
Installation manual 
CF5-D, CF5-D-Disp 
CO2 / temperature transmitter for mounting in 
ventilation ducts
Figure 1 
1 Sampling probe   6 O-ring 29,2x3,53 (Factory supplied mounted in box) 
2 Sealing gasket   7 PCB (Factory supplied mounted in box) 
3 Largest locking nob   8 Snap-in lid 
4 2 washers    9 PG9 cable entry bushing 
5 2 screws    10 Temperature sensor (to be put into the sampling tube) 

Mounting of CF5-D on to the duct. 
Figure 2 
10  Hole with 25 mm diameter 
11  Temperature sensor with 110 mm cable mounted in the sampling probe 
Mounting Instruction 
Since there might be a substantial pressure difference in duct mounting applications, 
it is essential to avoid ambient air from suction into the duct mounting box. For 
correct function it is indispensable that the sealing of the box cover, the cable entry 
bushings, the cable feed through and the duct entrance are absolutely tight. The duct 
entrance may need extra sealing paste in order to prevent leakage. The PCB must 
be handed carefully and protected from electrostatic discharge. 
1)  Electrical cable ent ry: The box has a factory mounted cable entry bushing in 
dimension PG9. Never feed more than one cable through each cable entry 
bushing, or else gas might leak through! 
2)  Mounting the tube: Drill a hole (10) with 25 mm diameter (or 1 inch) for the 
sampling probe and two holes with 4 mm diameter for the screws (5) into the air 
duct and mount the tube (1) with the gasket (2). The sampling probe should be 
mounted with the largest locking knob on top. The unit can be mounted with the 
air coming from the left or right. 
3)  Attaching the sensor box is made to the sampling probe by a snap-i n bayonet 
fitting. First, carefully stick the temperature probe (11) into the sampling probe. 
(1). Orient the box onto the sampling probe so that the box upside is on the same 
side as the largest locking knob (3). When the probe is fitted into the notches of 
the box, then turn the box clockwise until stop (see Figure 1). Position 1 indicates 
open where the box can be removed from the sampling probe. In position 2 the 
box is locked to the probe. 
If for some reason the PCB must be removed it must be handed carefully 
and protected from electrostatic discharge! Normally, removing the PCB is 
not required. 

Electrical con nections 
The power supply has to be connected to   and .   is considered as system 
ground. If the analogue output is connected to a controller the same ground reference 
has to be used for the CF5-D unit and for the control system! Unless different 
transformers are used, special precautions need to be taken. 
PLEASE NOTE! The CF5-D signal and power supply 
grounds are common. 
NOTE! The same ground refer e nce has to be 
used for the CF5-D unit and for the control 
system!
Connect the power after mounting. The analogue 
output should be connected before measuring. 
Connection 
Out(1) 
Out(2) 
Note 1:  The ground terminal is used as negative power supply DC input or AC phase 
ground   (halfwave rectifier). 
Note 2: CF5-D can deliver a voltage or a current loop for Out(1) / Out(2). To change 
between voltage and current output mode the hardware jumpers are used. There is one 
jumper for Out(1) and one for Out(2), so that one output can be a voltage output and the 
other a current output. Both, voltage output and current outputs, can have start points 0 % (010 VDC or 0-20mA) or 20% (2-10 VDC or 4-20mA). The same start point is used for both 
outputs. See the user manual. 
Analogue Output 1 (+) 
Analogue Output 2 (+) 
Function 
Power (+) 
Electrical Data 
24 VAC/DC+ (+-20%), 3W 
0-10 VDC or 0-20 mA, 
2-10 VDC or 4-20 mA, 
Same as Output 1 
Remarks 
2W without output load 
See note 1! 
According to positions of 
Out(1) and start point 
jumpers.  
See note 2! 
According to positions of 
Out(2) and start point 
jumpers.  
See note 2! 

Terminals and jumpers on CF5-D. The darker positions are default settings. 
Dimensions 
Dimensions of sensor in mm and inches