ROTRONIC CF3-W-EU User Manual

Dokument IMA 201
Press here to open.
Installation manual
CF3-W-EU, CF3-W-EU-Disp
CO2 transmitter
CF3-W-EU CF3-W-EU - Disp
General
The IAQ-sensor product CF3-W-EU (sensor for wall mounting) is designed to measure carbon dioxide (CO2) in rooms. Option - TR is prepared for temperature measurements by the resistive temperature probe mounted by the user. The temperature probe is potential free (floating). Option - Disp displays the measured CO2 value in ppm (parts-per-million) on the LCD.
The units are designed for connecting to Direct Digital Control (DDC) with 0-10V or 2-10V signal inputs. The two parallel signal outputs OUT1 (0-10V) and OUT2 (2-10V or 4-20 mA) give linear signal voltages or currents corresponding to the measuring range. The output OUT2 also indicates the status by setting the output voltage to 1V or the output current to 2 mA when the sensor self-diagnostics detects any error.
To open the wall mounted housing
Figure 1. Closed housing seen from above. The housing is opened by pressing a screw driver on the locking hook. The locking hook is then released.
Dokument IMA 201
Terminal
Function
Electrical data
Remarks
Remarks
this sensor
Power (+)
ground (-)
24 VAC/DC+
reference
Out(1)
Analogue
0-10 VDC
0 VDC or 0mA
0-2000 ppm CO2
Status = NOT READY
~
~
Option display
+ ~
Electrical connections
The power supply has to be connected to and . is considered as system
ground. The same ground reference has to be used for the CF3-W-EU unit and for the DDC/signal receiver.
PLEASE NOTE! The same ground refere nce has to be used for the CF3-W-
EU
unit and for the control s ystem!
Out(2)
Power
output 1 (+)
Analogue
output 2 (+)
Table I. Connections of the main terminal of CF3-W-EU
(+-20%), 2W
24 VAC/DC-
2,0-10,0 VDC or
4,0-20,0 mA
0,9-1,6 VDC or
1.5-2,5 mA
Standard settings
System voltage
0-2000 ppm CO
2
Status = ERROR
Settings of
Figure 2. PCB with jumper to configure OUT2 for current output 4-20mA or voltage output 2­10VDC
Dokument IMA 201
+ ~
+ ~
Figure 3. Enlarged picture of the PCB with the jumper set to current output (left position)
Figure 4. Enlarged picture of the PCB with the jumper set to voltage output (right position)

Self-diagnostics

The system contains a complete self-diagnostic procedure that is executed automatically when the sensor is in operation. The yellow LED is lit if an error is found. Sensors with display show a wrench if an error is found. The wrench is shown and the yellow LED is lit during the first seconds after power up and if the measuring range exceeded. They are automatically turned off when the sensor returns to normal operation. The output OUT2 indicates the same information by setting the output voltage to 1V or 2 mA.
Maintenance
The CF3-W-EU is basically maintenance free in normal environments thanks to the built-in self-correcting ABC algorithm.
PLEASE NOTE! The sensor accuracy is defined at continuous operation (at least 3 weeks after installation)
PLEASE NOTE! Electronic products should be disposed of via a suitable recycling centre.
Dokument IMA 201
80(3,15)
28(1,10)
30(1,18)
60(2,36)
4(0,16)
4(0,16)
30(1,18)
100(3,94)

Dimensions

Figure 5. The dimensions of the sensor in mm and (inches)
Mounting of the sensor onto the wall Please use screws with screw head diameter less than 7,5 mm (0,295 inches) and
screw head height less than 2,4 mm (0,094 inches).
Loading...