ROTRONIC CF5-D User Manual

Dokument IMA 207
1
2
1
2
3
4
5
6
7
9
8
10
Installation manual
CF5-D, CF5-D-Disp
CO2 / temperature transmitter for mounting in
ventilation ducts
Figure 1
1 Sampling probe 6 O-ring 29,2x3,53 (Factory supplied mounted in box) 2 Sealing gasket 7 PCB (Factory supplied mounted in box) 3 Largest locking nob 8 Snap-in lid
4 2 washers 9 PG9 cable entry bushing 5 2 screws 10 Temperature sensor (to be put into the sampling tube)
Dokument IMA 207
11
10
Mounting of CF5-D on to the duct.
Figure 2
10 Hole with 25 mm diameter
11 Temperature sensor with 110 mm cable mounted in the sampling probe
Mounting Instruction
Since there might be a substantial pressure difference in duct mounting applications, it is essential to avoid ambient air from suction into the duct mounting box. For correct function it is indispensable that the sealing of the box cover, the cable entry bushings, the cable feed through and the duct entrance are absolutely tight. The duct entrance may need extra sealing paste in order to prevent leakage. The PCB must be handed carefully and protected from electrostatic discharge.
1) Electrical cable ent ry: The box has a factory mounted cable entry bushing in dimension PG9. Never feed more than one cable through each cable entry bushing, or else gas might leak through!
2) Mounting the tube: Drill a hole (10) with 25 mm diameter (or 1 inch) for the sampling probe and two holes with 4 mm diameter for the screws (5) into the air duct and mount the tube (1) with the gasket (2). The sampling probe should be mounted with the largest locking knob on top. The unit can be mounted with the air coming from the left or right.
3) Attaching the sensor box is made to the sampling probe by a snap-i n bayonet
fitting. First, carefully stick the temperature probe (11) into the sampling probe. (1). Orient the box onto the sampling probe so that the box upside is on the same side as the largest locking knob (3). When the probe is fitted into the notches of the box, then turn the box clockwise until stop (see Figure 1). Position 1 indicates open where the box can be removed from the sampling probe. In position 2 the box is locked to the probe.
If for some reason the PCB must be removed it must be handed carefully and protected from electrostatic discharge! Normally, removing the PCB is not required.
Dokument IMA 207
Terminal
Power ground (-)
24 VAC/DC-
~
~
Electrical con nections
The power supply has to be connected to and . is considered as system
ground. If the analogue output is connected to a controller the same ground reference has to be used for the CF5-D unit and for the control system! Unless different
transformers are used, special precautions need to be taken.
PLEASE NOTE! The CF5-D signal and power supply grounds are common.
NOTE! The same ground refer e nce has to be used for the CF5-D unit and for the control system!
Connect the power after mounting. The analogue output should be connected before measuring.
Connection
Out(1)
Out(2)
Note 1: The ground terminal is used as negative power supply DC input or AC phase ground (halfwave rectifier).
Note 2: CF5-D can deliver a voltage or a current loop for Out(1) / Out(2). To change between voltage and current output mode the hardware jumpers are used. There is one jumper for Out(1) and one for Out(2), so that one output can be a voltage output and the other a current output. Both, voltage output and current outputs, can have start points 0 % (0­10 VDC or 0-20mA) or 20% (2-10 VDC or 4-20mA). The same start point is used for both outputs. See the user manual.
Analogue Output 1 (+)
Analogue Output 2 (+)
Function
Power (+)
Electrical Data
24 VAC/DC+ (+-20%), 3W
0-10 VDC or 0-20 mA,
2-10 VDC or 4-20 mA,
Same as Output 1
Remarks
2W without output load
See note 1!
According to positions of Out(1) and start point jumpers. See note 2!
According to positions of Out(2) and start point jumpers. See note 2!
Dokument IMA 207
+
~
Terminals and jumpers on CF5-D. The darker positions are default settings.
Dimensions
Dimensions of sensor in mm and inches
Loading...