Installation manual
CF8-W-Disp-GH
CO2 transmitter with relay for use in
greenhouses
1 Back plate 5 Snap-in lid
2 PCB (mounted in the box at delivery) 6 Lid locking screw (not shown)
3 PG7 Cable entry bushing 7 Temperature sensor
4 Attachment loop
Terminals and jumpers on CF8-W-Disp-GH. The darker positions are default settings
According to positions o f
Electrical con nections
The power supply has to be connected to and . is considered as
system ground. If the analogue output is connected to a controller the same ground
reference has to be used for the CF8-W-Disp-GH unit and for the control system!
Unless different transformers are used, special precautions need to be taken.
PLEASE NOTE! The CF8-W-Disp-GH
signal ground is not galvanically
separated from the CF8-W-Disp-GH
power supply!
NOTE!
The same ground reference has
to be used for the CF8-W-Disp-GH
unit and for the control system!
Connect the power after mounting. The
analogue output should be connected before
measuring.
Terminal
Out(2)
6
7
Power ground
Output 1 (+)
Analogue
Output 2 (+)
closed relay
Relay COM
Normally open
3W
24 VAC/DC-
2-10 VDC or 4-20 mA,
0-10 VDC or 0-20 mA,
2-10 VDC or 4-20 mA
minimum load 1mA/5V
rated load 0,5A/125VA C ;
1A/24VDC
See note 1!
OUT1 and start point
jumpers.
See note 2!
According to positio ns o f
OUT2 and start point
jumpers.
OUT(3)
Table 1: Electrical connections