C105 Circular Case Recorder
Operating Instructions
Fig. 1.
CONTENTS
|
Page No. |
|
Page No. |
INTRODUCTION |
2 |
MAINTENANCE |
11 |
Identification |
2 |
Cutting a programme cam |
11 |
Specification |
3 |
Pen Adjustment |
11 |
INSTALLATION |
4 |
Calibration |
11 |
Servicing |
12 |
||
Mounting |
4 |
Wet and Dry Bulb Water Bath |
13 |
Access to Recorder |
5 |
|
|
Process Connections |
5 |
SPECIAL INSTRUCTIONS & DIAGRAMS |
14 |
Electrical Connections |
5 |
|
|
OPERATION |
6 |
FAULT FINDING |
15 |
|
|
||
Mechanical Clock |
6 |
SPARES LIST |
15 & 16 |
Fitting a Chart |
6 |
|
|
Set Pointer Adjustment |
6 |
|
|
Inking System |
6 |
|
|
Zero Adjustment |
7 |
|
|
Start-up Check |
7 |
|
|
Start-up Procedure |
7 |
|
|
Description of Operation |
8 |
|
|
Electrical alarm/control system |
10 |
|
|
Programme Control |
10 |
|
|
The chart drive and control system on this instrument may be operated from a mains voltage supply. The mains must be switched off before making any mechanical adjustments other than of the set pointers or carrying out any maintenance or fault finding procedures. When making electrical adjustments observe the warning notes in the text.
instrumentation and control
INTRODUCTION
The C105 series of instruments is designed to measure, record and control process variables such as temperature, pressure and humidity. A maximum of two measuring systems is provided in each instrument; a fluid expansion type or bimetallic system is used for temperature recording, a hygroscopic element or a wet and dry bulb system for humidity and a Bourdon tube or diaphragm for pressure measurement. The measured values are continuously recorded on a calibrated circular chart which is rotated at a constant speed by a mechanical or electric clock. Control of the process variable is provided electrically.
|
|
|
|
|
Each Pen |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Basic |
No. of |
|
Alarm or Control Mode |
|
Set Points |
|
Programme |
|||||
Type |
Measuring |
Measured |
|
|
Control Cam |
|||||||
|
|
|
No. 1 |
|
No. 2 Nos. 3 & 4 |
(Single Pen |
||||||
Number |
Points |
Variable |
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
only) |
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
C10 |
5 One |
1 Temperature |
17 |
Record only |
|
– |
|
– |
|
– |
– |
– |
Recorder |
pen |
(Fluid |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
with |
|
expansion |
Electric Alarm/Control |
Position of Pen in relation to |
|
|
||||||
105mm |
6 Two |
system) |
with Relay Output |
Set Point when Relay is energised |
|
|
||||||
pen |
|
00 |
Two Step |
|
Above |
|
– |
|
None, or any |
– or C |
||
|
|
|
|
|||||||||
travel |
pen |
2 Pressure |
|
|
|
|||||||
on |
|
(‘C’ Spring– |
01 |
Two Step |
|
Below |
|
– |
|
combination |
– or C |
|
circular |
|
316 st.steel) |
05 |
Three Step |
|
Below |
|
Below |
|
applicable |
– |
|
chart |
|
3 Pressure |
06 |
Three Step |
|
Above |
|
Above |
|
to Set Points |
– |
|
|
|
09 |
High-low |
|
Above |
|
Below |
|
No. 1 & 2 |
|
– |
|
|
|
(Spiral |
03 |
Double 2 Step |
|
Above/Above |
|
– |
|
|
|
– or C |
|
|
Bourdon – |
|
|
|
|
|
|||||
|
|
04 |
Double 2 Step |
|
Below/Below |
|
– |
|
|
|
– or C |
|
|
|
phosphor |
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
bronze) |
|
|
|
Contact Action at Set Point |
|
|
|
|||
|
|
|
|
|
|
|
|
|
||||
|
|
4 Pressure |
Electric Alarm/Control |
when Pen moves towards |
|
|
|
|||||
|
|
Contacts only – no Relay |
outside of Chart |
|
|
|
|
|
|
|||
|
|
(Spiral |
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Bourdon – |
60 |
Two Step |
–Contact Mode C |
Make |
|
– |
|
|
|
– or C |
|
|
321 st.steel) |
|
|
|
|
||||||
|
|
61 |
Two Step |
–Contact Mode A |
Break |
|
– |
|
None, or any |
– or C |
||
|
|
|
|
|
||||||||
|
|
5 Pressure |
65 |
Three Step |
–Contact Mode AA |
Break |
|
Break |
|
combination |
– |
|
|
|
66 |
Three Step |
–Contact Mode CC |
Make |
|
Make |
|
applicable |
– |
||
|
|
Capsule |
|
|
||||||||
|
|
69 |
High-Low |
–Contact Mode CA |
Make |
|
Break |
|
to Set Points |
– |
||
|
|
Stack – |
|
|
||||||||
|
|
63 |
Double 2 Step |
–Contact Mode D |
Make/Make |
|
– |
|
No. 1 & 2 |
|
– or C |
|
|
|
beryllium |
|
|
|
|||||||
|
|
64 |
Double 2 Step |
–Contact Mode B |
Break/Break |
|
– |
|
|
|
– or C |
|
|
|
copper) |
|
|
|
|
||||||
|
|
6 Pressure |
|
|
|
|
|
|
|
|
|
|
|
|
(Diaphragm |
|
|
|
|
|
|
|
|
|
|
|
|
Stack – |
|
|
|
|
|
|
|
|
|
|
|
|
beryllium |
|
|
|
|
|
|
|
|
|
|
|
|
copper) |
|
|
|
|
|
|
|
|
|
|
|
|
7 Relative Humidity |
|
|
|
|
|
|
|
|
|
|
|
|
(Goldbeater skin) |
|
|
|
|
|
|
|
|
|
|
|
|
– External |
|
|
|
|
|
|
|
|
|
|
|
|
9 Pressure |
|
|
|
|
|
|
|
|
|
|
|
|
(Coiled Tube – |
|
|
|
|
|
|
|
|
|
|
|
|
316 st.steel |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Notes:
Code No. is built up thus:
Single Pen |
C105/1 1 63 C |
|
( |
One Pen
Temperature
Double 2 Step –
Contacts only (no relay)
Programme Cam
Two Pen |
C 1 0 6 / 3 0 0 / 1 |
1 7 |
|
( |
( |
Two Pens
No. 1 Pen – Pressure (Bourdon)
– 2 Step Elec. Alarm
with Relay
No. 2 Pen – Temperature
– Record only
2
Specification
General:
Chart diameter
Writing width
Intrinsic error
Operating temperature limits
Operating humidity limits
Zero error due to ambient temp. variations Chart speeds
Chart drive
Power supply voltage and frequency Mounting
Temperature measuring instruments: Measuring systems
Maximum length capillary
Minimum span
Maximum span
Span limits
Pressure measuring instruments:
Measuring system
Minimum span
Maximum span
Span limits
Connection size
Humidity measuring instruments:
Measuring systems
Spans
Operating temperature limits
Operating humidity limits
Maximum length of capillary
(wet and dry bulb system) Electric alarm or control:
Instrument contacts
Contact action
Relays
Relay action
Overall dimensions
Panel cut-out
Maximum panel thickness
Weight
255mm
105mm
± 1% span maximum (±2% R.H. for hygroscopic membrane system)
–10o to +50oC |
678 |
Except for |
0 to 80% R.H. |
humidity recorders |
±0.05% span/oC typical
1 rev every 12 hours, 24 hours or 7 days
Synchronous electric motor or mechanical clock
200/250V or 100/120V, 50 or 60Hz
Wall or panel
Fluid expansion
30m
40oC
500oC
– 30oC to +600oC
Capsule stack, Bourdon tube or coiled tube
0 to 1 bar vacuum or pressure.
1200 bar
–1 bar to 1200 bar
Ranges up to 40 bar: a inch B.S.P.) with nut and tail Ranges over 40 bar: 2 inch B.S.P.) piece for 8mm tube
Sensitive hygroscopic membrane and fluid filled system for temperature measurement, or wet and dry bulb fluid expansion systems.
20 to 100% R.H. (hygroscopic membrane);
0 to 40oC (fluid filled systems)
0 to 40oC
30 to 85% R.H.
30m (each bulb)
20mA inductive or 30mA non-inductive load max.
Make above or below set point as required
Delayed action double pole change-over, 5A, 240V 50Hz non-inductive load, as standard
(Refer to wiring Diagram, p.14).
Energised above or below set point as required.
350mm wide; 137mm deep; 350mm high (Temp & R.H. 582mm high)
318mm diameter
25mm
10kg
3
INSTALLATION
Mounting
The instrument can be wall or panel mounted using the same fixing brackets. Do not install near any very hot apparatus, e.g. ovens, steam pipes or flues. Mount the recorder vertically in a position free from vibration and excessive temperature.
For panel mounting remove the fixing screws and rotate the fixing brackets so that the instrument can be inserted in the hole in the panel. Return the brackets to their original position and insert the fixing screws. Tighten the screws until they bear against the back of the panel.
Hygroscopic measuring instruments have external measuring elements requiring a clearance of 240mm below the case, and must be wall mounted.
Temperature Recorder |
Pressure Recorder |
Panel Mounting |
|
|
41 mm 83 mm |
350 mm
Cable gland for |
a” or 2” B.S.P. union with nut, |
|
w” conduit |
||
and tailpiece |
||
|
Temperature and Relative Humidity Recorder |
Wall Mounting |
Three holes at 120º on 340 mm p.c.d. to take 6.4 mm diam. screws
for wall mounting
Panel cut-out dia. 318 mm
Fig. 2.
4
Access to Recorder
To open the door, unlock, and turn the latch anticlockwise. As the door is opened the pen lifter raises the pen (or pens) away from the chart. Remove the chart (see page 6).
If the instrument is connected to the mains, switch off the mains supply before dismantling further.
For access to the terminal blocks remove the lower plastic plate from behind the chart by undoing the one retaining screw.
For access to the relays and measuring systems, first remove the chart. Unhook the pens from their mounting (see Fig. 3.). Remove the three screws from the outside edge of the chart plate. (The pen lifter is secured by one of these screws and must also be removed). Lower the chart plate carefully. The chart motor is mounted on the back of the chart plate and if the motor is an electric one it remains connected to the terminal block in the lower part of the case.
When replacing the chart plate reverse the above procedure. The coil on the pen lifter should be against the side of the case when the retaining screw is tightened.
Process Connections
To avoid confusion on instruments with more than one measuring system, setting pointers are labelled and Bourdon tube capillary connections to the instrument are painted with the same colours as the inks used for the corresponding pens.
Process connections – temperature measuring instruments:
Install the sensing element (bulb) of the instrument in the apparatus where the temperature is to be measured. The circulation around this element should be good and it should not be too close to any heating or cooling coil or other controlling medium. Fasten the capillary tubing at frequent intervals to rigid supports avoiding sharp bends of less than 50mm. radius anywhere along its length. The tubing must not touch or run close to any hot apparatus and should take the path least subject to temperature variation. If the temperature source is likely to move or vibrate allow one or two coils of 100mm. diameter of the capillary tube to eliminate stress of the tubing.
If the atmosphere around the capillary tube is likely to be corrosive, paint the tube with anti-corrosive paint and ensure this is maintained.
Process connections – pressure measuring instruments:
Connect the Bourdon tube sensing element to the measuring point on the apparatus using pressure tubing of the same or similar material as the Bourdon tube and of sufficient pressure rating. Slope the run of the tubing so that any condensate is drained away from the instrument and does not affect the accuracy of measurement. For measurement of steam pressure or other hot vapours, form a condensate trap below the instrument.
Process connections – humidity measuring instruments (wet and dry bulb):
Install the sensing elements (bulbs) where the humidity is to be measured as described for temperature measuring instruments. The wet bulb (red pen system) is kept moist by a fabric covering, forming a wick which dips into a constant level water bath. A distilled water supply tank should be connected to the inlet feed pipe with a head of between 1 and 6 metres.
It is important to install the bulbs in a position where the air speed is 3.6 metres per second or more. Below this speed inaccuracies of bulb depression may occur. The air should pass over the bulbs in such a direction that the water evaporating from the wet bulb does not pass over the dry bulb. The water must be kept clean and free from impurities. The temperature of the bath and all piping must not fall below 0oC. See also page 13.
Electrical Connections
Before making any connections to the instrument switch off the mains supply to be connected.
All electrical connections are made to terminal blocks in the lower part of the case behind the lower section of the chart plate.
Insert the leads through the cable gland in the underside of the case (see Fig. 2.) and make the connections as shown on the terminal labels or Wiring Diagram (page 14). The live line should be switched and fused with a 2 amp fuse. If the instrument is mounted on an insulated panel the case should be earthed.
5