Water heater completely filled with water.
Air purged from water heater and piping.
C. Gas Supply
Gas line equipped with shut-off valve, union and sediment trap.
Approved pipe joint compound used.
Provisions made to protect area from water damage.
Sufficient room to service the water heater.
Combustible materials, such as clothing, clean­ing materials, rags, etc. clear of the base of the water heater.
Flammable vapor sensor is not blocked.
Water connections tight and free of leaks.
Soap and water solution used to check all con­nections and fittings for possible gas leak.
Gas Company inspected installation (if required).
D. Relief Valve
Temperature and Pressure Relief Valve properly installed and discharge line run to open drain.
Discharge line protected from freezing.
E. Venting and Combustion Air-Inlet Systems
Water Heater vented separately from all other appliances.
Flue baffle properly hung in top of water heater’s flue.
Blower assembly properly installed.
Proper materials and techniques used in the
installation of the vent and combustion air-inlet systems.
Vent pipe properly secured to the exhaust connec-
tor of the blower assembly.
Vent and combination air-inlet systems supported
at required intervals.
Appropriate minimum clearances observed.
Precautions taken to prevent moisture damage
around vent termination.
Vapors from non-metalic pipe cement and primer have dissipated prior to applying electri­cal power.
F. Wiring
Correct power supply (120 VAC).
Electrical connections tight.
Water Heater properly grounded and proper
polarity observed.
26
Page 27
Supplemental Instructions for Gas Water Heaters
Vacuum Relief Valve
(Not Supplied)
If required, install per local codes
and valve manufacturer’s
instructions.
Installed in Potable Water/Space Heating Applications
Local codes or plumbing authority requirements may vary from the instructions or diagrams provided in this manual and take precedent over these instructions.
Hot water
Combination Potable Water and Space Heating Application
supply to house
Hot water supply to heating unit
From HOT
outlet on
water heater
Tee fitting for vertical hot water supply lines.
Hot water supply to house
From HOT
outlet on
water heater
Hot water supply to heating unit
Tee fitting for horizontal hot water supply lines.
Typical Piping Diagram for Combination Potable/Space Heating Installation
Nominal 3/4" size mixing or tempering valve (refer to warning above). Follow mixing or tempering valve manufacturer’s instructions for installation of the valve.
Spring loaded check valve in heating unit hot water supply line and cold water return
line (not supplied with water heater)
NOTE: This check valve is incorporated
in some heating units. Refer to the
installation instructions supplied with
specific heating unit to determine if it is
Isolation valve in hot water supply line
to heating unit (not supplied with water
See diagrams above for proper
pipe application for vertical
or horizontal supply lines.
Temperature and Pressure Relief
Valve, tie to location approved by
required.
heater)
local code
Minimum of 2 ft. (61 cm) developed length of 3/4" pipe.
Tee fitting must be installed as shown. This ensures that any air in the water lines will be purged through the domestic water faucets and showers.
DANGER: When this system requires water for space heating at elevated temperatures (above 125°F [52°C.]), a mixing or tempering valve must be installed in the hot water supply line to the house in order to reduce the scald hazard potential.
DANGER: Any piping or components used in the installation of this water heater in a combination potable and space heating application must be suitable for use with drinking water.
3/4" Tempered domestic hot water
Air vent
3/4" Shut­Off Valve (Typ.)
supply to house.
Heat Trap 6 in. (15.2 cm) Min.
3/4" Shut-Off Valve (Typ.)
2 Gallon Thermal Expansion Tank (if required-not supplied with water heater)
140° F (60° C)
120° F to 130° F
49° C to 54° C
DANGER: If this water heater is installed in an application intended to supply domestic hot water needs and hot water for space heating purposes, do not connect the heater to an existing heating unit or components of a heating system that have previously been used with a non drinking water system. Toxic chemicals such as those used for boiler treatment may be present and will contaminate the drinking water supply causing possible health risks. Never introduce toxic chemicals, such as those used for boiler treatment, into this system.
Notice: 50 ft. (15.2 m) maximum
distance from water heater to fan coil (developed length) is required for Massachusetts State.
Pressure Gauge
3/4" Check Valve with 1/8" Hole
3/4" Shut-Off Valve (Typ.)
3/4" cold water supply
Hot water to space heater
Hot water coil
All bronze pump.
Check valve internal in pump.
Air bleed valve.
Water Sample Tap.
Water Heater to be in accordance with the Local and State Energy Code
All water piping shall be insulated in accordance with Local and State Energy Code.
Gas line to water heater
Temperature and pressure relief
Water Heater drain pan installed in
accordance with the Local and State
valve discharge line
Gas Control (Thermostat)
Code
22
Gas Fired
Water Heater
Isolation valve in cold water return line from heating unit (not supplied with water heater)
Gas Direct Vent discharge must comply with Local and State Codes
6 in. (15.2 cm) Air Gap
3/4" HWS & HWR to Heating Coil.
Drain valve (not supplied with water heater)
To HVAC Unit.
T
Air Handler
Electronically controlled pump timer. Activates every 6 hours for 60 seconds. Wire to bronze pump.
27
FAN ON OFF HEAT COOL
Page 28
Lighting the Water Heater
FOR YOUR SAFETY READ BEFORE OPERATING
OPERATING INSTRUCTIONS
TO TURN GAS OFF TO THE APPLIANCE
WARNING:
If you do not follow these instructions and the Use & Care Manual instructions exactly, a re or explosion may result causing property damage, personal injury or loss of life.
If you cannot reach your gas supplier, call the re department.
C.
Do not use this appliance if any part has been under water. Immediately call a qualied installer or service agency to replace a ooded water heater. Do not attempt to repair the unit! It must be replaced!
Use only your hand to push in the gas control buttons. Never use tools. If the control buttons will not push in, don’t try to repair them, call a qualied service technician. Force or attempted repair may result in re or explosion.
D.
gas supplier’s instructions.
10.
11.
1.
2.
3.
VACATION
WARNING
VERY
HOT
WARM
A B C
COOLER
HOTTER
This appliance does not have a pilot. It is equipped with an ignition device which auto­matically lights the burner. Do NOT try to light
the burner by hand.
A.
BEFORE PUTTING THIS APPLIANCE INTO SERVICE - Smell all around the appliance area for gas. Be sure to smell next to the oor because some gas is heavier than air and will settle on the oor.
B.
Immediately call your gas supplier from a neighbor’s phone. Follow the
Do not try to light any appliance. Do not touch any electric switch; do not use any phone in your building.
WHAT TO DO IF YOU SMELL GAS
Turn o all elec trical power to the appliance.
Set the thermostat to the lowest setting by rst depressing the COOLER and HOTTER buttons at the same time and holding for (1) second. Depress the COOLER button until only the WARM indicator light is lit.
Stop! Read the safety information above on this label.
Toggle the “ON/OFF” switch located on th e
blower assembly to the “OFF” position. Turn o all electrical powe r to the appliance. This appliance is equipped with a Hot
Surface Ignition System which auto­matically lights the burner. Do NOT open
the inner door of this appliance and try to light the burner by hand!
Wait ve (5) minutes to clear out any gas. If you smell gas, STOP! Follow “B” in the safety information above on this label. If you do not smell gas, go ahead to the nex t step.
Turn on all electrical power to the appliance.
Toggle the “ON/OF F” switch located on the blower assembly to the “ON” position.
Set thermostat to the desired temperature setting by pressing the COOLER and HOT TER buttons at the same time and holding them for (1) second. Depress the HOT TER button until the desired temperature display setting is lit. The preferred starting point for temperature setting is indicated by on the the rmo stat.
If the appliance will not operate, follow the instructions “TO TURN OFF GAS TO APPLIANCE” and call your service technician or gas supplier.
1.
4.
3.
5.
6.
7.
8.
9.
 
Set the thermostat to the lowest setting by pressing the COOLER and HOTTER buttons at the same time and holding them for (1) second. Depress the COOLER button until only the WARM indicator light is lit.
Toggle the “ON/OFF” switch located on the blower assembly to the “OFF” position.
Toggle the “ON/OF F” switch located on the blower assembly to the “ON” position.
2.
Before operating this water heater, be sure to read and follow the instructions on the label pictured below and all other labels on the water heater, as well as the warnings printed in this manual. Failure to do so can result in unsafe operation of the water heater resulting in property damage, personal injury, or death. Should you have any problems reading or following the instructions in this manual, STOP, and get help from a qualified person.
28
Page 29
Operating the water heater
!
CAUTION: Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a long period of time (generally two weeks or more). HYDROGEN GAS IS EXTREMELY FLAMMABLE!! To dissipate such gas and to reduce risk of injury, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipe as the water begins to flow. Do not smoke or use an open flame near the faucet at the time it is open.
Safety Precautions
Do turn off manual gas shut-off valve if water heater
has been subjected to over heating, fire, flood, physi­cal damage or if the gas supply fails to shut off.
Do Not turn on water heater unless it is completely
filled with water.
Do Not turn on water heater if cold water supply
shut-off valve is closed.
Do Not allow combustible materials such as newspa-
per, rags or mops to accumulate near water heater.
Operating Procedure
This water heater is equipped with a hot surface ignitor to light the main burner. There is no pilot light to be lit, but on initial start-up, it is recommended that the outer door be removed (leave inner door in place for safety) to view through the sight glass if the hot surface ignitor and main burner are operating properly.
Once filled with water, it is only necessary to plug the power cord in and make sure the “ON/OFF” switch located on the blower assembly is in the “ON” position to put the water heater into operation. Within seconds the hot surface ignitor should heat up, then
Do Not store or use gasoline or other flammable
vapors and liquids, such as adhesives or paint thinner, in vicinity of this or any other appliance. If such flammables must be used, open doors and windows for ventilation, and all gas burning appliances in the vicinity should be shut off including their pilot burners, to avoid vapors lighting.
NOTICE: Flammable vapors can be drawn by air currents from surrounding areas to the water heater.
If there is any difficulty in understanding or following
the Operating Instructions or the Care and Cleaning section, it is recommended that a qualified person or serviceman perform the work.
the gas valve should open and the main burner ignite. After the main burner ignites, replace the outer door. If no main burner flame is established, the gas control will go through three trials for ignition before going into a lock-out. A warning light will alert the user of this lock-out condition. If this hap­pens, refer to “Troubleshooting Guide.”
TO SHUT OFF WATER HEATER – Turn switch on the blower assembly to the “OFF” position.
Water Temperature Setting
DANGER: Hotter water
increases the Potential for Hot Water SCALDS
Households with small children, disabled, or elderly persons may require a 120°F (49°C ) or lower gas control (thermostat) setting to prevent contact with unsafe water temperatures.
.
The temperature of the water in the water heater can be regulated by pressing the buttons on the front of the gas control (thermostat).
Safety and energy conservation are factors to be considered when selecting the water temperature setting of the water heater’s gas control (thermostat(s)). The lower the temperature setting, the greater the savings in energy and operating costs.
To comply with safety regulations, the gas control (thermostat) was set at its lowest setting before the water heater was shipped from the factory. The recommended starting point temperature is 120°F (49°C).
Water temperatures above 125°F (52°C) can cause severe burns or death from scalding. Be sure to read and follow the warnings outlined in this manual and on the label located on the water heater near the gas control thermostat.
Mixing valves are available for reducing point of use water temperature by mixing hot and cold water in branch water lines. Contact a licensed plumber or the local plumbing authority for further informa­tion.
The chart on the next page may be used as a guide in determining the appropriate water temperature for your home.
29
Page 30
!
Operating the Water Heater
Water Temperature Setting
Maximum water temperatures occur just after the burn­er has shut off. To determine the water temperature, turn on a hot water faucet and place a thermometer in the water stream.
To avoid any unintentional changes in water temperature settings, the combination gas control (thermostat) has a tamper resistant feature for changing the temperature setting. To change the temperature setting follow these instructions.
1. "Wake Up" the temperature indicators by holding down both "COOLER" and "HOTTER" temperature adjustment buttons at the same time for one second, see Figure below. One or two of the temperature indicators will light up. These indicators will only remain on for 30 seconds if no further buttons are pressed. After 30 seconds the control will go back to "sleep" mode.
2. Release both of the temperature buttons.
a. To decrease the temperature press and release
the "COOLER" button until the desired setting is reached.
b. To increase the temperature press and release
the "HOTTER" button until the desired setting is reached.
NOTE: Holding down the button will not continue to lower or raise the temperature setting. The button must be pressed and released for each temperature change desired.
A condition known as “stacking” or “layering” can occur when a series of short and frequent hot water draws are taken.
The hottest temperature water will be at the top of the tank, closest to the outlet pipe delivering hot water to the home.
Stacking can cause this top layer of water to be hotter than the water toward the bottom of the tank near the combination gas control (thermostat). Therefore, always remember to test the water temperature with your hand before use and remember that hotter water increases the risk of scald injury.
Also, always supervise young children or others who are incapacitated.
The combination gas control (thermostat) is constructed with a built in safety shut-off device designed to shut off the gas supply to the burner if the main burner is extinguished for any reason.
The gas control (thermostat) is also equipped with a single use gas shut off device that will shut off the gas supply to the burner if the water heater exceeds normal operating temperatures. Refer to the Before You Call For Service section of this manual, or contact your dealer.
WARNING: Should overheating occur or the gas supply fail to shut off, turn off the manual gas control valve to the appliance.
If the water heater has been subjected to fire, flood or physical damage, turn off the manual gas control (shut­off) valve, and do not operate the water heater again until is has been checked by a qualified service techni­cian.
Time/Temperature Relationship in Scalds
Water Temperature Time To Produce a Serious Burn
120°F (49°C) More than 5 minutes
125°F (52°C) 11/2 to 2 minutes
130°F (54°C) About 30 seconds
135°F (57°C) About 10 seconds
140°F (60°C) Less than 5 seconds
145°F (63°C) Less than 3 seconds
150°F (66°C) About 11/2 seconds
155°F (68°C) About 1 second
Table courtesy of Shriners Burn Institute
VACATION
WARM
COOLER
A B C
WARNING
VERY
HOTTER
HOT
Temperature Setting
WARM = approx. 70°F (21°C)
▼ = approx. 120°F (49°C)
A = approx. 130°F (54°C)
B = approx. 140°F (60°C)
C = approx. 150°F (66°C)
C-Flashing = approx. 160°F (71°C)
Display
▼ A B C
● ○ ○ ○ ○ ○ ○ ○ ● ○ ○ ○ ○ ○ ○ ● ○ ○ ○ ○ ○ ○ ● ○ ○ ○ ○ ○ ○ ● ○ ○ ○ ○ ○ ●
Burns on Adult Skin
--------------------
More than 5 minutes
About 30 seconds
Less than 5 seconds
About 1-1/2 seconds
About 1/2 seconds
30
Page 31
Sequence of Operation
During initial start-up or a call for heat, the control will verify the vacuum switch is open.
Once the control verifies the vent pres­sure switch is open, the control will ener­gize the blower motor for the pre-purge sequence (approximately 5 seconds).
The control will verify that the vent pres­sure switch has closed, ensuring that the blower is functioning properly and that the venting system is not blocked.
The control will then proceed through a sequence of self-diagnostics before initi­ating a trial for ignition.
During the trial for ignition, the hot sur­face ignitor will warm up.
Once the hot surface ignitor warms up, the main gas valve will open allowing gas to flow to the main burner.
Once the main burner ignites, the control will verify that the burner flame is present through the flame sense circuit. The hot surface ignitor will then turn off.
The blower motor will stay energized for an additional 30 seconds after the control verifies that the burner flame is extinguished in order to clear combustion gases from the water heater.
After the post-purge sequence, the con­trol will de-energize the blower motor and go into a stand-by mode awaiting the next call for heat.
This water heater is equipped with a flammable vapor sensor that is monitored continuously by the electronic control in all modes of operation.
In the event that flammable vapors are detected, the control will automatically shut down the water heater and prevent the water heater from being started again.
The following is a list of materials that will cause the Flammable Vapor Sensor to shut down the water heater.
Vapors of Gasoline.
Vapors of certain flammable paints,
stains, and thinners.
The main burner will remain lit throughout the heat cycle until the water temperature setting is reached.
Once the water temperature setting is reached, the control will close the main gas valve which will extinguish the main burner flames.
Vapors of vent pipe Cement &
Solvents.
Bleach (direct contact with flammable
vapor sensor).
Some other flammable materials and
their vapors.
If the flammable vapor sensor shuts down the water heater, then the electronic control will display the appropriate error code and you should then promptly con­tact a qualified service technician.
Refer to the “Notice” on page 3 for addi­tional information.
31
Page 32
Care and Cleaning of the Water Heater
!
Draining the Water Heater
DANGER: Before manually operating the relief valve, make certain no one will be exposed to the danger of the hot water released by the valve. The water may be hot enough to create a scald hazard. The water should be released into a suitable drain to prevent injury or property damage.
DANGER: Hotter water increases the potential for Hot Water Scalds.
DANGER: Failure to perform the recommended Routine Preventative Maintenance can harm the proper operation of this water heater, which can cause carbon monoxide dangers, excessive hot water temperatures and other potentially hazardous conditions.
!
CAUTION: Shut off gas to the water heater at the manual gas shut-off valve before draining water.
!
DANGER: Before manually operating the temperature and pressure relief valve, make certain no one will be exposed to the hot water released by the valve. The water drained from the tank may be hot enough to present a scald hazard and should be directed to a suitable drain to prevent injury or damage.
Before turning off the cold water supply to the water heater, open a hot water faucet allowing sufficient cold water into the tank to prevent the risk of a scald injury while draining the water heater. Once the water in the tank is no longer hot, turn off the cold water supply to the water heater. Open a hot water faucet or lift the handle on the relief valve to admit air to the tank.
Attach a garden hose to the drain valve on the water heater and direct the stream of water to a drain. Open the valve.
Routine Preventative Maintenance
Properly maintained, your water heater will provide years of dependable trouble­free service.
It is recommended that a periodic inspec­tion of the gas control (thermostat), burner, relief valve, internal flue-way and venting system should be made by service person­nel qualified in gas appliance repair.
It is suggested that a routine preventative maintenance program be established and followed by the user.
Inspect the combustion air-inlet and vent systems. Make certain that all joints are secure and that combustion air-inlet and vent pipe supports are all in place. Check the outdoor combustion air-inlet and vent terminals to see that they are free of obstructions, and that there is no damage nearby caused by condensate.
Periodically, lift and release the lever handle on the temperature pressure relief valve, located near the top of the water heater, to make certain the valve oper­ates freely. Allow several gallons to flush through the discharge line to an open drain.
NOTICE: If the temperature and pressure relief valve on the water heater discharges periodically, this may be due to ther­mal expansion in a closed water system. Contact the water supplier or your plumb­ing contractor on how to correct this.
DO NOT plug the relief valve outlet.
A water heater’s tank can act as a settling basin for solids suspended in the water. It is therefore not uncommon for hard water deposits to accumulate in the bottom of
the tank. If allowed to accumulate, these solids can cover the gas control (thermo­stat) sensors, causing the sensors to operate erratically. Because accumulated solids can prevent the gas control (thermostat) sensors from accurately reading the water temperature, the water at the fixture can be hotter than the gas control (thermostat) setting. It is suggested that a few quarts of water be drained from the water heater’s tank every month to clean the tank of these deposits.
Rapid closing of faucets or solenoid valves in automatic water using appliances can cause a banging noise heard in a water pipe. Strategically located risers in the water pipe system or water hammer arrest­ing devices can be used to minimize the problem.
The anode rod should be removed from the water heater’s tank periodically,for inspec­tion and replaced when more than 6 in. (15.2 cm) of core wire is exposed at either end of the rod.
Make sure the cold water supply is turned off before removing anode rod.
This water heater incorporates a combus­tion shut off device that shuts the operation of the water heater down if undesirable combustion conditions occur, such as the presence of flammable vapors or blockage of the combustion air-inlet and/or vent sys­tems. Please contact a Qualified Service Technician if this occurs.
32
Page 33
!
Care and cleaning of the water heater
Housekeeping
DANGER: Combustible materials, such as clothing, cleaning materials, or flammable liquids, etc., must not be placed against or next to the water heater.
Representative burner flame pattern
Make sure the Flammable Vapor Sensor is not blocked or obstructed.
DO NOT expose the Flammable Vapor Sensor to cleaning agents.
Combustion Air-Inlet and Vent System Inspection
The water heater’s internal flue must be inspected periodically to be certain it is clean by removing the blower assembly and flue baffle.
When reinstalling the flue baffle make certain it is hung securely by its hanger at the top of the flue way.
Reinstall the blower assembly.
Burner Inspection
Visually inspect the hot surface ignitor and main burner periodically.
Through the sight glass, inspect the hot surface ignitor with the main burner off and inspect the main burner while firing.
If any unusual burner operation is noted, the water heater should be shut off until qualified service assistance can be obtained.
Inspect the combustion air-inlet and vent systems. Make certain that all joints are secure and that combustion air-inlet and vent system supports are all in place. Check the outdoor combustion air-inlet and vent system terminals to see that they are free of obstructions, and that there is no damage nearby caused by condensate.
!
CAUTION: For your safety, cleaning of the burner must be performed only by qualified service personnel, as it involves the disconnection of gas piping and leak testing. The burner chamber is a sealed area. If the burner access door is removed, the burner access door gasket must be replaced.
For cleaning, remove the burner from the water heater. A vacuum cleaner can be used on the burner and floor shield inside the water heater. The burner can also be cleaned by scrubbing with mild detergent.
NOTICE: Refer to the Hydrogen Gas Caution in the Operating Instructions.
NOTICE: Do not remove the anode rod from the water heater’s tank, except for inspection and/or replacement, as operation with the anode rod removed will greatly shorten the life of the glass lined tank and will exclude warranty coverage.
Vacation and Extended Shut-Down
If the water heater is to remain idle for an extended period of time, the power and water to the appliance should be turned off to conserve energy and prevent a build-up of dangerous hydrogen gas.
The water heater and piping should be drained if they might be subjected to freezing temperatures.
After a long shut-down period, the water heater’s operation and controls should be checked by qualified service personnel. Make certain the water heater is complete­ly filled again before placing it in operation.
Anode Rod
This water heater is equipped with an anode rod designed to prolong the life of the glass lined tank. The anode rod is slowly consumed, thereby eliminating or minimizing corrosion of the glass lined tank.
Water sometimes contains a high sulfate and/or mineral content and together with cathodic protection process can produce a hydrogen sulfide, or rotten egg odor in the heated water. Chlorination of the water supply should minimize the problem.
33
Page 34
Before You Call for Service
Troubleshooting Tips
Save time and money! Review the charts on the following pages first and you may not need to call for service.
This water heater incorporates shut off devices that shuts the operation of the water heater down if undesirable combustion conditions occur, such as the presence of flammable vapors or blockage of the vent inlet systems. Please contact a Qualified Service Technician if this occurs.
Problem Possible Causes What To Do
and/or combustion air-
Condensation This usually happens when a new
heater is filled for the first time.
This is normal, after the water in the tank warms up, the condensa­tion will disappear. Refer to page 10 for more information.
Moisture from the products of combustion condensing on the tank surface.
An undersized water heater will cause condensation.
This is normal and will disappear in time. Refer to page 10 for more information.
Use a water heater size that meets the requirements of your needs.
Yellow flame or soot Scale on top of the burner. Contact a qualified service techni-
cian to remove scale.
Vent and/or combustion air-inlet systems are blocked.
Remove obstruction or debris from vent and/or combustion air-inlet systems.
Unable to light the main burner Air in gas line. Contact a qualified service techni-
cian to purge the air from the gas line.
Blocked vent system. Contact a qualified service techni-
cian to evaluate vent system for blockage.
Blocked combustion air-inlet sys­tem
Contact a qualied service techni­cian to evaluate the combustion air-inlet system for blockage.
Pressure Switches Make sure the pressure switch
hoses are not "kinked".
Wire Connection(s) not fully secured.
Combustion Shut-off Device tripped.
Contact a qualified service techni­cian to confirm wire connections.
Combustion Shut-off Device(s) should be inspected by a qualified service technician.
Gas Control Problem Contact a qualified service techni-
cian.
Main burner does not Energy shut off device open. The combination gas control (ther-
mostat) should be replaced by a qualified service technician.
Combustion Shutoff Device Tripped.
The combustion shutoff device should be inspected by a qualified service technician.
CAUTION: label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.
CAUTION: For your safety DO NOT attempt repair of gas piping, combination gas control (thermostat), burners, vent and/ or combustion air-inlet systems or other safety devices. Refer repairs to qualified service personnel.
34
Page 35
Before You Call For Service
Troubleshooting Tips
Save time and money! Review the charts on the following pages first and you may not need to call for service.
This water heater incorporates shut off devices that shut the operation of the water heater down if undesirable combustion conditions occur, such as the presence of flammable vapors or blockage of the vent and /or combustion air-inlet systems. Please contact a Qualified Service Technician if this occurs.
Problem Possible Causes What to Do
Rumbling noise
Relief valve pro­ducing popping noise or draining
Not enough or no hot water
Water is too hot
Scale and sediment Drain the water heater to remove scale and
sediment from the tank. Refer to page 28.
Pressure build up caused by thermal expansion in a closed system.
This is an unacceptable condition and must be corrected. Contact the water supplier or plumbing contractor on how to correct this. Do not plug the relief valve outlet.
Water usage may have exceeded the capacity of the water heater.
Wait for the water heater to recover after an abnormal demand.
Low gas pressure. Check gas supply pressure and manifold pres-
sure.
The combination gas control (thermo­stat) may be set too low.
See the "Water Temperature Setting"of the water heater section of this manual.
Leaking or open hot water faucets. Make sure all faucets are closed.
Check valve error codes. Refer to gas valve error code table on page 36.
"ON / OFF" switch turned off. Turn "ON".
Blower unplugged. Plug in. verify power supply (120 VAC).
Combustion Shutoff System tripped. Contact a qualied service technician.
The combination gas control (thermo­stat) is set too high.
Combination gas control (thermostat) is defective.
See the "Water Temperature Setting"of the water heater section of this manual
Contact a qualied service technician to re­place the combination gas control (thermostat)
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.
CAUTION: For your safety DO NOT attempt repair of gas piping, combination gas control (thermostat), burners, vent and or combustion air-inlet systems or other safety devices. Refer repairs to qualified service personnel.
35
Page 36
Gas Valve LED Codes
LED Status Problem Solution
○ ○ ▼ A B C
● ○ ○ ● ○ ○
○ ○ ▼ A B C
● ○ ● ○ ● ○
○ ○ ▼ A B C
● ○ ● ○ ○ ○
○ ○ ▼ A B C
● ○ ● ○ ○ ●
○ ○ ▼ A B C
● ○ ● ○ ● ●
○ ○ ▼ A B C
● ○ ○ ● ● ○
○ ○ ▼ A B C
● ○ ○ ○ ● ●
○ ○ ▼ A B C
● ○ ● ● ● ○
○ ○ ▼ A B C
● ● ● ● ● ●
○ ○ ▼ A B C
● ○ ○ ○ ● ○
○ ○ ▼ A B C
● ○ ○ ● ● ●
○ ○ ▼ A B C
● ○ ● ● ○ ○
○ ○ ▼ A B C
● ○ ● ● ○ ●
○ ○ ▼ A B C
● ○ ○ ● ○ ●
○ ○ ▼ A B C
● ○ ○ ○ ○ ●
An open earth ground circuit to the ignition system.
Wiring error or a high resistance to earth ground.
Pressure switch remained closed lon­ger than 5 seconds after the call for heat began.
Pressure switch remained opened lon­ger than 5 seconds after the combus­tion blower was energized.
Error in the hot surface ignitor circuit. 1. Check that all wiring is correct and secure.
System in lockout.
Problem in the combination gas valve driver circuit.
Problem with the internal circuit. 1. Turn power to the water heater off for 10 seconds and
Problem with the internal circuit. 1. Turn power to the water heater off for 10 seconds and
Flame signal sensed out of proper sequence.
ECO activated. 1. Replace the combination gas control (thermostat).
One of the temperature adjust buttons stuck closed.
Water temperature sensor is either open or short circuited.
Unit shuts down. 1. Check for correct wiring to FV sensor.
Unit shuts down and in lockout.
1. Check that the earth ground connection is properly connected.
2. Check that the ground conductor on the water heater is properly connected.
1. Check proper connection of line neutral and hot wires.
2. Check that the water heater is securely connected to earth ground.
1. Verify that the wiring to the pressure switch(es) is correct.
2. Replace the pressure switch(es).
1. Verify that the wiring to the pressure switch(es) is correct.
2. Verify that the wiring to the pressure switch(es) is connected correctly.
3. Check the vent and / or combustion air-inlet systems for obstructions.
2. Replace hot surface ignitor.
1. Gas supply is off or too low to operate. Turn on the gas supply and / or increase the inlet gas supply pres­sure.
2. Hot surface ignitor not positioned correctly.
3. Low voltage to the water heater. Increase supply volt­age to rated voltage.
4. Electric polarity to unit is incorrect - test and correct.
5. Check the vent and /or combustion air-inlet systems for obstructions.
1. Turn power to the water heater off for 10 seconds and then back on.
2. Replace the combination gas control (thermostat).
then back on.
2. Replace the combination gas control (thermostat).
then back on.
2. Replace the combination gas control (thermostat).
1. Replace the combination gas control. (thermostat)
1. Press and release each of the buttons once.
2. Replace the combination gas control (thermostat).
1. Check that all wiring is correct and secure.
2. Replace the combination gas control (thermostat).
2. Check for open circuits to FV sensor.
3. Replace FV sensor.
1. FV sensor detected presence of ammable vapors.
2. Contact a service agency.
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. VERIFY PROPER OPERATION AFTER SERVICING.
CAUTION: For your safety DO NOT attempt repair of gas piping, combination gas control thermostat, burners, vent and/or combustion air-inlet systems or other safety devices. Refer repairs to qualified service personnel.
36
Page 37
Replacement Parts
For 40, 50, 65, and 75 Gallon Models equipped for use with Natural or Liquified Petroleum/LP gas.
Instructions For Placing a Parts Order
Rubber
Coupling
Blower
Assembly
** Heat
Trap
All parts orders should include:
The model and serial number of the
water heater from the rating plate.
Specify type of gas (Natural or
Liquified Petroleum/LP gas) as marked on the rating plate.
Part description (as noted below) and
number of parts desired.
Refer to page 40.
** Heat Trap Nipple
Flue Baffle
CAUTION: For your safety, DO NOT attempt repair of gas piping, gas control (thermostat), burners, vent connectors or other safety devices. Refer repairs to qualified service personnel.
Use only original equipment replacement parts.
*Burner Assembly Kit
Nipple
Anode Rod
Combustion
Air-Inlet
Assembly
Dip Tube
Dip Tube Gasket
Temperature and Pressure Relief Valve
The kit provides extra speed clips and tamper resistant screws.
** May differ in actual appearance.
Drain Valve
Combination Gas Control (Thermostat)
*Burner
*Burner Supply Tube
Flammable Vapor Sensor
*Burner Access Door Gasket
*Burner Orifice
*Igniter
*Burner Access Door
*Sight Glass
Jacket Door
*Burner Access Door Grommet
37
Page 38
Notes
38
Page 39
Notes
39
Page 40
IF YOU NEED SERVICE
1. Should you have any questions about your new water heater, or if it requires adjustment, repair, or routine mainte­nance, it is suggested that you first contact your installer, plumbing contractor or previously agreed upon service agency. In the event the firm has moved, or is unavailable, refer to the telephone directory, commercial listings or local utility for qualified service assistance.
2. Should your problem not be solved to your complete satisfaction, you should then contact the Manufacturer’s National Service Department at the following address:
1241 Carwood Court Montgomery, Alabama 36117 Phone: 1-800-432-8373
When contacting the manufacturer, the following information will be requested:
a. Model and serial number of the water heater as shown on the rating plate attached to the jacket of the heater.
b. Address where the water heater is located and physical location.
c. Name and address of installer and any service agency who performed service on the water heater.
d. Date of original installation and dates any service work was performed.
e. Details of the problems as you can best describe them.
f. List of people, with dates, who have been contacted regarding your problem.
Important Instructions for the Commonwealth of Massachusetts
The Commonwealth of Massachusetts requires compliance with regula-
5.08: Modications to NFPA-54, Chapter 10 : 248 CMR 4.00
tion and 5.00 for installation of through – the – wall vented gas appliances as follows:
(1) Revise NFPA-54 section 10.5.4.2 by adding a second exception as fol­lows: Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device that will automatically shut off the gas to the burner in the event of a sustained back-draft. (2) Revise 10.8.3 by adding the following additional requirements: (a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above
nished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satised:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the
installing plumber or gastter shall observe that a hard wired carbon monox­ide detector with an alarm and battery back-up is installed on the oor level
where the gas equipment is to be installed. In addition, the installing plumber or gastter shall observe that a battery operated or hard wired carbon mon­oxide detector with an alarm is installed on each additional level of the dwell­ing, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the
services of qualied licensed professionals for the installation of hard wired
carbon monoxide detectors a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detec-
tor with alarm and battery back-up may be installed on the next adjacent oor
level. b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certied.
3. SIGNAGE. A metal or plastic identication plate shall be permanently
mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizon­tally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS".
4. INSPECTION. The state or local gas inspector of the side wall horizon­tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. (b) EXEMPTIONS: The following equipment is exempt from 248 CMR
5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment in­stalled in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes. (c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system. (d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts
for venting the ue gases, but identies "special venting systems", the fol­lowing requirements shall be satised by the manufacturer:
1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and
2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions. (e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
40
Loading...