ROTRONIC CF3-W-US-FLI User Manual

Dokument IMA 212
Front
Wall
Insert screw driver Push upwards to open
Front
Wall
Installation manual
CF3-W-US-Disp-FLI
CO2 transmitter and alarm
CF3-W-US-Disp-FLI
General
The alarm product CF3-W-US-Disp-FLI is designed to measure carbon dioxide (CO2) in rooms. Option - Disp displays the measured CO2 value in ppm (parts-per-million) on the LCD. LEDs are lit to give an overview of the CO2 value.
An acoustic alarm sounds when the CO2 value is above 1400ppm. The acoustic alarm can be silenced with a push button on the side of the instrument.
The units are designed for connecting to Direct Digital Control (DDC) with 0-10V signal inputs.
To open the wall mounted housing
Figure 1. Closed housing seen from the top and the side. The housing is opened by inserting a screw driver and pushing to the front side of the housing. The locking hooks will then be released.
Dokument IMA 212
128,4(5,06)
85(3,34)
32,7(1,29)
30(1,18)30(1,18)
30(1,18)
30(1,18)
52,5(2,07)
30(1,18)
Figure 2. Closed housing seen from the side. Figure 3. Closed housing seen from the side. The housing is opened by inserting a screw Never push to the right. The locking hooks driver and pushing left (to the front side). may break and the housing is damaged The locking hooks will then be released.
Dimensions
Figure 3. The dimensions of the sensor in mm and (inches)
Dokument IMA 212
Terminal
Function
Electrical data
Remarks
+~
Power (+)
Power ground (-)
24 VAC/DC+ (+-20%),
24 VAC/DC-
System voltage reference
OUT1
Analogue output
acoustic alarm
0-10 VDC
0-2000 ppm CO2
for 30 minutes.
LED Colour
Electrical data
Remarks
Green
0VDC 10VDC
Lit between 0-800 pp m CO2
Yellow
0VDC 10VDC
Lit between 800-14 00 ppm CO2
Red
0VDC 10VDC
Lit above 1400 ppm CO2. Buzzer sounds.
Electrical connections
The power supply has to be connected to +~ and . is considered as system
ground. The same ground reference has to be used for the CF3-W-US-Disp-FLI unit and for the DDC/signal receiver.
PLEASE NOTE! The same ground reference has to be used for the CF3-W-US-Disp-FLI unit and for the control
system!
OUT2
1 (+)
Silences the
Table I. Connections of the main terminal of CF3-W-US-Disp-FLI
Table II. The LEDs
2W
A push on the push button silences the acoustic alarm

Self-diagnostics

The system contains complete self-diagnostic procedures that are executed automatically when the sensor is in operation. Sensors with display show a wrench if an error is found. The wrench is shown during the first seconds after power up and if the measuring range is exceeded.

Maintenance

The CF3-W-US-Disp-FLI is basically maintenance free in normal environments thanks to the built-in self-correcting ABC algorithm.
PLEASE NOTE! The sensor accuracy is defined at continuous operation (at least 3 weeks after installatio n )
Electronic products should be disposed of via a suitable recycling centre.
Dokument IMA 212
Figure 3. The
CF3-W-US-Disp-FLI PCB
Figure 4. The upper part of the
CF3-W-US-Disp-FLI PCB seen from the back with the
jumper in voltage (default) and current position
Loading...