ROTRONIC CF3-W-EU-FLI User Manual

Dokument IMA 205
Press here to open.
Figure 2 Closed housing seen from above. Pressing a screwdriver on the locking hook opens the housing. The locking hook is then released
Installation manual
CF3-W-EU-Disp-FLI
CO2 transmitter with acoustic alarm
Figure 1 CF3-W-EU-Disp-FLI
General
The IAQ (indoor air quality) sensor product CF3-W-EU-Disp-FLI (sensor for wall mounting) is desig ne d t o meas ur e carb on di o xide (CO2) in rooms. The acoustic alarm sounds when the carbon dioxide concentration is above 1400 ppm CO2. A push button silences the ala rm for 30 minutes. Green, yellow and red LEDs give a rough estimate of the CO2 concentration Option -Disp displays the measured CO2 value in ppm (parts-per-million) on the LCD.
The units are designed for connecting to Direct Digital Control (DDC) with 0-10V signal inputs. The signal output OUT1 (0-10V) gives linear signal voltage corresponding to the measuring range.
To open the wall mounted housing
Dokument IMA 205
Terminal
Function
Electrical
Remarks
settings
Remarks
sensor
+~
Power (+)
24 VAC/DC+
reference
Out(1)
Analogue output 1
0-10 VDC
0-2000 ppm CO2
Green LED
Lit when the CO2
The buzzer sounds
Push
Silences the buzzer
above 1400 ppm
Electrical connections
The power supply has to be connected to +~ and . is considered as system
ground. The same ground reference has to be used for the CF3-W-EU-Disp-FLI unit and for the DDC/signal receiver.
PLEASE NOTE! The same ground refere nce has to be use d for the CF3-W-
EU-Disp-FLI
unit and for the control system!
Out(2)
Yellow
LED
Red LED
Power ground (-)
(+)
data
(+-20%), 2W
24 VAC/DC-
Standard
System voltage
Settings of this
Buzzer connected
concentration is below 800 ppm
Lit when the CO
2
concentration is 800 to 1400 ppm
Lit when the CO
2
concentration is above 1400 ppm
button
30 minutes when pushed. After 30 minutes the buzzer sounds if the CO concentration is
Table I. Connections of the main terminal and other functions of CF3-W-EU-Disp-FLI
2